GE Industrial Solutions 300-400 Line NEMA User Manual

Max.Hp
Starter
Max.
AC
(open
(open
Note:
For starters with one or more
device. Remove return spring from center
Normally Closed
Contacts
normally open to normally closed with no
additional parts. Perform steps 1 through
and spring seat against movable contact
Check For Welded C
ontacts In
6.
Remove screws holding stationary
Combination
Motor branch circuit and control circuit
current protection should be
supplied in accordance with the
National Electrical Code. CR305
contactors are suitable for use on a
t capable of delivering not more
than 5,000 RMS symmetrical amperes,
600 volts maximum when protected by
H, J, K1, K5, RK1, RK5 class fuses, or a
circuit breaker having an interrupting
rating not less than 5,000 RMS
Installation
Operate movable magnet and operating
Coil Replacement
Contact Replacement
rom molded cover
Instructions F
or
NEMA size 0 & 1
GEH
-
5193 Instruction
CAUTION:
ore installing in a nuclear
application, determine that the product is
WARNING
:
Description
voltage
motor starters include a magnetic
leg block overload
relay, providing motor protection against
running and stalled motor overloads. The
overload relay is provided with a yellow
trip indicator located to the right of the
reset arm, and is visible when the
Ratings
600 V Maximum
Figure1.Ty
pical 300/400
-
Line magnetic starter
Figure2
Supersedes GEH-4793B & GEH4796B
intended for such use.
before Installing or servicing.
General Electric 300/400-Line full-
contactor and a three-
overload relay is tripped
Max
Rating
18 amp
and
enclosed)
27 amp
and
enclosed)
Bef
Contactor
Current
Rating
20 amp
(open)
18amp
(enclosed)
30 amp
(open)
27amp
(enclosed)
Disconnect power
.
Volts
Size 0
115 1 -
200 - 3
230 2 3
460—575 - 5
Size 1
115 2 -
200 -
230 3
460—575 - 10
For AC Motors
Single-
Phase
Poly-
Phase
Magnetic Starters
CR307-CR308, CR310-CR311, CR387, CR390, CR407-CR408 CR410-CR415, CR487, CR490, CR492, CR494 Series
over-
circui
symmetrical amperes.
Before connecting controller to power supply:
1. Remove all packing.
2. Clean magnet mating surfaces of any
dirt or foreign matter.
3. Select and install heaters in accordance with heater table.
4.
arm by pressing on the nameplate to assure free movement.
5. Mount on a sturdy vertical support.
6. Make the electrical connections.
7. The starter overload relay may be reset
manually by depressing and releasing the reset arm.
1. Remove power from device.
2. Press against coil while pulling up
slightly on coil retainers (A—Figure 1) and move retainers away from coil.
3. Withdraw magnet assembly, coil, molded cover, and movable arm from device.
4. Withdraw spring clip (B—Figure 1) and remove armature from movable arm.
5. Remove coil from magnet.
6. Replace coil.
7. Reassemble device by reversing
procedure.
1. Perform steps 1 through 5 under Coil Replacement.
2. Remove magnet f and movable arm.
3. Remove return spring from center of movable arm.
4. Remove molded cover from movable arm.
Depress and slide movable contact
5.
and spring from movable arm.
contacts in place and remove stationary contacts.
7. Reassemble device by reversing procedure.
normally closed contacts, perform steps 1 and 2 shown under Coil Replacement. Withdraw spring clip (B—Figure 1) and remove armature, coil, and magnet from
of movable arm. Remove molded cover and stationary contacts before lifting movable arm from device.
The contacts may be converted from
4 shown under Coil Replacement. Lift coil and magnet from movable arm. Remove return spring from center of movable arm. Depress movable contact spring
and rotate these parts 1/2 turn without removing them from window. Remove the stationary contacts. Install the movable arm in the device. Install the stationary contacts so that their silver pads face the movable contact silver pads. Reassemble the device. To change contacts from normally closed to normally open position, reverse the above procedure.
Overload Relay With power disconnected, disconnect the control wiring from the relay terminals. Place a bell set or resistance measuring instrument across relay terminals. Depress and release reset
.
arm to insure relay is reset
Left Cont..
Right Cont.
In this condition there should be continuity
Maintenance
The ultimate tripping current of the installed
Caution:
Before adjusting or operating reverser,
6.
On reversing and two
-
speed
starters, the
***
Coil Suffix Table
Accessory Kits
Principal
Ren
ewal Parts
between the terminals. Depress white manual check operator to trip the relay. In the tripped condition the circuit between the terminals should be open indicating the contacts are operating normally. Rewire the terminals and reset the relay for normal operation
1. Always remove power from device before performing any maintenance.
2. Keep magnet mating surface free of accumulated dirt or dust.
3. Do Not Oil Or Grease the magnet mating surfaces.
Contacts are carefully designed for
4.
maximum life. They need only be replaced when nearly all the silver tip is gone and the contact tip support is exposed. Do Not File the contacts. Filing or dressing the contacts only results in lost tip material and reduces life.
5.
relay heater can be adjusted ± 10% by using the adjustment dial, shown in Figure 1.
mechanical interlock has been factory adjusted and normally should never have to be readjusted. If readjustment is ever needed, these steps should be followed:
Close one contactor by hand by pushing down on
A.
armature. B. Using the other hand, loosen the nut on opposite contactor interlock arm and slide it towards the top of the elongated slot until all gap is taken up between the two arms. Follow the same procedure with the opposite contactor and interlock arm. C. Best adjustment is usually obtained when both mechanical interlock arm assemblies are as far up in the elongated slot as possible.
With both arms adjusted, there should be a very
D.
slight gap (approximately 1/16- inch) between the arms with both contactors open. Neither arm should overlap the other with both contactors open.
make sure the mechanical interlock arm is engaged with movable contact arm.
(Order 15D21G plus coil suffix number below)
60 Hertz
50 Hertz 110 ----- 220V 380V 440V 550V
Coil Suffix 002 023 003 064 004 005
115-
120V
200­208V
230-
240V
----
460­480V
First NO aux. cont.for CR305, CR306…………CR3O5X100A First NC aux. cont. for CR305, CR306…………CR3O5X100B First NO-NC aux. cont.for CR305, CR306.. .CR3O5X100C Additional NO aux. cont. for all forms. . … CR3O5X100D
Additional NC aux. cont. for all forms . . .. CR3O5X100E
Pushbutton………………………………………………….. CR305X120N Selector switch, H—O—A. ………………………… CR305X130N Selector switch, OFF—ON. ……………………… CR305X130P Indicating light. ………………………………………… CR305X150N Fifth pole. …………………………………………………… CR3O5X111B
Ref.No
Figure.4
1
Coil retainer assembly
2
Overload relay (3-heater, non-compensated form, 1 NC contact)
3
Overload relay (3-heater, non-compensated, 1 NO-1 NC contacts)
4
Set of stationary and movable contacts with springs and screws for four poles: NEMA Size 0 NEMA Size 1
5
Molded cover for stationary and movable contacts
6
Return spring for movable contact support
7
Molded movable contact support for 2-, 3-, 4- pole
8
Armature and frame (magnet)
9
Operating coil
10
Spring retainer for armature
11
Overload relay for 2-speed single-winding controller (1 NC contact)
12
*** Add coil suffix number from above table to complete the catalog number. Example: Cat. No. 15D21GO02 has ratings of 115—120V, 60 Hz and 11OV, 50 Hz. +Omitted on 2-speed single-winding controller. ++ Quantity one for multi-speed controller.
Overload relay for 2-speed single-winding controller (1 NO-1 NC contact)
Description
Catalog Number
546A301G050
CR324C310F CR324C360F
--------------­546A300G002 546A301G053 188D711P001 541A278P001 187D350P001 546A301G054
15D21G***
546A588P001
CR324C310G CR324C360G
CR307/CR308/
CR387
These instructions do not purport to cover all details or variations in equipment not to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to the GE Company.
Quantity Required
2 1 1
­1 1 1 1 1 1 1 1
-
-
CR301/CR311/CR390
2 1+ 1+
­1 1 1 1 1 1 1 1 1 1
575-
600V
2 ++ ++
­1 1 1 1 1 1 1 1
-
-
General Electric Company 41 Woodford Avenue, Plainville, CT 06062 GEH-5193B 08/10, 10-2049 © 2010 General Electric Visit us on the web at www.Geindustrial.com
Loading...