GE Digital STXPBS032, STXPBS132, STXPBS232, STXPBS332, STXPBS016 Specifications

...
Process Automation Control Systems
RSTi Slice I/O
The PROFIBUS and DeviceNet Network Interfaces are also available with built-in I/O to reduce cost and footprint. The network interfaces can be expanded and support all of the RSTi I/O types.
STXPBS032 STXPBS132 STXPBS232
Product Name
Lifecycle Status Active Active Active
Module Type Slave Network Interface Slave Network Interface Slave Network Interface
Field Busses/Device Networks PROFIBUS V1 PROFIBUS V1 PROFIBUS V1
Protocol Supported
Features
Baud Rate 9.6K to 12Mbps 9.6K to 12Mbps 9.6K to 12Mbps
I/O Data Size
LEDs Module Status, Network Status, I/O Status Module Status, Network Status, I/O Status Module Status, Network Status, I/O Status
Diagnostic Supported Yes Yes Yes
Maximum Bus Length 100 meters to 1.2Km depending on baud rate 100 meters to 1.2Km depending on baud rate 100 meters to 1.2Km depending on baud rate
Maximum Number of Nodes Supported
Number of Expansion I/O Supported 8 8 8
Number of Points 32 32 32
System Power Requirement
Field Power Requirement 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC)
Input Type 32 Point 24 VDC Positive Logic 32 Point 24 VDC Negative Logic
Input Voltage Range 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC)
Input Impedance ~5.4K ohms ~5.4K ohms
Input Signal Delay < 0.5msec < 0.5msec
Response Time (ms) < 0.3msec
Trigger Voltage ON State: 9 VDC, OFF State: 5 VDC ON State: 9 VDC, OFF State: 5 VDC
Points per Common 32 32 32
Output Type 32 Point 24 VDC Negative Logic
Output Range Nominal 0 VDC; 11 to 28.8 VDC
Protection
Minimum Output Load
Load Current per Point
Slave Network Interface with
32 Positive Logic Inputs Built-in
Freeze mode, Sync mode,
Auto baudrate, Fail safe mode
PROFIBUS DP Network Slave has
built-in 32 Positive Logic Inputs
with expansion support
Total: Inputs 36 bytes/Outputs 36 bytes total
(4 bytes In/ 4 bytes Out for base module and
32 bytes In/32 bytes Out for expansion
modules); Discrete I/O: Maximum Discrete
I/O: 256 inputs/ 256 outputs; Analog I/O:
16 Channels In/ 16 Channels Out
100 100 100
24 VDC (19.2 to 28.8 VDC) with Current
Limit, Reverse Polarity Protection
Slave Network Interface with
32 Negative Logic Inputs Built-in
Freeze mode, Sync mode,
Auto baudrate, Fail safe mode
PROFIBUS DP Network Slave has
built-in 32 Negative Logic Inputs
with expansion support
Total: Inputs 36 bytes/Outputs 36 bytes total
(4 bytes In/ 4 bytes Out for base module and
32 bytes In/32 bytes Out for expansion
modules); Discrete I/O: Maximum Discrete
I/O: 256 inputs/ 256 outputs; Analog I/O:
16 Channels In/ 16 Channels Out
24 VDC (19.2 to 28.8 VDC) with Current
Limit, Reverse Polarity Protection
Slave Network Interface with
32 Sink Outputs Built-in
Freeze mode, Sync mode
Auto baudrate, Fail safe mode
PROFIBUS DP Network Slave has
built-in 32 Sink Outputs with expansion support
Total: Inputs 36 bytes/Outputs 36 bytes total
(4 bytes In/ 4 bytes Out for base module and
32 bytes In/32 bytes Out for expansion
modules); Discrete I/O: Maximum Discrete
I/O: 256 inputs/ 256 outputs; Analog I/O:
16 Channels In/ 16 Channels Out
24 VDC (19.2 to 28.8 VDC) with Current
Limit, Reverse Polarity Protection
Short protection, Over Temperature
Protection, Over Current Limit
0.5 Amps per point
Output Inrush Current
Polarity Sink
Configuration Tool GSM File GSM File GSM File
Interface Connector Type DB 9 connector (RS-485) DB 9 connector (RS-485) DB 9 connector (RS-485)
Power Dissipation 50 mA typical @ 24 VDC 50 mA typical @ 24 VDC 50 mA typical @ 24 VDC
Connector Type Spring Clamp Terminal Block Spring Clamp Terminal Block Spring Clamp Terminal Block
Internal Power Used (5 VDC loading) 400 mA @ Maximum 5 VDC 400 mA @ Maximum 5 VDC 400 mA @ Maximum 5 VDC
Dimensions (H x W x D) in mm 99 x 83 x 70 99 x 83 x 70 99 x 83 x 70
www.geautomation.com
Automation & Control Systems
1.75
RSTi Slice I/O
Process Automation Control Systems
The PROFIBUS and DeviceNet Network Interfaces are also available with built-in I/O to reduce cost and footprint. The network interfaces can be expanded and support all of the RSTi I/O types.
STXPBS332 STXPBS016 STXPBS116
Product Name
Lifecycle Status Active Active Active
Module Type Slave Network Interface Slave Network Interface Slave Network Interface
Field Busses/Device Networks PROFIBUS V1 PROFIBUS V1 PROFIBUS V1
Protocol Supported
Features
Baud Rate 9.6K to 12Mbps 9.6K to 12Mbps 9.6K to 12Mbps
I/O Data Size
LEDs Module Status, Network Status, I/O Status Module Status, Network Status, I/O Status Module Status, Network Status, I/O Status
Diagnostic Supported Yes Yes Yes
Maximum Bus Length 100 meters to 1.2Km depending on baud rate 100 meters to 1.2Km depending on baud rate 100 meters to 1.2Km depending on baud rate
Maximum Number of Nodes Supported
Number of Expansion I/O Supported 8 8 8
Number of Points 32 16 16
System Power Requirement
Field Power Requirement 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC)
Input Type
Input Voltage Range
Input Impedance
Input Signal Delay
Response Time (ms) < 0.3msec 10msec 10msec
Trigger Voltage
Points per Common 32 4 1
Output Type 32 Point 24 VDC Positive Logic 16 Point Relay 16 Isolated Relay
Output Range Nominal 24 VDC; 11 to 28.8 VDC 5 to 28.8 VDC, 48 VDC , 110 VDC, 250 VAC 5 to 28.8 VDC, 48 VDC , 110 VDC, 250 VAC
Protection
Minimum Output Load 100 micro Amps, 100 millivolts VDC per point 100 micro Amps, 100 millivolts VDC per point
Load Current per Point 0.5 Amps per point
Output Inrush Current
Polarity Source
Configuration Tool GSM File GSM File GSM File
Interface Connector Type DB 9 connector (RS-485) DB 9 connector (RS-485) DB 9 connector (RS-485)
Power Dissipation 50 mA typical @ 24 VDC 50 mA typical @ 24 VDC 50 mA typical @ 24 VDC
Connector Type Spring Clamp Terminal Block Spring Clamp Terminal Block Spring Clamp Terminal Block
Internal Power Used (5 VDC loading) 400 mA @ Maximum 5 VDC 400 mA @ Maximum 5 VDC 400 mA @ Maximum 5 VDC
Dimensions (H x W x D) in mm 99 x 83 x 70 99 x 83 x 70 99 x 83 x 70
Slave Network Interface with
32 Source Outputs Built-in
Freeze mode, Sync mode,
Auto baudrate, Fail safe mode
PROFIBUS DP Network Slave has
built-in 32 Source Outputs
with expansion support
Total: Inputs 36 bytes/Outputs 36 bytes total
(4 bytes In/ 4 bytes Out for base module
and 32 bytes In/32 bytes Out for expansion
modules); Discrete I/O: Maximum Discrete
I/O: 256 inputs/ 256 outputs; Analog I/O:
16 Channels In/ 16 Channels Out
100 100 100
24 VDC (19.2 to 28.8 VDC) with Current
Limit, Reverse Polarity Protection
Short protection, Over Temperature
Protection, Over Current Limit
Slave Network Interface with
16 Relay Outputs
Freeze mode, Sync mode,
Auto baudrate, Fail safe mode
PROFIBUS DP Network Slave has
built-in 16 Relay Outputs
with expansion support
Total: Inputs 32bytes/Outputs 32bytes;
Discrete I/O: 256 inputs/ 256 outputs;
Analog I/O: 16 Channels In/
16 Channels Out
24 VDC (19.2 to 28.8 VDC) with Current
Limit, Reverse Polarity Protection
2 Amps at 5 to 28.8 VDC, 0.8 Amps at
48 VDC, 0.5 Amps at 110 VDC,
2 Amps at 250 VAC
Slave Network Interface with
16 Isolated Relay Outputs
Freeze mode, Sync mode,
Auto baudrate, Fail safe mode
PROFIBUS DP Network Slave has
built-in 16 Isolated Relay Outputs
with expansion support
Total: Inputs 36 bytes/Outputs 36 bytes total
(4 bytes In/ 4 bytes Out for base module
and 32 bytes In/32 bytes Out for expansion
modules); Discrete I/O: Maximum Discrete
I/O: 256 inputs/ 256 outputs; Analog I/O:
16 Channels In/ 16 Channels Out
24 VDC (19.2 to 28.8 VDC) with Current
Limit, Reverse Polarity Protection
2 Amps at 5 to 28.8 VDC, 0.8 Amps at
48 VDC, 0.5 Amps at 110 VDC,
2 Amps at 250 VAC
Automation & Control Systems
1.76
www.geautomation.com
Process Automation Control Systems
RSTi Slice I/O
The PROFIBUS and DeviceNet Network Interfaces are also available with built-in I/O to reduce cost and footprint. The network interfaces can be expanded and support all of the RSTi I/O types.
STXPBS432 STXPBS532 STXPBS824
Product Name
Lifecycle Status Active Active Active
Module Type Slave Network Interface Slave Network Interface Slave Network Interface
Field Busses/Device Networks PROFIBUS V1 PROFIBUS V1 PROFIBUS V1
Protocol Supported
Features
Baud Rate 9.6K to 12Mbps 9.6K to 12Mbps 9.6K to 12Mbps
I/O Data Size
LEDs Module Status, Network Status, I/O Status Module Status, Network Status, I/O Status Module Status, Network Status, I/O Status
Diagnostic Supported Yes Yes Yes
Maximum Bus Length 100 meters to 1.2Km depending on baud rate 100 meters to 1.2Km depending on baud rate 100 meters to 1.2Km depending on baud rate
Maximum Number of Nodes Supported
Number of Expansion I/O Supported 8 8 8
Number of Points 16 In/16 Out 16 In/16 Out 16 In/16 Out
System Power Requirement
Field Power Requirement 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC)
Input Type 16 Point 24 VDC Positive Logic 16 Point 24 VDC Negative Logic 16 Point 24 VDC Positive Logic
Input Voltage Range 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC)
Input Impedance ~5.4K ohms ~5.4K ohms ~5.4K ohms
Input Signal Delay < 0.5msec < 0.5msec < 0.5msec
Response Time (ms) < 0.3msec < 0.3msec 10msec
Trigger Voltage ON State: 9 VDC OFF State: 5 VDC ON State: 9 VDC OFF State: 5 VDC ON State: 9 VDC OFF State: 5 VDC
Points per Common 32 32 16 for Inputs and 4 for Outputs
Output Type 16 Point 24 VDC Positive Logic 16 Point 24 VDC Negative Logic 16 Point Relay
Output Range Nominal 24 VDC; 11 to 28.8 VDC Nominal 24 VDC; 11 to 28.8 VDC 5 to 28.8 VDC, 48 VDC, 110 VDC, 250 VAC
Protection
Minimum Output Load 100 micro Amps, 100 millivolts VDC per point
Load Current per Point 0.5 Amps per point 0.5 Amps per point
Output Inrush Current
Polarity Source Sink
Configuration Tool GSM File GSM File GSM File
Interface Connector Type DB 9 connector (RS-485) DB 9 connector (RS-485) DB 9 connector (RS-485)
Power Dissipation 50 mA typical @ 24 VDC 50 mA typical @ 24 VDC 50 mA typical @ 24 VDC
Connector Type Spring Clamp Terminal Block Spring Clamp Terminal Block Spring Clamp Terminal Block
Internal Power Used (5 VDC loading) 400 mA @ Maximum 5 VDC 400 mA @ Maximum 5 VDC 400 mA @ Maximum 5 VDC
Dimensions (H x W x D) in mm 99 x 83 x 70 99 x 83 x 70 99 x 83 x 70
Slave Network Interface with 16
Positive Logic Inputs and 16 Source
Outputs
Freeze mode, Sync mode,
Auto baudrate, Fail safe mode
Total: Inputs 36 bytes/Outputs 36 bytes total
(4 bytes In/ 4 bytes Out for base module
and 32 bytes In/32 bytes Out for expansion
modules); Discrete I/O: Maximum Discrete
I/O: 256 inputs/ 256 outputs; Analog I/O:
16 Channels In/ 16 Channels Out
100 100 100
24 VDC (19.2 to 28.8 VDC) with Current
Limit, Reverse Polarity Protection
Short protection, Over Temperature
Protection, Over Current Limit
Slave Network Interface with 16
Negative Logic Inputs and 16 Sink
Outputs
Freeze mode, Sync mode,
Auto baudrate, Fail safe mode
Total: Inputs 36 bytes/Outputs 36 bytes total
(4 bytes In/ 4 bytes Out for base module
and 32 bytes In/32 bytes Out for expansion
modules); Discrete I/O: Maximum Discrete
I/O: 256 inputs/ 256 outputs; Analog I/O:
16 Channels In/ 16 Channels Out
24 VDC (19.2 to 28.8 VDC) with Current
Limit, Reverse Polarity Protection
Short protection, Over Temperature
Protection, Over Current Limit
Slave Network Interface with 16
Positive Logic Inputs and 16 Relay
Outputs
Freeze mode, Sync mode,
Auto baudrate, Fail safe mode
Total: Inputs 36 bytes/Outputs 36 bytes total
(4 bytes In/ 4 bytes Out for base module
and 32 bytes In/32 bytes Out for expansion
modules); Discrete I/O: Maximum Discrete
I/O: 256 inputs/ 256 outputs; Analog I/O:
16 Channels In/ 16 Channels Out
24 VDC (19.2 to 28.8 VDC) with Current
Limit, Reverse Polarity Protection
2 Amps at 5 to 28.8 VDC, 0.8 Amps at 48
VDC, 0.5 Amps at 110 VDC, 2 Amps at 250
VAC
www.geautomation.com
Automation & Control Systems
1.77
RSTi Slice I/O
Process Automation Control Systems
The PROFIBUS and DeviceNet Network Interfaces are also available with built-in I/O to reduce cost and footprint. The network interfaces can be expanded and support all of the RSTi I/O types.
STXPBS924 STXPBS825 STXPBS925
Product Name
Lifecycle Status Active Active Active
Module Type Slave Network Interface Slave Network Interface Slave Network Interface
Field Busses/Device Networks PROFIBUS V1 PROFIBUS V1 PROFIBUS V1
Protocol Supported
Features
Baud Rate 9.6K to 12Mbps 9.6K to 12Mbps 9.6K to 12Mbps
I/O Data Size
LEDs Module Status, Network Status, I/O Status Module Status, Network Status, I/O Status Module Status, Network Status, I/O Status
Diagnostic Supported Yes Yes Yes
Maximum Bus Length 100 meters to 1.2Km depending on baud rate 100 meters to 1.2Km depending on baud rate 100 meters to 1.2Km depending on baud rate
Maximum Number of Nodes Supported
Number of Expansion I/O Supported 8 8 8
Number of Points 16 In/16 Out 16 In/16 Out 16 In/16 Out
System Power Requirement
Field Power Requirement 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC)
Input Type 16 Point 24 VDC Negative Logic 16 Point 24 VDC Positive Logic 16 Point 24 VDC Negative Logic
Input Voltage Range 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC)
Input Impedance ~5.4K ohms ~5.4K ohms ~5.4K ohms
Input Signal Delay < 0.5msec < 0.5msec < 0.5msec
Response Time (ms) 10msec 10msec 10msec
Trigger Voltage ON State: 9 VDC, OFF State: 5 VDC ON State: 9 VDC, OFF State: 5 VDC ON State: 9 VDC, OFF State: 5 VDC
Points per Common 16 for Inputs and 1 for Outputs 16 for Inputs and 1 for Outputs 16 for Inputs and 1 for Outputs
Output Type 16 Point Relay 16 Point Isolated Relay 16 Point Isolated Relay
Output Range 5 to 28.8 VDC, 48 VDC , 110 VDC, 250 VAC 5 to 28.8 VDC, 48 VDC, 110 VDC , 250 VAC 5 to 28.8 VDC, 48 VDC, 110 VDC, 250 VAC
Protection
Minimum Output Load
Load Current per Point
Output Inrush Current
Polarity
Configuration Tool GSM File GSM File GSM File
Interface Connector Type DB 9 connector (RS-485) DB 9 connector (RS-485) DB 9 connector (RS-485)
Power Dissipation 50 mA typical @ 24 VDC 50 mA typical @ 24 VDC 50 mA typical @ 24 VDC
Connector Type Spring Clamp Terminal Block Spring Clamp Terminal Block Spring Clamp Terminal Block
Internal Power Used (5 VDC loading) 400 mA @ Maximum 5 VDC 400 mA @ Maximum 5 VDC 400 mA @ Maximum 5 VDC
Dimensions (H x W x D) in mm 99 x 83 x 70 99 x 83 x 70 99 x 83 x 70
Slave Network Interface with 16
Negative Logic Inputs and 16 Relay
Outputs
Freeze mode, Sync mode,
Auto baudrate, Fail safe mode
Total: Inputs 36 bytes/Outputs 36 bytes total
(4 bytes In/ 4 bytes Out for base module
and 32 bytes In/32 bytes Out for expansion
modules); Discrete I/O: Maximum Discrete
I/O: 256 inputs/ 256 outputs; Analog I/O:
16 Channels In/ 16 Channels Out
100 100 100
24 VDC (19.2 to 28.8 VDC) with Current
Limit, Reverse Polarity Protection
100 micro Amps, 100 millivolts VDC per
point
2 Amps at 5 to 28.8 VDC, 0.8 Amps at 48
VDC, 0.5 Amps at 110 VDC, 2 Amps at 250
VAC
Slave Network Interface with 16
Positive Logic Inputs and 16 Isolated
Relay Outputs
Freeze mode, Sync mode,
Auto baudrate, Fail safe mode
Total: Inputs 36 bytes/Outputs 36 bytes total
(4 bytes In/ 4 bytes Out for base module
and 32 bytes In/32 bytes Out for expansion
modules); Discrete I/O: Maximum Discrete
I/O: 256 inputs/ 256 outputs; Analog I/O:
16 Channels In/ 16 Channels Out
24 VDC (19.2 to 28.8 VDC) with Current
Limit, Reverse Polarity Protection
100 micro Amps, 100 millivolts VDC per point 100 micro Amps, 100 millivolts VDC per point
2 Amps at 5 to 28.8 VDC, 0.8 Amps at 48
VDC, 0.5 Amps at 110 VDC, 2 Amps at 250
VAC
Slave Network Interface with 16
Negative Logic Inputs and 16 Isolated
Relay Outputs
Freeze mode, Sync mode,
Auto baudrate, Fail safe mode
Total: Inputs 36 bytes/Outputs 36 bytes total
(4 bytes In/ 4 bytes Out for base module
and 32 bytes In/32 bytes Out for expansion
modules); Discrete I/O: Maximum Discrete
I/O: 256 inputs/ 256 outputs; Analog I/O:
16 Channels In/ 16 Channels Out
24 VDC (19.2 to 28.8 VDC) with Current
Limit, Reverse Polarity Protection
2 Amps at 5 to 28.8 VDC, 0.8 Amps at 48
VDC, 0.5 Amps at 110 VDC, 2 Amps at 250
VAC