GE Industrial Solutions 2508, 4008, 5008, 6008 User Manual

Gerapid
Type 2508, 4008, 5008, 6008
UL LISTED - HIGH SPEED DC CIRCUIT BREAKERS
WITH ARC CHUTE 1X2
INDEX
1. Warnings .............................................................................................. 3
2. General Usage Conditions. .......................................................... 3
2.2 Installation ........................................................................................ 4
2.2.1 Operational environment
2.2.2 Installation and interfaces ................................................ 4
2.3 Usage .................................................................................................. 4
2.3.1 Supply and load ..................................................................... 4
2.3.2 Adjusting the over current release ................................ 4
3. Technical Information .................................................................... 5
3.1 Introduction ...................................................................................... 5
3.1.1 Key features and construction overview. .................. 5
3.2 Components and accessories ................................................. 5
3.2.1 Contact system ...................................................................... 5
3.2.2 Arc chute ................................................................................... 5
3.2.3 Mechanism ............................................................................... 6
3.2.4 Overcurrent release OCT .................................................. 6
3.2.5 ED impulse coil release ...................................................... 7
3.2.6 Auxiliary tripping devices ................................................... 7
3.2.7 Forced tripping release ...................................................... 7
3.2.8 Manual operation lever ...................................................... 8
3.2.9 Auxiliary switch ....................................................................... 9
3.2.10 Indicators ................................................................................ 9
3.2.11 Closing solenoid drive ....................................................... 9
3.2.12 Operation counter .......................................................... 10
3.2.13 UL type of local and remote interlock ................... 10
3.2.14 Electronic control system ........................................... 10
3.3 Technical data table................................................................. 12
3.4 Control circuits data ................................................................. 13
4. Electrical Circuits ........................................................................... 14
5. Dimensions & Safety distances ............................................... 28
5.1 Safety distances. ......................................................................... 28
5.2 Outline drawings ......................................................................... 29
5.2.1 Outline of Gerapid 2508,4008-drawout version ... 29
5.2.2 Outline of Gerapid 2508,4008-fixed version ......... 30
5.2.3 Outline of Gerapid 5008,6008-drawout version ... 31
5.2.4 Outline of Gerapid 5008,6008-fixed version ......... 32
5.2.5 Gerapid 2508, 4008 with H / H terminals – fixed
version ................................................................................................. 33
5.2.6 Gerapid 2508, 4008 with V / V terminals – fixed
version ................................................................................................. 35
5.2.7 Gerapid 2508,4008-drawout fingers ........................ 37
5.2.8 Gerapid 5008, 6008 V/V terminal–fixed version 39
5.2.9 Gerapid 5008, 6008 – drawout fingers .................... 41
6.1 List of inspections ...................................................................... 43
6.1.1 General visual inspection ................................................ 44
6.1.2 General functional inspection ....................................... 44
6.1.3 Inspection of the arc chute ............................................ 44
6.1.4 Inspection of the contact system ............................... 45
6.1.5 Inspection of contacts’ tilt and gap .......................... 46
6.1.6 Inspection of the screw connections ....................... 46
6.1.7 Inspection of the mechanical components ........... 46
6.2 List of maintenance tasks ...................................................... 47
6.2.1 Contact system . ................................................................. 48
6.2.2 Layout of control PCB inside control box ............... 51
6.2.4 Replacement of the control boards .......................... 51
6.2.5 Adjusting the auxiliary switch ...................................... 53
6.3 Spare parts lists. ......................................................................... 54
6.3.1 Mechanical spare parts. ................................................. 54
6.3.2 Electrical spare parts ....................................................... 55
6.3.3 Recommend materials for selected works ............ 55
4.1 Controls layout ........................................................................... 14
4.2 External connections to the breaker. ............................... 15
4.3 Standard wiring diagrams .................................................... 16
4.3.1 Wiring code positions ...................................................... 16
4.3.2 Breaker Internal Control Power Supply .................... 17
4.3.3 NEKO control circuit ......................................................... 18
4.3.4 SU control circuit ................................................................ 19
4.3.5 Shunt trip control circuit ................................................ 20
4.3.6 Zero Voltage release ......................................................... 23
4.3.7 Indicators ............................................................................... 24
4.3.8 Auxiliary switches ............................................................... 25
4.3.9 Operation counter and interlocks ............................... 26
7. Customer Support ......................................................................... 56
7.1 Options overview. ...................................................................... 56
7.3 Glossary .......................................................................................... 57
7.4 Troubleshooting .......................................................................... 58
7.5 GE service teams ........................................................................ 59
2 Design and specifications are subject to change without notice S47183De rev.02 2011-03-14
b
1. Warnings
Warnings:
During operation, electrical equipment carries dangerous voltages. In addition, circuit breaker emits hot, ionized gases when switching currents, especially short circuit currents.
Installing, commissioning, maintaining, changing or refitting of this equipment must be carried out only by qualified and suitably trained personnel and under strict observation of national and international applicable safety regulations.
During their operation, circuit breakers must be equipped with appropriately fitted covers, e.g. in suitable enclosures or panel boards. Safety distances must be preserved. Suitably trained service personnel shall only carry out certain works.
Non-compliance with these warnings may result in death, and/or severe physical damage and extensive damage to equipment.
Prior to carrying out maintenance, inspection or checks, the circuit breaker must be open, the both terminals must be grounded, the circuit breaker must be switched off and the control plugs removed.
Manual activation of the breaker while energized is forbidden. Manual activation must only be used for maintenance and inspection purposes, when breaker power is off and grounded.
The circuit breaker consists of high energy moving components. Do not touch the circuit breaker while it is being switched ON (closing) or OFF (opening). There is a high risk of major injury.
The control circuits may include capacitor banks, which can be charged with dangerous voltages. Work on this section must be carried out carefully.
2. General usage conditions
2.1 Transportation and storing
The breaker is transported on wooden palette. It is fixed by
shrunken plastic film. A cardboard box covers the breaker on the palette. Truck, railway, airplane and ship transport is possible. In case of sea transport, special protection against salty and humid environment is provided.
The circuit breaker must always be transported to the
installation site vertically and fully packed. The packaging protects the device against damage and dust; it should only be removed prior to installation.
If the packaging is damaged, the breaker and the arc chute
must be inspected for damage. Ensure that all packaging materials have been carefully removed prior to breaker installation.
For handling the unpacked breaker use canvas slings and
position them below the closing drive (a) and below the lower terminal (b) [Fig. 1]. Always follow information labels, which are placed on the breaker’s frame.
a
Fig. 1 Handling the breaker
WARNING: Breaker and arc chute must be transported
separately. Never handle the breaker with arc chute installed!
Take care that the bottom isolation plate of the unpacked
breaker is not damaged during handling. Do not push the breaker back and forth on any rough surface.
The breaker’s weight, including arc chute is listed in Table 1,
page 12. Arc chute’s weight is ca. 30 kG (66 lb)
WARNING:
Store in original packaging! Do not store outdoors! Use protection against crush and blow! Do not store the breaker in a damp area! Storing temperature-range–25 °C(-13F)…+55 °C(131F)!
2011-03-14 S47183De rev.01 Design and specifications are subject to change without notice 3
2.2 Installation
2.3 Usage
2.2.1 Operational environment
The breaker, as delivered, is NEMA 1 protected. It is intended
for service in indoor applications, without pollution, with non­conductive dust, protected against high humidity and heavy condensation. Low conductivity dust deposit due to frequent condensation of humidity is acceptable. For general environmental conditions refer to EN 50123-1 - annex B, and IEC 60947, class PD3.
The breaker can operate at rated current within ambient
temperature range of –5 °C to +40 °C (23 °F to 104 °F). Maximum operating ambient temperature is +55 °C (131 °F) with continuous current derated by 10 %.
The breaker can operate at altitudes up to 2000 m (~6500 ft)
without derating.
The breaker shall not be subjected to strong vibrations.
Maximum vibrations of 0.5 g per 30 sec in vertical and horizontal directions are allowed.
Air shall be clean and its relative humidity shall be not more
than 50 % r.h. at the maximum temperature of +40 °C (104 °F). Relative humidity may be higher if the temperatures are lower, for example, 90 %r.h. at +20 °C (68 °F). Slight condensation might occur during variations of temperature.
2.2.2 Installation and interfaces
The lower and upper main terminals must be connected
directly to the main cables or bus bars.
WARNING: The breaker must only be used in an upright
operation position with the arc chute in place and fully secured.
After arc chute installation check for tightness both
connections to the arc runners. See Fig. 48-2
The safety distances as listed in section 5.1 shall be
maintained to grounded or insulated parts. Suitable measures must be taken to protect personnel from arcs.
Strong, external magnetic fields, caused by improperly
located supply conductors or stray fields from other devices, can lead to a shift of the trip setting thresholds. This may result in premature tripping, or no tripping at all during low­level short circuit current events. This has to be accounted for when installing and operating the device with shielding added if appropriate.
The control wires must be connected to the control terminals
as shown in the schematic circuit diagrams. The protective grounding wire must be connected at the marked contact [Fig. 2].
2.3.1 Supply and load
In accordance with its type, the breaker has been designed
for the current and voltage listed in Table 1, section 3.3.
During continuous operation, breaker must only be loaded up
to its maximum rated current. Load currents in excess of breaker nameplate rating are allowable for brief periods only. Refer to the short time currents listed in Table 1.
Do not exceed the rated nominal voltage shown on the
breaker’s nameplate.
Supply voltage for the drive and the auxiliary-tripping devices
shall be within the specified control voltage range. Maximum current values for the auxiliary-tripping devices are listed in Table 2a.
WARNING: Plugging in or unplugging of the auxiliary
connectors (-X2 :1/:2) (-X3 :4/:5) is only allowed with disconnected primary (mains) and secondary voltages.
2.3.2 Adjusting the over current release
OCT is an over-current tripping release , which trips and
releases the breaker in case of overload or short circuit currents. This is an instantaneous and direct acting device.
If equipped with an adjustable OCT, the response threshold
can be easily adjusted [Fig.3], by turning the adjustment nut (1) with a SW6 hexagon wrench (2).
The adjustment must only be carried out after the breaker
has been disconnected from the main circuit. For fixed installations breaker’s main terminals shall be grounded.
Turning the adjustment screw clockwise increases the trip
threshold, turning the screw counter-clockwise decreases the tripping threshold. Align the arrow and the desired marking 3, to perform adjustment.
Fig. 3 Setting of the OCT unit
Fig. 2 Termination for grounding wire
4 Design and specifications are subject to change without notice S47183De rev.02 2011-03-14
3. Technical information
3.2 Components and accessories
3.1 Introduction
UL listed type of Gerapid is a DC single pole, high-speed, air circuit breaker available in either fixed-mounted or drawout versions. This breaker has been primarily designed for use in traction applications. The new UL version can be can be used as a feeder breaker in various other installations, such as industrial plants (metals industry), as field breakers for motor and generator field applications, and as disconnects for DC drives to name a few. Current ratings from 2500 A up to 6000A and voltage ratings up to 800V are available with UL certification. For different current and voltage ratings please refer to non UL version of the breaker.
3.1.1 Key features and construction overview.
UL listed and type tested up to 200 kA acc. ANSI C37.14. Fixed and draw-out versions with available OEM cell. High speed TRIP with opening delay less 3ms. High speed internal, self-powered, direct acting,
instantaneous and adjustable bidirectional OC release .
High speed electrodynamic impulse release with or without
capacitor and charging unit.
High speed CLOSE (approx. 150 ms), by means of solenoid
drive with integral control circuit.
Mechanical forced tripping device for safe withdrawing. Shunt trip or zero-voltage release for service opening. Up to 8 form C auxiliary contacts. Variable main terminal configurations. Plug connectors for auxiliary circuits. Hand lever for manual actuation. Contact Position indication. Internal power supply with a wide range of input supply
voltage options.
2-stage main contact system. Compact, enclosed and modular design [Fig. 4] with high
serviceability and extensive accessories.
Easily accessible control and auxiliary connections
3.2.1 Contact system
All Gerapid breakers are equipped with a two-stage contact
system [Fig. 5], consisting of a main contact and an arcing contact. With this proven design, the main contact is not subjected to any appreciable wear or tear.
The main contact is made of a silver composite material. The
arcing contact and link braid are made of copper and can be easily replaced.
The flexible bend is linked to the arcing contact by means of
very tight braid.
Flex Braid
Flex Band
Arcing Contact
Main Contacts
Fig. 5 Two -stage contact system
Arc Runner
3.2.2 Arc chute
Compact and modular design of the arc containment system
requires no additional magnetic support and allows small safety clearances with high breaking capacity up to 200 kA.
Because of the compact dimensions, these breakers can be
installed in extremely small enclosures (from 500 mm; 1.65 ft) and offers a cost-effective solution for replacements.
An arc chute adaptor [Fig.43] is used to mount the various arc
chutes for different operating voltages on the breakers. The arc chutes consist of a highly durable, arc-proof material, in which the arc plates have been integrated. The arc plates split the arc into partial arcs and increase the arcing voltage by multiplying the anode and cathode voltage drop. Because of their high heat capacity, the plates and arc chute walls absorb a large amount of the arc’s energy.
Fig. 4 Modular construction overview
2011-03-14 S47183De rev.01 Design and specifications are subject to change without notice 5
3.2.3 Mechanism
The Gerapid is equipped with a modular designed
mechanism, which is wear-resistant and nearly maintenance­free. This mechanism ensures an extended electrical and mechanical endurance of the breaker as well as a high level of safety under all operation conditions.
Breaker can operate 20 000 cycles without maintenance
when opened by the shunt trip or zero voltage release coils, and 1 000 operations by means of impulse coil or OCT releases.
This mechanism is mechanically latched in the CLOSED
position. A mechanically latched mechanism offers advantage compared to often used electro magnet holding system. No auxiliary control power source is required to keep breaker closed.
The mechanism is provided with two tripping latches [Fig. 6].
One latch, called “slow latch”, is used for opening under normal conditions, like actuation of shunt trip or zero-voltage release. The second one, “quick latch”, de-clutches the main contact arm from the mechanism and opens the contacts with an extremely short delay. This is used when interrupting short-circuit or overloads. All safety releases operate onto “quick latch”.
Different main springs are used in mechanisms for different
breaker frames. Therefore mechanisms cannot be exchanged between breakers of different frame.
the flexible armature [3]. During this operation, the armature
hits the seesaw, which releases the quick latch in the mechanism. The latch and contacts are opened immediately.
The OCT is available in either a fixed setting or adjustable over
specific ranges. On the adjustable OCT, the response threshold can be easily adjusted by turning the adjustment nut with a SW6 hexagon wrench. The available ranges are described in the table below. Other ranges might be possible on request.
6
7
Fig. 7 OCT device.
Default tripping bands for the OCT release 1).
1) Customer specific bands on request.
Code OCT bands 2508 4008 5008 6008
A 1.5 kA – 2.5 kA
Fig. 6 Latching and tripping system
3.2.4 Overcurrent release OCT
The OCT release is a magnet with two magnetic circuits,
optimizing the twin magnetic field principle [Fig. 7]. This technology ensures equally fast tripping in both current directions. This system does not require an auxiliary control voltage to operate. It is a direct acting and instantaneous tripping device.
The OCT consists of the holding circuit [6], the movable
armature [3] and the tripping circuit [7]. The holding and the tripping magnetic circuits are both excited by load current [1]. Until the static overload release’s response threshold has been reached, the armature [3] is held in position by the holding flux (H) [2] and the counter spring’s force [4]. Once the load current exceeds the set static response threshold, the attraction flux (A) [2] takes over and rapidly pulls down
6 Design and specifications are subject to change without notice S47183De rev.02 2011-03-14
B 1.5 kA – 3 kA C 1.5 kA – 4 kA D 1.5 kA – 5 kA E 2 kA – 6 kA F 2 kA – 7 kA G 2 kA – 8 kA H 2,5 kA - 5,5 kA J 3 kA – 7 kA K 3 kA – 8 kA
L 3 kA – 9 kA M 3 kA – 12 kA N 5 kA – 10 kA
P 6 kA – 14 kA Q 7 kA – 15 kA
S 8 kA – 18 kA
T 10 kA – 16 kA U 12 kA – 24 kA
3.2.5 ED impulse coil release
ED (electrodynamic) impulse release is a high speed trip coil, and is intended to be used with external protective relays or systems monitoring current increase. External relays must be provided and installed by the customer. The ED coil must be energized by a capacitor storage trip device. An optional internal capacitor trip and control (NEKO), can be furnished with the breaker or must be supplied by the user externally. Rated voltage of 300 V and capacity of 2 000 µF is required. If a fault is detected by the external relay, a firing signal must be sent to the capacitors’ control unit (internal NEKO) causing NEKO unit to discharge its energy into ED coil. If the capacitor and controls are external, then user must supply the 300V directly to the ED coil. The coil releases the quick latch and opens breaker’s contacts in 3-4 ms. ED trip coil is an optional accessory. It can be selected as a complete set consisting of ED coil and electronic control unit with C-bank called NEKO, or just the ED coil with user supplied capacitor trip unit . The external release signal shall be 6 V to 24 V DC, and shall be connected at terminals (-X2 :10 / :11) in standard wiring scheme.
WARNING: Firing signal voltage of 6 VDC to 24 VDC must be filtered. There should be no spikes on the signal of duration less 3 ms. This can lead to defect of the NEKO board. Maximum duration of the firing signal must not exceed ~1 sec. Longer duration can cause the NEKO board to overheat! It is recommended to use an auxiliary breaker contact in series connection with firing circuit (-X2 :10/:11). It will automatically cut off the firing circuit after breaker opening.
WARNING: Manual closing of the breaker with ST installed, while pushbutton OPEN is pressed and control power applied, might lead to ST coil’s overheating and damage.
The UVR [Fig. 9] can be used for remote actuation and, in combination with an internal electronic control, for voltage control. The UVR releases at voltage interruption or supply voltage drop below 20 V. In these cases UVR trips the breaker. It is therefore possible to use this device in combination with the electronic trip unit for voltage monitoring, where an unintended re-start of machines after a temporary voltage breakdown is to be prevented. The UVR is intended for continuous operation. Its rated power is 10 W. Due to its operational mode, the UVR is a self­monitoring device, i.e. when the breaker is tripped upon a break of the pilot wire (EMERGENCY-OFF principle).
Fig. 8 ED impulse coil with seesaw interface
3.2.6 Auxiliary tripping devices
The breaker can be equipped with either a shunt trip (ST) or a
zero voltage release (UVR). It is not possible to have both devices installed in the same breaker. Both devices are interchangeable.
In normal configuration, the internal voltage converter
transforms the external voltage into 24 V DC, which is required by standard ST or UVR. Both devices are tripped by a dry contact connected as shown in section 4.3, [Fig. 27a] and [Fig. 28]. Optionally, the ST can be ordered for connection directly to an external 24 V DC (± 5%), 125 V DC or 220 V DC supply. A double winding shunt trip coil is available with this option for 125/220 V DC external control supply, for back-up or redundancy.
The ST is used for remote actuation and normal opening
operations.. It is designed for short time operation with max. duty cycle of 9 %. ST’s supply is connected through auxiliary breaker contacts, which cut off supply voltage after opening. This protects ST against overheating.
Fig. 9 Zero voltage release in the mechanism’s module.
3.2.7 Forced tripping release
For drawout installations or as an manual trip interlock, the forced tripping release (FT) is installed in the breaker [Fig. 10a].. This unit, which mounts in the breaker base plate, mechanically trips the breaker, by pressing the pin against the seesaw linkage. Force required to trip the breaker is about 30 N (~7 ft-lb). The tripping pin position is as on Fig. 10b.
Fig. 10a Forced tripping release
2011-03-14 S47183De rev.01 Design and specifications are subject to change without notice 7
With a correctly designed interlock in an enclosure, FT provides
safety-tripping function. During withdrawal operation of the trolley, the breaker is tripped BEFORE its main terminals disconnect from the mains.
Fig. 10b Positioning of the forced tripping pin
3.2.8 Manual operation lever
Optionally, a hand lever for manual closing and opening
operation during maintenance is available. This tool must not be use while breaker is energized!
To close the contacts, install hand lever on the drive’s rod, and
pull it out smoothly until latches snap [Fig. 11a].
To open the contacts, install the tool into the ring and push it
hard against the drive’s rod until breaker opens [Fig. 11b].
WARNING: Manual closing and opening – only during maintenance!
WARNING: Manual closing and opening – only during maintenance!
Fig. 11b Opening operation by using hand lever
Alternative manual closing and opening operation is possible
by rotating the main shaft of the breaker mechanism, which is accessible from the side. Use 10 mm hexagon-socket wrench to OPEN/CLOSE [Fig. 11c].
WARNING: Pay attention to control rotation speed of the shaft
during manual opening. Impede the wrench to avoid hitting it to the ground, which may lead to a hand injury.
WARNING: Manual closing and opening – only during maintenance!
Fig. 11c ON/OFF operation by using a 10 mm wrench
Fig. 11a Closing operation by using hand lever
8 Design and specifications are subject to change without notice S47183De rev.02 2011-03-14
3.2.9 Auxiliary switch
UL listed breaker is equipped with 3, 5 or 8 isolated, form C, invertible auxiliary contacts (1 NO/NC each). The movable main arm activates the contacts. The contacts are wired to 15-pin control terminals (-X4 and -X5), on the front of the control box [Fig. 30]. Conventional thermal current rating is10 A. Maximum electrical ratings for switches are 1 A/230 V, 0.5 A/110 V and
0.3 A/220 V.
ARC CHUTE INDICATOR – a potential free, NO contact mounted on the sidewall. Locks electrically the closing drive when arc chute is not installed on [Fig. 15].
Fig. 12 Auxiliary contacts layout in control box
3.2.10 Indicators
POSITION INDICATOR is- mounted at the front of the closing
solenoid. It is mechanically switched by the solenoid’s shaft
and indicates position of the main contacts. Green “OPEN” – means contacts are open Red “CLOSED” – means contacts are closed
Operations Counter
Position Indicator
Fig. 13 Position indicator
Optionally, the circuit breaker can be equipped with following indicators:
OC TRIP TARGET is a potential free, NO contact mounted at
the top of the OCT [Fig. 14]. Provides a signal when OCT
operates.
Fig. 15 Arc chute indicator
3.2.11 Closing solenoid drive
A high power solenoid is used to perform fast closing
operation. This drive is mounted at the front of the breaker and is enclosed in a grounded casing [Fig. 16].
Closing solenoid is supplied from an external power source,
independent from the breaker internal controls. Voltage level must be defined at order placement. Rated power, depends on breaker type, but is between 1.8 kW and 2.6 kW.
CLOSING is enabled by external dry contact closure (-X2 :4/:5).
Minimal close signal duration shall be 100 ms.
The closing drive system always includes a self-interrupt
control circuit (SU circuit board). This circuit enables short activation with a time of ~150 ms. The SU switches power to the solenoid and automatically disconnects it after ~400 ms.
The SU unit also prevents repeated drive closing, due to an
existing and continuous short circuit conditions and provides an “anti-pumping” safety feature.
Fig. 14 OC trip target
2011-03-14 S47183De rev.01 Design and specifications are subject to change without notice 9
Fig. 16 Solenoid closing drive and control box
After a closing attempt, the switch-in mechanism is
electrically blocked for approximately 8 sec. Lock time increases to 14 sec, if internal C-bank (NEKO) is present. This prevents premature closing following a short circuit.
3.2.12 Operation counter
An operations counter is available on the UL Gerapid Breaker. It is an electro-mechanical, non-resettable design, and increments with each open/close cycle as long as control power is available (manual operation of the breaker with control power removed with not increment the counter).
3.2.14 Electronic control system
All the control cards are installed in the upper compartment of the control box [Fig. 18]. There are six slots. Slots 1 and 5 are empty. Starting from left following cards are installed:
Fig, 17.1 Control box with counter.
Fig. 17.2 UL with Close-Stop Interlock and Cover
.
Fig. 18 Control box inside
Slot (2) NEKO control unit [Fig. 19-1] – internal control unit
with capacitor bank. Releases firing signal for ED coil (-X2 :10/:11) and provides indication of the capacitors charging (­X3 :6/:7). NEKO control unit also blocks the firing signal until C­bank is fully charged (~15 sec).
WARNING: NEKO unit requires a high quality firing signal. Be
sure, that voltage level is between 6 V…24 V DC and there are no short spikes on signal (<3 ms). This might lead to major defect of the NEKO control unit!
Fig. 19-1 NEKO control unit
Slot (3) Internal voltage converter [Fig. 19-2] - converts
external supply voltage (-X3:4/:5) to the internal 24 V DC. Required by controls (except for the drive supply).
3.2.13 Remote/Local Close-Stop Interlock
As a standard feature on UL Labeled breakers, the Close-Stop Interlock switch mounted on the control box front cover provides the means to electrically block both local and remote closing signals from closing the breaker. The selector switch can be padlocked in the “Disabled” position for LOTO procedures. The Close-Stop Interlock feature is optional on non-UL breakers.
10 Design and specifications are subject to change without notice S47183De rev.02 2011-03-14
Fig. 19-2 Voltage converter 110V/24 V DC.
3.2.14 Electronic control system
Slot (4) SU control unit – see point 3.2.11
Fig. 19-3 SU control unit.
(6) ST/UVR control unit – simple relay system. It controls
operation of shunt trip or zero voltage release.
Fig. 19-4a UVR control unit
Fig. 19-4b- ST control unit
Fig. 19-4c ST control card for external supply.
2011-03-14 S47183De rev.01 Design and specifications are subject to change without notice 11
12 Design and specifications are subject to change without notice S47183De rev.02 2011-03-14
3.4 Control circuits data
Control box terminals
Closing solenoid drive
Internal voltage converter
1)
1)
for Gerapid 2607, 4207, 6007, 8007
Aux. contact HS 1…HS 8, OC trip target Arc chutes indicator
Shunt trip standard
Shunt trip double winded
UVR
(Zero voltage release) Operating range: OFF < 4 V
ED impulse release
1)
Standard ambient conditions acc. to EN 50123-1 Attachement B. For meeting outside of this standard range, please call back.
1x12-pole AC 400 V, 20 A 4x15-pole AC 250 V, 8 A Rated voltage AC 120 V, 230 V and DC 125 V, 250 V Operating range 80 % - 115 % of rated voltage Power consumption Gerapid 2508 / 4008 1750 W / 2000 W Power consumption Gerapid 5008 / 6008 2600 W / 2600 W Minimal CLOSING command duration 100 ms min.interval between two "CLOSE" operations ~8 s w/o NEKO installed; ~14 s with NEKO Input: Voltage range DC 88 - 145 V Output: Voltage range DC 24 V (±5%) Current 6 A permanent Model description PCMD 150 110 S24W-GE
Input: Voltage range AC 115 - 240 V, DC 125 - 353 V Output: Voltage range DC 24 V (±5%) Current 3 A permanent, 5 A/100 ms Model description PCMA 70 S24W-GE Rated operational voltage Ue/AC 230 V Rated operational current Ie/AC-15 1 A Conventional thermal current Ie/AC-12 (Ith) 10 A
Rated operational voltage Ue/DC 110 V / 220 V Rated operational current Ie/DC-13 0.5 A / 0.3 A Minimum current/voltage ratings 0,1 mA / 6 V DC Contact duty (min. value) DC 10 V / 2 mA Rated voltage/power Uc/Pc 24 V / 100 W Operating range: OFF 21.6 V - 26.4 V Rated voltage/power Uc DC 125 V/ DC 220 V Rated power for a single winding Pc 230 W Rated voltage Uc 24 V
Operating range: ON 24 V (±10%) Power consumption ~ 10 W Required C-bank capacity 2000 µF Charging voltage 300 V Switching interval max. 2/min with 10 consecutive operations Endurance 1 000 operations with 1 operation per 180 s Firing signal level / duration
6 - 24 V / 100 - 1000 ms
Charging signalization relay AC duty AC 250 V/ 0.5 A - AC 120 V /1 A
DC duty : DC 220V/0.1A - DC 125V/0.3A - DC 10V/3A
Table 2a: Technical data of auxiliary circuits
Components Technical datas of control circuits
Us / In
SU-Control CLOSE-push-button -S1 DC 24 V / approx. 10 mA ST releasing push-button-S2 DC 24 V / approx. 4 A short time UVR releasing push-button -S2 ( -X2 :6 / :7) DC 24 V / approx. 10 mA
push-button -S2 ( -X2 :8 / :9 ) DC 24 V / approx. 450 mA
ED-coil tripping w/o NEKO push-button -S3 DC 300 V / 750 A / 3 ms ED-coil tripping with NEKO Connect "Firing signal" at ( -X2 :10 / :11 ) DC 6 V…24 V / approx.20 mA
Table 2b: Control circuits ( directional values to rate the components )
2011-03-14 S47183De rev.01 Design and specifications are subject to change without notice 13
4. Electrical circuits
4.1 Controls layout
Description Designation
X2 1.Connector: Auxiliary- and control circuits X3 2.Connector: Auxiliary- and control circuits X4 3.Connector: Auxiliary contacts HS1...HS5 X5 4.Connector: Auxiliary contacts HS6...HS8
X10 Control board: Voltage converter
X12 Control board: SU control unit X13 Control board: Shunt trip control unit X14 Control board: Zero voltage release X16 Control board: NEKO control unit for ED coil control X20 UL interlock
14 Design and specifications are subject to change without notice S47183De rev.02 2011-03-14
4.2 External connections to the breaker
Fig. 21 Typical terminals wiring system, external customer connections.
2011-03-14 S47183De rev.01 Design and specifications are subject to change without notice 15
4.3 Standard Wiring Diagrams
4.3.1 Wiring Code Positions
The internal wiring for Gerapid breakers is composed of several typical diagrams, for such components as tripping devices and indicators. These basic diagrams are shown on the following pages. The power circuit is not shown for clarity. Using the key numbers and codes shown below, the complete wiring diagram number can be obtained or deciphered. Gray shaded options are not available of UL Listed breakers.
Note: Some special, non-standard circuit requirements may not comply with the wiring diagram coding below. In such cases, the diagram will be assigned a unique number, for example 36/0033. For breaker with special diagrams, a copy of the special diagram is shipped with the breaker.
Fig. 22 Example of code on the nameplate.
16 Design and specifications are subject to change without notice S47183De rev.02 2011-03-14
4.3.2 Breaker Internal Control Power Supply
Breaker Internal Control Power Supply (UL)
Breaker Internal Control Power Supply
Breaker
-X3
User Supplied
User Supplied
Control Power
Control Power
Source
Source
115-240VAC +/- 10%
115-240VAC +/- 10%
or
88-350VDC +/- 10%
or
35-350VDC +/- 10%
4 (+ or ~)
5 (- or N)
Breaker
-X3
User Supplied Control Power
Source
24VDC +/- 5%
4 (+)
5 ( - )
- User external connection point
- Factory interna l c o nn ection point
PCB - Printed Circuit Board
-X10: PCB
1 (+)
3 (-)
-X11: PCB
1 (+)
3 (-)
8 9
10
6 7
8 9
10
6 7
+24VDC +/- 2%
to other PCBs
Ground
+24VDC +/- 2%
to other PCBs
Ground
Fig. 23 Supply with voltage converter or with direct external 24 V DC ±5%.
2011-03-14 S47183De rev.01 Design and specifications are subject to change without notice 17
4.3.3 NEKO control circuit
Firing signal at (-X2 :10/:11) is processed by opto-coupler. Pay attention to the polarity! Closing STOP signal is provided to lock CLOSE command, until capacitors are fully charged. Be sure that voltage level is between DC 6 V - 24 V and there are no transient spikes (<3 ms) on firing signal. This
can lead to major defect of the NEKO control unit!
Maximum duration of the firing command must not exceed ~1 sec. Longer signal might cause NEKO failure! It is
recommended to use one of HS auxiliary contacts connected in series with firing circuit (-X2 :10). It will automatically cut off the firing circuit after breaker opening.
Fig. 25 ED coil with internal NEKO control unit
18 Design and specifications are subject to change without notice S47183De rev.02 2011-03-14
Loading...
+ 42 hidden pages