Product Technical Information
November 5, 2020
Data shown is for the current revision model #. Ensure your nameplate model # matches.
Accessory Connection Diagrams
Performance Characteristics
Model Number:5KS509DAJ6020A
Enclosure is Weather Protected One
NEMA ENCLOSURE WP-I, CSA ENCL DP
THERMOSTAT LEADS TB1-TB2:TRIP
HTR LDS HE1-HE2 115V 350W
UPPER BRG LUBE OIL: 10.25 QTS
LOWER BRG LUBE OIL: 2.5 QTS
0 DEG C TO 40 DEG C :ISO 32(MINERAL OR
SYNTHETIC)
-15 DEG C TO 0 DEG C : ISO 32 SYNTHETIC
ROT CCW FACING TOP LEAD/PH SEQ 1-2-3/1-2-3
VERTICAL NPI
INVERTER DUTY PER NEMA MG1 PART 31
ALTERNATE RATING FOR PWM CONTROL
1.0 SF. VAR TORQUE RANGE 5-60 HZ
SUITABLE FOR 400 HP, 380V, 50 HZ WITH
532 AMPS AND 1485 RPM AT 1.0 S.F