These instructions do notpurport to cover alldetails or variations in equipment nor to provide every
possible contingency to be metduringinstallation,operation,andmaintenance. If further information
isdesired or if particular problems arise that are notcovered sufficiently for the purchaser’s purpose,
the matter should be referred to GE Interlogix, Gladewater, Texas, USA.
This documentcontains proprietary information of GEInterlogix, USA and is furnishedto its customer
solely to assist that customer in the installation, testing, operations, and/or maintenance of the
equipment described. This document shall not be reproduced in whole or in part nor shall its
contents be disclosed to any third party without the written approval of GE Interlogix.
Please refer to the current GE Interlogix product catalog for detailed warranty information.
Main800-727-2339Technical Support800-727-2339
Outside the US903-845-6941Tech Suppor t Fax903-845-8409
Main Fax903-845-6811Sales & Literature800-547-2556
Web:www.caddx.com
4.PROGRAMMING THE CONTROL ................................................................................................................................11
ENTERING THE PROGRAM MODE...........................................................................................................................11
SELECTING THE MODULE TO PROGRAM ............................................................................................................. 11
PROGRAMMING A LOCATION .................................................................................................................................11
EXITING A LOCATION................................................................................................................................................12
EXITING THE PROGRAM MODE...............................................................................................................................12
KEYPAD MAXIMUM WIRE RUN...............................................................................................................................48
16.LOCAL TELEPHONE COMPANY INTERFACE INFORMATION ......................................................................49
17.UNDERWRITERS LABORATORIES INFORMATION ..........................................................................................50
Indicates a procedure, practice, condition, or statement that, if not strictly
observed, could result in personal injury.
*
This symbol indicates electrical warnings and cautions.
Indicates a procedure, practice, condition, or statement that, if not strictly
observed, could result in damage to ordestruction of equipment orproperty.
**
This symbol indicates general warnings and cautions.
Indicates an essential or important procedure, instruction, condition, or
statement.
Tip
Indicates a user tip. Provides helpful information that is not normally defined
in regular use, but from an experienced user.
TheNetworX NX-8-CF represents a new approach to security systemsdesign. Drawingon ourexperiencein the world
marketas the largest exporter ofUSA manufactured controls, the NetworXseries is the most flexible,durable, and userfriendly control ever seen in our industry. Featuring sophisticated software, the NX-8-CF allows up to 99 users to
interface with 48 zones, 8 partitions, and a host of integrated fire, access, verification, and input/output modules, all
reported with the most comprehensive and fast SIA and Contact ID formats. The NetworX design allows a fully loaded
system to be housed in one singlemetal enclosure,establishingfor thefirst time,a logicalsolution anddesign response
to modular systems. Up to 32 modules can be added to expand the capabilities of the NX-8-CF. Please refer to the
current GE Interlogix product catalog for detailed warranty information.
2.ORDERING INFORMATION
Minimum system configuration for local and central station protected premise unit UL Commercial Fire
applications includes these individual modules:
PART #DESCRIPTIONMIN QTY
NX-8-CFNX-8-CF Co ntrol Only1 ea
NX-148E-CFAlphanumeric LCD Keypad for Commercial Fire applications (red plastic)2 ea
NX-870EFire Supervision Module1 ea
PART #DESCRIPTION
NX-8-CF-KITNX-8 COMMERCIAL FIRE KIT
Includes NX-8-CF Control, (2) NX-1 48E-CF LCD Keypads, NX-870E Fire Supervision &
16.5V, 50VA Transformer
Other available NetworX modules:
NX-216E16 Zone Expander Module
NX-320ESmart Power Supply and Buss Extender
NX-507ESeven Relay Module
NX-508E —Eight Output Module
NX-540E **"Operator" Telephone Interface Module
NX-580E **Cellemetry Interface
— These products are not approved for Commercial Fire use with the UL listed NX-8-CF.
** These products have not been tested and approved by Underwriters Laboratories, Inc.
location 40 prior to sending an alarm. To abort the report, type in acode
must be enabled in the
CF can be programmed to report AC failure and/or Low
Battery conditions to the central station. It can also be programmed to
iately upon detection of the condition. The AC
CF will beep the keypad sounder upon arming or
r is missing or a low battery has been detected.
be
arming or
disarming if the AC power is missing or a low battery has been detected.
digit codes to
same number of digits.
digit code, or
digit code. This code can then be used to enter
CF will Auto Arm at a specified time. At this
time, the keypad will beep for 50 seconds before the panel arms. If the
CF
tended if there is
activity in the building. The Auto Arming of a partition can be
programmed to be silent. If closing reports are sent, the user code will
If enabled, the Cancel and/or Abort features will be automatic (pressing
button is not required). The Cancel and Abort features, in
ed to permit this Auto
149Zone
Default OFF. Not for Commercial Fire use. Any delay shall not
When enabled, the control panel can automatically bypass interior
follower zones if an exit is not detected during the exit delay time. Entry
This feature will cause the panel to call the central station to report a
CF has four programmable outputs that can be used to
TERM
Abort
AC Fail
Low Battery
Report/Warning
AC Power
Low Battery
Sounder Alert
AC Power / Low
Battery Sounder
Alert
Arm / Disarm
Codes
Automatic Arming
DESCRIPTIONLOCPG
If enabled, the NX-8and press CANCEL. ADialer Delay@
ACharacteristic Select@ of locations 110-149.
The NX-8-
sound the keypad immed
failure report/warning can be delayed.
If enabled, the NX-8disarming if the AC powe
For UL Commercial Fire installations, this feature must
ENABLED.
If enabled, the NX-8-CF will beep the keypad sounder upon
The NX-8-CF can have 99 four-digit codes or 66 sixarm/disarm the control. All codes musthave the
The factory default for User #1 is 1234 when using a 4-
123456 for a 6-
the new arm/disarm codes.
If programmed, the NX-8-
40
110-149
37,
39
2318)
2318
4123
23,
22
30
21
18
Auto Cancel /
Abort
Automatic Bypass
Instant Arming
Auto Test
Auxiliary Outputs
arming process is stopped by typing a code on the keypad, the NX-8will attempt to arm 45minutes later. Thistime will beex
be 97.
For UL installations, this feature shall be DISABLED.
CANCEL
locations 23 and 40 respectively, must be enabl
feature to work. For proper operation of these features, ADialer Delay@
mustbe enabled in the ACharacteristic Select@ oflocations 110Types.
when too much current is drawn from anydevice powered by the system.
amper switch (see
terminaldrawing). The Box Tamper can be programmed to report and/or
sound the siren and/or the keypad. These terminals can be enabled or
in
amp voltage output through
off) the bypass
CF will send a "Cancel" report if when the system is
es of an
of
res two or more trips on azone or zones programmed
as "cross zones" within a specified time before reporting an alarm.
CF can be programmed to
CF can also be
to report an alarm after two or more tripson the same zone.
o three different phone
numbersfor dual, split or multiple reports selectablebyevent or partition.
nal
whenever the panel is armed or disarmed with this code. If open/close
CFcan be programmed to perform a Dynamic BatteryTest for
ed duration the first time the panel is armed or disarmed every
day. If the panel is not armed or disarmed during the day it will perform
CFcanalsobeprogrammedtoperforma
level arming mode has been developed to reduce the
,the
opening of any zones designated as "Entry Guard zone" will initiate the
sounder and start the entry delay before creating an alarm. All
other zones will function as normal. This arming mode will encourage
system owners to use their system more frequently when the premises
CF will send an "Exit Error Report" if an entry/exit
zone is faulted at the instant the exit delay expires. This report will be
sent along with the user number that armed the system, if the panel is
not disarmed before the entry delay expires. The alarm report will also
be sent. Even if this feature is not enabled, the siren will sound if any
Auxiliary Power
Overcurrent
Box Tamper
Built In Siren
Driver
Bypass Toggle
Cancel
Communication
Formats
Cross Zoning
DESCRIPTIONLOCPG
The NX-8-CF will display a "Servi
This condition can be reported to the central station.
The NX-8-CF has an input for a normally closed t
disabled in programming.
TheNX-8-CF has a built-in 112db siren driver.When desired,thisbuilt-
driver can be easily converted to a 1programming.
This feature will enable the end user to toggle (turnon or
of an interior zone with th e system armed by pressing BYPASS.
If enabled, the NX-8disarmed and the [Cancel] button is pressed within 5 minut
alarm. ADialer Delay@ must be enabled in the ACharacteristic Select@
locations 110-149.
The NX-8-CF can report in Contact ID or SIA formats.APPENDIX 144
This feature requi
3721
37,
39
3721
2318
2318
37,39,40,
21
21,
Dual/Split/
Multiple Reports
Duress Code
Dynamic Battery
Test
Entry-Guard
During the time between trips, the NX-8sound the keypad and/or the siren.The NX-8programmed
The NX-8-CF can send communication reports t
If a duress code is programmed the NX-8-CF will send a duress sig
reports are sent, the user code will be 254.
TheNX-8a select
thetest at midnight. The NX-8missing battery test every 12 seconds.
This unique lowmost common source of false alarms. When armed as AInstant@
keypad
are occupied.
110-149
4, 10,
16
4424
37, 4021
111-14930-32
30-32
15-17
For UL installations, this feature shall be DISABLED.
This feature allows a zone or zones to be automatically bypassed after a
specified number of alarms. When azone is tripped, the alarm ‘counter’
) alarm is detected in a different
zone, the counter remains at “1”.If an alarm is detected on a previously
tripped zone, the count increments to “2”. The ‘counter’ will increment
each time an alarm is detected on a zone with multiple trips. Bypassing
l occur on the zone that causes the count to equal the number
programmed in location 38; the‘counter’ will resetto zero(0); and begin
a new trip count where the next alarm will set the ‘counter’ to 1. If
alarms (and restores, if
enabled) will be sent asthey occur. If immediate restore isnot enabled,
a second or subsequent alarm will not be sent until the siren times out.
CF has a Telephone Line Monitor that monitors the voltage
and current of the telephone line for a detection of a faulted phone line.
tis
Out will bethe
same as Burglary (continuous).Otherwise, the Fire Siren will be
reporting). The number of the faulted zone(s) will be displayed on the
d into alarm memory and the internal
log. To exit at any time duringthis mode, enter a user code. Otherwise
CF will send a report to the central station when a wireless
sensor has detected a low battery or has not reported to the receiver.
CF will beep the keypad sounder
CF has 20 programmable Zone Types that determine how
all
f zone 2 is a Fire Zone in partition1, then zone 2 willbe a
Telephone Line
Monitor
Temporal Siren
Disable
DESCRIPTIONLOCPG
reflects “1” in memory. If a new (first
wil
immediate restore is enabled in location 37, the
For UL installations, this feature shall be DISABLED.
The NX-8This condition can also be reported to the central station. If the repor
enabled,only the Telephone Line Restore will be reported unless the NX870E is being used.
If disabled, the Fire Siren willbe steady and Fire Voltage
temporal.
37, 3821
37,39,4021-22
3721
User Code
Walk-Test Mode
Wireless Sensor
Missing/Low
Battery
Zone Bypassed
Sounder Alert
Zone Types
(Configurations)
For UL installations, this must be ENABLED.
A four- or six-digit entry code used to arm or disarm the system.
If enabled, entering
through zone test where all zones become silent and local (nonLCD keypad. It will also be entere
the AWalk-Test Mode@ will automatically exit after 15 minutes.
The NX-8The "Service Required" message will appear when either condition
exists.
If this feature is enabled, the NX-8-
upon arming if a zone is bypassed.
The NX-8-
each zone will function and report.
If any zone is programmed as a Fire Zone, that zone will be a Fire Zone in
partitions. (Example: I
Fire Zone in all partitions.)
CHIME followed by a user code will allow a walk-
Enters the Program Mode.
Prompts for the programming code.
[Go To Program Code]
Factory Default is
9713
If the "Go To Program Code" is valid, the LCD screen will
prompt for the device address to program.
Program Mode and ready to select the module.
Youarenowinthe
SELECTING THE MODULE TO PROGRAM
Since all modules connected to the NX-8-CF are programmed through the keypad, the module you are
programming should be the first entry.
ActionResult
0 #
PROGRAMMING A LOCATION
Once the number of the module to be programmed has been entered, the LCD screen will prompt you for a location
number. Any location can be accessed by directly entering the desired programming location followed by #.Ifthe
location ente red is a valid location, the top line of the LCD screen will display the location number on the left and the
segmentnumberon the right. The bottom line of the display will show thecurrentdata. This data will be displayed and
entered according to the type of data used (numerical, binary, or character data).
Programs the NX-8-CF Commercial Fire Panel
is the module number of the control and # is the entrykey.
Other module entry numbers can be found in their
corresponding manuals.
1.
NUMERICAL DATA
The top line of the display will show the current location number on the left and the segment number on the
right.The data will be displayed on the bottom line. The hexequivalentwill be shown in parenthesis. Tochange
the data in the currentlocation, enterthe number followedby .The datawill be enteredand thesegment will
be incremented by 1. The data for this segment will now be displayed. Continue this process until the last
segmentis programmed. When the last segment is reached, the keypad willprompt you for the nextlocation. If
you wish to exit this location before the last segment is reached, press #. This keypress will not save the
changes made to current segment, but will exit the location.
The top line of the display will show the current location number on the left and the segment number on the
right. The data will be displayed on the bottom line with the numbers 1-8in the first 8 characters. If thenumber
appears, this binary switch is on. If a minus sign (-) appears where the number should be, this switch is off.
Togglenumbers on or off using the corresponding number digit(1 to toggle 1; 8 to toggle8). Whenthe numbers
are in the desired state, enter . The data will be entered andthe segment will be incremented by 1. The data
for this segment will now bedisplayed. Continue this process until the last segment is programmed. When the
last segment is reached, the keypad willprompt for the next location. If youwish to exit thislocation before the
lastsegment is reached, press #. This keypress will not save thechanges made to current segment, but will exit
the location. “Shortcut Keys” shown in Numerical Data can also be used for Binary Data.
3.
CHARACTER DATA
Character Data is used to enter LCD text when programming. (Refer to the NX-148ECF instruction manual for
custom messages
data type. This information is programmedusing the bottom line ofthe display as a text editor. Once a character
location has been entered, the currentdata will bedisplayed on thebottom line. As is always the case, the top
line will displaythe current location and segment number. The five(5) function keys,as well as the upand down
arrowto the right of the display, are nowused to edit the message prior to saving it back to the location storage.
An underscore (_) in the display indicates the current cursor location.
feature.) Custom zone descriptions and messages are stored character or ASCII
Shortcut keys:
CANCEL
or
STAY
CHIME
EXIT
BYPASS
#
EXITING A LOCATION
ActionResult
Saves the data and exits that location.
You are now ready to program another location.
Saves character or word; moves cursor to right
Moves cursor to left.
Scrolls through available characters.
(In Library Mode) Scrolls through available words.
Tip: Refer to the NX-148ECF instructions for more details.
Inserts blank space.
Deletes characters.
Accesses the Library
Tip: Refer to the NX-148ECF instructions for more details.
Makes the character “flash”.
(In Library Mode) Makes the entire word “flash”.
Exits the edit mode.
Tip: The must be pressed or the data will not be saved.
Exits this program level. Advances to “Select a Module”.
Exits the programming mode entirely.
NX-8 Commercial Fire
Page 13
5.LOADING FACTORY DEFAULTS
ActionResult
Follow procedures on page 11 to enter the Program Mode.
910#
Keypad will beep 3 times (loading is in progress).The loading
takes about 6 seconds.
6.ENROLLING MODULES AND KEYPADS
For supervision purposes, the NetworX control panel has the ability to automatically find and store in its memory the
presenceof all keypads, zone expanders, wirelessreceivers, and any other moduleconnected to the dataterminal.This
allowsthese modules to be supervised by the control panel. NOTE:All modules should be connected and setto unique
addresses prior to enrolling modules. To enroll the modules, enter the Program Mode of the NetworX control panel.
When the Program Mode is exited,the control will enroll the devices. The enrollingprocess takes about12 seconds,
during which time the "Service Required" will be displayed. Once a module is enrolled, if it is not detected by the
control, the "Service Required@ will be displayed.
Please refer to the NX-148ECF installation manual for complete instructions on programming the keypads.
7. QUICK START INSTALLATION
For most routine installations, the "Quick Start" option will allow for enabling a majority of the options available with the
NX-8-CF, when communicating in Contact ID orSIA formatsand withoutpartitioning. The "QuickStart" locations can
(20segments, numerical data) The first telephone number is programmed in location0. A "14" indicates the end of the
phonenumber. Delays of four seconds can be programmed a t any point in the phone numberby programming a "13" in
the appropriate segment. If tone dialing is desired, program a"15" in the segment where tone dialing should begin. Ifthe
entire number should be tone dialing, program a "15" in the first segment. Program an A11"for a Ar@, and a A12" for a
A#@.
LOCATION 1 - ACCOUNT CODE FOR THE PHONE #1
(6segments, numerical data) The account code sent when Phone #1 isdialedis programmed in location 1.Program a
A10"in the segment immediately after the last digit of the account code. If theaccount code is 6 digitslong, programall
6 segments.
LOCATION 2 - COMMUNICATOR FORMAT FOR PHONE #1
(1 segment, numerical data) Location 2 contains the communicator format used to transmit to the receiver connected
toPhone #1. Consult the instructions for your central station receiverto determine whichformat iscompatible. Select a
format from the list on thefollowing page. Ifthis location contains a"0", the built-incommunicator will bedisabled, and
the NX-8-CF will function as a local only control.
LOCATION 3 - DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE # 1
(2 segments, numerical data) Segment1-Dialattempts:Location 3,Segment 1 is used to enterthe number of dial
attempts (1 to 15 Attempts) the communicator will make to Phone #1 before ending the notification process. Factory
default is "8" and the com municator will m ake eight (8) attempts to the first number.
Segment 2- Phone #1 Backup Control: Programming a "0" in Segment 2 of this location will cause the NX-8-CF to
make the designated number of attempts to Phone #2 before setting the "Fail To Communicate" condition and stop
reporting.Programming a "1" in this segment will cause the NX-8-CF to stop trying to communicate afterthe designated
number of attempts have been made to Phone #1. If a "2" is programmed in this segment, it will cause t he NX-8-CFto
make the dial attempts in increments of two. T he firsttwo attempts will be madeto Phone #1, thenext two attempts to
Phone #2, then repeating until the total number of attempts designated in Segment 1 is completed.
Table 8-1FORMAT SELECTIONS
DATAFORMATDESCRIPTION
0LocalCommunicator is disabled
1 - 6Reserved
7SIA with Area ModifierSends the area modifier with events associated with a partition. The
receiver must be able to accept this modifier.
8 - 12Reserved
13Contact IDContact ID - DTMF (see pages 51-52)
14SIAFSK (see pages 51-52)
15Reserved
REPORTING EVENTS TO PHONE NUMBER 1
Phone #1 has two programming locations that are used to select which events are reported to this phone number.
Location 4 is used to select which events are reported to Phone #1. Location 5 is used to select which partitions are
reported to Phone #1. If dual or split reporting is not desired, location 4 should be used to select all events to Pho ne
#1 and location 5 should be left at thefactory default of "0". If dual orsplit reporting is desired, and the splitis based on
the event type (such as alarm, open/close, etc.), location4 should be used to select only those events that should be
reported to Phone #1 and location 5 should be left at the factory default of "0". If dual or split reporting is desired, and
the split is based onpartition, location 4should beprogrammed as a"0" and location5 shouldbe used to select those
partitions that should be reported to Phone#1. If no eventsshould be reported to Phone #1, both locations shouldbe
programmed as "0" (disabling all options).
1 = Alarms and Alarm Restores.
2 = Opening and Closings.
3 = Zone Bypass and Bypass Restores.
4 = Zone Trouble and Trouble Restores.
5 = Power Fail, Low Battery, Power Restore, and Low Battery Restore.
6 = Bell Cut, Telephone Line Cut, Bell Cut Restore, Telephone Line Restore.
7 = Test Reports.
8=Start and End programming.
Segment 2
1 = Zone and Box Tamper and Tamper Restore.
2 = Auxiliary Power Overcurrent, Ground Fault, and Restore for both.
3 = Wireless Sensor Missing and Restore.
4 = Wireless Sensor Low Battery and Restore.
5 = Expander Trouble and Restore.
6 = Fail To Communicate.
7 = Reserved.
8 = Reserved.
LOCATION 5 - PARTITIONS REPORTED TO PHONE #1
(1 segment, feature selection data) Location 5 is used when events to be reported to a phone number are based upon
the partition regardless of the event. If this location is used, location 4 should be programmed as "0".
(20 segments, numerical data) Phone #2 is programmedin location 6. A "14" indicates theend of thephone number.
Delaysof four seconds can be programmed at any point inthe phone number by programminga "13" in theappropriate
segment. If tone dialing is desired, program a "15" in the segmentwhere tone dialing should begin. Ifthe entire number
should be tone dialing, program a "15" in the first segment. Program an A11" for a Ar@, and a A12" for a A#@.
LOCATION 7 - ACCOUNT CODE FOR THE PHONE #2
(6segments of numerical data) The account code sent when Phone #2is dialedis programmedin location7. Program
a A10" in the segment immediately after the last digit of the account code. If the account code is6 digits long, program
all 6 segments. If this location is left unprogrammed, account code 1 will be used when the second phone number is
dialed.
LOCATION 8 - COMMUNICATOR FORMAT FOR PHONE # 2
(1 segment, numerical data) Location 8contains the communicator format usedto transmit to thereceiver connected to
Phone #2. Consult the instruction manual for your central station receiver to determine which format is compatible If
this location contains a "0", Phone #3 will use the same format programmed for Phone #1 in Location 2.
LOCATION 9 - DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE #2
(2 segments, numerical data)
Segment 1, Dial attempts
Segment 1 of Location 9 is used to enterthe number of dial attempts (1 to 15 attempts) thecommunicator will
make to Phone #2 before ending the notification process. Factory default is "0" and the communicator will
make the same number of attempts as those programmed in location 3.
Programming a "0" in Segment 2 of this location will cause the NX-8-CF to make the designated number of
attempts to Phone #1before setting the "FailTo Communicate"condition and stop reporting. Programming a
"1" in this segment will cause the NX-8-CF to stop trying to communicate after the designated number of
attempts have been made to Phone #2. If a "2" is programmed in this segment, it will cause the NX-8-CF to
make the dial attempts in increments of two. The first two attempts will be made to Phone #2, the next two
attemptsto Phone #1, then repeating until the totalnumber of attempts designated in Segment 1is completed.
REPORTING EVENTS TO PHONE NUMBER 2
Phone#2 can be used to back up Phone #1 or for a second receiver to multi-report or splitreport events. Phone #2 has
twoprogramming locations that are used to select which events are reportedto this phone number.Location 10 is used
to select which events are reported to Phone #2, and location 11 is used to select which partitions are reported to
Phone #2. If dual or split reporting is not desired, location 10 and location 11 should be left at the factory default of "0".
If multi-reporting or split reporting is desired, and the split is based on the event type (such as alarm, open close etc.),
location 10 should be used to select only those events that should be reported to Phone #2, and location 11 should be
left at thefactory default of "0". If dual orsplit reporting is desired, and the split is based on partition, then location 10
should be programmed as "0",and location 11should beused toselect those partitionsthat shouldbe reported tothe
Phone #2. If no events should be reported to Phone #2, both locations should be "0".
LOCATION 10 - EVENTS REPORTED TO PHONE #2
(2 segments of feature selection data)
Segment 1
1 = Alarms and Alarm Restores.
2 = Opening and Closings.
3 = Zone Bypass and Bypass Restores.
4 = Zone Trouble and Trouble Restores.
5 = Power Fail, Low Battery, Power Restore, and Low Battery Restore.
6 = Bell Cut, Telephone Line Cut, Bell Cut Restore, Telephone Line Restore.
7 = Test Reports.
8 = Start and End programming.
Segment 2
1 = Zone and Box Tamper and Tamper Restore.
2 = Auxiliary Power Overcurrent and Ground Fault and Restore for both.
3 = Sensor Missing and Restore.
4 = Sensor Low Battery and Restore.
5 = Expander Trouble and Restore.
6 = Fail To Communicate.
7 = Reserved.
8 = Reserved.
LOCATION 11 - PARTITIONS REPORTED TO PHONE #2
(1 segment, feature selection data) Location 11 is used when eventsto be reported to a phone number are basedupon
the partition regardless of the event. If this location is used, location 10 should be "0".
(20segments, numerical data) Phone #3 is programmed in location 12. A "14" indicates the end of the phone number.
Delaysof four seconds can be programmed at any point inthe phone number by programming a "13" in the appropriate
segment. If tone dialing is desired, program a "15" in the segmentwhere tone dialing should begin. Ifthe entire number
should be tone dialing, program a "15" in the first segment. Program an A11" for a Ar@, and a A12" for a A#@.
(6segments, numerical data) The account code sent when Phone #3 isdialed is programmed in location 13. Program
a A10" in the segment immediatelyafter the lastdigit of the accountcode. If the account codeis 6 digits long,program
all 6 segments. If location 6 is left unprogrammed, account code 1 will be used when the Phone #3 is dialed.
LOCATION 14 - COMMUNICATOR FORMAT FOR PHONE #3
(1 segment, numerical data) Location 14 contains the communicator format used to transmit to the receiver connected
tophone #3. Consult the instruction manual for your central stationreceiverto determinewhich format is compatible. If
this location contains a "0", Phone #3 will use the same format programmed for Phone #1 in Location 2.
LOCATION 15 - DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE #3
(2 segments, numerical data)
Segment 1, Dial Attempts
Segment1 of Location 15 is used to enter thenumber of dial attempts (1 to 15 attempts)the communicator will
try to Phone #3 beforeending thenotification process. Factory default is "0"and thecommunicator willmake
the same number of attempts as those programmed in location 3.
Segment2,Phone#3Backup Control
Programming a "0" in Segment 2 of this location will cause the NX-8-CF to make the designated number of
attempts to Phone #2before setting the "FailTo Communicate"condition and stop reporting. Programming a
"1" in this segment will cause the NX-8-CF to stop trying to communicate after the designated number of
attempts have been made to Phone #3. If a "2" is programmed in this segment, it will cause the NX-8-CF to
make the dial attempts in increments of two. The first two attempts will be made to Phone #3, the next two
attemptsto Phone #2, then repeating until the totalnumber of attempts designated in Segment 1is completed.
REPORTING EVENTS TO PHONE NUMBER 3
Phone #3can be used for a third receiver tomulti-report or split reportevents. Phone #3 hastwo programming locations
that are used to select which events are reported to this phone number. Location 16 is used to select which events are
reported to Phone #3, and Location 17 is used to select which partitions are reported to Phone #3. If dual or split
reporting is not desired, location 16 and location 17 should be left at the factory default of "0". If multi-reporting or split
reporting is desired, and thesplit is basedon theevent type (suchas alarm,open/close, etc.), thenlocation 16 should
be used to select only those events that should be reported to Phone #3 and location 17 should be left at the factory
default of "0". If dual or split reporting is desired, and the split is based on partition, then location 16 should be
programmed to "0" and location 17 should be used to select those partitions that should be reported to Phone #3. If no
events should be reported to Phone #3, both locations should be "0".
LOCATION 16 - EVENTS REPORTED TO PHONE #3
(2 segments, feature selection data)
Segment 1
1 = Alarms and Alarm Restores.
2 = Opening and Closings.
3 = Zone Bypass and Bypass Restores.
4 = Zone Trouble and Trouble Restores.
5 = Power Fail, Low Battery, Power Restore, and Low Battery Restore.
6 = Bell Cut, Telephone Line Cut, Bell Cut Restore, Telephone Line Restore.
7 = Test Reports.
8 = Start and End programming.
Segment 2
1 = Zone and Box Tamper and Tamper Restore.
2 = Auxiliary Power Overcurrent and Ground Fault and Restore for both.
3 = Sensor Missing and Restore.
4 = Sensor Low Battery and Restore.
5 = Expander Trouble and Restore.
6 = Fail To Communicate.
7 = Reserved.
8 = Reserved.
LOCATION 17 - PARTITIONS REPORTED TO PHONE #3
(1 segment, feature selection data) Location 17 is used when eventsto be reported to a phone number are basedupon
the partition regardless of the event. If this location is used, location 16 should be "0".
LOCATION 23 - PARTITION 1, FEATURE AND REPORT SELECTIONS
(3segments, feature selection data) Location23 is used to enable certain features that can be accessed or are visible
to the user from the keypad of thesystem. In addition, certain communicator reports are enabled inlocation 23. Each
of these features can be enabled bypartition. For additional partition informationsee locations 88-109. If the feature
selection location for an y partition is left blank, that partition will use this location for the feature selection.
This location contains 3 segments of 8 features each. (Refer to GLOSSARY on page 6.)
Segment 1
1 = On enables the Quick Arm feature.
2 = On enables the Re-exit feature.
3 = On enables the Automatic Bypass feature.
4 = On enables the Silent Keypad Panic feature (overrides the audible panic selection).
5 = On enables the Audible Keypad Panic feature.
6 = On enables the Keypad Aux 1 feature (FIRE).
7 = On enables the Keypad Aux 2 feature (AUXILIARY).
8 = On enables the Keypad Multiple Code Attempt Tamper feature.
Segment 2
1 = On enables the LED Extinguish feature.
2 = On enables the Require Code for Bypassing feature.
3 = On enables the Zone Bypassed Sounder Alert feature.
4=Reserved
5 = On enables Bypass toggle.
6 = On enables Silent Auto Arm.
7 = On enables the Automatic Instant feature.
8 = Reserved.
Segment 3
1 = On enables Opening and Closing reports.
2 = On enables Zone Bypass reporting.
3 = On enables Zone Restore reporting. Factory default is on.
4 = On enables Zone Trouble reporting. Factory default is on.
5 = On enables Zone Tamper reporting.
6 = On enables the Cancel reporting.
7 = On enables the Recent Closing report.
8 = On enables the Exit Error report.
LOCATION 24 - ENTRY / EXIT TIMERS
(4 segments, numerical data) Location 24 is used to program the Entry/Exit times. There are 2 separate Entry/Exit
times.
Segment 1,Entry time 1:This is the entry time that will be used when a delay 1 zone type initiates an entry
delay. Valid entries are 10-255 seconds.
Segment 2,Exit time 1:Thisis the exit time that will be used for all zones designated as delay 1. Valid entries
are 10-255 seconds.
Segment 3,Entry time 2:This is the entry time that will be used when a delay 2 zone type initiates an entry
delay. Valid entries are 10-255 seconds.
Segment 4,Exit time 2:Thisis the exit time that will be used for all zones designated as delay 2. Valid entries
are 10-255 seconds.
A trip will startentry delay1. The lackof a trip during exit delay will enablethe
This zone will be instant when the system is armed
and no entry or exit delays are being timed. It is delayed during entry and exit delay times. This zone will
Thiszone will be instant when the system
is armed and no entry or exit delay is being timed. It is delayed during entry and exit delay times. This
el. It
Thiszone will light the Fire LED and sound the temporal siren each time thezone is shorted.Itwill
as a Fire Zone, that zone will be a Fire Zone in all partitions. (i.e. if zone 2 is a Fire Zone in partition 1,
elay will enable the
Creates an instant silent alarm regardless of the armed state of the
will arm and disarm the partition or partitions of the control panel
will b e instant when the system
is armed and no entry or exit delay is being timed. It is delayed during entry and exit delay times. If a
"Cross Zone" is not being timed it will start a "Cross Zone"timer. If a "Cross Zone" is being timed it will
Thiszone creates an instant alarm whenever it istripped and theStay LED
Atrip will start entry delay1. This zone will
bypass when the "Group Bypass"command is entered at the keypad. Thelack of a tripduring exit delay
Thiszone will be instant when the system
Thiszone
will bypass when the "Group Bypass" command is entered at the keypad. This zone will automatically
A trip will start entry delay 1. The lack of a trip
This zone type
This zone will be instant
d during entry and exit
Thiszone type
neverit is tripped and the
A trip will start entry delay 2. The lack of a trip
This zone type
All Fire zones are pre-programmed for UL settings.
Zones can be programmed to be one of twenty different zone types (configurations). Zone types # 17 - 20 can be used
for wireless or hardwired zones using European double EOL configuration. The default zone types are listed below.
These zone types can be customized by programming locations 110-149.
Table 9-1DEFAULT ZONE TYPES
DATADESCRIPTION
1DAY ZONE - Instant when system is armed trouble zone when system is disarmed.
224-HOUR AUDIBLE - Creates an instant yelping siren alarm regardless of the armed state of the panel.
3
4
5
6INSTANT - This zone creates an instant alarm whenever it is tripped and the Armed LED is on.
7
8
ENTRY/EXIT DELAY 1-
Automatic Bypass or Instant mode if so programmed.
FOLLOWER WITH AUTO- BYPASS DISABLED -
not automatically bypass even if enabled in Segment 1 of Location 23.
INTERIOR FOLLOWER WITH AUTO- BYPASS ENABLED -
zone will automatically bypass if enabled in Segment 1 of Location 23.
24 HOUR SILENT - Createsan instant silent alarmregardless of thearmed state of thecontrol pan
will not display on the keypad.
FIRE -
alsorapidly flash the Fire LED indicating a trouble if the zone is open. NOTE: If anyzone is programmed
then zone 2 will be a Fire Zone in all partitions.)
9
10
11
12
13
14
15
16SUPERVISORY - This zone creates an instant Sprinkler Supervisory report.
17
18
19
20
NX-8 Commercial Fire
ENTRY/EXIT DELAY 2- A trip will start entrydelay 2. The lack ofa tripduring exitd
Automatic Bypass or Instant mode if so programmed.
24-HOUR SILENT SUPERVISED-
control panel. It will display on the keypad.
KEYSWITCH ZONE - This zone type
that it resides in each time the zone is shorted. Keyswitch arming will report as user #99.
INTERIOR FOLLOWER WITH "CROSS ZONE" ENABLED -This zone
create an instant alarm. This zone will automatically bypass when enabled in Segment 1 of Location 23.
INSTANTENTRY GUARD -
is off. It will start an entry delay time 2 if it is tripped and the system is armed and the Stay LED is on.
ENTRY/EXIT DELAY1 WITH GROUP BYPASSENABLED -
will enable the Automatic Bypass or Instant mode if so programmed.
INTERIOR FOLLOWER WITH GROUP BYPASS ENABLED -
isarmed and no entry or exit delays are being timed. It isdelayed duringentry/exitdelaytimes.
bypass if enabled in Segment 1 of Location 23.
ENTRY/EXIT DELAY 1 WITH TAMPER ENABLED-
during exit delay will enable the Automatic Bypass or Instant mode if so programmed.
can be used to enable tamper on a wireless transmitter.
INTERIOR FOLLOWER WITH TAMPER AND AUTO-BYPASS ENABLED -
when the system is armed and no entry or exit delay is being timed. It is delaye
delaytimes. This zone will automatically bypass if enabled in Segment 1 of Location 23.
can be used to enable tamper on a wireless transmitter.
INSTANT WITH TAMPER ENABLED - Thiszone creates an instant alarm whe
Armed LED is on. This zone type can be used to enable tamper on a wireless transmitter.
ENTRY/EXIT DELAY 2 WITH TAMPER ENABLED-
during exit delay will enable the Automatic Bypass or Instant mode if so programmed.
can be used to enable tamper on a wireless transmitter.
(8 segments, numerical data) Location 25 contains the Zone Type for zones 1-8. Segment 1 is for zone 1, and
Segment8 is for zone 8. Default Zone Types are found in Table 9-1 onpage 19. To customize a Zone Type, see page
29.
LOCATION 26 - PARTITION SELECT, ZONES 1-8
(8 segments, feature selection data) Location 26 is used to select the partition(s) that zones 1 - 8 reside in. A zone
may reside in any combination of the 8 partitions. If a burglary zone resides in more than 1 partition, it will only be
active when all partitions it resides in are armed. A zone that resides in more than 1 partition willbe reported to
its lowest partition. Location 26 has 8 segments.Segment 1 correspondsto zone1, and Segment 8corresponds to
(8 segments, numerical data) Location 27contains the Zone Type for zones 9 -16. Segment 1 is for zone9, Segment
8 is for zone 16. Default Zone Types are found in Table 9-1 on page 19. To customize a Zone Type, see page29.
LOCATION 28 - PARTITION SELECT, ZONES 9-16
(8 segments, feature selection data) Location 28 is used to select the partition(s) that zones 9-16reside in. A zone may
reside in any combination of the 8 partitions. If a burglary zone resides in more than 1 partition, it will only be
active when all partitions it resides in are armed. A zone that resides in more than 1 partition willbe reported to
its lowest partition. Location 28 has 8 segments. Segment 1 corresponds to zone 9 and Segment 8 corresponds to
(8 segments, numerical data) Location 29 contains the Zone Typefor zones 17-24. Segment 1is for zone 17,Segment
8 is for zone 24. Default Zone Types are found in Table 9-1 on page 19. To customize a Zone Type, see page 29.
LOCATION 30 - PARTITION SELECT, ZONES 17-24
(8 segments, feature selection data) Location 30 is used to select the partition(s) that zones 17-24 reside in. A zone
may reside in any combination of the 8 partitions. If a burglary zone resides in more than 1 partition, it will only be
active when all partitions it resides inare armed. A zone that resides in more than 1partition will be reported
to its lowest partition. Location 30 has 8 segments. Segment 1 corresponds to zone 17 and Segment 8corresponds
(8 segments, numerical data) Location 31 contains the Zone Typefor zones 25-32. Segment 1is for zone 25,Segment
8 is for zone 32. Default Zone Types are found in Table 9-1 on page 19. To customize a Zone Type, see page 29.
(8 segments, feature selection data) Location 32 is used to select the partition(s) that zones 25-32 reside in. A zone
may reside in any combination of the 8partitions. If a burglary zone resides in more than 1 partitionit will only be
active when all partitions it resides in are armed. A zone that resides in more than 1 partition willbe reported to
its lowest partition. Segment 1 corresponds to zone 25 and Segment 8 corresponds to zone 32.
(8 segments, numerical data) Location 33 contains the Zone Type for zones 33-40. Segment 1 is forzone 33 Segment
8 is for zone 40. Default Zone Types are found in Table 9-1 on page 19. To customize a Zone Type, see page 29.
LOCATION 34 - PARTITION SELECT, ZONES 33-40
(8 segments, feature selection data) Location 34 is used to select the partition(s) that zones 33-40 reside in. A zone
may reside in any combination of the 8 partitions. If a burglary zone resides in more than 1 partition, it will only be
active when all partitions are armed. A zone thatresides in more than1 partition will be reported to its lowest
partition. Segment 1 corresponds to zone 33 and Segment 8 corresponds to zone 40.
(8segments, numerical data) Location35 contains the Zone type for zones 41-48. Segment 1 is for zone 41 Segment
8 is for zone 48. Default Zone Types are found in Table 9-1 on page 19. To customize a Zone Type, see page 29.
LOCATION 36 - PARTITION SELECT, ZONES 41-48
(8 segments, feature selection data) Location 36 is used to select the partition orpartitions that zones 41-48 reside in.
A zone may reside in any combination of the 8 partitions. If a burglary zone resides in more than 1 partition itwill
only be active when all partitions are armed. A zone that resides in more than 1 partition will be reported to its
lowest partition. Location 36 has 8 segments. Segment 1 corresponds to zone 41 and Segment 8 corresponds to
(5 segments, feature selection data) Location 37 is used to enable various system feature and reporting options.
(Refer to GLOSSARY on page 6.)
Segment 1
1 = On if siren sounds for "Telephone Line Cut" when armed.
2 = On if siren sounds for "Telephone Line Cut" when disarmed.
3 = On if siren blast at arming.
4 = On if siren blast at exit expiration.
5 = On if siren blast at closing kissoff.
6 = On if siren sounds during a "Cross Zone" verification time.
7 = On if siren sounds for a Zone or Box Tamper.
8 = On if siren blasts 1 time for keyswitch or wireless arming; 2 times for disarming.
1 = On if siren driver should be a voltage output. Off if on board siren driver enabled.
2 = On if siren sounds for expander trouble (required for UL installations).
3 = On for Immediate Restore by zone. Off for zones to restore only when siren is off.
4 = On if Dynamic Battery Test performed at arming. Off if performed at disarming. (Loc. 40)
5 = On if Battery Missing Test is performed every 12 seconds.
6 = On if Manual Bell Test performed during [r]-[4] test function.
7 = On if Manual Communicator Test performed during [r]- [4] test function.
8 = On if Box Tamper terminals on the control panel are enabled.
Segment 3
1=OnifBox Tamper report enabled.
2=OnifAC Fail reporting enabled.
3 = On if Low Battery reporting enabled.
4 = On if Aux. Power Overcurrent report enabled.
5 = On if Siren Supervision report enabled.
6 = On if Telephone Line Cut report enabled.
7 = On if Ground Fault Detection report enabled.
8 = On if Expander Trouble reporting enabled.
Segment 4
1 = On if Fail To Communicate report enabled.
2 = On if Log Full report enabled.
3 = On if Autotest report enabled.
4 = On if Start/End programming report enabled.
5 = Reserved.
6 = On if Sensor Low Battery report enabled.
7 = On if Sensor Missing report enabled.
8 = Reserved.
Segment 5
1 = On enables Lost Clock “Service Required” message.
2=Reserved
3 = On disables On-Board 8 zones.
4 = On will allow two trips on same cross-zone to activate an alarm.
5 = On will not allow zones that are force armed to report bypass.
6 = On enables Silent Exit option.
7 = Use internal crystal for clock.
8 = Disable Temporal Siren on Fire. NOTE: DO NOT disable for UL listed systems.
LOCATION 38 - SWINGER SHUTDOWN COUNT
Location 38 containsthe number of trips duringan arming cycle that theNX-8-CF will allow before bypassing a zone.
The count determination is described in the GLOSSARY on page 6. NOTE: For UL installations, this feature shall
be disabled.
LOCATION 39 - KEYPAD SOUND ER CONTROL
(1 segment, feature selection data)
Segment 1
1 = On if keypad sounds for ATelephone Line Cut@ when the system is armed.
2 = On if keypad sounds for ATelephone Line Cut@ when disarmed.
3 = On if keypad sounds upon AC Power Failure.
4 = On if keypad sounds when a Low Battery is detected.
5 = On if keypad sounds during Cross Zone trip time.
6 = On if keypad sounds for zone and box tampers.
7 = Reserved.
8 = On if keypad sounds for expander trouble (required for UL installations).
LOCATION 40 - SYSTEM TIMERS
(10 segments, numerical data) Location 40 contains the duration of varioussystem timing functions. Example: If you
desirethe duration of the Dynamic Battery Test to be 30 m inutes, program [3]-[0]-[r] in segment 1 of this location. The
[3]-[0] is the number of minutes, and the [r] stores the data and moves to the next segment of this location.
Segment 1Dynamic Battery Test duration in minutes 0-255 minutes ("0" = no test)
The "Dynamic Battery Test" feature cannot exceed four (4) hours. The dial delay shall be set to -0-.
Segment 2AC Fail report delay in 0-255 hours.
Segment 3Power Up Delay in seconds 0-60 seconds ("0" = no power up delay).
Segment 4Siren Time in minutes 1-255 minutes.
Segment 5Telephone Line Cut delay in seconds 10-175 seconds.
Segment 6Cross Zone time in minutes 0-255 ("0" = no cross zoning).
Segment 7Chimetime in 50 mS (1/20th second) increments from 0-12 seconds ("0" = f ollows zone255 latched).
Segment 8Dial delay in seconds 0-255 seconds (“0 ” = no abort delay).
Segment 9FireAlarm Verification time in seconds 120-240 seconds ("0" = no firealarm verification). NOTE: This
feature is not approved for residential use in California.
Segment 10Reserved
LOCATION 41 - SPECIAL FEATURES
(1 segment, feature selection data)
Segment 1
1=Reserved
2=Reserved
3 = Enable Auto Cancel / Abort (Refer to GLOSSARY on page 6.)
4 = Enable Walk-Test Mode (Refer to GLOSSARY on page 6.)
5-8 Reserved.
LOCATION 42 - GO TO PROGRAM CODE
(6 segments, numerical data) Location 42 contains the"Go To Program Code". This location contains either a 4or 6digit code. If the 6-digit code option is enabled in Location 41, THIS CODE MUST CONTAIN SIX (6) DIGITS. If this
optionis not enabled in location 41, the last 2 segments(digits) will be ignored. Withthe NX-8-CF disarmed, the"Go To
Program Code" can be used to enter the Program Mode.
LOCATION 43 - GO TO PROGRAM CODE PARTITION AND AUTHORIZATION
(2segments, feature selection) The "Go To Program Code" can be used as a standard arm/disarm code. When using
the code to arm or disarm, the user ID is 255. (This code may not be changed in the Run Mode.)
Segment 1
1 = Reserved.
2 = On enables "Go To Program Code" as an arm only code.
3 = On enables "Go To Program Code" as an arm only after closing.
4 = On enables "Go To Program Code" as a master arm/disarm code (can change user codes)
5 = On enables "Go To Program Code" as an arm/disarm code.
6 = On enables "Go To Program Code" to bypass zones.
7 = On enables "Go To Program Code" opening and closing reports.
8 = Reserved.
1 = On enables the "Go To Program Code" for Partition #1.
2 = On enables the "Go To Program Code" for Partition #2.
3 = On enables the "Go To Program Code" for Partition #3.
4 = On enables the "Go To Program Code" for Partition #4.
5 = On enables the "Go To Program Code" for Partition #5.
6 = On enables the "Go To Program Code" for Partition #6.
7 = On enables the "Go To Program Code" for Partition #7.
8 = On enables the "Go To Program Code" for Partition #8.
LOCATION 44 - DURESS CODE
(6 segments, numerical data) Location 44 containsthe Duresscode. This Location contains either 4 or 6digits. If the
6-digit code option is enabled in Location41, THIS CODE MUSTCONTAIN SIX (6) DIGITS. If the 6-digit option is not
enabled in location 41, the last 2 digits will be ignored. If programmed, the duress code will work for all partitions.
LOCATION 45 - OUTPUTS 1-4 PARTITION SELECTION
(4segments, feature selection data) Location 45 is used toselect whichpartition(s)the eventsmustoccur in beforethe
output will activate. Location 45 has 4 segments. Segments 1 and 2 correspond to relays/outputs 1 and 2, while
segments 3 and 4 correspond to auxiliary outputs 3 and 4.
(4segments, feature selection data) Location 46 contains special timing feature activation foroutputs 1 - 4. Segments
1 and 2 correspond to relays/outputs 1 and 2, while segments 3 and 4 correspond to auxiliary outputs 3 and 4.
Segments 1 - 4
1 = On if output should be timed in minutes; Off if timed in seconds.
2 = On if output should latch; Off if output should be timed.
3 = On if output should stop timing upon code entry;Off if the output should continue to time upon code entry.
4 = On if output should only activate between the closing and opening time in loc. 52 & 53.
5 = On if output should only activate between the opening and closing time in loc. 52 & 53.
6 = On if output should be inverted (0 volts going to 12 volts when activated).
7 = Reserved.
8 = Reserved.
LOCATION 47 – RELAY / OUTPUT #1, EVENT AND TIME
(2 segments, numerical data)
Segment 1:Use Table 9-2 on page 25 to select the event that will activate output relay/output 1.
Segment 2:Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 1,
Location 46). Programming a "0" makes the relay/output follow the event.
LOCATION 48 – RELAY / OUTPUT #2, EVENT AND TIME
(2 segments, numerical data)
Segment 1:Use Table 9-2 on page 25 to select the event that will activate output relay/output 2.
Segment 2:Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 2,
Location 46). Programming a "0" makes the relay/output follow the event.
LOCATION 49- OUTPUT #3, EVENT AND TIME
(2 segments, numerical data)
Segment 1:Use Table 9-2on page 25 to select the event that will activate output 3.
Segment 2:Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 3,
Location 46). Programming a "0" makes the output follow the event.
Segment 1:Use Table 9-2 on page 25 to select the event that will activate output 4.
Segment 2:Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 4,
Location 46). Programming a "0" makes the output follow the event.
Table 9-2 AUXILIARY OUTPUT EVENT SELECTION
DATAEVENTDATAEVENT
0/Burglary Alarm26Fire Trouble
1/Fire Alarm27Chime
2/24 Hour Alarm28/Expander Trouble
3/Trouble Alarm29Dynamic Battery Test Time
4/Tamper Alarm30Open Period
5Yelping Siren (Burglary)31Closed Period
6Temporal Sir en (Fire)32Reserved
7Any Siren33Line Seizure
8Any Bypass34Ground Start
9AC Fail35Fail To Communicate
10Low Battery36Telephone Line Fault
11/Duress37Program Mode
12/Aux 1 Keypad Zone38Reserved
13/Aux 2 Keypad Zone39Ground Fault
14/Panic Keypad Zone40Short Circuit (Over-current)
15Keypad Tamper41Box Tamper
16/Autotest42Siren Tamper
17Alarm Memory43Any Open
18Entry44Any Short
19Exit45Any Fault (Open/ Short on Non-Fire Zone)
20Entry or Exit46/Any Alarm
21Armed State47Beeping Keypad
22Disarmed State48/Code Entry (See note below)
23Ready49 ˜/Key FOB Function 1
24Not Ready50 ˜/Key FOB Function 2
25Fire
˜ Events 49 & 50 require NX-408, NX-416, or NX-448 wireless receivers to operate.
/ If set to follow condition, these events will be 1 second.
Notes : When Event 48 is programmed, it is possible to programa user code's authorization toselect which output(s) a
particular code will activate. (Refer to “Assigning User Authority” in the NX-148ECF installation manual.)
LOCATION 51 - AUTOTEST CONTROL
(4 segments, numerical data)
Segment 1:Program a "1"if the intervalis to bein hours;Program a "0"if indays. Add a A2"to suppre ss thedaily
test or a A3" to suppress the hourly test if any report has been sent.
Segment 2:Program the Autotest interval from 1-255 hours/days.
Segment 3:Program the Autotest report hour in24-hour format (if the interval is in hours,thissegment is ignored).
Segment 4:Program the Autotest report time, number of minutes after the hour.
LOCATION 52 - OPENING TIME
(2 segments, numerical data) Location 52 contains the timein 24 hour format the NX-8-CF enables codes designated
as arm only after closing. This time is only valid on those days programmed in location 54.
Opening time must be earlier than closing timefor Auto Arm, Relays, Auxiliary Outputs, or Code Authorization
to function properly.
Segment 1:Program the hour of the opening time.
Segment 2:Program the minutes after the hour of the opening time.
(2 segments, numerical data) Location 53 contains the time in 24 hour format the NX-8-CF disables the disarm
capabilityfor codes designated as armonly after closing. This isalso the time the Automatic Arming sequence will begin
(if enabled in location 55).
Opening time must be earlier than closing timefor Auto Arm, Relays, Auxiliary Outputs, or Code Authorization
to function properly.
Segment 1:Program the hour of the closing / auto arm time.
Segment 2:Program the minutes after the hour of the closing / auto arm time.
LOCATION 54 - DAYS OF THE WEEK EACH PARTITION IS OPEN
(8 Segments, feature selection data) Location 54 selects which days of the week each partition is open. On these
days, Aarm only after close window@ codes will be able to arm and disarm during open window.
If any partition is not programmed to be opened and is programmed to Auto-Arm (Location 55), the NX-8-CF
will try to arm every 45 minutes for the duration of the closed period.
On days not selected here, Aarm only after close window@ codes will not disarm. Segment 1 is for partition 1, and
segment 8 is for partition 8 . (Locations 52 and 53 for the opening and closing times for the open days.)
Segment 1-8
1 = Open on Sunday.
2 = Open on Monday.
3 = Open on Tuesday.
4 = Open on Wednesday.
5 = Open on Thursday.
6 = Open on Friday.
7 = Open on Saturday.
8 = Reserved.
LOCATION 55 - DAYS OF THE WEEK FOR AUTO ARMING IN PARTITIONS 1 THRU 8
(8 Segments, feature selection data) Location 55 selects which days each partition will auto arm. Segment 1 is for
partition 1, and segment 8 is for partition 8. If a zone is faulted when the panel tries to auto arm, the zone will be
bypassed.
Segments 1-8
1 = Auto Arming on Sunday.
2 = Auto Arming on Monday.
3 = Auto Arming on Tuesday.
4 = Auto Arming on Wednesday.
5 = Auto Arming on Thursday.
6 = Auto Arming on Friday.
7 = Auto Arming on Saturday.
8 = Reserved.
LOCATIONS 88 – 109 ARE FORPROGRAMMINGDIFFERENTACCOUNT CODES AND/OR FEATURES FOR EACH
PARTITION. IFA LOCATION IS LEFT UNPROGRAMMED,THEFEATUREFOR PARTITION1 ANDACCOUNT CODE
FOR THE PHONE NUMBER WILL BE USED.
LOCATION 88 - ACCOUNT CODE FOR PARTITION 1
(6 segments, numerical data) Location 88 containsthe account codesent when partition1 is r eported. If location 88
is left unprogrammed (all A10"s), then the account code corresponding to the Phone number dialed will be
used. If the account code is less than six digits, program a A10" in the segment immediately after the last d igit of the
account code. If the account code is 6 digits long, program all 6 segments.
LOCATION 89 - ACCOUNT CODE FOR PARTITION 2
(6 segments, numerical data) Location 89 containsthe account codesent when partition2 is r eported. If location 89
is left unprogrammed (all A10"s), then the account code corresponding to the Phone number dialed will be
used. If the account code is less than six digits, program a A10" in the segment immediately after the last digit of the
account code. If the account code is 6 digits long program all 6 segments.
LOCATION 90 - PARTITION 2 FEATURE AND REPORTING SELECTIONS
(3 segments, feature selection data) Location 90 is used to enable certain features that can be accessed or are visible
tothe user from the keypad of the system. Inaddition, certain communicator reports are enabled in this location. Each
of these features can be enabled by partition. This location contains 3 segments, with eight possible features per
segment. Refer to Location 23, Segments 1 - 3 on page 18 for the feature selections. If all segments are blank
(nothing enabled), the features for partition 1 will be used.
LOCATION 91 - PARTITION 2 ENTRY EXIT TIMERS
(4 segments, numerical data) Location 91is used to enter in seconds the Entry and Exit times. There are 2separate
entry and exit times.Valid entries are 10-255 seconds. If all segments are A0", the entry and exit times for
partition 1 will be used.
Segment 1, Entry time 1:Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Segment 2, Exit time 1:Exit time that will be used for all zones designated as Delay 1.
Segment 3, Entry time 2:Entry time that will be used when a Delay 2 zone type initiates an entry delay.
Segment 4, Exit time 2:Exit time that will be used for all zones designated as Delay 2.
LOCATION 92 - ACCOUNT CODE FOR PARTITION 3
(6 segments, numerical data) The account code sent when pa r tition 3 is reported is programmed in location 92. If
location 92 is left unprogrammed (all A10" ) thenthe account code correspondingto the Phone number dialed
will be used. If the accountcode is lessthan sixdigits, program a A10"in the segmentimmediately afterthe last digit
of the account code. If the account code is 6 digits long program all 6 segments.
LOCATION 93 - PARTITION 3 FEATURE AND REPORTING SELECTIONS
(3 segments, feature selection data) Location 93 is used to enable certain features that can be accessed or are visible
tothe user from the keypad of the system. In addition, certain communicator reports are enabled in this location. Each
of these features can be enabled by partition. This location contains 3 segments, with eight possible features per
segment. Refer to Location 23, Segments 1 - 3 on page 18 for the feature selections. If all segments are blank
(nothing enabled), the features for partition 1 will be used.
LOCATION 94 - PARTITION 3 ENTRY EXIT TIMERS
(4 segments, numerical data) Location 94is usedto enterin seconds the Entry and Exittimes. There are 2 separate
entryand exit times. Valid entries are 10-255 seconds. If all segments are A0", the entry and exit times for partition
1 will be used.
Segment 1, Entry time 1:Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Segment 2, Exit time 1:Exit time that will be used for all zones designated as Delay 1.
Segment 3, Entry time 2:Entry time that will be used when a Delay 2 zone type initiates an entry delay.
Segment 4, Exit time 2:Exit time that will be used for all zones designated as Delay 2.
(6 segments, numerical data) The account code sent when pa r tition 4 is reported is programmed in location 95. If
location 95 is leftunprogrammed (all A10") then the account code corresponding tothe Phonenumber dialed
will be used. If the account code isless than six digits, program a A10" in the segment immediately after the last digitof
the account code. If the account code is 6 digits l ong, program all 6 segments.
LOCATION 96 - PARTITION 4 FEATURE AND REPORTING SELECTIONS
(3 segments, feature selection data) Location 96 is used to enable certain features that can be accessed or are visible
tothe user from the keypad of the system. Inaddition, certain communicator reports are enabled in this location. Each
of these features can be enabled by partition. This location contains 3 segments, with eight possible features per
segment. Refer to Location 23, Segments 1 - 3 on page 18 for the feature selections. If all segments are blank
(nothing enabled), the features for partition 1 will be used.
LOCATION 97 - PARTITION 4 ENTRY EXIT TIMERS
(4 segments, numerical data) Locatio n 97 is used to enter in seconds the Entry and exit times. There are 2 separate
entryand exit times. Valid entries are 10-255 seconds. If all segments are A0", the entry and exit times for partition
1 will be used.
Segment 1, Entry time 1:Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Segment 2, Exit time 1:Exit time that will be used for all zones designated as Delay 1.
Segment 3, Entry time 2:Entry time that will be used when a Delay 2 zone type initiates an entry delay.
Segment 4, Exit time 2:Exit time that will be used for all zones designated as Delay 2.
LOCATION 98 - ACCOUNT CODE FOR PARTITION 5
(6 segments, numerical data) The account code sent when pa r tition 5 is reported is programmed in location 98. If
location 98 is left unprogrammed (all A10" ) thenthe account code correspondingto the Phone number dialed
will be used. If the account code isless than six digits, program a A10" in the segment immediately after the last digitof
the account code. If the account code is 6 digits l ong, program all 6 segments.
LOCATION 99 - PARTITION 5 FEATURE AND REPORTING SELECTIONS
(3 segments, numerical data) Location 99 is used to enable certain features that can beaccessed or are visible to the
user from the keypad of the system. In addition, certain communicator reports are enabled in this location. Each of
these featurescan be enabled by partition.This location contains 3 segments,with eight possible features per segment.
Refer to Location 23, Segments 1 - 3 on page 18 for the feature selections. If all segments are blank (nothing
enabled), the features for partition 1 will be used.
LOCATION 100 - PARTITION 5 ENTRY EXIT TIMERS
(4 segments, numerical data) Location 100 isused to enterin seconds theEntry and exittimes. There are2 separat e
entryand exit times. Valid entries are 10-255 seconds. If all segments are A0", the entry and exit times for partition
1 will be used.
Segment 1, Entry Time 1:Entry time that will be used when a delay 1 zone type initiates an entry delay.
Segment 2, Exit Time 1:Exit time that will be used for all zones designated as delay 1.
Segment 3, Entry Time 2:Entry time that will be used when a delay 2 zone type initiates an entry delay.
Segment 4, Exit Time 2:Exit time that will be used for all zones designated as delay 2.
LOCATION 101 - ACCOUNT CODE FOR PARTITION 6
(6 segments, numerical data) The account code sent when partition 6 is reported is programmed in location 101. If
location 101 is left unprogrammed (all A10" ) then the account code corresponding to the Phone numberdialed
will be used. Program the account code is lessthansix digits, program a A10" in the segment immediatelyafter the last
digit of the account code. If the account code is 6 digits long, program all 6 segments.
LOCATION 102 - PARTITION 6 FEATURE AND REPORTING SELECTIONS
(3 segments, feature selection data) Location 102 isused to enable certain featuresthat can be accessed or are visible
to the user from the keypad of thesystem. In addition, certain communicator reports are enabled in this location. Each
of these features can be enabled by partition. This location contains 3 segments, with eight possible features per
segment. Refer to Location 23, Segments 1 - 3 on page 18 for the feature selections. If all segments are blank
(nothing enabled), the features for partition 1 will be used.
(4 segments, numerical data) Location 103 is used to enterin seconds the Entryand Exit times. Thereare 2 separate
entryand exit times. Valid entries are 10-255 seconds. If all segments are A0", the entry and exit times for partition
1 will be used.
Segment 1, Entry Time 1:Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Segment 2, Exit Time 1:Exit time that will be used for all zones designated as Delay 1.
Segment 3, Entry Time 2:Entry time that will be used when a Delay 2 zone type initiates a n entry delay.
Segment 4, Exit Time 2:Exit time that will be used for all zones designated as Delay 2.
LOCATION 104 - ACCOUNT CODE FOR PARTITION 7
(6 segments, numerical data) The account code sent when partition 7 is reported is programmed in location 104. If
location 104 is left unprogrammed (all A10") t hen the account code corresponding to the Phone number dialed
will be used. If the account code isless than six digits, program a A10" in the segment immediately after the last digitof
the account code. If the account code is 6 digits l ong, program all 6 segments.
LOCATION 105 - PARTITION 7 FEATURE AND REPORTING SELECTIONS
(3 segments, feature selection data) Location 105 isused to enable certain featuresthat can be accessed or are visible
to the user from the keypad of the system. In addition, certain communicator reports are enabled in this location. Each
of these features can be enabled by partition. This location contains 3 segments, with eight possible features per
segment. Refer to Location 23, Segments 1 - 3 on page 18 for the feature selections. If all segments are blank
(nothing enabled), the features for partition 1 will be used.
LOCATION 106 - PARTITION 7 ENTRY EXIT TIMERS
(4 segments, numerical data) Location 106 is used to enterin seconds the Entryand Exit times. Thereare 2 separate
entryand exit times. Valid entries are 10-255 seconds. If all segments are A0", the entry and exit times for partition
1 will be used.
Segment 1, Entry Time 1:Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Segment 2, Exit Time 1:Exit time that will be used for all zones designated as Delay 1.
Segment 3, Entry Time 2:Entry time that will be used when a Delay 2 zone type initiates a n entry delay.
Segment 4, Exit Time 2:Exit time that will be used for all zones designated as Delay 2.
LOCATION 107 - ACCOUNT CODE FOR PARTITION 8
(6 segments, numerical data) The account code sent when partition 8 is reported is programmed in location 107. If
location 107 is left unprogrammed (all A10") t hen the account code corresponding to the Phone number dialed
will be used. If the account code isless than six digits, program a A10" in the segment immediately after the last digitof
the account code. If the account code is 6 digits l ong, program all 6 segments.
LOCATION 108 - PARTITION 8 FEATURE AND REPORTING SELECTIONS
(3 segments, feature selection data) Location 108 isused to enable certain featuresthat can be accessed or are visible
to the user from the keypad of the system. In addition, certain communicator reports are enabled in this location. Each
of these features can be enabled by partition. This location contains 3 segments, with eight possible features per
segment. Refer to Location 23, Segments 1 - 3 on page 18 for the feature selections. If all segments are blank
(nothing enabled), the features for partition 1 will be used.
LOCATION 109 - PARTITION 8 ENTRY EXIT TIMERS
(4 segments, numerical data) Location 109 is used to enterin seconds the Entryand Exit times. Thereare 2 separate
entryand exit times. Valid entries are 10-255 seconds. If all segments are A0", the entry and exit times for partition
1 will be used.
Segment 1, Entry Time 1:Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Segment 2, Exit Time 1:Exit time that will be used for all zones designated as Delay 1.
Segment 3, Entry Time 2:Entry time that will be used when a Delay 2 zone type initiates an entry Delay.
Segment 4, Exit Time 2:Exit time that will be used for all zones designated as Delay 2.
LOCATIONS 110 - 149 ARE USED TO CHANGE THE ZONE TYPES (Configurations) AS LISTED INTable 9-1 ON
FIRE ZONE CHARACTERISTICS ARE PRESETAND CANNOTBE CHANGED INUL LISTED SYSTEMS.
PAGE 19. THESE LOCATIONS ARE CONSIDERED ADVANCED PROGRAMMING AND SHOULD ONLY BE
CHANGED WITH A THOROUGH UNDERSTANDING OF THE OPERATION OF EACH BIT.
(LOCATIONS 110 –149)
LOCATION 110 - ZONE TYPE 1 ALARM EVENT CODE
(1 segment, numerical data) Location 110 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 111 - ZONE TYPE 1 CHARACTERISTIC SELECT
(3 segments, feature selection data)
Segment 1:1 = Fire (turn on if this is a fire zone).
2 = 24 hour (turn on for non-fire 24 hour zones).
3 = Keyswitch zone. (normally open switch)
4 = Follower ( turn on for burglary zones that are Instant during non-entry times).
5 = Delay 1 zone (follows timer 1 entry and exit times).
6 = Delay 2 zone (follows timer 2 entry and exit times).
7 = Interior (turn on if this zone should Automatically Bypass or Bypass for Stay Arming).
8 = Local only (turn on if this zone should not be reported).
Segment 2:1 = On if Zone Type will beep the keypad for alarm.
2 = On if Zone Type will sound the yelping siren for alarm.
3 = On if Zone Type will sound the temporal siren for alarm.
4 = On if Zone Type will chime.
5 = On if Zone Type can be bypassed.
6 = On if Zone Type is included in the group shunt.
7 = On if Zone Type is force armable.
8 = On if Zone Type is entry guard.
Segment 3:1 = On enables Sprinkler Supervisory
2 = On enables Double End Of Line Tamper zone. (Mainly used for tamper on wireless zones)
3 = On enables Trouble Reporting zone. (Day zone and Fire zones)
4 = On if Zone Type is a Cross Zone.
5 = On enables Dialer Delay zone. (Location 40, page 22)
6 = On if Zone Type will swinger shutdown. (Location 38, page 22)
7 = On enables Restore reporting.
8=Reserved
LOCATION 112 - ZONE TYPE 2 ALARM EVENT CODE
(1 segment, numerical data) Location 112 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 113 - ZONE TYPE 2 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 114 - ZONE TYPE 3 ALARM EVENT CODE
(1 segment, numerical data) Location 114 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 115 - ZONE TYPE 3 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
(1 segment, numerical data) Location 116 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 117 - ZONE TYPE 4 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 118 - ZONE TYPE 5 ALARM EVENT CODE
(1 segment, numerical data) Location 118 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 119 - ZONE TYPE 5 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 120 - ZONE TYPE 6 ALARM EVENT CODE
(1 segment, numerical data) Location 120 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 121 - ZONE TYPE 6 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 122 - ZONE TYPE 7 ALARM EVENT CODE
(1 segment, numerical data) Location 122 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 123 - ZONE TYPE 7 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 124 - ZONE TYPE 8 ALARM EVENT CODE
(1 segment, numerical data) Location 124 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 125 - ZONE TYPE 8 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 126 - ZONE TYPE 9 ALARM EVENT CODE
(1 segment, numerical data) Location 126 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 127 - ZONE TYPE 9 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 128 - ZONE TYPE 10 ALARM EVENT CODE
(1 segment, numerical data) Location 128 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 129 - ZONE TYPE 10 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 130 - ZONE TYPE 11 ALARM EVENT CODE
(1 segment, numerical data) Location 130 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 131 - ZONE TYPE 11 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 132 - ZONE TYPE 12 ALARM EVENT CODE
(1 segment, numerical data) Location 132 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 134 - ZONE TYPE 13 ALARM EVENT CODE
(1 segment, numerical data) Location 134 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 135 - ZONE TYPE 13 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 136 - ZONE TYPE 14 ALARM EVENT CODE
(1 segment, numerical data) Location 136 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 137 - ZONE TYPE 14 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 138 - ZONE TYPE 15 ALARM EVENT CODE
(1 segment, numerical data) Location 138 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 139 - ZONE TYPE 15 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 140 - ZONE TYPE 16 ALARM EVENT CODE
(1 segment, numerical data) Location 140 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 141 - ZONE TYPE 16 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 142 - ZONE TYPE 17 ALARM EVENT CODE
(1 segment, numerical data) Location 142 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 143 - ZONE TYPE 17 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 144 - ZONE TYPE 18 ALARM EVENT CODE
(1 segment, numerical data) Location 144 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 145 - ZONE TYPE 18 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 146 - ZONE TYPE 19 ALARM EVENT CODE
(1 segment, numerical data) Location 146 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 147 - ZONE TYPE 19 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 148 - ZONE TYPE 20 ALARM EVENT CODE
(1 segment, numerical data) Location 148 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 149 - ZONE TYPE 20 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
1 = Siren sounds for telephone line cut while armed ‘
2 = Siren sounds for telephone line cut while disarmed ‘
3 = Siren blast at arming ‘
4 = Siren blast at exit delay expiration ‘
5 = Siren blast at closing kissoff ‘
6 = Siren sounds during a cross zone verification time ‘
7 = Siren sounds for a tamper ‘
8 = Siren bla st one time for keyswitch arming, two times for disarming ‘
Segment #2
1 = Convert siren driver to voltage out ‘
2 = Siren sounds for expander trouble (required for U.L.) ‘
3 = Immediate Restore by zone ‘
4 = Dynamic battery test performed upon arming ‘
5 = Battery missing test performed every 12 seconds ‘
6 = Manual bell test performed during [r]-[4] test function ‘
7 = Manual communicator test performed during [r]-[4] test function ‘
8=Box tamper enabled ‘
1 = Lost Clock “Service Required” message enable ‘
2=Reserved
3 = Disable on-board eight zones ‘
4 = Enables two trips on the same cross-zone to activate the alarm ‘
5 = Disables bypass reports for force armed zones ‘
6 = Silent exit ‘
7 = Clock uses internal crystal ‘
8 = Disable Temporal Siren on Fire (Do not disable on UL listed systems) ‘
3822 SWINGER SHUTDOWN COUNT0_
3922
KEYPAD SOUNDER CONTROL
Segment #1
1 = Keypad sounds for Telephone Line Cut when in the Armed state ‘
2 = Keypad sounds for Telephone Line Cut when in the Disarmed state ‘
3 = Keypad sounds upon AC Power Failure ‘
4 = Keypad sounds upon Low Battery Detection ‘
5 = Keypad sounds during Cross Zone Trip Time ‘
6 = Keypad sounds for Tamper Alarm ‘
7=Reserved
8 = Keypad sounds for expander trouble (required for UL) ‘
4022
SYSTEM TIMERS
Segment #1 Dynamic Battery Test duration (0-255
minutes)
Segment #2 AC Failure report delay (0-255 hours)6_____
Segment #3 Power Up Delay (0-60 seconds)0_____
Segment #4 Siren Time (1-255 minutes)8_____
Segment #5 Telephone Line Cut delay (10-175 seconds)30_____
Segment #6 Cross Zone Time (0-255 minutes)5_____
Segment #7 Chime Time in 50 mS increments (0-255)3_____
Segment #8 Dialer delay ( 0-255 seconds)0_____
Segment #9 Fire Alarm Verification Time (120-240 sec.)0_____
Segment #10 Reserved
4123
SPECIAL FEATURES
Segment #1
1-2=Reserved
3 = Enable Auto Cancel / Abort ‘
4 = Enable Walk-Test Mode ‘
5-8=Reserved
4223 GO TO PROGRAM CODE9-7-1-3-0-0______
4323
GO TO PROGRAM CODE PARTITION AND AUTHORIZATION
Segment #1
1=Reserved
2 = Enables "Go To Program Code" as an arm only code ‘
3 = Enables "Go To Program Code" as an arm only after closing ‘
4 = Enables "Go To Program Code" as a master arm/disarm code (can change user codes) ‘
5 = Enables "Go To Program Code" as an arm/disarm code ‘
6 = Enables "Go To Program Code" to bypass zones ‘
7 = Enables "Go To Program Code" opening and closing reports ‘
8=Reserved
Segment #2
1 = Enables "Go To Prog ram Code" for partition #1 ‘
2 = Enables "Go To Prog ram Code" for partition #2 ‘
3 = Enables "Go To Prog ram Code" for partition #3 ‘
4 = Enables "Go To Prog ram Code" for partition #4 ‘
5 = Enables "Go To Prog ram Code" for partition #5 ‘
6 = Enables "Go To Prog ram Code" for partition #6 ‘
7 = Enables "Go To Prog ram Code" for partition #7 ‘
8 = Enables "Go To Prog ram Code" for partition #8 ‘
Output to activate only between closing & opening
Output to activate only between opening & closing
Invert output (0 volts going to 12V when activated).
Reserved
Reserved
RELAY #1, EVENT & TIME
1
2
3
4
5
6
7
8
Segment #1: Program the event number for relay #10=Burglary alarm
Segment #2: Program the timing for relay #110 seconds
4824
RELAY #2, EVENT & TIME
Segment #1: Program the event number for relay #21=Fire alarm
Segment #2: Program the timing for relay #210 seconds
4924
AUXILIARY OUTPUT #3, EVENT & TIME
Segment #1: Program the event number for output #32= 24 Hour Alarm
Segment #2: Program the timing for output #310 seconds
5025
AUXILIARY OUTPUT #4, EVENT & TIME
Segment #1: Program the event number for output #421-Armed State
Segment #2: Program the timing for output #40=Follow condition
5125
AUTOTEST CONTROL
Segment #1: Program a "1" if the interval is hours, a "0" if
in days. Add a A2" to suppress the daily test or a A3" to
0
suppress the hourly test.
5225
Segment #2: Program the autotest interval from 1-255
days or hours.
Segment #3: Program the autotest report in 24-hour time
format.
Segment #4: Program the autotest report time (minutes
after the hour)
OPENING TIME
24
2
0
Segment #1: Program the hour of the opening time.8
5326
Segment #2: Program the minutes after the hour of the
opening time.
CLOSING TIME / AUTO ARMING TIME
Segment #1: Program the hour of the closing time / auto
arming time.
Segment #2: Program the minutes after hour of closing /
auto arming time.
112 30 ZONE TYPE 2 ALARM EVENT CODE2___
113 30 ZONE TYPE 2 CHARACTERISTIC SELECT2-125-78____ ____ ____
114 30 ZONE TYPE 3 ALARM EVENT CODE7___
115 30 ZONE TYPE 3 CHARACTERISTIC SELECT5-1245-5678____ ____ ____
116 31 ZONE TYPE 4 ALARM EVENT CODE5___
117 31 ZONE TYPE 4 CHARACTERISTIC SELECT45-125-5678____ ____ ____
118 31 ZONE TYPE 5 ALARM EVENT CODE5___
119 31 ZONE TYPE 5 CHARACTERISTIC SELECT457-125-5678____ ____ ____
120 31 ZONE TYPE 6 ALARM EVENT CODE4___
121 31 ZONE TYPE 6 CHARACTERISTIC SELECT0-1245-5678____ ____ ____
122 31 ZONE TYPE 7 ALARM EVENT CODE0___
123 31 ZONE TYPE 7 CHARACTERISTIC SELECT2-0-78____ ____ ____
124 31 ZONE TYPE 8 ALARM EVENT CODE1___
125 31 ZONE TYPE 8 CHARACTERISTIC SELECT1-13-378____ ____ ____
126 31 ZONE TYPE 9 ALARM EVENT CODE7___
127 31 ZONE TYPE 9 CHARACTERISTIC SELECT6-1245-5678____ ____ ____
128 31 ZONE TYPE 10 ALARM EVENT CODE2___
129 31 ZONE TYPE 10 CHARACTERISTIC SELECT24-5-78____ ____ ____
130 31 ZONE TYPE 11 ALARM EVENT CODE3___
131 31 ZONE TYPE 11 CHARACTERISTIC SELECT3-0-0____ ____ ____
132 31 ZONE TYPE 12 ALARM EVENT CODE5___
133 32 ZONE TYPE 12 CHARACTERISTIC SELECT457-125-45678____ ____ ____
134 32 ZONE TYPE 13 ALARM EVENT CODE4___
135 32 ZONE TYPE 13 CHARACTERISTIC SELECT0-12458-5678____ ____ ____
136 32 ZONE TYPE 14 ALARM EVENT CODE7___
137 32 ZONE TYPE 14 CHARACTERISTIC SELECT5-12456-5678____ ____ ____
138 32 ZONE TYPE 15 ALARM EVENT CODE5___
139 32 ZONE TYPE 15 CHARACTERISTIC SELECT457-1256-5678____ ____ ____
140 32 ZONE TYPE 16 ALARM EVENT CODENot Used___
141 32 ZONE TYPE 16 CHARACTERISTIC SELECT2-15-17____ ____ ____
142 32 ZONE TYPE 17 ALARM EVENT CODE7___
143 32 ZONE TYPE 17 CHARACTERISTIC SELECT5-1245-25678____ ____ ____
144 32 ZONE TYPE 18 ALARM EVENT CODE5___
145 32 ZONE TYPE 18 CHARACTERISTIC SELECT457-125-25678____ ____ ____
146 32 ZONE TYPE 19 ALARM EVENT CODE4___
147 32 ZONE TYPE 19 CHARACTERISTIC SELECT0-1245-25678____ ____ ____
148 32 ZONE TYPE 20 ALARM EVENT CODE7___
149 32 ZONE TYPE 20 CHARACTERISTIC SELECT6-1245-25678____ ____ ____
KEYPAD AUXILIARY 1110FA
KEYPAD AUXILIARY 2100MA
RF SENSOR LOST (zone number)381*T
RF SENSO R RESTORE (zone number)381*R
SENSOR LOW BATTERY (zone number)384XT
SENSOR BATTERY RESTORE (zone number)384XR
ZONE SPRINKLER SUPERVISORY200SS
ZONE SPRINKLER SUPERVISORY RESTORE200SR
ZONE TROUBLE (zone number)380*T
ZONE TROUBLE RESTORE (zone number)380*R
ZONE TAMPER (zone number)137TA
ZONE TAMPER RESTORE (zone number)137TR
ZONE BYPASS (zone number)570*B
BYPASS RESTORE (zone number)570*U
THENUMBER IN PARENTHESESFOLLOWING THE EVENT IS THENUMBER THAT WILL BEREPORTED ASTHE
ZONENUM BER. IF THERE ARE NO PARENTHESES, THE ZONE WILL BE A0". REFER TO APPENDIX 3 FOR THE
DEVICE NUMBERS.
* The character transmittedin thisslot will be the first character from theevent codeof the zone that is bypassed or in
trouble. (Locations 110 - 141)
The NX-8-CF has the ability to report SIA level 1 transmissions to either or both phone numbers. Each report in SIA
consistsof an Event Code and a Zone or User ID. TheZone ID will be the zone number that isin alarm. The eventcode
will come from the chart below and be programmed in the zone type event code.
TheNX-8-CF has the ability to report Ademco Contact IDtransmissions. Eachreport in Contact IDconsists of anEvent
Code and a Zone ID. The zone ID is the zone that created the alarm. The event code will come from the chart below
and be programmed in the zone type event code.
EARTHEarth Ground. Connect to a cold water pipe or a 6 to 10 foot driven rod.
ACAC input. Connect to a 16.5V 50 VA Class ll U.L. approved transformer.
Ifused as a siren output (default), the speakerrating should be 15 watt at 8 or 16 ohm, or 30/40 watt
BELL + &
BELL -
KP DATA
KP COMConnect to the Common terminal on the keypads and the expanders.
KP POS
SMOKE+
COMConnect negative wire of powered devices such as motion detectors and smoke detectors.
AUX PWR+
ZONE 8
COMCommon (-) terminal for zones 7 & 8. (See the wiring diagram for examples.)
ZONE 7
ZONE 6 -
ZONE 1
RELAY 2Refer to Relay 1 shown below.
N.O.Normally open dry contact rated 1 Amp at 30 Volts.
1
COMCommon dry contact rated 1 Amp at 30 VDC.
RELAY
N.C.Normally closed dry contact rated 1 Amp at 30 Volts.
AUX 4 –
AUX 1
at 4, 8, or 16 ohms. If voltage outputis selected inlocation 37, this outputbecomes voltage output,
12VDC, 600mA maximum load. NOTE: A 3.3K Ω resistor may be required across the bell
terminals when a 12 VDC siren is used. If no resistor is used, you may experience voltage
leakage into the siren, which will cause these devices to output a small signal.
Connect to the data terminal on the keypads and the expanders. Maximum number of devices
(keypads + expanders) is 32. See AMaximum Wire Run@ chart below.
Connectto the POS terminal on the keypads and the expanders. Thisterminal and AUX PWR + are
limited to 400mA total current when added together.
Smoke detector power 12VDC, 400mA maximum (For those jurisdictions which allow the Priority
zone to be used with smoke detectors.)
Connect positive wire of all powered devices except smoke detectors and keypads. This terminal
and KP POS are limited to 400mAtotal current when added together.
Connect to one side of zone8 loop. Connect the other side to com terminal. Open or short causes
alarm. Zone 8 may be used fora two wire smoke detector using a 680 Ω E.O.L. resistor. W3 must
be set for two-wire smoke detector loop. For normal zone operation, W4 must be set.
Connect to one side of zone7 loop. Connectthe other side toCOM terminal. Openor short causes
alarm.
Connect as described for zones 7 & 8. Only zone 8 can be a two-wire zone. (See the wiring
diagram for examples.)
Connect negative lead of low current device [relay, LED (install 1kΩ resistor in series with LED),
etc.]. Connect positive lead of device to AUX PWR +. Current is limited to 25mA when output is
negative.
KEYPAD MAXIMUM WIRE RUN
These numbers are for one keypad at the end of the wire. When connecting more than one keypad to the end of
the wire, a higher gauge wire will be required.
WHEN CONNECTED TO NX-8-CFWHEN CONNECTED TO NX-320E
TELEPHONE CONNECTION REQUIREMENTS
Except for telephone company provided ringers, all connections to the telephone network shall be made through
standard plugs and standard telephone company provided jacks or equivalent in such a manner as to allow for
immediate disconnection of the terminal equipment. Standard jacks shall be so arranged that if the plug connected
thereto is withdrawn, no interference to the operation of the equipment at the customers’ premises which remains
connected to the telephone network, shall occur by reason of such withdrawal.
INCIDENCE OF HARM
Should terminal equipment orprotective circuitry causeharm tothe telephonenetwork, the telephone company sh all,
where practical, notify the customer that temporary discontinuance of service may be required. However, where prior
notice is not practical, the telephone company may temporarilydiscontinue service if suchaction is deemed reasonable
in the circumstances.In the case of such temporary discontinuance, the telephone company shall promptly notify the
customerwhowill be given the opportunity to correct the situation.The customer also has the right to bring a complaint
to the FCC if he feels the disconnection is not warranted.
CHANGES IN TELEPHONE COMPANY EQUIPMENT OR FACILITIES
The telephone company may make changes in its communications facilities, equipment, operations, or procedures
where such action is reasonably required and proper in its business. Should any such change render the customers
terminalequipment incompatible with the telephone company facilities, the customer shall be given adequate notice to
make modifications to maintain uninterrupted service.
GENERAL
The FCC prohibits customer provided terminal equipment be connected to party lines.
IMPORTANCE OF THE RINGER EQUIVALENCE NUMBER
TheRinger Equivalence Number (REN) ofthis deviceis 0.1B. This numberis a representationof the electrical load that
it applies to your telephone line.
MALFUNCTION OF THE EQUIPMENT
In the event that the device should fail to operate properly, the customer shall disconnect the equipment from the
telephone line to determine if it is the customers equipment that is not functioning properly. If the problem is with the
device, the customer shall discontinue use until it is repaired.
EQUIPMENT INFORMATION
MANUFACTURER OF CONNECTING EQUIPMENT:CADDX CONTROLS, INC.
FCC REGISTRATION NUMBER: GCQUSA-31771-AL-T, RINGER EQUIVALENCE: 0.1 B
The NetworX NX-8-CF control panel holds the following listings from Underwriters Laboratories:
(UL864)Control Units for Fire-Protective Signaling
Systems
(UL1023)Household Burglar-Alarm System Units(UL1637)Home Health Care Signaling
(UL609)Local Grade AMercantile, Police Station Connect With BasicLineSecurity (requires #NX-003-C enclosure)
(UL1610)Grade B & C Central Station Burglar Alarm
Unit
Section I - All UL installations require the following:
! At least one NetworX NX-8-CF control panel
! At least one compatible keypad
! At least one bell fixture is required for all applications, except Grade C Central Station. For Grade A Local, the
AD10-12 bell and Grade A bell housing shall be used.
! Initiating and indicating devices must be rated at 11.5 to 12.4 V DC residential, 12.0 V DC commercial.
! The Siren/Bell Test shall be enabled
! The Entry-Guard feature shall be disabled.
! Swinger Shutdown shall be disabled.
! Group Bypassing shall be disabled.
! Delay before dial seizure shall be set to "0".
! Total current draw fromaux powerconnections atterminal positionsPOS, AUX PWR,and SMOKEPWR mustnot
exceed 400 mA.
! The keyswitch option shall not be used.
! The telephone line monitor shall be enabled.
! The telephone line cut delay shall not exceed 200 seconds maximum.
! 24-hour communicator test transmission is required.
! For 24 hours of standby power using a 7.0 AH battery, limit auxiliary power load to 140 mA.
! For 24 hours of standby power using a 17.2 AH battery, limit auxiliary power load to 400 mA.
! The silent keypad option shall not be enabled.
! UL has only verified compatibility with the foll owing listed DACRs and formats: Sure-Gard SG-MLR2-DG:
2,9,10,12,13,14; Silent Knight 9000 - 2,12; FBI - CP220FBI, 13; and Ademco 685: 2,11,12, and 13.
! Expander trouble must activate the siren (Loc 37, Segment 2, LED 2)
! Use type FPL, FPLR, or FPLR cables as required by Article 760 of the National Electrical Code.
Section II - Commercial Fire applications must follow these requirements in addition to Section I:
! At least two NX-148E-CF LCD keypads. Connect one to DATA/COM/POS and the other to DATA/COM/AUX+.
! At least one NX-870E Fire Supervision module.
! Commercial UL applications require #NX-003-CF metal enclosure. Supplied screws to be used.
! The DACT shall be enabled.
! Compatible listed devices: (Special Applications)
! Bell Output (Sirens): Wheelock, Models NS-1215W, NX-121575W
! Smoke Output (4 wire detectors): ESL 500N series; ESL 449CTE series; ESL 521 series; ESL 541 series
Section III - Commercial Burglary applications must follow these requirements in addition to
Section I:
! Commercial UL applications require #NX-003-C metal enclosure. Supplied screws to be used.
! When using partitioning in Commercial Burglary applications, a 24-hour alarm circuitmust protect the main control.
! Force Arming and Auto Arming shall not be enabled.
! The Siren/Bell Test shallbe enabled. The auxiliary outputs controllingthe audible devicerequire a minimumcutoff
time of 15 minutes.
! Ringback shall be enabled.
! Cross-zoned detectors shall overlap 100 percent in the area of coverageand similar coverage areas must be used.
For example, interior protection is cross-zoned with interior protection, and so on.
! The exit delay time shall not exceed 60 seconds.
! The DACT shall be enabled.
Section IV - Residential Fire applications must follow these requirements in addition to Section I:
! The indicating devices shall be a Wheelock 34T-12 or equivalent.
! The Dynamic Battery Test time cannot exceed four (4) hours.
! The Siren/Bell Test shallbe enabled. The auxiliary outputs controllingthe audible devicerequire a minimumcutoff
time of 4 min utes.
Section V – Home Health Care applications must follow these requirements in addition to Section I:
! A minimum of two (2)keypads are required for Home Healthapplications and each keypadmust be set to a unique
address.
! For UL 1637, expander trouble must activate keypad sounder (Loc 39, Seg 1, LED 8).
For additional details, please refer to the specific programming instructions in the NX-8-CF Installation Manual.
OPERATING POWER16.5 VAC 50 VA Transformer
AUXILIARY POWER
w/50 VA Transformer12 VDC Special Applications 1 AMP
w/NX-320 Power Supply12 VDC Special Applications 2 AMPS
LOOP RESISTANCE
Standard Loop300 Ohms Maximum
2-Wire Smokes30 Ohms Maximum
BUILT-IN SIREN DRIVER2-tone (Temporal and Yelp)
LOOP RESPONSESelectable 50mS or 500mS
OPERATING TEMPERATURE32 to 120 degrees F
NX-148E-CF LCD KEYPAD
Current Draw110 mA max.
w/o Sounder75 mA
Dimensions6.4" Wide
+ Control Panel Power
5.3" High
1.0" Deep
METAL ENCLOSURE DIMENSION11.25" Wide
11.25" High
3.50" Deep
SHIPPING WEIGHT9 lbs.
GE INTERLOGIX
1420 NORTH MAIN STREET
GLADEWATER, TEXAS 75647
Main800-727-2339Technical Support800-727-2339
Outside the US903-845-6941Tech Support Fax903-845-8409
Main Fax903-845-6811Sales & Literature800-547-2556
Web:www.caddx.com
www.ge-interlogix.com
NX-8-CF INSTALLATION MANUAL
NX8CFIA02REV. A (10-05-02)