8. Additional Information ............................................................................................... 18
2RSTi-EP EPSCPE100 Standalone CPU Quick Start GuideGFK-3012
Page 3
The PACSystems* RSTi-EP EPSCPE100, is an enhanced
performance standalone 1GHz programmable controller
equipped with 1MB of user memory and four Ethernet ports
to run real time deterministic control applications. LAN1 is
dedicated to highspeed Ethernet and LAN2 comprised of 3
switched ports configurable as either an embedded
Ethernet controller or an embedded PROFINET controller,
which provides the PROFINET functionality and supports
only simplex mode of operation. It is a standalone PLC that
supports distributed I/O. From now on in rest of the
document this controller will be referred to as CPE100.
Figure 1: EPSCPE100
Features at a Glance
The CPE100 is programmed and configured over Ethernet
via GE’s Proficy Machine Edition (PME) software. It can
control/process up to 2K I/O points.
Highlights include:
A built-in PACSystems RSTi-EP PLC CPU
oUser may program in Ladder Diagram,
Structured Text, Function Block Diagram.
oContains 1Mbytes of configurable data and
program memory.
oSupports auto-located Symbolic Variables that
can use any amount of user memory.
oReference table sizes include 2k bits for discrete
%I and %Q and up to 2k words each for analog
%AI and %AQ. Bulk memory (%W) also
supported for data exchanges.
oSupports up to 512 program blocks. Maximum
block size is 128KB.
Supports two independent 10/100 Ethernet LANs. LAN1 has only one port and is
dedicated to highspeed Ethernet and whereas LAN2 comprises of 3 switched
ports configurable as either an embedded Ethernet controller or an embedded
1. User Features
GFK-3012 April 2017 3
Page 4
PROFINET controller. All four ports are located on the front panel, as shown in
Figure 1.
The embedded communications interface has dedicated processing capability,
which permits the CPU to independently support LAN1 and LAN2 with:
oup to 16 combined SRTP Server and Modbus TCP Server connections out
of which Modbus TCP cannot exceed more than 8 connections (or) up to
16 simultaneous SRTP Server connections (or) up to 8 simultaneous
Modbus TCP Server connections.
o8 Clients are permitted; each may be SRTP or Modbus TCP or a
Combination of both.
o up to 8 simultaneous Class 1 Ethernet Global Data (EGD) exchanges.
o When used in combination for optimal performance, user must not
exceed 4 Channels for Server (Modbus/SRTP) & 4 Channels for client
(Modbus/SRTP), 8 PROFINET nodes and 8 EGD data exchanges.
Ability to display serial number and date code in PME Device Information Details.
Operating temperature range -40C to 70C (-40F to 158F).
STOP/IO
Disabled
RUN/IO
Enabled
1.1. Membrane Run/Stop push button
Pressing Membrane Run/Stop push button briefly, will change the
state of CPU from the state it is in to the next state. Switch operation
state as given in the following state diagram:
The Run/Stop switch is enabled by default; it can be disabled in PME Hardware
Configuration (HWC) settings.
4RSTi-EP EPSCPE100 Standalone CPU Quick Start GuideGFK-3012
Page 5
LED
LED State
Operating State
OK
On Green
PLC has passed its power-up diagnostics and is
functioning properly
Off
Power is not applied or PLC has a problem.
Blinking; All
other LEDs
off
PLC in STOP/Halt state; possible watchdog timer fault.
If the programmer cannot connect, cycle power and
refer to the fault tables.
RUN
On Green
PLC is in RUN mode.
Off
PLC is in STOP mode.
Blinking; All
other LEDs
off
Indicates that PLC has encountered a fatal error and is
blinking the error code.
Fault
On Green
PLC is in STOP/Faulted mode: a fatal fault has
occurred.
Off
No fatal faults detected.
1.2. LED Indicators (LEDs)
Ethernet Status Indicators
There are two LEDs (Yellow/Green) for each Ethernet ports of LAN1 and LAN2, which
are embedded in the RJ-45 connectors. The green LED indicates an Ethernet
connection has been established. The yellow LED indicates packet traffic.
Module status Indicators
There are three LEDs and one Membrane Push Button on the front panel
(The one in blue color) as shown in the figure. The below table describes
the behavior of each module LED:
Push Button: Toggles the current mode of the PLC.
GFK-3012 April 2017 5
Page 6
EPSCPE100
LAN1
LAN2
Default IP Address:
192.168.0.100
0.0.0.0
Subnet Mask:
255.255.255.0
0.0.0.0
Gateway:
0.0.0.0
0.0.0.0
1.3 Ethernet Ports
LAN 1 connects to the uppermost RJ-45 connector. It is not switched. LAN2 connects
to the three lower RJ-45 connectors. They are switched internally.
The embedded Ethernet interfaces automatically senses the link data rate (10 Mbps or
100 Mbps), communications mode (half-duplex or full-duplex), and cabling
arrangement (straight-through or crossover).
The embedded Ethernet LAN 1 port may be used to communicate with PME
programming software using the Service Request Transport Protocol (SRTP, a
proprietary GE protocol, used primarily for communication with the programmer).
To establish Ethernet communications between the PME programming package and
the CPU, you first need to set an IP address.
Note: LAN2 will not be operational unless it is configured from the programmer with a
valid IP address.
A typical application will take advantage of the two independent LANs. The dedicated
LAN 1 port will be used for communications with plant-level or supervisory layers. The
6RSTi-EP EPSCPE100 Standalone CPU Quick Start GuideGFK-3012
Page 7
Figure 2: Typical Multi-Tier LAN Application (supports only Star/Bus network topology)
switched LAN 2 will be used to communicate with devices over PROFINET within the
manufacturing cell or process.
GFK-3012 April 2017 7
Page 8
2. Hardware Installation
2.1. Initial Checks
Upon receiving your equipment, carefully inspect all shipping containers for damage.
If any part of the system is damaged, notify the carrier immediately. The damaged
shipping container should be saved as evidence for inspection by carrier.
As the consignee, it is your responsibility to register a claim with the carrier for damage
incurred during shipment. GE Automation & Controls will fully cooperate with you,
however, should such action be necessary.
After unpacking the equipment, record all serial numbers. Serial numbers are required
if you should need to contact Customer Care during the warranty period. All shipping
containers and all packing material should be saved should it be necessary to
transport or ship any part of the system.
Verify that all components of the system have been received and that they agree with
your order. If the system received does not agree with your order, contact Customer
Care.
2.2. Installation Location
As shipped, the CPE100 is intended for mounting on a DIN rail. An optional panel-mount
adaptor is also available with part number (ICMFAACC001-AA). If panel-mounting is
required, replace the DIN-rail adaptor with the panel-mount adaptor using the screws
supplied with that adaptor. Both adaptors attach to the rear of the CPE100 chassis
using four Torx M3 screws. Torque newly-installed screws to 5.3 in-Ibs (0.6 Nm) if
installing a new adaptor plate.
Thermal Requirements:
When mounting the CPE100, allow a minimum clearance of 50mm on the left & right
side of the unit and a minimum clearance of 100mm on the top & bottom sides.
Instructions to mount the CPE100 on a DIN Rail:
The CPE100 snaps easily onto the DIN rail. No additional tools are required.
(1) Incline the unit so that the upper hooks of the DIN rail adaptor engage with the
upper edge of the DIN rail.
8RSTi-EP EPSCPE100 Standalone CPU Quick Start GuideGFK-3012
Page 9
(2) Press on the lower part of the unit until you hear a click. The click indicates that the
lower hooks of the DIN rail adaptor have engaged with the lower edge of the DIN rail.
If you need any technical help, please contact Technical Support. For phone numbers
and email addresses, refer to the back cover of this Guide.
Figure 3: Mounting positions of the EPSCPE100 on DIN rail
Instructions to mount the CPE100 on a Panel
(1) Attach the panel mount plate to the rear side of CPE100 using the four M3 screws
supplied with the adapter.
(2) Fasten the tabs of panel mount adapter in the appropriate location of panel with
the four screws. The screw size used for each panel mount tab should not exceed M5.
GFK-3012 April 2017 9
Page 10
Figure 4: Mounting position of the EPSCPE100 in panel
10RSTi-EP EPSCPE100 Standalone CPU Quick Start GuideGFK-3012
Page 11
2.3. Grounding
Proper grounding of the CPE100 is essential using the provided ground terminal as
shown in the below figure. Use a 16-22 AWG braided wire with lugs to connect the
ground terminal of CPE100 to DIN Rail. The DIN rail into which this product will be
mounted must be grounded as per the instructions provided in RSTi-EP System Manual,
GFK-2958.
Figure 5: Ground Terminal of EPSCPE100
GFK-3012 April 2017 11
Page 12
3. Module Start-up
3.1. You Will Need:
This PACSystems standalone controller RSTi-EP CPE100.
Generic power source which can output 9-30 V DC, 5 W.
A DIN rail, typically mounted in an enclosure, as discussed above. Alternately,
mount the unit using the (optional) compatible panel-mount adaptor.
A computer running Proficy Machine Edition (PME) configuration and
programming software. PME Version 9.50 & SIM 1 or later.
Ethernet cable for connecting the PME programmer computer to the EPSCPE100.
Very small slotted screwdriver (1.4mm jeweler’s size).
3.2. Basic Installation Steps:
For startup and configuration of the EPSCPE100, complete the following steps.
1. Be sure to disconnect the power to EPSCPE100,
2. The ESCPE100 is designed to be DIN-rail-mounted.
3. An external power supply 9- 30 V DC provided by a Class II power supply
marked as "double insulated", Limited Power Source (LPS), or a SELV source
with a minimum 32 V dc listed fuse with 3 A max rating is required to power
the EPSCPE100. Wire sizes: 22 to 16 AWG Screw torque: 2 in-Ib. Temperature
rating for copper wire: 80 °C. Wiring to power input terminals shall be limited
to 30 meters in length.
4. Plug the Ethernet cable for Programmer & Protocol (SRTP, Modbus, EGD) on
LAN 1 port.
5. Plug the Ethernet cable for PROFINET network in LAN 1 port.
6. Apply power to EPSCPE100.
12RSTi-EP EPSCPE100 Standalone CPU Quick Start GuideGFK-3012
Page 13
4. Programming the EPSCPE100
To configure the CPE100, connect the computer running the PME programming
software to an Ethernet port of LAN1 using the default IP address 192.168.0.100. PME
9.5 SIM 1 or later is required.
Configuration will either start out using the RSTi-EP CPE100 template when creating a
new project, or will convert an existing project to the CPE100 using the Family Conversion feature in PME.
4.1. Backwards Compatibility
To convert an existing project which uses any other PLC, use the Family Conversion
feature in PME. Be aware of the constraints involved, as will be notified in PME. For
instance, the first PROFINET Controller in an RX3i CPU320 application will be assigned
to the embedded PROFINET Controller feature of the CPE100.
4.2. PROFINET Controller Configuration
An Embedded PROFINET Controller may be configured on LAN2. To enable the
PROFINET Controller in a CPE100 project, select the CPE100 target in the PME Navigator
(Figure 10) and open the Hardware Configuration. On the Settings tab, change the
LAN2 Mode of the selected port to PROFINET. The PROFINET Controller node description
then displays that a PROFINET node exists on the selected LAN (under the CPE100). For
further details, refer to the PACSystems RX3i & RSTi-EP PROFINET IO Controller User
Manual, GFK-2571.
GFK-3012 April 2017 13
Page 14
5. Firmware upgrade procedure
EPSCPE100 comes with the default IP address 192.168.0.100 assigned to the Ethernet
Port of LAN1, user can change the default IP address through PME (Proficy Machine
Edition). Use the Ethernet Port of LAN1 to connect to the webserver of CPE100 through
which user can upgrade the Firmware.
It is always recommended to check if there are any new firmware updates available
for this product at our support site prior to proceeding with upgrading the module
firmware.
Steps are as below (For detailed instructions follow upgrade instructions manual
provided with upgrade kit):
1. Copy the firmware upgrade file (PAC) to any directory on your PC.
2. Use programming software or the controller’s Run/Stop switch place the
Controller module in Stop Disabled mode.
3. If your PC uses a proxy server, it may be necessary to modify your Network
Settings to disable the proxy server (or disable use of automatic proxy
configuration scripts).
4. Open a browser window and go to the EPSCPE100 Controller’s homepage using
the IP address you have configured for Programmer communications (e.g.
http://192.168.0.100).
5. At the EPSCPE100 Controller’s homepage, you will be prompted for a user name
and password. Username is “update” (without the quotes). Password is “sierra”
(without the quotes). Click on Log On.
14RSTi-EP EPSCPE100 Standalone CPU Quick Start GuideGFK-3012
Page 15
6. Click on “Choose File” and navigate to the location of the firmware update file
obtained and saved earlier. Select the file and click “Open”.
7. Click on “Upload File” to get the file upload started. The
EPSCPE100 Controller’s Firmware Update web page will indicate the upload
progress.
8. The firmware upgrade process may take up to four minutes to complete
depending on the module being upgraded. Do not power cycle the EPSCPE100
Controller during the update process as this may place the module being
updated in an unrecoverable and unusable state. Once the file upload is
completed, EPSCPE100 will automatically reset
9. When the firmware upgrade completes successfully the browser will remain on
the Firmware Update web page and will indicate that the upgrade process is
complete. Note: The processing is complete when the DONE status is displayed.
10. If the firmware upgrade is not successful, a Firmware Update Status page is
displayed with an error status.
11. When you have successfully completed the firmware upgrade:
Close your browser window.
Mark or label your EPSCPE100 to indicate the new firmware version.
Ensure the label does not cover any vents.
12. Return the EPSCPE100 Controller to Run Enabled mode using the programming
software.
GFK-3012 April 2017 15
Page 16
6. Product Limitations
1. MRP (Media Redundancy Protocol) is not supported on Release 1.0.
2. C Toolkit is not supported in Release 1.0.
3. Timed interrupt blocks are not supported.
4. RDSD not supported in Release 1.0.
Note: The above features may be supported in the subsequent FW release. Refer to
the data sheet.
16RSTi-EP EPSCPE100 Standalone CPU Quick Start GuideGFK-3012
Page 17
7. Troubleshooting
1. Resetting of the IP Address to default one i.e. 192.168.0.100 or to restore the
controller from undermined state, user need to press the Run/Stop switch during
the power-up (till it gets powered up, approx. 60 sec), this action will reset IP
address back to default one i.e. 192.168.0.100 in addition to this it will also clear
the contents of Flash and RAM.
GFK-3012 April 2017 17
Page 18
Proficy* Logic Developer-PLC Getting Started
GFK-1918
PACSystems* RX3i, RX7i and RSTi-EP CPU Reference Manual
GFK-2222
PACSystems* RX3i, RX7i and RSTi-EP TCP/IP Ethernet
Communications User’s Manual
GFK-2224
PACSystems* RX3i System Manual
GFK-2314
PACSystems* RXi, RX3i, RX7i and RSTi-EP Controller Secure
Deployment Guide
GFK-2830
PACSystems* Rx3i & RSTi-EP PROFINET IO-Controller User Manual
GFK-2571
PACSystems* RX3i, RX7i and RSTi-EP CPU Programmer’s
Reference Manual
GFK-2950
RSTi-EP User’s Manual
GFK-2958
8. Additional Information
User manuals, product updates and other information sources are available on the
Support website, https://ge-ip.force.com/communities/CC_Home, under Controllers and IO, RX3i Controllers.
18RSTi-EP EPSCPE100 Standalone CPU Quick Start GuideGFK-3012
Page 19
GE Automation & Controls
Contact Information
Americas: 1-800-433-2682 or 1-780-420-2010 (if toll free 800 option is
unavailable)
Global regional phone numbers are available on our web site
www.geautomation.com
* Trademark of General Electric Company and/or its subsidiaries.
All other trademarks are property of their respective holders