GE Digital IC695ETM001, IC695PNC001, IC695PNS001, IC695CMX128, IC695PBM300 Data sheet

...
Process Automation Control Systems
PACSystems RX3i Controller
Networks and Distributed I/O Systems
The RX3i features a variety of communications options for distributed control and/or I/O. Choose from PROFINET Controller, Ethernet EGD, PROFIBUS-DP, Genius and DeviceNet. These high­performance communication modules are easy to install, quick to configure, and can be provided as “in rack” solutions to reduce engineering design cycles and system complexity. In addition, communication capabilities up to the SCADA level and down to the device (IED) level improve connectivity, and time stamping capabilities deliver insight into operations to improve productivity and uptime.
IC695ETM001 IC695PNC001 IC695PNS001 IC695CMX128
PACSystems RX3i Ethernet
TCP/IP 10/100Mbits, two RJ-45
Product Name
Lifecycle Status Active Active Active Active
Module Type Ethernet PROFINET Controller PROFINET Scanner Reflective Memory
Backplane Support
Number of Slots Module Occupies on Backplane
Protocol Support
Entity Type
Communication Ports
Bus Speed
I/O Device Update Rate N/A Configurable: 1 ms to 512 ms Configurable: 1 ms to 512 ms
Maximum I/O Memory
System Maximum Limits
Network Distance
Bus Diagnostics Yes Yes Yes Network error detection.
Number of Drops Supported
Message Size
Connector Type
Internal Power Used
ports with built-in switch
Universal Backplane Only.
Uses PCI Bus.
1 1 1 1
SRT, Ethernet Global Data (EGD),
Channels (Client and Server),
Modbus TCP (Client and Server)
Client/Server Master I/O Device (Scanner) Deterministic Peer to Peer.
Two RJ-45 ports one MAC Address Two RJ-45 and Two SFP Cages
10/100Mbaud 10/100/1000Mbaud 10/100/1000Mbaud Network link speed of 2.1 Gigabits/
N/A 128 Kbytes of combined input/
N/A Up to 4 PNC001 per CPU IO
Network Dependent 100 meters for copper
Network Dependent 64 Drops
N/A N/A N/A Up to 128 Mbytes reflective memory
Two RJ-45 Two RJ-45 and two optional SFP
840 mA @ 3.3 VDC; 614 mA @ 5 VDC 3.3 V: 0.5 A with no SFP devices
PROFINET Controller (PNC)
module, connects a PACSystems
RX3i controller to a high-speed
PROFINET local area network.
It enables the RX3i controller to
communicate with IO-Devices on
the LAN.
Universal Backplane Only.
Uses PCI Bus.
PROFINET PROFINET None Required
(SFPs not included, available
separately). 5 MAC addresses.
output memory per PROFINET
Controller
64 IO-Devices per Network
255 IO-Devices across 4 PROFINET
controllers per CPU
256 PROFINET Slots per device
2048 Number of PROFINET
Submodules per CPU
Up to 70,000 meters with Fiber
256 Subslots
plug connectors for copper or fiber
(single or multimode) connections
installed 1.2 A maximum (two SFP
devices installed, 0.35 A per SFP
device) 5 V: 1.5 A maximum
PACSystems RX3i PROFINET
Scanner (PNS) module, connects
a remote node of 90-30 or RX3i
modules to a PROFINET IO-
Controller
Universal Backplane Only.
Uses PCI Bus.
Two RJ-45 and Two SFP Cages
(SFPs not included, available
separately). 5 MAC addresses.
2880 bytes total: 1440 bytes of input
data, 1440 bytes of output data
1 PNS per rack
32 input status bits and
32 output control bits
100 meters for copper
Up to 70,000 meters with Fiber
Supports number of modules
allowed per rack
Does not support LRE for
Series 90-30 expansion racks
Two RJ-45 and two optional SFP plug connectors for copper or fiber (single or multimode) connections
3.3 V: 0.5 A with no SFP devices
installed 1.2 A maximum (two SFP
devices installed, 0.35 A per SFP
device) 5 V: 1.5 A maximum
RX3i Control Memory Xchange
Module for Peer to Peer network.
128Megbytes of user
shared memory.
Universal Backplane Only.
Uses PCI Bus.
Programmable Interrupt support.
sec. Network transfer rate of 43 Mbyte/s (4 byte packets) to 174
Mbyte/s (64 byte packets)
Multimode Fiber up to 300 meters
between nodes. 10Km when
HUB is used
256
with parity. Dynamic packet sizes
of 4 to 64 bytes, automatically controlled by the CMX module
Fiber optic LC type, conforms to
IEC 61754-20; Zirconium ceramic
ferrule; Insertion loss 0.35 dB
(maximum); Return loss -30 dB
660 mA @ 3.3 VDC; 253 mA @ 5 VDC
www.geautomation.com
Automation & Control Systems
1.41
PACSystems RX3i Controller
Process Automation Control Systems
Networks and Distributed I/O Systems
The RX3i features a variety of communications options for distributed control and/or I/O. Choose from PROFINET Controller, Ethernet EGD, PROFIBUS-DP, Genius and DeviceNet. These high­performance communication modules are easy to install, quick to configure, and can be provided as “in rack” solutions to reduce engineering design cycles and system complexity. In addition, communication capabilities up to the SCADA level and down to the device (IED) level improve connectivity, and time stamping capabilities deliver insight into operations to improve productivity and uptime.
IC695PBM300 IC695PBS301 IC694BEM331 IC694DNM200
PACSystems RX3i PROFIBUS
Product Name
Lifecycle Status Active Active Active Active Module Type PROFIBUS Master PROFIBUS Slave Genius Bus Controller DeviceNet Master
Backplane Support
Number of Slots Module Occupies on Backplane
Protocol Support
Master Module, Supports DPV1
Class 1 and Class 2.
Universal Backplane Only.
Uses PCI Bus.
1 1 1 1
PROFIBUS DPV1 PROFIBUS DPV1 Genius DeviceNet
PACSystems RX3i PROFIBUS
Slave Module, Supports DPV1
Class 1 and Class 2.
Universal Backplane Only.
Uses PCI Bus.
PACSystems RX3i
Genius Bus Controller
No Backplane Restrictions CPU Rack Only
PACSystems RX3i
DeviceNet Master Module
Entity Type Master Slave Master Master
PROFIBUS DB-9 connector PROFIBUS DB-9 connector Screw Terminal Screw Terminal
Communication Ports
Bus Speed 12Mbaud 12Mbaud 153.6Kbaud 500Kbaud
I/O Device Update Rate
Maximum I/O Memory
System Maximum Limits
Network Distance
Bus Diagnostics
Number of Drops Supported
Message Size
Baud Rate Dependent. Supports
all standard data rates (9.6 kBit/s,
19.2 kBit/s, 93.75 kBit/s, 187.5 kBit/s, 500 kBit/s, 1.5 MBit/s, 3
MBit/s, 6 MBit/s and 12 MBit/s)
Yes, Slave Status Bit Array Table,
Network Diagnostic Counters,
DP Master Diagnostic Counters,
Firmware Module Revision, Slave
Diagnostic Address
Up To 125 (Requires repeater
every 25 nodes)
244 bytes of input and 244 bytes
of output for each slave. Not to
exceed 3584 bytes input and
3584 bytes outputs total for the
system.
PROFIBUS Connector PROFIBUS Connector Screw Terminal Screw Terminal
Baud Rate Dependent. Supports
all standard data rates (9.6 kBit/s,
19.2 kBit/s, 93.75 kBit/s, 187.5 kBit/s, 500 kBit/s, 1.5 MBit/s, 3
MBit/s, 6 MBit/s and 12 MBit/s)
Yes, Alarms Yes Yes
N/A 32 64
244 bytes of input and
244 bytes of output
7500 feet (2286 meters) at 38.4 Kbaud; 4500 feet (1371 meters)
at 76.8 Kbaud; 3500 feet (1066
meters) at 153.6 Kbaud extended;
2000 feet (609 meters) at 153.6
Kbaud standard. Maximum length
at each baud rate also depends on
cable type.
128 bytes 127 bytes
500Kbaud 100 meters to 125Kbaud
500 meters. Maximum length at
each baud rate also depends on
cable type.
Connector Type
Internal Power Used
Automation & Control Systems
1.42
420 mA @ 5 VDC 420 mA @ 5 VDC 300 mA @ 5 VDC 300 mA @ 5 VDC
www.geautomation.com
Loading...
+ 1 hidden pages