Before installing in a nuclear
application, determine that the product is
magnetic combination starter consists of a
overload relay and a manually operated
circuit breaker or disconnect switch. The
disconnect switch may either be fusible or
switch provides a means of manually
disconnecting the motor from the line. The
uit breaker or fusible disconnect switch
protection. The overload relay provides,
motor protection against running and
The overload relay is provided with a
yellow trip indicator which is located to
the right of the reset arm, and is visible
Clean magnet mating surfaces of any
NEMA size 5
intended for such use.
Disconnect power
before Installing or servicing.
Max.
Volt-
age
600 270 115
A General Electric 300-
magnetic contactor with a three l
non-fusible. The non-
circ
provides motor branch short-
Max.
Contin
ous
Amp
Rating
AC Volts
200
230
460/575
Max.Hp
For AC Motors
Single-
Phase
-
-
-
-
Poly-
Phase
-
75
100
200
when the overload relay is tr
1. Strongbox coil.
Overload relay, incorporates a dial
2.
for ±10% field adjustment of tripping
current, so that it is no longer
necessary to change heaters to
eliminate such problems as nuisance
tripping in hot weather.
3. Overload trip indicator.
4. Straight through wiring.
5. Oversized power terminals will
accommodate up to 500MCM wire.
Starter can be disassembled and
6.
inspected in a matter of seconds.
7. Circuit breaker or disconnect switch
is mechanically interlocked with the
enclosure door to prevent opening the
door until the handle is moved to the
OFF position.
Before connecting the starter:
Remove all packing.
1.
Magnetic Starters
CR307-CR308, CR310-CR311, CR387,
CR390 Series
dust or foreign matter.
3. Select heaters in accordance with
heater table, which accompanies each
device.
4. Operate movable magnet and
operating arm by pressing on the
nameplate to assure free movement.
5. Mount the starter on a sturdy vertical
support.
6. The overload relay may be reset
manually by depressing and releasing
the reset arm. Overload relays with an
optional normally open contact are
electrically isolated from the normally
closed contact.
7. Provide motor branch circuit
protection in accordance with the
National Electrical Code.
The encapsulated coil is impervious
to moisture, dirt, and oil. It resists
mechanical damage and failure due
to high humidity. No tools are
required to remove coil.
1. Remove power from device.
Press against coil while pulling up
2.
slightly on coil retainers (A—Figure 1
or 2) and move retainers away from
coil.
3. Withdraw magnet assembly, coil,
molded cover, and movable arm
from device.
4. Withdraw spring clip (B—Figure 1
or 2) and remove armature from
movable arm.
Remove coil from magnet.
5.
6. Replace coil.
7. Reassemble device by reversing
Movable contacts can be inspected
and replaced in seconds—without
tools (Figure 3).
These instructions do not purport to cover all details or variations in equipment not to provide for every possible contingency to
be met in connection with installation, operation or maintenance. Should further information be desired or should particular
problems arise which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to the GE Company.
CHECK FOR WELDED CONTACTS IN
Perform steps 1 through 5 under
contact, spring, and spring seat from
Remove screws holding stationary
Do not attempt to remove or
replace arc traps in arc chute cover.
arc chute cover will only fit one way and
corner. Magnet and movable arm will fit
either way but will be quieter if
reassembled the same way they were
*** Insert numbers for particular coil rating required. See Coil Table above
Surge Suppressor……………………………………………………………………………
pole devices, order coil catalog
“Coil Removal”.
2. Remove magnet from molded
cover and movable arm.
Remove return spring from center
3.
of movable arm.
4. Remove molded cover from
movable arm.
5. Depress and slide movable
movable arm.
6.
contacts in place and remove
stationary contacts
Reassemble device by reversing
7.
procedure
When reassembling, no
is marked “TOP”
taken apart.
OVERLOAD RELAY
This feature permits the maintenance
man to check for welded relay contacts
by simply depressing the white operator
located at the top of the overload relay
contact housing. When the relay is in the
reset condition, an audible “click” will be
heard when the operator is depressed,
indicating that the contacts are
operating normally. A continuity check
can also be made by disconnecting the
control wiring from the terminals of the
relay and placing a bell set or a
resistance-measuring instrument in the
circuit. Connecting either of these across
the relay terminals will indicate the relay
contact is closed until the contact-check
operator is depressed, opening the
circuit.
The exclusive manual contact operation
check gives positive assurance that
contacts have not welded due to short
circuits in the control wiring.
First NO aux. cont. for CR305, CR306 (right side mtg)……………CR3O5X500A
First NC aux. cont. for CR305, CR306 (right side mtg)……………CR3O5X500B
First NO-NC aux. cont.for CR305, CR306 (right side mtg)……. CR3O5X500C
Additional NO aux. cont. for all forms . . ……………………………………CR3O5X100D
Additional NC aux. cont. for all forms . . ……………………………………CR3O5X100E
Pushbutton……………………………………………………………………………………… CR305X520B
Selector switch, H—O—A. …………………………………………………………… .CR305X530B
Selector switch, OFF—ON. …………………………………………………………… CR305X530D
Indicating light. ……………………………………………………………………………… CR305X550B
Fifth pole. (for adding to 4-pole form only)……………………………… CR3O5X511B
Control circuit fuse………………………………………………………………CR305X541A, B, C, D
300-Line starters and contactors require virtually
no corrective maintenance. Preventive
maintenance will assure many years of
dependable on-line service.
1. Always remove power from device before
performing any maintenance.
Keep magnet mating surfaces free of
2.
accumulated dirt or dust.
3. DO NOT OIL OR GREASE the magnet mating
surfaces.
4. Contacts are carefully designed for maximum
life. They need only be replaced when
silver tip is gone and the contact tip support is ex
posed. DO NOT FILE the contacts. Filing or
otherwise dressing the contacts only results in lost
tip material and reduces contactor or starter life.
The ultimate tripping current of the installed
5.
relay heater can be adjusted ±10% by using
For two- and threenumber 55-530249G plus number in table below.
For four- and five-pole devices, order coil catalog
number 55-501493G plus number in table below.
Example: 55-530249G002 is rated 115-120V, 60
Hz/110V, 50 Hz.
Frequency
(Hertz)
60 002 023 003 ------ 004 005
Frequency
(Hertz)
50 002 ----- 003 064 004 005
115-
200-
208V
230-
240V
120V
110V ----- 220V 380V 440V 550V
-----
460-
480V
575-
600V
Ref.No Description
1
Coil retainer assembly
2
Overload relay (3-heater, non-compensated form, 1 NC contact)
3
Overload relay (3-heater, non-compensated form, 1 NO-1 NC contact)
4
Set of stationary & movable contacts with springs and screws for three-
5
Molded cover for three-poles
6
Return spring for movable arm
7
Molded movable arm with return spring for 2, 3 pole
8
Armature and frame (magnet) with retainer
9
Operating coil for 2-and 3-pole
10
Retainer for armature
General Electric Company
41 Woodford Avenue, Plainville, CT 06062
DEH-40630 R01 08/10, 10-2049 © 2010 General Electric
Visit us on the web at www.Geindustrial.com
Number
55-154607G003
CR324G310F
CR324G360F
55-154607G041
55-530245G001
55-153205G002
55-154607G042
55-154607G045
55-530249G***
55-154607G046
Required
4
1
1
1
3
1
1
1
1
1