GE Digital IC755CxS06RDx, IC755CxW07CDx, IC755CxS10CDx, IC755CxS12CDx, IC755CxS15CDx Operating Manual

Page 1
GFK-2847V
QuickPanel Operator
Dec 2016
IC755CxS06RDx (6” Display) IC755CxW07CDx (7” Display) IC755CxS10CDx (10" Display) IC755CxS12CDx (12” Display) IC755CxS15CDx (15” Display)
Manual
Interface
For public
disclosure
Page 2
For public disclosure
These instructions do not purport to cover all details or variations in equipment, nor to provide for every contingency
to be met during installation, operation, and maintenance. The information is supplied for informational
possible
purposes only, and GE makes no warranty as to the accuracy of the information included herein. Changes, modifications, and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein. It is understood that GE may make changes, modifications, or improvements to the equipment referenced herein or to the document itself at any time. This document is intended for trained personnel familiar with the GE products referenced herein.
GE may have patents or pending patent applications covering subject matter in this document. The furnishing of this document does not provide any license whatsoever to any of these patents.
Public – This document is approved for public disclosure.
GE provides the following document and the information included therein as is and without warranty of any kind, expressed or implied, including but not limited to any implied statutory warranty of merchantability or fitness for particular purpose.
For further assistance or technical information, contact the nearest GE Sales or Service Office, or an authorized GE Sales Representative.
Revised: Dec 2016 Issued: Nov 2013
© 2013 - 2016 General Electric Company.
* Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective owners.
We would appreciate your feedback about our documentation. Please send comments or suggestions to controls.doc@ge.com
Page 3
GFK-2847V 3
For public disclosure
Document Updates
Location
Description
Updated ATEX Directive to 14/34/EU
Removed ATEX protection string - refer to the QP+ Operator Interface
Added the procedure for USB retaining clamps used in hazardous
Appendix A Product Certifications and Installation Guidelines, Agency Approval
Conditions of Safe Use for Installation in Hazardous Locations
Installation and Maintenance Requirements (IMR) (GFK-2981)
location installations for 7” Display units
Acronyms and Abbreviations
ARM Advanced RISC Machine BBSRAM Battery-backed SRAM
DRAM Dynamic Random Access Memory
FG Frame Ground FTP File Transfer Protocol GND Ground GUI Graphical user interface HTTP
HyperText Transfer Protocol
LCD Liquid Crystal Display
LED Light-emitting Diode
MIB Management Information Base (or Database)
OS Operating System
PME Proficy Machine Edition
RoHS Restrictions on Hazardous Substances SELV Safety Extra Low Voltage
SNMP Simple Network Management Protocol
USB Universal Serial Bus VESA Video Electronics Standards Association
Page 4
4 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
Safety Symbol Legend
Warning
Caution
Attention
Indicates a procedure or condition that, if not strictly observed, could result in personal injury or death.
Indicates a procedure or condition that, if not strictly observed, could result in damage to or destruction of equipment.
Indicates a procedure or condition that should be strictly followed to improve these applications.
Page 5
GFK-2847V 5
For public disclosure
Contact Information
1-780-420-2010 (if toll free 800 option is unavailable)
GE Intelligent Platforms GmbH
+ 49-821–5034–0
If you purchased this product through an Authorized Channel Partner, then contact the seller directly.
Online technical support and GlobalCare
Additional information
Solution Provider
Technical Support
Contact us by telephone, email, or at http://support.ge-ip.com.
Online Technical Support
Phone
International Americas Direct Dial
Technical Support Email
Customer Care Email
Primary language of support
Online Technical Support
Phone
EMEA Direct Dial
Technical Support Email
Customer Care Email
Primary languages of support
Online Technical Support
Europe (not Germany), Middle East, and Africa (EMEA)
General Contact
http://support.ge-ip.com
http://www.ge-ip.com/
solutionprovider.ip@ge.com
http://support.ge-ip.com
1-800-433-2682
support.ip@ge.com
customercare.ip@ge.com
English
http://support.ge-ip.com
+ 800-1-433-2682
+ 420-23-901-5850 (if toll free 800 option is unavailable or dialing from a
mobile telephone)
support.emea.ip@ge.com
customercare.emea.ip@ge.com
English, French, Italian, Czech, Spanish
http://support.ge-ip.com
Information
Americas
Germany
Address
Phone
Fax
Technical Support Email
Online Technical Support
Phone
Technical Support Email
Customer Care Email
Memminger Str. 14
86159 Augsburg
Germany
+ 800–322–3616
+ 49–821–5034–119
sales.augsburg.ip@ge.com
Asia Pacific
http://support.ge-ip.com
+ 86-400-820-8208
+ 86-21-3217-4826 (India, Indonesia, and Pakistan)
support.cn.ip@ge.com (China)
support.jp.ip@ge.com (Japan)
support.in.ip@ge.com (remaining Asia customers)
customercare.apo.ip@ge.com
customercare.cn.ip@ge.com
(APO)
(China)
Page 6
6 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
Notes
Page 7
GFK-2847V 7
For public disclosure
Contents
1
1.1 Specifications
1.1.1 Physical Specifications and Mounting
Overview ..................................................................................................................................... 9
............................................................................................................................................ 10
1.1.2 Environmental
Specifications ........................................................................................................ 15
Options............................................................................. 10
2
2.1 Physical Characteristics
2.2 LED
3
3.1 Operating System
3.2 Backup
3.3 Storage Manager
3.4 Copy Project to SD
3.5 Proficy Machine Edition Project
3.6 FTP
3.6.1 Remote User Authentication
3.7 HTTP Server
3.8 SNTP
3.9 QuickPanel
3.9.1 Firmware Upgrade
3.10 Display Screen Sensitivity
3.11 Launch
3.12 VNC
3.13 Battery Life
3.14 Simple Network Management Protocol
Hardware.................................................................................................................................. 17
........................................................................................................................... 17
Indicators............................................................................................................................................ 23
2.2.1 Operation Status
2.2.2 Ethernet Port Operation LEDs
LEDs.................................................................................................................... 23
Software .................................................................................................................................... 25
..................................................................................................................................... 25
Utility............................................................................................................................................. 25
...................................................................................................................................... 25
Card ............................................................................................................................ 26
Update................................................................................................... 26
Server .................................................................................................................................................. 27
3.6.2 FTP with Removable Flash Devices
.............................................................................................................................................. 28
Server............................................................................................................................................... 28
+
OS Utilities Settings Tool
......................................................................................................................... 30
3.9.2 Firmware Upgrade for Specific Build
3.9.3 Bypass Startup
3.9.4 Reset Enhanced Security
3.9.5 Enable or Disable
Application .................................................................................................................................. 39
Server ............................................................................................................................................... 40
Prediction............................................................................................................................. 41
3.14.1 Configure Trap
3.14.2 Enable or Disable
3.14.3 Export MIB to SD
3.14.4 Load MIB into SNMP
3.14.5 Data Types Mapping between PME Project and SNMP
3.14.6 Establish SNMP
3.15 Screensaver…………..
Programs ............................................................................................................... 33
................................................................................................................ 35
SNMP
Agent
Tool ................................................................................................................ 38
Destinations........................................................................................................ 49
SNMP
Agent
Card.................................................................................................................. 50
Manager .................................................................................................... 51
Communication ................................................................................................. 52
................................................................................................................................ 53
....................................................................................................... 23
......................................................................................................... 27
.............................................................................................. 27
..................................................................................................... 29
Version................................................................................ 32
....................................................................................................... 36
(SNMP) .................................................................................... 45
.................................................................................................... 50
............................................................. 52
4 Pre-installation
Checks........................................................................................................ 55
4.1 Unpacking and Inspection
4.2 Basic Setup
4.3 Initial
4.3.1 Connecting Input
4.3.2 Initial
............................................................................................................................................ 57
Startup ......................................................................................................................................... 58
Configuration ............................................................................................................ 59
................................................................................................................... 55
Power ..................................................................................................... 58
Page 8
8 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
4.4 Runtime Setup
4.5 Firmware
4.6
Shutdown .............................................................................................................................................. 60
...................................................................................................................................... 59
Updates................................................................................................................................. 60
5 Mounting and
5.1 Protective Sheet
5.2 Mounting Location
5.3 Panel
5.4 Mounting and Installation Procedure
5.5 VESA Arm
5.6 Battery Installation and
5.6.1
5.6.2
5.6.3
5.7
5.7.1 Power Connector Pin-out for IC755CxS06RDx, IC755CxW07CDx, and
5.7.2 Ethernet for IC755CxS06RDx, IC755CxW07CDx, and IC755CxSxxCDx
5.7.3 Serial Port Details
5.7.4 Universal Serial Bus (USB)
5.7.5 Audio (LINE OUT) Details for IC755CxS06RDx, IC755CxW07CDx, and
5.7.6 Audio (MIC IN) Details (Only Applicable to IC755CxS06RDx and
5.7.7 SD Card Slot and Storage
6
6.1 Touchscreen Display
6.2 Keyboard
6.2.1 External Keyboard
6.2.2 Soft Input
6.3 Mouse
6.4
6.5 Memory
6.5.1 DRAM Memory
6.5.2 Memory Allocation
Mounting ......................................................................................................................................... 63
Mounting.................................................................................................................................. 68
IC755CxS06RDx ............................................................................................................................... 70
IC755CxW07CDx............................................................................................................................. 72
IC755CxSxxCDx ............................................................................................................................... 74
Connectors ............................................................................................................................................... 76
Operation ...................................................................................................................................... 89
6.1.1 Display Brightness
6.1.2 Display Backlight
6.1.3 Touchscreen
Configuration............................................................................................................................ 92
........................................................................................................................................................ 92
Printing....................................................................................................................................................... 93
..................................................................................................................................................... 94
7 Secomea Security
7.1 Secomea Configuration
7.2 Secomea
Products .................................................................................................................................... 98
Installation...................................................................................................... 61
Installation .................................................................................................................... 61
................................................................................................................................... 62
..................................................................................................... 66
Replacement .................................................................................................... 69
........................................................................................................................... 78
Ports ..................................................................................................... 84
IC755CxW07CDx).................... 85
............................................................................................................... 86
................................................................................................................................ 89
Adjustment ............................................................................................... 89
Configuration .............................................................................................. 90
Re-calibration ..................................................................................................... 91
(Optional).................................................................................................... 92
Panel ......................................................................................................................... 92
..................................................................................................................... 94
Modification .............................................................................................. 95
(Optional).................................................................................................... 97
Tool .................................................................................................................... 97
IC755CxSxxCDx ........... 76
...................................... 76
IC755CxSxxCDx ............. 85
Appendix A Product Certifications and Installation Appendix B Orderable Part Appendix C IC755CxS10CDx, IC755CxS12CDA, and IC755CxS15CDx Serial Port
Details .......................................................................................................................................................
Guidelines.........................................
Numbers .............................................................................................
101
107
109
Page 9
Overview
For public disclosure
GFK-2847V 9
1 Overview
Note This manual specifically describes the QuickPanel+ IC755CxS06RDx, IC755CxWxxCDx and IC755CxSxxCDx
display units.
The QuickPanel based on an Advanced RISC Machine (ARM) core micro-processor to combine a high-resolution touchscreen operator interface with a variety of communications options. Users can connect to most industrial equipment using the QuickPanel
The QuickPanel+ is equipped with several memory types to satisfy the most demanding applications. A section of Dynamic Random Access Memory (DRAM) is split between the operating system, an object store, and application memory. Additionally, a section of Non-volatile Random Access Flash Memory (NOVRAM), functioning as a virtual hard drive, is divided between the operating system and persistent storage for application programs. Retentive memory is a battery-backed Static Random Access Memory (SRAM) to store and protect data during a power failure.
+
Operator Interface is an all-in-one micro-computer designed for maximum flexibility. The design is
+
communications ports.
QuickPanel+ Operator Interface
Display
Page 10
10 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
1.1 Specifications
Item
Specification
Freescale i.MX535 (1 GHz ARM Cortex A8)
RAM
DDR3 SDRAM 512 MB
ROM
NAND FLASH 256 MB
512 KB (with battery backup)
Operating System
Microsoft Windows Embedded Compact 7
Type
5.7” TFT LCD
320(W) x 240(H) pixels QVGA
65,536
Brightness
Backlight
Touch Panel Type
Analog Resistive
Single-touch
Ethernet Port
1x10Base-T / 100Base-TX
1x RS-232C (COM1) (5-pin connector)
2x USB 2.0 (Type-A) maximum power (5 V at 0.5 A)
USB, Device
1x USB 2.0 (mini Type-B)
Storage
1x Mic In (Mono) (3.5 mm jack), Noise Voltage
1500 V p-p
1µs
Rise Time
1ns
Rated Voltage
24 V dc ±20% (3-pin connector)
Power Consumption
Frame Ground (FG)
Frame Ground (GND) is connected internally to Signal GND
Dimensions (L×W×D)
192 × 137 × 36 mm (7.56 × 5.39 × 1.42 in)
Weight
0.7 Kg (1.54 lb)
183.50 × 128.50 mm (7.22 × 5.06 in)
75 x 75 mm (2.95 x 2.95 in)
1.1.1 Physical Specifications and Mounting Options
1.1.1.1 IC755CxS06RDx Specifications
Processor
Memory
SRAM
Resolution
Display
Color
375 cd/m
LED
2
Touchscreen
Communications
Audio
Noise Immunity
Input power
Mounting Options
Multi-touch
Serial Port USB, Host
1x SD/SDHC card slot
1x Line Out (Stereo) (3.5 mm jack)
Pulse Duration
15 W maximum
Panel Cutout Dimensions VESA Mount
Page 11
Overview
For public disclosure
GFK-2847V 11
1.1.1.2 IC755CxW07CDx Specifications
Item Specification
Processor
Freescale i.MX535 (1 GHz ARM Cortex A8)
RAM
DDR2 SDRAM 512 MB
ROM
SLC NAND 256 MB
SRAM
512 KB (with battery backup)
Operating System
Microsoft Windows Embedded Compact 7
Type
7" Widescreen TFT LCD
Resolution
800(W) x 480(H) pixels WVGA
Color
65,536
Brightness
310 cd/m
Backlight
LED
Touch Panel Type
Projected capacitive
Multi-touch
Two-point
Ethernet Port
1x 10/100Base-T (RJ-45)
Serial Port
1x RS-232 UART port (5-pin connector)
USB, Host
2x USB 2.0 (Type-A) maximum power (5 V at 0.5 A)
USB, Device
1x USB 2.0 (mini Type-B)
Storage
1x SD/SDHC card slot
1x Mic In (Mono) (3.5 mm jack) Noise voltage
1500 V p-p
Pulse duration
1µs
Rise time
1ns
Rated Voltage
24 V dc ±20% (3-pin connector)
Power Consumption
15 W maximum, 0.625 A
Frame Ground (FG)
Frame GND is connected internally to Signal GND
Dimensions (L×W×D)
192 × 137 × 36 mm (7.56 × 5.39 × 1.42 in)
Weight
0.80 kg (1.76 lbs)
183.50 × 128.50 mm (7.22 × 5.06 in)
75 x 75 mm (2.95 x 2.95 in)
Memory
Display
Touchscreen
Communications
2
Audio
Noise Immunity
Input power
Mounting Options
1x Line Out (Stereo) (3.5 mm jack)
Panel Cutout Dimensions
VESA Mount
Page 12
12 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
1.1.1.3 IC755CxS10CDx Specifications
Item Specification
Processor
Freescale i.MX535 (1 GHz ARM Cortex A8)
RAM
DDR3 SDRAM 1 GB
ROM
SLC NAND 512 MB
SRAM
512 KB (with battery backup)
Operating System
Microsoft Windows Embedded Compact 7
Type
10.5" Standard TFT LCD
Resolution
800(W) x 600(H) pixels SVGA
Color
65,536
Brightness
400 cd/m
Backlight
LED
Touch Panel Type
Projected capacitive
Multi-touch
Two-point
2x 10/100Base-T (RJ-45)
1x RS-232 UART port USB, Host
2x USB 2.0 (Type-A) maximum power (5 V at 0.5 A)
USB, Device
1x USB 2.0 (mini Type-B)
Storage
1x SD/SDHC card slot
1x Line Out (Stereo) (3.5 mm jack)
Noise voltage
1500 V p-p
Pulse duration
1µs
Rise time
1ns
Rated Voltage
12/24 V dc ±20% (3-pin connector)
Power Consumption
Frame Ground (FG)
Frame GND is connected internally to Signal GND
Dimensions (L×W×D)
278 × 222 × 65 mm (10.95 × 8.74 × 2.56 in)
Weight
2.40 kg (5.29 lbs)
266 × 210 mm (10.47 × 8.27 in)
100 x 100 mm (3.94 x 3.94 in)
Memory
Display
Touchscreen
Ethernet Port
2
Communications
Audio
Noise Immunity
Input power
Mounting Options
Serial Port
Panel Cutout Dimensions
VESA Mount
1x RS-232/485 port (2x 5-pin connector)
18 W maximum 1.5 / 0.75 A
Page 13
Overview
For public disclosure
GFK-2847V 13
1.1.1.4 IC755CxS12CDx Specifications
Item Specification
Processor
Freescale i.MX535 (1 GHz ARM Cortex A8)
RAM
DDR3 SDRAM 1 GB
ROM
SLC NAND 512 MB
SRAM
512 KB (with battery backup)
Operating System
Microsoft Windows Embedded Compact 7
Type
12.1" Standard TFT LCD
Resolution
800(W) x 600(H) pixels SVGA
Color
65,536
Brightness
450 cd/m
Backlight
LED
Touch Panel Type
Projected capacitive
Multi-touch
Two-point
2x 10/100Base-T (RJ-45)
1x RS-232 UART port
USB, Host
2x USB 2.0 (Type-A) max power (5 V at 0.5 A)
USB, Device
1x USB 2.0 (mini Type-B)
Storage
1x SD/SDHC card slot
1x Line Out (Stereo) (3.5 mm jack)
Noise voltage
1500 V p-p
Pulse duration
1µs
Rise time
1ns
Rated Voltage
12/24 V dc ±20% (3-pin connector)
Power Consumption
30 W maximum, 2.5 / 1.25 A
Frame Ground (FG)
Frame GND is connected internally to Signal GND
Dimensions (L×W×D)
314 × 248 × 65 mm (12.36 × 9.76 × 2.56 in)
Weight
3 kg (6.61 lbs)
Panel Cutout Dimensions
302 × 228 mm (11.89 × 8.98 in)
VESA Mount
100 x 100 mm (3.94 x 3.94 in)
Memory
Display
Touchscreen
2
Communications
Audio
Noise Immunity
Input power
Mounting Options
Ethernet Port
Serial Port
1x 10/100Base-T (RJ-45) for IC755CxS12CDA
1x RS-232/485 port (2x 5-pin connector) (1x 10-pin connector for IC755CxS12CDA)
Page 14
14 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
1.1.1.5 IC755CxS15CDx Specifications
Item Specification
Processor
Freescale i.MX535 (1 GHz ARM Cortex A8)
RAM
DDR3 SDRAM 1 GB
ROM
SLC NAND 512 MB
SRAM
512 KB (with battery backup)
Operating System
Microsoft Windows Embedded Compact 7
Type
15" Standard TFT LCD
Resolution
1024(W) x 768(H) pixels XGA
Color
65,536
Brightness
310 cd/m
Backlight
LED
Touch Panel Type
Projected capacitive
Multi-touch
Two-point
2x 10/100Base-T (RJ-45)
1x RS-232 UART port USB, Host
2x USB 2.0 (Type-A) maximum power (5 V at 0.5 A)
USB, Device
1x USB 2.0 (mini Type-B)
Storage
1x SD/SDHC card slot
1x Line Out (Stereo) (3.5 mm jack)
Noise voltage
1500 V p-p
Pulse duration
1µs
Rise time
1ns
Rated Voltage
12/24 V dc ±20% (3-pin connector)
Power Consumption
30 W maximum, 2.5 / 1.25 A
Frame Ground (FG)
Frame GND is connected internally to Signal GND
Dimensions (L×W×D)
399 × 323 × 70 mm (15.71 × 12.72 × 2.76 in)
Weight
4.46 kg (9.83 lbs)
Panel Cutout Dimensions
379 × 305 mm (14.92 × 12.01 in)
VESA Mount
100 x 100 mm (3.94 x 3.94 in)
Memory
Display
Touchscreen
Ethernet Port
2
Communications
Audio
Noise Immunity
Input power
Mounting Options
Serial Port
1x RS-232/485 port (2x 5-pin connector)
Page 15
Overview
For public disclosure
GFK-2847V 15
1.1.2 Environmental Specifications
Item
IC755CxS06RDx
IC755CxW07CDx
IC755CxS10CDx
IC755CxS12CDx
IC755CxS15CDx
Cooling
Ambient
Ambient
Ambient
Pollution Degree 2, Indoor use
only
5 to 9 Hz single-amplitude 3.5 mm; 9 to 150 Hz
constant-accelerated
velocity 9.8 m/s2; X, Y,
800~1114 hPa, altitude up to 2000 m (6561.68 ft)
Compliant with EU RoHS Directive 2011/65/EU
Enclosure
Note Install the QuickPanel
+
in a well-ventilated location that is not exposed to dust, corrosive gases or liquids, rain,
strong ultra-violet light or direct sunlight, and meets the following specifications.
Natural
convection
Operating Temperature
Storage Temperature
Humidity (Operating and Storage)
Environment Vibration
Resistance Altitude
RoHS
Rating
0 to 55°C (32 to 131
-10 to 60°C (14 to 140
85% RH Non-condensing, wet-bulb temperature: 30°C (86 °F) or less
Z directions 10 time (100 minutes) (Compliance 3502, IEC61131-2 JIS B)
UL
Type 4X rating; IP65 in panel mount only
°F)
°F)
Note For additional product standards and agency approvals, refer to Appendix A.
Page 16
16 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
Notes
Page 17
Hardware
For public disclosure
GFK-2847V 17
2 Hardware
This chapter describes the QuickPanel+ hardware features, including physical characteristics and LED indicators.
2.1 Physical Characteristics
In addition to the primary touchscreen interface, the QuickPanel+ Operator Interface supports a variety of communication ports. The following diagrams illustrate the physical layout of the QuickPanel including locations of status LEDs, communications ports, and connectors.
+
Operator Interface,
Page 18
18 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
144.7 (5.70 in)
1
)
75 (2.95 in)
137 (5.39 in) x 2
192 (7.56 in) x 2
36 (1.42 in) x 2
115.2
(4.5 in)
SD Card
LCD Active Area
115.2 x 86.4 (4.5 x 3.4 in)
USB Device
LINE OUT
MIC IN
Input Power
LAN
USB Host Ports
183.50 (7.22 in) 75 (2.95 in)
Serial Interface
Battery Cover
28.50 (5.06 in
Effective Screw Depth 6 mm (0.24 in)
IC755CxS06RDx Hardware
License Label
Product Nameplate
Features
Page 19
Hardware
For public disclosure
GFK-2847V 19
Indicator LED
Touchscreen
LCD
I
nput
Power
LAN
USB Host
Por
t
s
COM
IC755CxW07CDx Hardware
Features
Note Refer to the section IC755CxW07CDx Specifications for drawing dimensions.
tat
us
S
Battery Cover
SD Card
MICRO USB
LINE OUT
I
N
MIC
Page 20
20 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
SD Card
T
ouchscreen
LCD
A
LAN2
U Hos P
orts
SB
t
N1
L
IC755CxS10CDx Hardware
Note Refer to the section IC755CxS10CDx Specifications for drawing dimensions.
MICRO C
U
SB
O
M2
O
M1 LIN
C
O
UT
Features
Stat
us
E
Indicator L
I
nput
E
P
ower
D
Page 21
Hardware
For public disclosure
GFK-2847V 21
!
!
IC755CxS12CDx Hardware
Features
Note Refer to the section IC755CxS12CDx Specifications for drawing dimensions.
Page 22
22 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
SD Card
T
ouchscreen
LCD
I
Stat
us
ndicator
E
D
L
LAN2
LAN1
USB
MICRO C
Hos
t
SB
U
Port
s
O
M2
COM1
L
INE OUT
I
nput
P
ower
Note Refer to the section IC755CxS15CDx Specifications for drawing dimensions.
IC755CxS15CDx Hardware
Features
Page 23
Hardware
For public disclosure
GFK-2847V 23
2.2 LED Indicators
LED State
QuickPanel+ State
Amber, solid
Operating system starting
Normal operating state
Green, blinking
Backlight off
Red, blinking
Backlight failure
Off
Power not applied to unit
Operating State
Speed
Yellow, on
The QuickPanel+ Operator Interface provides LED indication for the following:
Operation status
Ethernet Port operation
2.2.1 Operation Status LEDs
The QuickPanel+ has one tri-color LED that provides visual operation status indication for IC755CxS06RDx, IC755CxW07CDx, the and IC755CxSxxCDx units.
Green, solid
2.2.2 Ethernet Port Operation LEDs
The Ethernet port has two LED indicators: Speed and Link Activity.
Speed Link Activity
LED
LED State
10/100
Link Activity
Green, on
Link status
Page 24
24 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
Notes
Page 25
Software
For public disclosure
GFK-2847V 25
3 Software
This chapter provides QuickPanel+ software information and procedures to perform the most common tasks.
3.1 Operating System
Note Refer to http://windows.microsoft.com.
The QuickPanel user interface (GUI). It is stored in flash memory and copied to a block of DRAM for execution. The OS automatically starts following QuickPanel
3.2 Backup Utility
+
operating system (OS), Microsoft Windows Embedded Compact 7, is a full 32-bit OS with graphical
+
unit powerup or reset.
Attention
The QuickPanel Registry or Desktop to Flash Memory. The Backup Utility achieves the following:
Stores the Windows Embedded Compact 7 registry (including any control panel settings) in Flash memory
Stores changes (or additions) made to the \Windows sub-tree of the file system in the user block of flash memory
+
is not battery powered; therefore, a Backup Utility feature saves the changes made to the Windows
Run the Backup Utility after configuration changes to the operating system or installing applications, and before shutdown.
3.3 Storage Manager
Note Storage Manager is accessed from the Control Panel folder. Online help is available.
Use Microsoft Storage Manager to repair or format lost or corrupted data volumes existing in the SD Card, battery-backed SRAM (BBSRAM), or USB Flash Keys (thumb drives).
Note Data volumes existing in the main flash file system of the QuickPanel
+
may not be repaired by Storage Manager.
Page 26
26 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
3.4 Copy Project to SD Card
The custom utility Copy Project to SD Card transfers Proficy Machine Edition View and Control projects between compatible QuickPanel
+
units using SD cards.
Caution
To copy a Proficy Machine Edition project to an SD card
1. Verify that there is a blank SD card in the SD card port.
2. Double tap the Copy Project to SD Card icon on the desktop.
3. If the project is secured with an enhanced security password, then the password authentication window will be
displayed. The user shall be able to proceed only when the password is successfully authenticated.
4. From the Copy Project Query confirmation window, tap Yes.
Caution
Before disconnecting power, verify that the copy or update operation is complete (no busy message or wait cursor).
Copying a project while Proficy Machine Edition runtimes are active may cause an incomplete copy to be created if the runtimes are also writing to files in the project folders. If the utility detects this situation, it will notify you to stop the runtimes before making the backup. You will not be able to create a backup while the runtimes are writing files.
3.5 Proficy Machine Edition Project Update
Update a Proficy Machine Edition (PME) application that is currently stored on the QuickPanel+ unit with a revision stored on a
flash device, such as an SD card.
To update a Machine Edition project
1. Insert the flash device containing an upgraded version of the Proficy Machine Edition project into the appropriate port.
2. Restart the unit.
Note Depending on set options, the update may or may not be enabled, or may update automatically. If there is more than one flash device with a valid project copy present, a Select Media confirmation window displays, prompting you to choose with which flash device to update Select the device from the list and click OK to continue. When a valid project is found on the flash device, you will be prompted to install the project or skip it. Tap OK to install or Cancel to skip the installation, and continue to restart. If an invalid project is found, an error message displays. This window must be closed before the unit will restart.
3. Remove the flash device from the port.
Page 27
Software
For public disclosure
GFK-2847V 27
3.6 FTP Server
The File Transfer Protocol (FTP) server included with the QuickPanel+ unit supports standard (RFC 959). It does not support Secure File Transfer Protocol (SFTP) or implicit FTPS, which uses different ports and is based on Secure Shell (SSH) rather than Secure Sockets Layer (SSL).
The FTP server is configured with the Quick Panel+ Setup Tool. By default, the server is not enabled. Once enabled, a background program will run, waiting for clients to connect. Up to ten connections are supported. Sessions that are idle for five minutes are terminated by the server.
The server supports non-secure operation. All information including username, password, and data is transmitted with no encryption and is susceptible to packet sniffing and various FTP attacks.
Note If the server status is changed, the QuickPanel
+
must be restarted before changes take effect.
3.6.1 Remote User Authentication
Note The FTP root directory is available from the QuickPanel
+
as \, and is the root of the flash device.
The server only supports anonymous login with password requested (but not validated). This may prevent some types of attacks and is required by some clients. Once connected, the remote user is logged into the FTP root directory.
3.6.2 FTP with Removable Flash Devices
All removable flash devices remote-FTP users as directories off the FTP root directory. Computer Flash card partitions display as directories such as \SDMemory and USB Flash Keys display as directories such as \Hard Disk. Full access privileges are granted for the client in these folders/devices.
Removable flash device directories are captured when a session is opened and are not changed while the session exists. If you start without an installed SD Card, close your session and log on again to view the SD Card directory. If the SD Card existed when you logged on, and is removed and inserted, it will still work, provided the SD Card’s device name did not change during
reinsertion.
Page 28
28 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
3.7 HTTP Server
The HyperText Transfer Protocol (HTTP) server included with the QuickPanel+ supports standard (RFC 2616). The HTTP server is configured with the Quick Panel+ Setup Tool. By default, the server is not enabled. Once enabled, a background program will run, waiting for clients to connect. From the QuickPanel
+
Operator Interface, the default web page is located in \Windows\www\wwwpub.
The server supports non-secure port 80 operation.
Note If the server status is changed, the QuickPanel
+
must be restarted before changes take effect.
3.8 SNTP Server
The SNTP server included with the QuickPanel+ supports SNTP Version 4 for IPv4, IPv6 and OSI. The SNTP server is configured with the Quick Panel+ Setup Tool. By default, the server is not enabled. Once enabled, the server will refresh the time specified in the setup tool configuration. Pressing the Update Now button immediately obtains the time from the configured time server.
The SNTP server supports non-secure UDP port 123 operation.
Page 29
Software
For public disclosure
GFK-2847V 29
3.9 QuickPanel+ OS Utilities Settings Tool
QuickPanel+ Product
Firmware Build
IC755CxS06RDx (6" Display)
01 (initial
release)
IC755CxW07CDx (7” Display)
IC755CxS10CDx (10” Display)
IC755CxS15CDx (15” Display)
Note DIP switches are set in the OFF position (default) in the factory.
The QuickPanel
+
Operator Interface is equipped with DIP switches to perform control functionality, as follows:
DIP Switch 1 (SW2 Switch) enables firmware upgrade. Firmware upgrade is allowed only after turning this switch in the ON position. It is highly recommended to turn the switch position to OFF after firmware upgrade is completed as a security measurement.
DIP Switch 2 (SW2 Switch) controls Force Startup. Turning this switch to the ON position forces the startup applications to run when the operating system is started.
Note The DIP Switch feature is designed as a security measurement. However, security requirements can also be met using the gesture-based feature.Prior to the listed firmware builds, these operations were only supported using the DIP Switch settings.
Some operators find it difficult to use the DIP Switch settings to perform these functions (such as removing the back plate of the device and adjusting the positions of DIP Switch for each operation). As an alternative to using the DIP Switch settings, the QuickPanel
+
OS Utilities Settings tool contains finger gesture-based utilities to perform the same
operations. This functionality is available with the firmware builds listed in the following table.
QuickPanel+ OS Utilities Settings Tool Support
21
IC755CxS12CDx (12” Display)
12
The tool operation buttons for each utility only respond to a double-tap finger gesture. It will not accept any keyboard or mouse clicks, finger simulator-based inputs, or click inputs from any remote touch-based device. The user can access the tool from the Start menu by selecting Programs, System, and QuickPanel
+
OS Utilities Settings on the device. The
tool can be used to perform the following operations using the double-tap feature, without adjusting the DIP Switch positions:
Firmware Upgrade
Bypass Startup Programs
Reset Enhanced Security
Enable/Disable
SNMP
Agent
For security, only permit these operations when the operator is physically located near the QuickPanel
+
and require that users perform a physical action on the device.
Attention
Page 30
30 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
3.9.1 Firmware Upgrade
Note This utility operates similar to the QuickPanel
The operator can continue to use the QuickPanel
+
Update Tool, which comes with the OS image upgrade binaries.
+
Update Tool to use the DIP Switch feature.
The Firmware Upgrade utility setting enables operators to upgrade the firmware. Firmware updates are not supported over
Ethernet or Serial interfaces. Insert the media (SD Card) containing the required files for firmware upgrade and perform the following procedure.
Note Make sure the copy of required binaries to the SD card is not within a folder.
Note The firmware package contains encrypted .nbo files. Use the PreUpdate.exe tool to decrypt the .nbo files before
using them for upgrade.
After a firmware upgrade, which refreshes the device fresh, the user must download the project again and install their own tools (including third party tools) on the device.
Note It is recommended that the user back up any important data prior to firmware upgrade so that they can replace the data after firmware upgrade if necessary.
If the current firmware build version on the QuickPanel+ is any of the following, refer to the section Firmware Upgrade for Specific Build Version:
• Build 3 or below for IC755CxS06RDx
(6” Display)
• Build 23 or below for IC755CxW07CDx
Attention
(7” Display)
• Build 14 or below for
IC755CxS10CDx
(10" Display), IC755CxS12CDx
(12” Display), and IC755CxS15CDx
(15” Display)
Page 31
Software
For public disclosure
GFK-2847V 31
To perform a firmware upgrade
1. From the Start menu, select Programs, System, and QuickPanel+ OS Utilities Settings Tool to display the
QuickPanel
2. Upgrade the firmware.
+
OS Utilities Settings window.
From the QuickPanel + OS Utilities Settings window , select Firmware
Upgrade, then double- tap Upgrade.
3. The operator interface guides the operator through the firmware upgrade process. After successful upgrade,
restart the device.
4. Download the project and install any site-specific tools, including third party tools, on the device.
Page 32
32 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
3.9.2 Firmware Upgrade for Specific Build Version
The following procedure is applicable to the following QuickPanel+ display units:
QuickPanel+ IC755CxS06RDx (6” Display) with build 3 or below
+
QuickPanel
QuickPanel 14 or below
To perform a firmware upgrade for a specific firmware build version
1. Put the files in the firmware package on the SD Card.
2. Double-click QPPlusUpdate.exe and run the program.
3. Perform the firmware upgrade.
Attention
IC755CxW07CDx (7” Display) with build 23 or below
+
IC755CxS10CDx (10" Display), IC755CxS12CDx (12” Display), and IC755CxS15CDx (15” Display) with build
From the QuickPanel+ Update Tool dialog box, click Upgrad e.
For a QuickPanel+ 7” inch Display unit, the following message displays during the process of firmware upgrade. You must re-run the QPPlusUpdate.exe program after reboot, which means you will run the QPPlusUpdate.exe program a total of two times to complete the upgrade process.
QuickPanel+ 7” inch Display Reboot and Run Program Message
Page 33
Software
For public disclosure
GFK-2847V 33
3.9.3 Bypass Startup Programs
Note This utility functions the same as disabling or enabling the Don’t startup Program functionality using DIP Switch
Position 2.
The Bypass Startup Programs utility enables the operator to choose the gesture-based feature or DIP Switch (Use DIP Switch)
feature to perform the Force Startup operation.
To bypass startup programs and force startup
1. From the Start menu, select Programs, System, and QuickPanel+ OS Utilities Settings Tool to display the
QuickPanel
2. Enable or disable the bypass startup programs feature.
+
OS Utilities Settings window.
From the QuickPanel window , select Bypass Startup
+
OS Utilities
Settings
Prog rams.
To use th e DIP Switch feature to perform operation , select Use DIP
Switch.
To use the double-tap feature to this operation , double -tap
Enab le.
this
perform
Page 34
34 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
If Enable is double- tapped, the startup window displays and all startup
.
programs are enabled to run
If Disab le is double- tapped, the startup window displays . Click Don’t run Startup programs to stop all s
.
from running
If Use DIP Switch is selected, Don’t run StartUp Programs displays on the startup window based on the position of DIP Switch 2.
tart
up programs
Page 35
Software
For public disclosure
GFK-2847V 35
3.9.4 Reset Enhanced Security
The QuickPanel+ Operator Interface is configured using the Proficy Machine Edition (PME) application. Using the PME Enhanced Security feature, users can specify password protection for any network-connected QuickPanel perform certain operations, such as the download operation. Every operation to connect to the device requires a password.
If you forget or do not know your password, the Reset Enhanced Security feature enables a QuickPanel configuration download on the device by permitting the user to disable the Enhanced Security feature using the double-tap feature.
Note Prior to support of the QuickPanel
+
OS Utilities Settings Tool, if the user forgot or did not know their password,
the only resolution was to contact Technical Support to reset the password or upgrade the firmware on the device.
To disable Enhanced Security
1. From the Start menu, select Programs, System, and QuickPanel+ OS Utilities Settings Tool to display the
QuickPanel
2. Disable the Enhanced Security setting.
+
OS Utilities Settings window.
From the QuickPanel + OS Utilities Settings window , select Reset Enhanced Security, then double ­tap Disable.
+
+
device to
Page 36
36 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
3.9.5 Enable or Disable
SNMP
Agent
The QuickPanel+ Operator Interface can be enabled as a Simple Network Management Protocol (SNMP) Agent with the capability to communicate with SNMP Managers for notification of Traps and responding to Query HMI Tag values.
Since it is designed to run over a public network, SNMP communication is disabled by default on the QuickPanel+ device for security reasons. As a security measure, the SNMP feature requires a tactile input gesture to enable and disable SNMP communication.
Note Refer to the section Simple Network Management Protocol (SNMP) for further details.
Note Enabling or disabling SNMP communication is a one-time user configuration.
To enable the
SNMP
Agent
1. From the Start menu, select Programs, System, and QuickPanel+ OS Utilities Settings Tool to display the
QuickPanel
2. Enable SNMP communication.
+
OS Utilities Settings window.
From the QuickPanel+ OS Utilities Settings window, select SNMP.
Double-tap Enabl e to enable SNMP communication .
Attention
SNMP communication is enabled on the device only when the user acknowledges this security dialog box and clicks Yes.
Click Yes to acknowledge the security risk and enable SNMP
communication
.
Page 37
Software
For public disclosure
GFK-2847V 37
Note Any failure or errors while enabling or disabling the SNMP service would be communicated to the user through a dialog box.
To disable the
1. From the Start menu, select Programs, System, and QuickPanel+ OS Utilities Settings Tool to display the
QuickPanel
2. Disable SNMP communication.
SNMP
Agent
+
OS Utilities Settings window.
From the QuickPanel+ OS Utilities Settings window, select SNMP.
Double-tap Disable to disable SNMP communication .
Page 38
38 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
3.10 Display Screen Sensitivity Tool
The QuickPanel+ 7”, 10”, 12”, and 15” display units use capacitive screen technology that is far more responsive than the previously used resistive touchscreen technology. Resistive screens required the operator to firmly press down on the resistive overlay for a response. Capacitive screens rely on the capacitive properties of the operators finger pressing lightly on the screen.
If the operator is wearing gloves, this can affect the operation of the capacitive screens. The thickness of the glove keeps the operator’s finger slightly further from the screen. To accommodate gloved operation, the Sensitivity Tool allows the screen sensitivity to be set to a higher level. Setting the screen sensitivity to High enables the QuickPanel display screen to operate with the user wearing most types of work gloves. For thicker gloves, the user may need to press down more firmly to place the finger closer to the screen, which causes the finger pad to spread out slightly to make a larger capacitive area.
Note Gloved operation works best when the operator is wearing gloves that fit. If the fingers do not extend to the end of the glove, the empty space at the fingertip may make it difficult to operate the display screen while wearing gloves.
Setting the screen sensitivity to Low enables the QuickPanel
+
operator actions to be slow and deliberate as they were
using resistive screens. With low sensitivity, the operator must press firmly down on the display screen for a response.
To modify the Sensitivity Tool
1. From the Start menu, select Programs, System, and Sensitivity Tool to display the Sensitivity Setting window.
2. Set the sensitivity level.
Select the sensitivity level and press OK.
+
Page 39
Software
For public disclosure
GFK-2847V 39
3.11 Launch Application
The Launch application window contains the shortcuts to launch some of the major QuickPanel+ Operator Interface applications.
To launch an application
From the Start menu , select
Programs, System , and Launch Appli catio n.
From the Launch Application window, tap an applicatio n icon to start the application.
If the application is not listed, select to browse f or and select an application, then click to open (start) the application.
Page 40
40 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
3.12 VNC Server
The VNC Server enables remote, visual connectivity to the QuickPanel+ Operator Interface from a laptop computer or a mobile device through the remote VNC Viewers. User authentication of the VNC Server in the QuickPanel by the configuration of the Enhanced Security feature on the device. If the Enhanced Security feature is enabled for the device, a VNC Viewer can connect to the QuickPanel
+
on the VNC Server. Connection is dependent upon user authentication with the correct password. User password entry is validated with the Enhanced Security password. If the Enhanced Security feature is disabled for the device, the VNC Server does not enforce authentication of VNC Viewers.
The VNC Server is automatically launched during QuickPanel+ startup. It can also be launched manually from the Launch Application.
To manually launch the VNC Server: from the Start menu, select Programs, System, Launch Application
and start the VNC Server application.
From the Launch Application window , tap the QP
Server application
Note The VNC server starts approximately 40 sec after the QuickPanel
+
startup process has completed.
+
is determined
+
VNC
icon
.
Page 41
Software
For public disclosure
GFK-2847V 41
3.13 Battery Life Prediction
The QuickPanel+ Operator Interface provides an estimated lifespan of the battery in the device. To display the battery life prediction, the current time on the QuickPanel
+
device must be set. If a battery is not present, the QuickPanel
BatteryStatus tab cannot provide battery life prediction.
To display the battery life prediction: from the Start menu, select System, open the QuickPanel+ Setup tool, and
select the BatteryStatus tab.
+
Battery Life Prediction
Example
Note If the current time is not set on the device, the QuickPanel+ Setup Tool dialog box will not be capable of provide
an accurate battery life prediction.
To set the current time to display battery life prediction
1. If the current time is not set on the device, the QuickPanel+ Setup Tool displays the following message stating that
the current date and time must be set on the device to display the correct battery life prediction.
Click OK and set the current date and time on the device.
Current Time Not Set
Message
Page 42
42 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
2. After setting the current time, open the QuickPanel+ Setup Tool, and select the BatteryStatus tab to display the
correct battery life prediction information.
Example of Battery Life Prediction Displayed After Current Time
Set
3. If the battery was replaced or removed on the QuickPanel+, QuickPanel+ Setup Tool BatteryStatus displays
two possible scenarios related to the battery. (The battery life prediction is estimated based on this selection.)
Battery Status
Options
Page 43
Software
For public disclosure
GFK-2847V 43
4. If the option The battery is not present is selected, a message displays stating that battery life cannot be predicted without a battery installed on the device.
Battery is Not Present
Message
5. If the option The battery was replaced is selected, enter the date of when the battery was first used in a QuickPanel
device. (This date should reflect the date of first use in any QuickPanel+ device, not just the current device.)
+
6. Enter the current date.
Select the current d ate and from the calendar and click Apply.
Select the date from the calendar and click Next.
Page 44
44 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
7. Close and re-open the QuickPanel+ Setup Tool dialog box to display the battery life prediction information.
Close and Reopen
Message
Battery Life Prediction Example after Battery
Replacement
Page 45
Software
For public disclosure
GFK-2847V 45
3.14 Simple Network Management Protocol (SNMP)
The SNMP is an application–layer protocol defined by the Internet Architecture Board (IAB) in RFC1157 that is used for exchanging management information between network devices. It is a part of the Transmission Control Protocol/Internet Protocol (TCP/IP) suite.
The QuickPanel+ Operator Interface is enabled as an Managers
(software tools run independently and are not part of QuickPanel
Send notification of HMI Alarms as Traps
Provide live values for SNMP Manager’s GET/GETNEXT Query calls for HMI Tags
The following diagram illustrates the QuickPanel+ operating as the Traps notification and responding to Query HMI Tag values.
HMI
Tags Alarms System
Info
QuickPanel+ Management Information Base (MIB) Overview
The QuickPanel+ SNMP such. The SNMP Manager uses the MIB to request specific information for the as needed for the SNMP Managers or Network Management System (NMS).
The MIB is a collection of information for managing network elements. It is a plain text file, self-explanatory, and prepared based on the Structure of Management Information (SMI), an adapted subset of Abstract Syntax Notation One (ASN.1) standard and notation.
Attention
The MIB is comprised of managed objects identified as Object Identifier (Object ID or OID). Each Identifier is unique and denotes specific characteristics of a managed device. When queried, the return value of each identifier may be different.
Agent maintains a MIB that describes the managed device parameters like HMI Tags, alarms, and
The QuickPanel+ MIB is follows the SNMP V2c and is also be compatible with SNMP V1 based on the strictness of MIB compilers supported by SNMP Managers.
SNMP
Agent with the capability to communicate with SNMP
+
Operator Interface) for the following purposes:
SNMP
Agent to communicate with a SNMP Manager for
+
QuickPanel
Device
SNMP
Manager
SNMP
Agent and translates the information
Page 46
46 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
The following figure displays the MIB tree structure and the private enterprise number allocated by the Internet Assigned Numbers Authority (IANA) for the GE SNMP products and OID for the QuickPanel
OID for GEIP node: .1.3.6.1.4.1.24893
OID for qppMIB node: .1.3.6.1.4.1.24893.1.5.2.1.1
+
MIB:
It is highly recommended that you pre-load GE MIBs (GEIP-SMI.txt and GEIP-PRODUCTS-MIB.txt
Attention
into SNMP Managers to avoid any MIB compiler errors.
Contact technical support or download the MIBs GEIP-SMI.txt and GEIP-PRODUCTS-MIB.txt copied from the QuickPanel+ device by performing the procedure Export MIB to SD
Card.
in sequence) prior to loading the QuickPanelMIB.mib file
from the Support Site and QuickPanelMIB.mib can be
Page 47
Software
For public disclosure
GFK-2847V 47
The following figure displays the HMI Alarms notification (TRAP information) with alarm objects as part of the Alarm Record. The SNMP Manager is notified with the TRAP information when alarms are generated on the HMI running on a QuickPanel
+
device.
OID for Alarm Trap: .1.3.6.1.4.1.24893.1.5.2.1.1.10
Page 48
48 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
The following figure displays the list of HMI Tags that the SNMP Manager can query to retrieve live values from the HMI running on a QuickPanel
+
device.
Note The list of all HMI tags are populated within the hmiTags node of MIB tree and the HMI Tag access level is currently restricted to Read-only for the SNMP Manager.
OID for starting HMI Tag element (also called Index element): .1.3.6.1.4.1.24893.1.5.2.1.1.50.1.1
If there are 40 HMI tags in total, the last OID would be .1.3.6.1.4.1.24893.1.5.2.1.1.50.1.40
Page 49
Software
For public disclosure
GFK-2847V 49
The following sections provide the procedures to enable and configure the QuickPanel+ device to operate as a
SNMP
Agent and establish communication with a SNMP Manager.
Configure Trap Destinations
Enable or Disable
SNMP
Agent
Export MIB to SD Card
Load MIB into SNMP Manager
Data Types Mapping between PME Project and SNMP
Establish SNMP Communication
3.14.1 Configure Trap Destinations
TRAP Destinations are configured through the QuickPanel+ Setup Tool by providing the IP Address of the SNMP Manager to which Traps should be sent. The user can configure two different Trap Destinations (IP Addresses).
Note If you do not want to be notified of Traps, you do not need to configure Trap Destinations.
To configure Trap Destinations
Attention
1. From the Start menu, select System, open the QuickPanel
2. Configure the Trap destination(s) of the SNMP Manager.
3. Click OK to save the changes.
Close the QuickPanel+ Setup Tool, then re-open the tool to view the configured Trap Destination details from the SNMP Agent tab.
If Trap Destination(s) is/are configured after enabling the it
is highly recommended that you disable and then re-enable the
SNMP
Agent on the
service on the device.
+
Setup Tool, and select the
SNMP
Agent tab.
Enter the IP Address(es) of the SNMP Manager to which Traps should be sent.
SNMP
device,
Agent
Page 50
50 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
3.14.2 Enable or Disable
SNMP communication disabled by default on the QuickPanel+ device for security purposes. To enable or disable SNMP communication using the QuickPanel+ OS Utilities Settings tool refer to the procedure Enable or Disable
Note Enabling or disabling SNMP communication is a one-time user configuration.
SNMP
Agent
SNMP
Agent.
3.14.3 Export MIB to SD Card
With the QuickPanelMIB.mib file to a SD Card.
SNMP
Agent is enabled on the QuickPanel+ device, export the QuickPanel+ Management Information Base (MIB)
Attention
It is highly recommended that you pre-load GE MIBs (GEIP-SMI.txt and GEIP-PRODUCTS-MIB.txt
into SNMP Managers to avoid any MIB compiler errors.
Contact technical support or download the MIBs GEIP-SMI.txt and GEIP-PRODUCTS-MIB.txt copied from the QuickPanel+ device by performing the following procedure.
in sequence) prior to loading the QuickPanelMIB.mib file
from the Support Site and QuickPanelMIB.mib can be
To export the MIB to a SD Card
1. Insert a working SD Card into the external card slot on the QuickPanel+ device.
2. From the Start menu, select System, open the QuickPanel+ Setup Tool, and select the
3. Copy the MIB file to the SD Card.
Click Copy MIB T o SD Card.
SNMP
Agent tab.
Page 51
Software
For public disclosure
GFK-2847V 51
A dialog box displays when the copy is successful or if a failure occurs.
3.14.4 Load MIB into SNMP Manager
After successfully exporting the MIB to a SD Card, archive the QuickPanel+ MIB file to a folder on a machine running with SNMP Manager.
To load the MIB into the SNMP Manager: from the SNMP Manager tool File menu, select Load the MIBs.
Loading MIBs in 3
rd
Party SNMP Manager
Tool
If there are no errors, the MIB will be loaded successfully and the SNMP Manager will be ready for communication with QuickPanel
+
device operating as a
SNMP
Agent.
Page 52
52 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
3.14.5 Data Types Mapping between PME Project and SNMP
PME VIEW Data Types
SNMP Data
Types
BOOL
INTEGER
DINT
INTEGER
LREAL
DISPLAYSTRING
STRING
DISPLAYSTRING
When you configure HMI tags in a PME project and you would like to use them in SNMP communication, all of the HMI tags are mapped to the corresponding data type in SNMP as listed in the following table. To verify this, review the Sequence of HMI Tags object in the MIB file.
Note The PME VIEW LREAL data type is mapped to DISPLAYSTRING to retain the data intact.
You can continue to use the data type override/suffix mechanism in PME for the LREAL data type to represent a INT/DINT if you have configured the data type for driver variables. This enables you to map to the DISPLAYSTRING data type in the SNMP communication as well.
For example, for the GE SRTP driver, you can override the IO Address of LREAL variable LREALVar data type as %R100 [INT]. This maps LREALVar to DISPLAYSTRING in the MIB file.
3.14.6 Establish SNMP Communication
Attention
SNMP communication requires that both the QuickPanel+ device and the SNMP Manager running on a machine are connected on a valid Ethernet network.
To establish SNMP communication with the QuickPanel+ device
1. Download the Project to the network connected QuickPanel+ device and start Runtime.
2. Configure the Trap Destinations with the IP Address of the SNMP Manager.
Note If you do not want to be notified of Traps, you do not need to configure Trap Destinations.
3. Enable a
4. Export the MIB to a SD Card.
5. Auto-discover or connect the QuickPanel+ SNMP
SNMP Manager tool.
The SNMP Manager communicating with QuickPanel Alarms/Trap notification from the QuickPanel
SNMP
Agent.
Agent from the SNMP Manager. Once connected, load the MIB to the
+
device can query values for HMI Tags and receive
+
device operating as a
SNMP
Agent.
Tip If you get out of sequence in the steps for configuring Traps and starting the SNMP service to establish the SNMP communication, enable or disable the
SNMP
Agent again using the QuickPanel+ OS Utilities Setting tool.
Page 53
Software
For public disclosure
GFK-2847V 53
3.15 ScreenSaver
QuickPanel+ shall have the ability to run a video as a screensaver. The configuration for this can be done at the ‘ScreenSaver’ Tab in the ‘QuickPanel+ Setup Tool’ window.
The dialog provides the following options
1) Enabiling\Disabling the ScreenSaver
2) Browsing the video file to be run as the ScreenSaver
3) The elapse idle time setting to trigger the ScreenSaver
Page 54
54 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
Notes
Page 55
Pre-installation Checks
For public disclosure
GFK-2847V 55
4 Pre-installation Checks
This chapter provides information and procedures to perform pre-installation checks of the QuickPanel+ Operator
Interface. Before installing and using the QuickPanel
Unpacking and Inspection
Basic Setup
Initial Startup
Runtime Setup
Firmware Updates
Shutdown
4.1 Unpacking and Inspection
Upon receipt of the QuickPanel+ Operator Interface, carefully inspect all shipping containers for damage. If any part of the system is damaged, notify the carrier immediately. Save the damaged shipping container for inspection by the carrier. It is the consignee’s responsibility to register a claim with the carrier for damage incurred during shipment.
Note For phone numbers and email addresses, refer to the section, Contact Information.
After unpacking the unit, record all serial numbers. These are needed to contact Customer Care during the warranty period. Save all shipping containers and packing material for future transport or shipping. Verify that all system components have been received and agree with the order. If the system received does not agree with your order, contact Customer Care.
+
, complete the following procedures:
Before initial powerup, inspect the unit for loose or damaged components. If damage is found (such as bent component leads or loose components), contact GE Intelligent Platforms for additional instructions.
Do not apply power to the unit if it has visible damage. Applying power to a unit with damaged components may cause additional damage.
Caution
Page 56
56 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
+
QuickPanel
Operator Interface
Battery (Qty 1) (pre- installed)
Serial Port Connector (Qty 1)
Power Connector (Qty 1)
Mounting Brackets (Qty 4)
Protective Sheet (Qty 1) (not shown) Gasket
( Qty 1) (not shown, pre- inst alled)
IC755CxWxxCDx Example Package Contents
Page 57
Pre-installation Checks
For public disclosure
GFK-2847V 57
4.2 Basic Setup
The QuickPanel+ Operator Interface is shipped ready for use after initial configuration.
To power up the unit, connect a dc power supply using the supplied quick-connect plug. Depending on the application, you may also want to connect and configure optional input devices, communications ports, and expansion adapters.
Power
Warning
Warning
Supply
To avoid personal injury or damage to equipment, ensure that the dc supply is disconnected from power and the leads are not energized before attaching them to the unit's power supply plug.
If this equipment is used in a manner not specified by the manufacturer, equipment protection may be impaired.
Optional USB Keyboard and
Basic Setup
Diagram
Mouse
Optional
Serial
I/O
Optional Serial
Ethernet
Connection
I/O
Page 58
58 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
4.3 Initial Startup
You will need the following:
Safety Extra Low Voltage (SELV) and Limited Energy Circuit or
The power terminal block is supplied with the product. For voltage and requirements, refer to the Input Power specifications in the table, General Specifications.
The mating power terminal block supports stranded 30 to 14 AWG (0.05 to 2.00 mm
2
) wires. The user calculates proper gauge wiring for current carrying capacity and loss according to
local regulations.
At a minimum, the cable must be rated for 75°C (167 °F) or more.
USB-compatible keyboard (optional)
USB-compatible mouse (optional)
4.3.1 Connecting Input Power
To connect input power
1. Verify that the power cable is not energized.
2. Loosen the screw clamps on the mating power connector.
3. Strip the insulation from the power cables.
4. Secure the power cable to the mating connector, noting polarity, and
tighten the screw clamps. The torque for the attaching screws is 0.3 Nm (2.66 in-lb).
5. Apply dc power to the unit. During normal startup and operation, the QuickPanel
Solid amber while the QuickPanel+ is starting up
Solid green during normal operation
6. Once power is applied, the QuickPanel splash screen is the initial display.
To skip running any programs included in the StartUp folder: tap
Don’t run Startup programs. The Microsoft Windows Embedded
Compact 7 operating system starts automatically.
+
status LED indicator displays as follows:
+
begins initializing. The
SELV
and Class 2 dc power supply.
M2.5
Mounting
FG
GND +24 V dc
Power Connector
clamps
Screw
M2
clamps
Page 59
Pre-installation Checks
For public disclosure
GFK-2847V 59
4.3.2 Initial Configuration
Perform the following procedure during initial startup.
To configure the QuickPanel
1. Tap Start , point to Settings, then tap Control Panel.
2. Configure the system clock.
+
display
From the
Date and Time
3. From the Control Panel, double-tap System to configure a Network Device Name. Many applications, including Proficy
Historian, require a unique Device Name.
Attention
4. From the Control Panel, double-tap Network and Dial-up Connections to configure network settings.
5. Run the Backup Utility to save the settings.
It is recommended to set a unique Device Name for the QuickPanel+ to avoid future conflicts.
4.4 Runtime Setup
To download an application to a QuickPanel+ Operator Interface, set up a data link between the unit and the development workstation. Refer to the section, Ethernet for IC755CxS06RDx, IC755CxWxxCDx and IC755CxSxxCDx, and the PME online help, Downloading a Machine Edition Project.
Page 60
60 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
4.5 Firmware Updates
Update the unit to the most recent released version of the firmware, with the latest feature upgrades and issues addressed. Firmware updates for the QuickPanel
+
are available on the Support website.
Note The firmware update will remove the application and change the IP Address of the QuickPanel
+
Operator Interface.
Note The firmware package contains encrypted .nbo files. Use the PreUpdate.exe tool to decrypt the .nbo files before using them for upgrade.
4.6 Shutdown
There are no specific dangers associated with a power failure or other unplanned shutdown of the QuickPanel+ unit. In general, programs are retained in flash memory and user data can be retained in BBSRAM. Some operating system settings are retained only with user intervention. Perform the following procedure to properly shut down the QuickPanel
To shut down the QuickPanel+ unit
1. Quit any programs that are running and wait for all file operations to complete.
2. If you have not changed operating system settings (for example, brightness or touchscreen sensitivity), or do not
3. Run the Backup Utility to save changes to operating system settings. When the Backup window displays Completed
+
unit.
want to save the changes, remove ac power from the dc supply.
Successfully, remove power from the dc power supply connected to the QuickPanel+ unit.
Page 61
Mounting and Installation
For public disclosure
GFK-2847V 61
5 Mounting and Installation
This chapter provides the following procedures to mount and install the QuickPanel+ Operator Interface:
Protective Sheet Installation
Mounting Location
Panel Mounting
VESA Arm Mounting
Battery Installation and Replacement
Connectors
5.1 Protective Sheet Installation
To install the protective sheet
1. Remove the protective film from the QuickPanel+ display screen.
2. Wipe the display unit of any dust or fingerprints.
3. Peel back a corner of the clear side of the protective sheet.
4. Begin applying the corner to the display screen.
5. Slowly apply the rest of the protective sheet, smoothing out as you go.
6. Peel the green curing film from the protective sheet.
Page 62
62 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
5.2 Mounting Location
Note Refer to the section, Environmental Specifications.
When mounting the QuickPanel+ Operator Interface, make sure the mounting area allows room to insert and remove the SD card, cables, and mounting brackets. Select a location that allows natural convection air flow from bottom to top of the QuickPanel+ enclosure. Do not mount the QuickPanel+ at an angle more than 30° from the vertical, as illustrated in the following figure.
Mounting
Angle
Page 63
Mounting and Installation
For public disclosure
GFK-2847V 63
5.3 Panel Mounting
To mount the QuickPanel+ in an enclosure, you will need the following equipment:
One #2 Phillips head screwdriver
Mounting brackets (supplied)
The mounting holes for IC755CxS06RDx, IC755CxW07CDx, and IC755CxS10CDx are located on the top and bottom sides of the unit.
IC755CxS06RDx Mounting
Holes
IC755CxW07CDx Mounting
Holes
Page 64
64 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
IC755CxS10CDx Mounting
Holes
The IC755CxS12CDx and IC755CxS15CDx mounting holes are located on the top, bottom, and sides of the unit.
IC755CxS12CDx Mounting
Holes
Page 65
Mounting and Installation
For public disclosure
GFK-2847V 65
IC755CxS15CDx Mounting
Holes
Page 66
66 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
228 mm
(
8.98 in)
128.50 mm (5.06 in)
305
m
m (12.01 in)
210 mm (8.27 in)
5.4 Mounting and Installation Procedure
Observe the following guidelines to properly mount and install the QuickPanel+ Operator Interface:
Note To order replacement gaskets, refer to the part number listed in Appendix B.
The enclosure should be of metal material.
The metal enclosure panel should ensure proper thickness and rigidity suitable to minimize impact to the QuickPanel unit.
The recommended torque for the plastic back cover and interior metal cover for the 10, 12, and 15” QuickPanel display units that is accessed for panel updates and serial port DIP Switches is 0.5 Nm (4.4 in-lb).
To avoid gasket degradation, limit repeated insertions or removals of the unit and retightening of the mounting clips. For full protection, always use a fresh gasket.
The unit will not fit through the cutout with any cables connected, or with the power supply plug inserted in the
socket.
Caution
To install the QuickPanel
1. Cut an opening in the panel according to the specifications in the following figures.
Note Panel cutout tolerances are +0.50, –0.00 mm (+0.02, –0.00 in).
When installing the QuickPanel+ into the panel, pay careful attention while handling the unit so it does not drop and damage the unit.
+
183.50 mm (7.22 in)
266 mm (10.47 in)
Panel T
1.0 to 5.0
(0.04 to 0.20 in)
Panel T
1.6 to 5.0
(0.06 to 0.20 in)
hickness
hickness
:
mm
IC755CxSO6RDx or
Panel Cutout
:
mm
IC755CxS12CDx Panel Cutout Dimensions
IC755CxW07CDx
Dimensions
302 mm ( 11.89 in)
hickness
Panel T
1.6 to 5.0
(0.06 to 0.20 in)
Panel T
hickness
1.6 to 5.0
(0.06 to 0.20 in)
:
mm
IC755CxS10CDx Panel Cutout Dimensions
379 mm (14.92 in)
:
mm
IC755CxS15CDx Panel Cutout Dimensions
+
+
Page 67
Mounting and Installation
For public disclosure
GFK-2847V 67
2. Verify that the gasket is present and properly seated in the bezel channel located on the sides of the unit.
Display Unit
Torque Range
IC755CxS06RDx
0.3 Nm (2.66 in-lb)
IC755CxW07CDx
0.3 Nm (2.66 in-lb)
IC755CxS10CDx
0.7 Nm (6 in-lb)
IC755CxS12CDx
1.0 to 1.2 Nm (8.9 to 10.6 in-lb)
IC755CxS15CDx
1.0 to 1.2 Nm (8.9 to 10.6 in-lb)
3. Insert the QuickPanel+ into the mounting panel cutout.
4. Insert the hook of the mounting bracket into the mounting hole as displayed in the following figure.
5. Tighten the screws on the mounting bracket in a clock-wise direction.
Torque Range for Mounting Clamp Screws
Page 68
68 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
75
mm
(2.95
in)
100 mm
(3.94 in)
5.5 VESA Arm Mounting
Display Unit
Torque Range
IC755CxS06RDx
0.7 to 0.8 Nm (6.2 to 7.1 in-lb)
IC755CxW07CDx
0.7 to 0.8 Nm (6.2 to 7.1 in-lb)
IC755CxSxxCDx
1.0 to 1.2 Nm (8.9 to 10.6 in-lb)
The QuickPanel+ unit can be installed on a commercially available Video Electronics Standards Association (VESA) MIS-D arm, stand, or apparatus that complies with the UL1678 standard.
Note Refer to the mounting arm manual for instructions.
To VESA mount the QuickPanel
following figures).
+
unit: use the mounting holes located on the back of the unit (displayed in the
The mounting holes for IC755CxS06RDx and IC755CxW07CDx attach with M4 screws that are 6 mm (0.24 in) or less in length.
The mounting holes for IC755CxSxxCDx attach with M4 screws that are 8 mm (0.32 in) or less in length.
Torque Range for Mounting M4
Screws
75 mm
75 mm
(2.95
in)
m m 5
7
IC755CxW07CDx or IC755CxS06RDx VESA Mounting Holes
100 mm
(3.94 in)
IC755CxSxxCDx VESA Mounting
Holes
Page 69
Mounting and Installation
For public disclosure
GFK-2847V 69
5.6 Battery Installation and Replacement
Batteries may present a risk of fire, explosion, or chemical burn if mistreated. Do not crush, disassemble, short-circuit, or dispose of in fire.
Warning
Warning
Caution
Attention
Use of batteries not specified for use with the QuickPanel+ product may present a risk of fire or explosion.
Do not recharge, disassemble, heat or incinerate lithium batteries.
Dispose of lithium batteries in accordance with federal, state, and local regulations. Be sure to consult with the appropriate regulatory agencies before disposing of batteries.
1) Replacing the battery should only be performed by trained personnel and in a non-hazardous location.
2) If the QuickPanel+ Operator Interface is VESA mounted, detach from the VESA arm when replacing the battery.
3) The battery should only be replaced when the unit is powered off.
4) Care should be taken to protect and insert the battery with correct polarity.
5) Do not use any metallic item to remove the battery (such as screwdrivers, knives, pliers, and so forth).
6) Be careful to not drop the battery or any associated screws into the unit.
7) Be careful of edges on internal sides of the enclosure and frame.
The PC controller does not start automatically when the battery is replaced in QuickPanel using the #Command in the Proficy Machine Edition (PME) runtime.
+
Operator Interface. After battery replacement, start the controller
Page 70
70 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
5.6.1 IC755CxS06RDx
To install or replace the battery for IC755CxS06RDx
Caution
1. Remove the battery cover by pressing down while sliding outward.
Replace the battery for the IC755CxS06RDx only with GE battery part number IC755ACCBATT.
IC755CxS06RDx Battery Cover
Removal
2. Connect the battery harness connector to the header, noting keyed orientation.
Battery Part Number
I
C755ACC
BATT
IC755CxS06RDx Battery Harness Connection
3. Verify that the positive (red) is down and negative (black) is up.
Page 71
Mounting and Installation
For public disclosure
GFK-2847V 71
4. Wrap the harness connector around to match the following figure. Do not let the harness connector go above the tab.
Harness Connector
Orientation
5. Slide the battery cover into place, taking care not to pinch the harness connector.
Page 72
72 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
5.6.2 IC755CxW07CDx
To install or replace the battery for the IC755CxW07CDx
Caution
1. Remove the battery cover by pressing down while sliding outward.
Replace the battery for the IC755CxW07CDx only with GE battery part number IC755ACCBATT.
2. Connect the battery harness connector to the header, noting keyed orientation.
IC755CxW07CDx Battery Cover Removal
Battery Part Number
IC755ACCBATT
3. Verify that the positive (red) connection is down and the negative (black) connection is up.
Battery Harness
Connection
Page 73
Mounting and Installation
For public disclosure
GFK-2847V 73
4. Wrap the harness connector around to match the following figure. Do not let the harness connector go above the tab.
Harness Connector
Orientation
5. Slide the battery cover into place, taking care not to pinch the harness connector.
Page 74
74 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
5.6.3 IC755CxSxxCDx
To install or replace the battery for the IC755CxSxxCDx
Caution
1. Remove the screws (quantity 7) from the back cover.
Replace the battery for the IC755CxSxxCDx only with GE battery part number IC755ACCBATTNL.
2. Gently press on either side tab to release the back cover.
3. Lift up and remove the back
cover.
IC755CxSxxCDx Screw Locations (Back Cover)
Side Tab for Cover Release
Page 75
Mounting and Installation
For public disclosure
GFK-2847V 75
The battery will be exposed on the back of the unit.
Battery Part Number IC755ACCBATTNL
IC755CxSxxCDx
Battery
4. Gently remove the coin battery and replace with a new one, noting the polarity of the battery.
5. Replace the battery cover and tighten all screws to 0.5 Nm (4.4 in-lb).
Page 76
76 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
5.7 Connectors
Pin #
Signal Name
Pin-out
1
+24 V
dc
2
GND
IC755CxSxxCDx supports both +12 V dc or +24 V dc IN
Pin #
Signal Name
Pin-out
1
TX+
2
TX-
3
RX+
4
NC
5
NC
6
RX-
7
NC
5.7.1 Power Connector Pin-out for IC755CxS06RDx, IC755CxW07CDx, and
IC755CxSxxCDx
Note Refer to the section Connecting Input Power.
Connector: Terminal Euro (Tyco Electronics 284539-3) Mating Connector: (Tyco Electronics 284510-3)
3
5.7.2 Ethernet for IC755CxS06RDx, IC755CxW07CDx, and IC755CxSxxCDx
Note Refer to the section Ethernet Port LED Operation.
The QuickPanel (unshielded-twisted pair, CAT 5) to the unit through the RJ-45 connector(s) on the bottom of the enclosure. LED indicators on the port indicate channel status. The port can be accessed by Windows Embedded Compact 7 network communications or by your application.
+
display is equipped with 10Base-T/100-Base-TX Ethernet port(s). Connect an Ethernet network cable
FG
1 3
5.7.2.1 Ethernet Port Details
Interface: Ethernet 10BASE-T/100BASE-TX
8
Note Dual Ethernet ports are separate ports (only applicable to QuickPanel
NC
Yellow Green
8 1
+
IC755CxSxxCDx 10, 12, and 15" display units)
Page 77
Mounting and Installation
For public disclosure
GFK-2847V 77
5.7.2.2
IP
Address Setting
The QuickPanel+ Operator Interface provides two methods to set an IP address:
DHCP (Dynamic Host Configuration Protocol)
+
The network server assigns an IP address during QuickPanel
initialization. There must be a DHCP server on the connected network for a valid IP address to be assigned. Contact your network administrator to ensure correct DHCP server configuration.
Manual Method Specify the numeric addresses obtained from your network administrator for the QuickPanel
+
IP Address, Subnet
Mask and Default Gateway (if applicable).
Note Run the Backup utility to save the settings.
Page 78
78 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
5.7.3 Serial Port Details
Pin
#
Signal Name
1
TXD
2
RXD
3
RTS
4
CTS
5
SGND
5.7.3.1 IC755CxS06RDx
Adhere to the following guidelines:
A terminal block is supplied with the unit.
2
The mating terminal block supports stranded 30 to 14 AWG (0.05 to 2.00 mm
At a minimum, the cable must be rated for 75°C (167 °F) or more.
Secure the serial cable to the mating connector while noting signal orientation and tighten the screw clamps.
The torque for the attaching screws is 0.3 Nm (2.66 in-lb).
Connectors: Euro Terminal (Tyco Electronics 284539-5) Mating Connectors: Tyco Electronics 284510-5
Serial Port COM1 Details
Interface: RS-232
COM1 Pin Details
) wires.
Pin 1
Pin 5
IC755CxS06RDx Serial Port COM1 Pin-out
Page 79
Mounting and Installation
For public disclosure
GFK-2847V 79
5.7.3.2 IC755CxW07CDx
Signal Name
1
TXD
2
RXD
3
RTS
4
CTS
5
SGND
Adhere to the following guidelines:
A terminal block is supplied with the unit.
2
The mating terminal block supports stranded 30 to 14 AWG (0.05 to 2.00 mm
) wires.
At a minimum, the cable must be rated for 75°C (167 °F) or more.
Secure the serial cable to the mating connector while noting signal orientation and tighten the screw clamps.
The torque for the attaching screws is 0.3 Nm (2.66 in-lb).
Serial Port COM1 Details
Interface: x1 RS-232 Connectors: Euro Terminal (Tyco Electronics 284539-5) Mating Connector: (Tyco Electronics 284510-5)
Pin
#
COM1 Pin
Details
Pin 1
Pin 5
IC755CxW07CDx Serial Port COM1 Pin-out
Page 80
80 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
5.7.3.3 IC755CxSxxCDx
Note For an IC755CxS12CDA serial port, refer to Appendix C IC755CxS12CDA Serial Port Details.
Adhere to the following guidelines:
Terminal blocks are supplied.
2
The mating terminal blocks support stranded 30 to 14 AWG (0.05 to 2.00 mm
) wires.
At a minimum, the cable must be rated for 75°C (167 °F) or more.
Secure the serial cable to the mating connector while noting signal orientation and tighten the screw clamps.
The torque for the attaching screws is 0.3 Nm (2.66 in-lb).
Connectors: Euro Terminal (Tyco Electronics 284539-5) Mating Connectors: Tyco Electronics 284510-5
Serial Port COM1 Details
Interface: RS-232C
Pin #
1 2 3 4 5
COM1 Pin
Details
Signal
TXD RXD RTS CTS
SGND
Name
COM1 COM2
Pin 1 Pin 5
IC755CxSxxCDx Serial Port COM1 Pin-out
Page 81
Mounting and Installation
For public disclosure
GFK-2847V 81
DIPSW
Bit
ON/OFF
1 OFF 2 OFF
3 OFF
4 OFF
5 OFF 6 OFF
7 OFF
8 OFF
1 ON 2 ON 3 ON 4 ON
DIPSW
Bit
ON/OFF
1 OFF 2 OFF
3 OFF
4 OFF
5 ON 6 ON 7 OFF 8 ON
1 ON
2 OFF 3 OFF 4 OFF
RS–232C
RS–485
Signal Name
Signal Name
DATA+
2 RXD TXD-
DATA-
DATA+
4 CTS RXD-
DATA-
5 SGND SG SG
Full-duplex RS–485 is backwards compatible to RS–422 mode.
SW2
SW3
COM2 DIP Switch Setting for
Serial Port COM2 Details
Interface: RS-232C/485 (default is RS-485 Half-duplex)
COM2 Pin
Details
SW4
SW5
RS-232C
Pin #
1
3
Pins 1-3 and 2-4 are connected internally.
Signal Name
COM1
(Full-duplex†)
TXD
RTS
Pin 1 Pin 5
IC755CxSxxCDx Serial Port COM2 Pin-out
COM2
TXD+
RXD+
(Half-duplex†)
Page 82
82 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
DIP SW
Bit
ON/OFF
1 ON 2 ON
3 OFF
4 OFF
5 ON
6 ON
7 OFF 8 OFF
1 OFF 2 OFF 3 OFF 4 OFF
DIP SW
Bit
ON/OFF
1 OFF
2 OFF 3 OFF 4 OFF 5 ON 6 ON 7 OFF 8 ON
1 OFF
2 ON 3 OFF 4 OFF
Example of Full-duplex (RS–422 Mode)
Connection
SW2
SW3
COM2 DIP Switch Setting for
SW4
SW5
RS–422
Example of Half-duplex (RS–485 Mode) Connection
Page 83
Mounting and Installation
For public disclosure
GFK-2847V 83
DIPSW
Bit
ON/OFF
1 ON 2 ON
3 ON
4 ON
5 ON 6 ON
7 OFF
8 OFF
1 OFF 2 OFF 3 OFF 4 OFF
DIPSW
Bit
ON/OFF
1 OFF 2 OFF
3 ON
4 OFF
5 ON 6 ON 7 OFF 8 ON
1 OFF
2 ON 3 OFF 4 ON
SW2
SW3
COM2 DIP Switch Setting for
SW4
SW5
RS–485
Page 84
84 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
5.7.4 Universal Serial Bus (USB) Ports
Signal Name
1
USB_VCC
USB_D-
USB_D+
Signal Name
1 VCC
2 D-
3 D+
4 NC
5 GND
5.7.4.1 USB Host Port Details for IC755CxS06RDx, IC755CxW07CDx, and IC755CxSxxCDx
The QuickPanel+ has two full-speed USB 2.0 host ports. A variety of third party USB peripheral devices are also available. Each connected USB device requires a specific driver. The driver supplied with the QuickPanel keyboard or mouse support; other devices require installation of the custom driver software.
Interface: USB 2.0 Number of Ports: Two Connectors: Type-A connector Maximum Supply Current: 0.5 A (per port)
Pin #
2 3
Pin-out
+
is for optional
4
USB_GND
5.7.4.2 USB Device Port Details for IC755CxS06RDx, IC755CxW07CDx, and IC755CxSxxCDx
The USB device port allows the QuickPanel+ Operator Interface to be used as Slave
device. Interface: USB 2.0 Number of Ports: One Connectors: Type-B Mini connector
Pin #
Pin-out
5 1
Page 85
Mounting and Installation
For public disclosure
GFK-2847V 85
5.7.4.3 Serial USB and Ethernet USB Adapters for All Models Using Adapters
Signal Name
1 GND
2 Lineout R
Signal Name
1 GND
2 Lineout R
Recommended adapters are as follows:
Serial USB adapters based on FTDI chipset
Ethernet USB adapters based on ASIX AX88179 or AX88772B
Note For serial USB adapters (USB to RS-485 and such), configure the correct COM port depicted in the System Info tool and configure the same port in the Driver configuration. In the System Info tool, the USB ports shown (COM3, COM4) are based on the USB connection sequence on the device, and need to be configured accordingly.
5.7.4.4 Wi-Fi Support for All Models Using Adapters
Recommended USB wifi adapters based on the Ralink chipset are as follows:
RT–2070
RT–2870
RT–3070
RT–3071
RT– 3072
5.7.5 Audio (LINE OUT) Details for IC755CxS06RDx, IC755CxW07CDx, and
IC755CxSxxCDx
Interface: LINE OUT (stereo) Number of Ports: One Connectors: φ3.5 mm jack Maximum output level: 1 Vrms
Pin #
Pin-out
1 2
3
Lineout L
3
5.7.6 Audio (MIC IN) Details (Only Applicable to IC755CxS06RDx and
IC755CxW07CDx)
Interface: MIC IN (monaural) Number of Ports: One Connectors: φ3.5 mm jack Maximum output level: 250 mVrms
Pin #
3
Lineout L
Pin-out
1 2
3
Page 86
86 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
5.7.7 SD Card Slot and Storage
The QuickPanel+ is equipped with one standard SD Card port. SD/SDHC memory cards are supported. The SD card slot is spring-loaded for easy insertion and removal.
Note Micro SD slot is not supported on the 6” display unit (IC755CxS06RDx).
Connectors: SD card slot (push in-push out method) Card support: SD/SDHC memory card Maximum capacity: 32 GB
Note During insertion, observe the orientation of the SD card as displayed in the following figures.
IC755CxS06RDx SD Card
Location
IC755CxW07CDx SD Card
Location
Page 87
Mounting and Installation
For public disclosure
GFK-2847V 87
IC755CxSxxCDx SD Card
Location
Page 88
88 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
Notes
Page 89
Operation
For public disclosure
GFK-2847V 89
6 Operation
6.1 Touchscreen Display
The QuickPanel+ Operator Interface features a LED Backlight LCD touchscreen display with two-point touch The
touch technology is based on projected capacitance that allows finger tracking without pressured contact. It is conducive to smooth scrolling and multi-touch gesturing capability. Display brightness and backlight operation can be configured using the QuickPanel
Caution
+
Setup tool available in the program system menu.
Although we recommend the use of the protective sheet, do not operate the touchscreen with any hard materials, such as a screwdriver. This could damage the touchscreen display.
Note IC755CxS06RDx (6” display) is an Analog Resistive touch display that does not support two-point touch capability. Single point gestures such as swipe, pan, and double-tap are supported.
6.1.1 Display Brightness Adjustment
To adjust the brightness of the display
1. Open the QuickPanel+ Setup Tool and select the Backlight tab to display the Backlight Display Properties window.
2. Set the backlight brightness value.
From the Setting backlight brightness drop-down menu ,
select a value between 1 (lowest setting ) and 16 (highest setting ).
3. Tap OK to exit the QuickPanel
4. Run the Backup Utility to save the settings.
+
Setup Tool.
technology.
Page 90
90 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
6.1.2 Display Backlight Configuration
To configure the display backlight
1. Open the QuickPanel+ Setup Tool and select the Backlight tab to display the Backlight Display Properties window.
2. Set the backlight to automatically turn off in a specific amount of time.
Select Automatically turn off the backlight . From the drop-
down menu, select a time between 15 sec to 2 hr.
3. Tap OK to exit the QuickPanel
+
Setup Tool.
4. Run the Backup Utility to save the settings.
Page 91
Operation
For public disclosure
GFK-2847V 91
6.1.3 Touchscreen Re-calibration
The QuickPanel+ touchscreen is shipped pre-calibrated. However, if there are any issues with touchscreen responsiveness, it may need to be re-calibrated.
To re-calibrate the touchscreen
1. Open the QuickPanel+ Setup tool.
2. Select the TouchPanel tab.
3. Select Recalibrate Touch Screen.
4. Select Recalibrate Touch Sensor.
Note During IC755CxS06RDx or IC755CxW07CDx touchscreen sensor re-calibration, the user is prompted to activate a
switch located in the battery compartment. This is not applicable to any other display units.
5. Remove the battery cover and press the switch.
6. Replace the battery
cover.
Switch
Touchscreen Sensor Calibration Switch
Battery
Cover
Page 92
92 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
6.2 Keyboard Configuration
The QuickPanel+ Operator Interface can be configured to use either or both a hardware keyboard and a software emulation keyboard as operator data input devices. Typically, an optional external hardware keyboard is used when in development mode, while the included Soft Input Panel (SIP) is more applicable in an operational environment.
6.2.1 External Keyboard (Optional)
Any USB-compatible keyboard may be used as an input device for the unit. The USB driver for the keyboard is included with the operating system and no configuration is required. To use an external keyboard, connect the keyboard to the unit using the USB cable.
6.2.2 Soft Input Panel
The Soft Input Panel (SIP) is a touchscreen keyboard that may be used in place of a standard hardware keyboard. An icon in the system tray enables the user to view or hide the SIP.
To show or hide the SIP: from the system tray located on the task bar, tap the icon and select Hide Input Panel.
Note When visible, the SIP can be moved around the screen by dragging the title bar to reveal parts of the screen that would be obstructed from view by the SIP.
6.3 Mouse
Any USB-compatible mouse may be used as an input device for the unit. The USB driver for the mouse is included with the operating system and no configuration is required. To use an external mouse, plug it into the appropriate port.
Page 93
Operation
For public disclosure
GFK-2847V 93
6.4 Printing
Warning
USB-connected printers will violate the electrical compliance ratings. They can only be used for maintenance and are not supported as a standard service.
The QuickPanel+ Operator Interface supports printing with PCL v5 compatible laser and inkjet printers. The printer can be connected by either USB (on models with USB ports) or by a network shared printer over Ethernet. The control panel applet Printers is used to configure the port connection and other general printing options.
For the fastest printing performance, select draft mode and portrait orientation, and disable color for print settings. These settings also minimize the amount of memory needed to print a document.
The built-in driver has a document spooling function to improve GUI performance. This spooler supports only one document at a time. However, on an Ethernet connected printer, the print server usually supports multiple documents in its queue. Windows Embedded Compact 7 does not support the ability to observe which documents are queued up at the printer.
For a list of printers that are compatible with that QuickPanel+ Operator Interface, refer to the document Third Party Device Compatibility (KB8259).
Page 94
94 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
6.5 Memory
6.5.1 DRAM Memory
The QuickPanel+ Operator Interface is equipped with Dynamic RAM (DRAM). Part of the DRAM is reserved for the Windows operating system and is not accessible by user applications. The remaining memory is split between two functions: an object store for temporary file storage and the main memory for running programs.
Typically, compressed programs stored in flash memory are expanded and moved to DRAM for execution. Temporary storage of program variables or data files is also provided by DRAM. Any data stored in DRAM is not retained through a power cycle or restart.
The split between program memory and storage memory can be adjusted as necessary to make more room for one or the other, depending on specific application needs. For example, if an application is short of memory, alter the DRAM memory allocation from the System Properties window.
Setting the Program Memory too low may prevent additional applications from starting, or may cause currently running applications to fail due to lack of memory.
Setting the Storage Memory too low may prevent the saving of files into the object store portion of the file system, which may also cause application failures.
Caution
For the QuickPanel+ 6” display unit, setting the Storage Memory too high or extreme or windows and it may also require a power cycle. It is recommended that the Storage Memory is set to a valid limit.
to
limit may make the device become unresponsive to launch any applications
Page 95
Operation
For public disclosure
GFK-2847V 95
6.5.2 Memory Allocation Modification
To change the memory allocation
1. From the Control Panel, double-tap System to display the System Properties window.
2. From the Memory tab, drag the slider bar to divide into Storage and Program memory. The amount of memory
allocated to and used by each area is displayed in the window. The blue slider bar indicates the current amount of unallocated SDRAM and determines the boundaries within which the slider can move.
System Memory Slider
Bar
Note Storage memory is limited to a maximum of 128 MB. Using the slider bar to increase storage memory will
provide more RAM-based storage in the folder \Object Store.
3. Tap OK to apply the new setting.
4. Run the Backup Utility to save the settings.
Page 96
96 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
Notes
Page 97
Secomea Security (Optional)
For public disclosure
GFK-2847V 97
7 Secomea Security (Optional)
7.1 Secomea Configuration Tool
Note The SiteManager™ and its related GateManager™, LinkManager™ and LinkManager™ Mobile products are
licensed, sold, and supported by Secomea and Secomea’s licensed distributors. Additional information, is available at
www.secomea. com.
Secomea SiteManager software (also known as the Secomea Configuration tool) is installed on QuickPanel Secomea Configuration tool enables the user to configure and enable the QuickPanel
Note It is recommended to have a Network Architect on-site and working with Secomea team to enable this functionality.
To access the Secomea Configuration tool and enable the QuickPanel
1. From the QuickPanel+ Start menu, select Programs to display the Secomea Configuration tool window.
2. Enable the QuickPanel+ device on the Secomea network.
+
on the Secomea network
+
device on the Secomea network.
Select Enable Remote Management and enter the values provided to you by the Secomea team.
+
products. The
Note The Appliance Name can be any name but should be unique so that Secomea network can identify the
device. Proxy Address allows the user to connect from their local network with firewall enabled and blocking ports
80, 443, and
11444. The SiteManager will attempt to establish a connection with and without proxy.
Page 98
98 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
7.2 Secomea Products
Note Activation and deployment of the Secomea product features is optional. SiteManager, GateManager, and
LinkManager products are licensed, sold, and supported by Secomea and Secomea’s licensed distributors. QuickPanel customers wanting to activate licenses for Secomea products can do so at www.secomea.com.
The available Secomea SiteManager (embedded on QuickPanel
+
), GateManager, and LinkManager products are
described as follows:
SiteManager is a device-monitoring front-end feature for multiple industrial devices on a location. Working with GateManager and LinkManager, it ensures uninterrupted and secure access to remote devices over the Internet or a private Wide-area Network (WAN) for all users.
LinkManager is an off-the-shelf software component in Remote Device Management Solutions from Secomea that provides security for external programming and monitoring applications. LinkManager Mobile provides similar functionality for mobile devices.
GateManager is the central component of Secomea’s Industry solution. The GateManager M2M Server operates as a termination point for all LinkManagers and SiteManagers. All connections and the encrypted traffic between LinkManagers and devices controlled by SiteManagers are handled by the GateManager, where all events are also logged.
Note The GateManager is typically offered as a service hosted by Secomea. Users will receive an isolated domain on the GateManager and benefit from central hosting and back-up by Secomea. Or, the user can host their own GateManager.
Additionally, other devices such as PLCs and PCs (in addition to the QuickPanel Secomea network to be part of Secured Communication using the Add Agents feature in the SiteManager GUI. This can be achieved using extended license feature from Secomea.
Note Secomea products installed throughout the application as suggested by the following figure do not intrinsically provide the level of security associated with firewalls. The network architect needs to satisfy himself or herself that the security level required by the application is present in the overall implementation.
+
) can be added as new agents on the
+
Page 99
Secomea Security (Optional)
For public disclosure
GFK-2847V 99
Secomea Products used with QuickPanel+ in Application
Page 100
100 GFK-2847V
For public disclosure
QuickPanel Operator Interface User
Notes