![](/html/1e/1ee2/1ee20c26517c58c59b713a8dba3a77344732d69dc47481781cbab71bfd066fbc/bg1.png)
PACSystems RX3i Controller
Process Automation Control Systems
Resistive I/O Module
The Resistive module allows the user to easily connect to resistive loads without the need of
external devices.
IC695ALG600 Resistive IC695ALG508 Resistive
Universal Analog and configurable for Current,
Product Name
Lifecycle Status Active Active
Module Type Resistive Input Resistive (and RTD) Input Channel to Channel Isolation
Backplane Support Universal Backplane Only. Uses PCI Bus. Universal Backplane Only. Uses PCI Bus.
Number of Slots Module Occupies
on Backplane
Range 0 to 250 / 500 / 1000 / 2000 / 3000 / 4000 Ohms 250 / 500 / 1000 / 2000 / 3000 / 4000 Ohms
Diagnostics
Number of Channels 8 8
Channel-to-Channel Isolation Two Groups of Four 250 VAC Continuous 1500 VAC 1 minute 2550 VDC 1 second
Notch Filter Yes N/A
Resolution
Accuracy
Input Impedance >1M ohm N/A
Input Filter Response Configurable: 8Hz, 12Hz, 16Hz, 40Hz, 200Hz, 1000Hz Configurable: 2.3Hz, 4Hz, 4.7Hz, 24Hz, 28Hz
A/D Conversion Type Sigma Delta Sigma Delta
A/D Conversion Time
Maximum Voltage Input ±14.5 VDC continuous N/A
Connector Type IC694TBBx32, IC694TBSx32 or IC694TBC032. Sold Separately. IC694TBBx32, IC694TBSx32 or IC694TBC032. Sold Separately.
Internal Power Used 400 mA @ 5 V; 350 mA @ 3.3 V 150 mA @ 5 V; 300 mA @ 3.3 V
Voltage, RTD, Thermocouple and Resistive.
High Density (8 Channel) Requires Cold Junction
Compensation; are available for Thermocouple
configurations (IC695ACC600 contains 2 CJCs)
1 1
Open wire, short circuit, positive/negative rate of change, High,
High-High, Low, Low-Low
32-bit IEEE floating point or 16-bit integer
(in 32-bit field) input data format
Calibrated Accuracy at 25ºC. Better than 0.1% of range.
Accuracy depends on A/D filter, data format, input noise, and
ambient temperature.
(Assumes 2 ADC’s running in parallel, no CJC or lead resistance)
10ms per Channel 4 Channels = 40ms (1KHz filter) 127ms per
Channel 4 Channels = 508ms (8Hz filter) Channels that are
disabled are not scanned, shortening scan time.
Isolated Resistive Input module (also supports RTD)
provides eight isolated differential Resistive or RTD input
channels. Each channel can be individually configured
for 2, 3, 4 wire RTD or Resistance.
Open wire, short circuit, positive/negative rate of change, High,
High-High, Low, Low-Low
32-bit IEEE floating point or 16-bit integer
(in 32-bit field) input data format
Calibrated Accuracy at 25ºC. Typical is ± 0.5%
15 msec @ 28 Hz to 120 msec @ 2.3 Hz
Automation & Control Systems
1.40
www.geautomation.com