GE Digital IC200MDD840, IC200MDD842, IC200MDD843, IC200MDD844, IC200MDD845 Data sheet

...
Process Automation Control Systems
VersaMax Control
Discrete Mixed I/O Modules
Discrete mixed modules provide maximum flexibility by combining inputs and outputs in a single, compact module. Discrete input modules receive signals from input devices such as sensors, pushbuttons, and switches that can have two states: on or off, open or closed. Discrete output modules send control signals to devices such as contactors, indicator lamps, and interposing relays that can also have two states. Discrete mixed modules provide maximum flexibility by combining inputs and outputs in a single, compact module. Modules require a carrier base (IC200CHSxxx).
IC200MDD840 IC200MDD842 IC200MDD843
VersaMax Discrete Mixed Modules,
Product Name
Lifecycle Status Active Active Active
Input Voltage 24 VDC 24 VDC 24 VDC
Output Voltage
Number of Points 20 in/12 out 16 in/16 out 10 in/6 out
Channel to Channel Isolation No No No
Load Current per Point
Input and Output Response Time- On/Off(ms)
Protection
On State Current 2.0-5.5 mA 2.0-5.5 mA 2.0-5.5 mA
Off State Current 0-0.5 mA 0-0.5 mA 0-0.5 mA
External Power Supply
Input Impedance 10 kOhms maximum 10 kOhms maximum 10 kOhms maximum
Load Current
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
24 VDC Pos Logic Input 20 points/
Output Relay 2.0 A, 12 points
0-125 VDC, 5/24/125 VDC nominal;
0-265 VAC (47-63 Hz), 120/240 VAC nominal
2.0 A for 5-265 VAC, 2.0 A for 5-30 VDC 0.5 A for 30 VDC 2.0 A for 5-265 VAC, 2.0 A for 5-30 VDC, 0.2 A
0.5 and 10 0.5 and 0.5 0.5 and 10
No internal fuses or snubbers Short circuit protection, overcurrent
0-125 VDC, 5/24/125 VDC nominal; 0-265
VAC (47-63 Hz), 120/240 VAC nominal
2.0 A for 5-265 VAC or
5-30 VDC, 0.2 A for 31-125 VDC
375 maximum 100 maximum 190 maximum
One LED per point shows individual point on/off state (logic side); OK LED indicates backplane power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Mixed Modules 24 VDC Pos Logic Input 16/Output
24 VDC 0.5 A with ESCP
24 VDC 0-125 VDC, 5/24/125 VDC nominal;
protection, free-wheeling diodes
18-30 VDC, 24 VDC nominal 0-125 VDC, 5/24/125 VDC nominal, 0-265
0.5 Amp at 30 VDC
maximum (resistive);
2.0 Amps maximum for 100ms inrush
One LED per point shows individual point on/off state (logic side); OK LED indicates backplane power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Mixed Modules
24 VDC Positive Logic Input
10/Output Relay 6
0-265 VAC (47-63 Hz), 120/240 VAC nominal
for 31-125 VDC
No internal fuses or snubbers
VAC (47-63 Hz), 120/240 VAC nominal
10 mA per point minimum,
8.0 A maximum per module;
2.0 Amps for 5 to 265 VAC maximum (resistive);
2.0 Amps for 5 to 30 VDC maximum (resistive);
0.2 Amp for 31 to 125 VDC maximum (resistive)
One LED per point shows individual point on/off state (logic side); OK LED indicates backplane power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
www.geautomation.com
Automation & Control Systems
1.123
VersaMax Control
Process Automation Control Systems
Discrete Mixed I/O Modules
Discrete mixed modules provide maximum flexibility by combining inputs and outputs in a single, compact module. Discrete input modules receive signals from input devices such as sensors, pushbuttons, and switches that can have two states: on or off, open or closed. Discrete output modules send control signals to devices such as contactors, indicator lamps, and interposing relays that can also have two states. Discrete mixed modules provide maximum flexibility by combining inputs and outputs in a single, compact module. Modules require a carrier base (IC200CHSxxx).
IC200MDD844 IC200MDD845 IC200MDD846
VersaMax Discrete Mixed
Product Name
Lifecycle Status Active Active Active
Input Voltage 24 VDC 24 VDC 120 VAC
Output Voltage
Number of Points 16 in/16 out 16 in/8 out 8 in/8 out
Channel to Channel Isolation No Yes, outputs Yes, outputs
Load Current per Point
Input and Output Response Time- On/Off(ms)
Protection No internal fuses No internal fuses or snubbers No internal fuses or snubbers
On State Current 2.0-5.5 mA 2.0-5.5 mA 5 mA minimum
Off State Current 0-0.5 mA 0-0.5 mA 2.5 mA maximum
External Power Supply
Input Impedance
Load Current
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
Modules 24 VDC Positive Logic
Input 16/Output 24 VDC 0.5 A 16 points
24 VDC 0-125 VDC, 5/24/125 VDC nominal;
0.5 A for 30 VDC 2.0 A for 5-265 VAC, 2.0 A for 5-30 VDC,
0.5 and 0.2 ON / 1.0 OFF 0.5 and 10
18-30 VDC, 24 VDC nominal 0-125 VDC, 5/24/125 VDC nominal;
10 kOhms maximum 10 kOhms maximum 8.6 kOhms (reactive) at 60 Hz, typical;
0.5 Amp at 30 VDC maximum (resistive) 2.0 Amps maximum for 100ms inrush
70 maximum 270 maximum 300 maximum
One LED per point shows individual point on/off state (logic side); OK LED indicates backplane power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Mixed
Modules 24 VDC Positive Logic Input
16/Output Relay 2.0A Isolated 8 points
0-265 VAC (47-63 Hz), 120/240 VAC nominal
0.2 A for 31-125 VDC
0-265 VAC (47-63 Hz), 120/240 VAC nominal
10 mA per point minimum
2.0 A for 5 to 265 VAC maximum (resistive)
2.0 A for 5 to 30 VDC maximum (resistive)
0.2 A for 31 to 125 VDC maximum (resistive)
One LED per point shows individual point on/off state (logic side); OK LED indicates backplane power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Mixed Modules 120 VAC Input 8 points/Outpoints
Relay 2.0A Isolated 8 points
0-125 VDC, 5/24/125 VDC nominal;
0-265 VAC (47-63 Hz), 120/240 VAC nominal
2.0 A for 5-265 VAC, 2.0 A for 5-30 VDC,
0.2 A for 31-125 VDC
1 AC cycle minimum and 2 AC cycle
(Hz dependent) maximum and 10.0 OFF
0-125 VDC, 5/24/125 VDC nominal;
0-265 VAC (47-63 Hz), 120/240 VAC nominal
10.32 kOhms (reactive) at 50 Hz, typical
10 mA per point minimum
2.0 A for 5 to 265 VAC maximum (resistive)
2.0 A for 5 to 30 VDC maximum (resistive)
0.2 A for 31 to 125 VDC maximum (resistive)
One LED per point shows individual point on/off state (logic side); OK LED indicates backplane power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
Automation & Control Systems
1.124
www.geautomation.com
Process Automation Control Systems
VersaMax Control
Discrete Mixed I/O Modules
Discrete mixed modules provide maximum flexibility by combining inputs and outputs in a single, compact module. Discrete input modules receive signals from input devices such as sensors, pushbuttons, and switches that can have two states: on or off, open or closed. Discrete output modules send control signals to devices such as contactors, indicator lamps, and interposing relays that can also have two states. Discrete mixed modules provide maximum flexibility by combining inputs and outputs in a single, compact module. Modules require a carrier base (IC200CHSxxx).
IC200MDD847 IC200MDD848 IC200MDD849
VersaMax Discrete Mixed Modules
Product Name
Lifecycle Status Active Active Active
Input Voltage 240 VAC 120 VAC 0-132 VAC (47 to 63 Hz), 120 VAC nominal
Output Voltage
Number of Points 8 in/8 out 8 in/8 out 8 in/8 out
Channel to Channel Isolation Yes, outputs Yes Yes
Load Current per Point
Input and Output Response Time- On/Off(ms)
Protection No internal fuses or snubbers Snubber and MOVs (each output) No internal fuses or snubbers
On State Current 4 mA minimum 5 mA minimum 5 mA minimum
Off State Current 1.5 mA maximum 2.5 mA maximum 2.5 mA maximum
External Power Supply
Input Impedance
Load Current
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
240 VAC Input 8 points/Output Relay
2.0A Isolated 8 points
0-125 VDC, 5/24/125 VDC nominal;
0-265 VAC (47-63 Hz), 120/240 VAC nominal
2.0 A for 5-265 VAC, 2.0 A for 5-30 VDC,
0.2 A for 31-125 VDC
1 AC cycle minimum and 2 AC cycle
(Hz dependent) maximum and 10.0 OFF
0-125 VDC, 5/24/125 VDC nominal;
0-265 VAC (47-63 Hz), 120/240 VAC nominal
38.5 kOhms (reactive) at 60 Hz, typical;
46.3 kOhms (reactive) at 50 Hz, typical
10 mA per point minimum
2.0 Amps for 5 to 265 VAC maximum (resistive)
2.0 Amps for 5 to 30 VDC maximum (resistive)
0.2 Amp for 31 to 125 VDC maximum (resistive)
300 maximum 125 maximum 300 maximum
One LED per point shows individual point on/off state (logic side); OK LED indicates
backplane power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Mixed Modules
120 VAC Input 8 points/Output 120 VAC 0.5A Isolated 8 points
120 VAC 0-125 VDC, 5/24/125 VDC nominal;
10 mA min, 0.5 A max., 5 A for 1 cycle
(20 ms) max. inrush
1 cycle/2 cycle and
<1/2 cycle/<1/2 cycle
0-125 VDC, 5/24/125 VDC nominal;
0-265 VAC (47-63 Hz), 120/240 VAC nominal
8.6 kOhms (reactive) at 60 Hz, typical;
10.32 kOhms (reactive) at 50 Hz, typical
10 mA minimum per point,
0.5 A maximum per point, 5.0 A for one cycle (20 ms) maximum inrush
One LED per point shows individual point on/off state (logic side); OK LED indicates
backplane power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Mixed Modules
120 VAC Input Isolated 8 points/Output
Relay 2.0 A Isolated 8 points
0-265 VAC (47-63 Hz),
120/240 VAC nominal
2.0 A
1 cycle/2 cycle and
10/10
N/A
8.6 kOhms (reactive) at 60 Hz, typical;
10.32 kOhms (reactive) at 50 Hz, typical
10 mA per point minimum;
2.0 A for 5-265 VAC maximum (resistive);
2.0 A for 5-30 VDC maximum (resistive);
0.2 A for 31-125 VDC maximum (resistive)
One LED per point shows individual point on/off state (logic side); OK LED indicates
backplane power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm 1.956 in), not including the
height of (the carrier or the
mating connectors
www.geautomation.com
Automation & Control Systems
1.125
VersaMax Control
Process Automation Control Systems
Discrete Mixed I/O Modules
Discrete mixed modules provide maximum flexibility by combining inputs and outputs in a single, compact module. Discrete input modules receive signals from input devices such as sensors, pushbuttons, and switches that can have two states: on or off, open or closed. Discrete output modules send control signals to devices such as contactors, indicator lamps, and interposing relays that can also have two states. Discrete mixed modules provide maximum flexibility by combining inputs and outputs in a single, compact module. Modules require a carrier base (IC200CHSxxx).
IC200MDD850 IC200MDD851
VersaMax Discrete Mixed Modules
Product Name
Lifecycle Status Active Active
Input Voltage 0-264 VAC (47-63 Hz), 240 VAC nominal 0 to 15 VDC, +5/12 VDC nominal
Output Voltage
Number of Points 8 out/4 in 16 out/16 in
Channel to Channel Isolation Yes No
Load Current per Point
Input and Output Response Time- On/Off(ms)
Protection No internal fuses or snubbers No internal fuses or snubbers
On State Current 4 mA minimum 1.45 mA minimum
Off State Current 1.5 mA maximum 0 to 0.7 mA maximum
External Power Supply N/A +10.2 to +30 VDC, +12/24 VDC nominal
Input Impedance
Load Current
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
240 VAC Input Isolated 4 points/Output
Relay 2.0 A Isolated 8 points
0-125 VDC, 5/24/125 VDC nominal;
0-265 VAC (47-63 Hz), 120/240 VAC nominal
2.0 A 0.5 Amps at 30 VDC maximum (resistive)
1 cycle/2 cycle
and 10/10
38.5 kOhms (reactive) at 60 Hz, typical;
46.3 kOhms (reactive) at 50 Hz, typical
10 mA per point minimum;
2.0 A for 5-265 VAC maximum (resistive);
2.0 A for 5-30 VDC maximum (resistive);
0.2 A for 31-125 VDC maximum (resistive)
260 maximum 115 maximum
One LED per point shows individual point
on/off state logic side); OK LED indicates
backplane power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Mixed Modules
5/12 VDC Input 16 points/Output
12/24 VDC 16 points
+10.2 to +30 VDC, +12/24 VDC nominal
2.0 Amps maximum for 100ms inrush
0.25ms maximum/0.2ms ON and 1.0ms OFF maximum
2.4kOhms typical @ 12 VDC
0.5 Amps at 30 VDC maximum (resistive);
2.0 Amps maximum for 100ms inrush
One LED per point shows individual point on/off state (logic side); OK LED indicates
backplane power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
Automation & Control Systems
1.126
www.geautomation.com
Process Automation Control Systems
VersaMax Control
Discrete Input Modules
Discrete input modules receive signals from input devices such as sensors, pushbuttons, and switches that can have two states: on or off, open or closed. Modules require a carrier base (IC200CHSxxx).
IC200MDL140 IC200MDL141 IC200MDL143
VersaMax Discrete Input
Product Name
Lifecycle Status Active Active Active
Input Voltage 0-132 VAC 0-264 VAC 0-132 VAC
Number of Points 8 8 8
Channel to Channel Isolation No No Yes
Input and Output Response Time- On/Off (ms)
Points per Common 1 group of 8 1 group of 8 8 groups of 1
On State Current 5 mA minimum 7 mA minimum 5 mA minimum
Off State Current 2.5 mA maximum 1.5 mA maximum 2.5 mA maximum
Input Impedance
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
10.32 kOhms (reactive) at 50 Hz, typical
Module 120 VAC,
8 points
1 cycle/2 cycles 1 cycle/2 cycles 1 cycle/2 cycles
8.6 kOhms (reactive) at 60 Hz, typical;
55 maximum 55 maximum 50 maximum
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Input
Module 240 VAC,
8 points
38.5 kOhms (reactive) at 60 Hz, typical;
46.3 kOhms (reactive) at 50 Hz, typical
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Input
Module 120 VAC Isolated,
8 points
8.6 kOhms (reactive) at 60 Hz, typical;
10.32 kOhms (reactive) at 50 Hz, typical
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
www.geautomation.com
Automation & Control Systems
1.127
VersaMax Control
Process Automation Control Systems
Discrete Input Modules
Discrete input modules receive signals from input devices such as sensors, pushbuttons, and switches that can have two states: on or off, open or closed. Modules require a carrier base (IC200CHSxxx).
IC200MDL144 IC200MDL240 IC200MDL241
VersaMax Discrete Input
Product Name
Lifecycle Status Active Active Active
Input Voltage 0-264 VAC 0-132 VAC 0-264 VAC
Number of Points 4 16 16
Channel to Channel Isolation Yes No No
Input and Output Response Time- On/Off (ms)
Points per Common 4 groups of 1 2 groups of 8 2 groups of 8
On State Current 7 mA minimum 5 mA minimum 4 mA minimum
Off State Current 3 mA maximum 2.5 mA maximum 1.5 mA maximum
Input Impedance
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
Module 240 VAC Isolated,
4 points
1 cycle/2 cycles 1 cycle/2 cycles 1 cycle/2 cycles
38.5 kOhms (reactive) at 60 Hz, typical;
46.3 kOhms (reactive) at 50 Hz, typical
30 maximum 110 maximum 110 maximum
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Input
Module, 120 VAC Positive Logic,
16 points
8.6 kOhms (reactive) at 60 Hz, typical;
10.32 kOhms (reactive) at 50 Hz, typical
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Input
Module, 240 VAC Positive Logic,
16 points
38.5 kOhms (reactive) at 60 Hz, typical;
46.3 kOhms (reactive) at 50 Hz, typical
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
Automation & Control Systems
1.128
www.geautomation.com
Process Automation Control Systems
VersaMax Control
Discrete Input Modules
Discrete input modules receive signals from input devices such as sensors, pushbuttons, and switches that can have two states: on or off, open or closed. Modules require a carrier base (IC200CHSxxx).
IC200MDL243 IC200MDL244 IC200MDL631
VersaMax Discrete Input
Product Name
Lifecycle Status Active Active Active
Input Voltage 0-132 VAC 0-264 VAC 0-150 VDC , 125 VDC nominal
Number of Points 16 8 8 isolated inputs
Channel to Channel Isolation Yes Yes Yes
Input and Output Response Time- On/Off (ms)
Points per Common 16 groups of 1 8 groups of 1 8 groups of 1
On State Current 5 mA minimum 7 mA minimum 1.0 mA minimum
Off State Current 2.5 mA maximum 3 mA maximum 0 to 0.1 mA maximum
Input Impedance
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
Module, 120 VAC Isolated,
16 points
1 cycle/2 cycles 1 cycle/2 cycles 0.5 maximum
8.6 kOhms (reactive) at 60 Hz, typical;
10.32 kOhms (reactive) at 50 Hz, typical
100 maximum 60 maximum 40 maximum
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Input
Module, 240 VAC Isolated,
8 points
38.5 kOhms (reactive) at 60 Hz, typical;
46.3 kOhms (reactive) at 50 Hz, typical
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Input
Module 125 VDC, Pos/Neg Logic,
Isolated, 8 points
74 K Ohm typical at 125 VDC
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
www.geautomation.com
Automation & Control Systems
1.129
VersaMax Control
Process Automation Control Systems
Discrete Input Modules
Discrete input modules receive signals from input devices such as sensors, pushbuttons, and switches that can have two states: on or off, open or closed. Modules require a carrier base (IC200CHSxxx).
IC200MDL632 IC200MDL635 IC200MDL636
VersaMax Discrete Input
Product Name
Lifecycle Status Active Active Active
Input Voltage 0-150 VDC, 125 VDC nominal 0-60 VDC, 48 VDC nominal 0-60 VDC, 48 VDC nominal
Number of Points 16 isolated inputs 16 inputs (2 groups of 8) 32 (4 groups of 8)
Channel to Channel Isolation Yes No No
Input and Output Response Time- On/Off (ms)
Points per Common 16 groups of 1 2 groups of 8 4 groups of 8
On State Current 1.0 mA minimum 1.0 mA minimum 1.0 mA minimum
Off State Current 0 to 0.1 mA maximum 0 to 0.4 mA maximum 0 to 0.4 mA maximum
Input Impedance 74 K Ohm typical at 125 VDC 28 K Ohm typical 28 K Ohm typical
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
Module 125 VDC, Pos/Neg Logic,
Isolated, 16 points
0.5 maximum 0.5 maximum 0.5 maximum
80 maximum 70 maximum 140 maximum
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Input Module
48 VDC, Pos/Neg Logic
(2 Groups of 8), 16 points
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Input
Module 48 VDC, Pos/Neg Logic
(4 Groups of 8), 32 points
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
Automation & Control Systems
1.130
www.geautomation.com
Process Automation Control Systems
VersaMax Control
Discrete Input Modules
Discrete input modules receive signals from input devices such as sensors, pushbuttons, and switches that can have two states: on or off, open or closed. Modules require a carrier base (IC200CHSxxx).
IC200MDL640 IC200MDL643 IC200MDL644 IC200MDL650
VersaMax Discrete Input
Product Name
Lifecycle Status Active Active Active Active
Input Voltage 0-30 VDC 0-15 VDC 0-15 VDC 0-30 VDC
Number of Points 16 16 32 32
Channel to Channel Isolation No No No No
Input and Output Response Time- On/Off (ms)
Points per Common 2 groups of 8 2 groups of 8 4 groups of 8 2 groups of 8
On State Current 2.0-5.5 mA 1.45 mA minimum 1.45 mA minimum 2.0-5.5 mA
Off State Current 0-0.5 mA 0-0.7 mA maximum 0-0.7 mA maximum 0-0.5 mA
Input Impedance 10 kOhms maximum 2.4 kOhms at 12 VDC, typical 2.4 kOhms at 12 VDC, typical 10 kOhms maximum
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
Module, 24 VDC
Pos/Neg Logic, 16 points
0.5 0.25 0.25 0.5
25 maximum 70 maximum 140 maximum 50 maximum
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in)
x 50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Input
Module, 5/12 VDC (TTL)
Pos/Neg Logic, 16 points
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane power
is present
110 mm (4.3 in) x 66.8 mm (2.63 in)
x 50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Input
Module, 5/12 VDC (TTL)
Pos/Neg Logic, 32 points
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane power
is present
110 mm (4.3 in) x 66.8 mm (2.63 in)
x 50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Discrete Input
Module, 24 VDC
Positive Logic, 32 points
One LED per point shows
individual point ON/OFF status.
OK LED indicates backplane power
is present
110 mm (4.3 in) x 66.8 mm (2.63 in)
x 50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
www.geautomation.com
Automation & Control Systems
1.131
VersaMax Control
Process Automation Control Systems
Discrete Output Modules
Discrete output modules send control signals to devices such as contactors, indicator lamps, and interposing relays that can also have two states. Modules require a carrier base (IC200CHSxxx).
IC200MDL329 IC200MDL330 IC200MDL331
VersaMax Discrete Output Module,
Product Name
Lifecycle Status Active Active Active
Output Voltage
Number of Points 8 16 8
Channel to Channel Isolation Yes Yes Yes
Load Current per Point
120 VAC, 0.5A per point Isolated,
8 points
85-132 VAC (47-63 Hz), 120 VAC nominal 85-132 VAC (47-63 Hz), 120 VAC nominal 85-132 VAC (47-63 Hz), 120 VAC nominal
0.5 A per point 0.5 A per point 2.0 A per point
VersaMax Discrete Output Module,
120 VAC 0.5A per point Isolated,
16 points
VersaMax Discrete Output Module,
120 VAC 2.0A per point Isolated,
8 points
Input and Output Response Time- On/Off (ms)
Protection
Points per Common 8 groups of 1 Isolated points Isolated points
External Power Supply
Load Current
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
<1/2 cycle/<1/2 cycle <1/2 cycle/<1/2 cycle <1/2 cycle/<1/2 cycle
Snubber and MOVs (each output) Snubber and MOVs (each output) Snubber and MOVs (each output)
85-132 VAC (47-63 Hz), 120 VAC nominal 85-132 VAC (47-63 Hz), 120 VAC nominal 85-132 VAC (47-63 Hz), 120 VAC nominal
10 mA minimum per point,
0.5 A maximum per point,
5.0 A for one cycle (20 ms) maximum inrush
70 maximum 140 maximum 85 maximum
One LED per point shows individual
point ON/OFF status (logic side).
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
10 mA minimum per point,
0.5 A maximum per point,
5.0 A for one cycle (20 ms) maximum inrush
One LED per point shows individual
point ON/OFF status (logic side).
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
10 mA minimum per point,
2.0 A maximum per point, 20 A for one cycle (20 ms)
maximum inrush
One LED per point shows individual
point ON/OFF status (logic side).
OK LED indicates backplane
power is present
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
Automation & Control Systems
1.132
www.geautomation.com
Process Automation Control Systems
VersaMax Control
Discrete Output Modules
Discrete output modules send control signals to devices such as contactors, indicator lamps, and interposing relays that can also have two states. Modules require a carrier base (IC200CHSxxx).
IC200MDL730 IC200MDL740 IC200MDL741
VersaMax Discrete Output Module,
Product Name
Lifecycle Status Active Active Active
Output Voltage
Number of Points 8 16 16
Channel to Channel Isolation No No No
Load Current per Point
24 VDC Positive Logic 2.0A per point
w/ESCP, 8 points
17.5-30 VDC, 24 VDC nominal 10.2-30 VDC, 12/24 VDC nominal 18-30 VDC, 24 VDC nominal
2.0 A per point 0.5 A per point 0.5 A per point
VersaMax Discrete Output Module,
24 VDC Positive Logic, 0.5A per point,
16 points
VersaMax Discrete Output Module,
24 VDC Positive Logic, 0.5A per point
w/ESCP, 16 points
Input and Output Response Time- On/Off (ms)
Short circuit protection, overcurrent
Protection
Points per Common 1 group of 8 1 group of 16 1 group of 16
External Power Supply
Load Current
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
protection (each output)
18-30 VDC, 24 VDC nominal 10.2-30 VDC , 12/24 VDC nominal 18-30 VDC, 24 VDC nominal
2.0 A at 30 VDC maximum (resistive) per point, 8.0 A max. per module
One LED per point shows individual
point ON/OFF state (logic side).
FLD PWR LED indicates field power is
present. OK LED indicates backplane
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
0.5 0.2/1.0 0.5/0.5
No internal fuses (each output) Short circuit protection, overcurrent
protection, free-wheeling diodes
(each output)
0.5 A at 30 VDC maximum (resistive);
2.0 A inrush maximum for 100 ms
50 maximum 45 maximum 75 maximum
One LED per point shows individual
point ON/OFF state (logic side).
FLD PWR LED indicates field power is
power is present.
mating connectors
present. OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
0.5 A at 30 VDC maximum (resistive);
2.0 A inrush maximum for 100 ms
One LED per point shows individual
point ON/OFF state (logic side).
FLD PWR LED indicates field power is
present. OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
www.geautomation.com
Automation & Control Systems
1.133
VersaMax Control
Process Automation Control Systems
Discrete Output Modules
Discrete output modules send control signals to devices such as contactors, indicator lamps, and interposing relays that can also have two states. Modules require a carrier base (IC200CHSxxx).
IC200MDL742 IC200MDL743 IC200MDL744
VersaMax Discrete Output Module,
Product Name
Lifecycle Status Active Active Active
Output Voltage
Number of Points 32 16 (1 group of 16) 32 (2 groups of 16)
Channel to Channel Isolation No No No
Load Current per Point
24 VDC Positive Logic 0.5A with
ESCP, 32 points
18-30 VDC, 24 VDC nominal 5/12/24 VDC 5/12/24 VDC
0.5 A per point 0.5 A per point 0.5 A per point
VersaMax Discrete Output Module,
5/12/24 VDC Negative Logic, 0.5 A per
point (1 group of 16) 16 points
VersaMax Discrete Output Module,
5/12/24 VDC Negative Logic, 0.5 A per
point (2 groups of 16) 32 points
Input and Output Response Time- On/Off (ms)
Short circuit protection, overcurrent
Protection
Points per Common 2 groups of 16 1 group of 16 2 groups of 16
External Power Supply
Load Current
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
protection, free-wheeling diodes
18-30 VDC, 24 VDC nominal 4.75 to 5.25 VDC, 5 VDC nominal
0.5 A at 30 VDC maximum (resistive);
2.0 A inrush maximum for 100 ms
One LED per point shows individual
point ON/OFF state (logic side).
FLD PWR LED indicates field power is
present. OK LED indicates backplane
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
0.5/0.5 0.2/1.0 0.2/1.0
No internal fuse No internal fuse
(each output)
for 5 VDC-TTL mode; 10.2 to 30 VDC,
12/24 VDC nominal for 12/24 VDC mode
25 mA maximum for 5 VDC-TTL mode,
0.5 A at 30 VDC maximum,
2.0 A inrush maximum for 100 ms for 12/24 VDC mode
150 maximum 70 maximum 140 maximum
One LED per point shows individual
point ON/OFF state (logic side).
FLD PWR LED indicates field power is
power is present.
height of the carrier or the
mating connectors
present. OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
4.75 to 5.25 VDC, 5 VDC nominal
for 5 VDC-TTL mode; 10.2 to 30 VDC,
12/24 VDC nominal for 12/24 VDC mode
25 mA maximum for 5 VDC-TTL mode,
0.5 A at 30 VDC maximum,
2.0 A inrush maximum for 100 ms for 12/24 VDC mode
One LED per point shows individual
point ON/OFF state (logic side).
FLD PWR LED indicates field power is
present. OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
Automation & Control Systems
1.134
www.geautomation.com
Process Automation Control Systems
VersaMax Control
Discrete Output Modules
Discrete output modules send control signals to devices such as contactors, indicator lamps, and interposing relays that can also have two states. Modules require a carrier base (IC200CHSxxx).
IC200MDL750 IC200MDL930 IC200MDL940
VersaMax Discrete Output Module,
Product Name
Lifecycle Status Active Active Active
Output Voltage
Number of Points 32 8 16
Channel to Channel Isolation No Yes Yes
Load Current per Point
Input and Output Response Time- On/Off (ms)
Protection
24 VDC Positive Logic, 0.5A per point,
32 points
10.2-30 VDC, 12/24 VDC nominal 0-125 VDC, 5/24/125 VDC nominal;
0.5 A per point 2.0 A for 5-265 VAC, 2.0 A for 5-30 VDC,
0.2/1.0 10.0/10.0 10.0/10.0
No internal fuses No internal fuses or snubbers No internal fuses or snubbers
VersaMax Discrete Output Module,
Relay 2.0 A per point Isolated
Form A, 8 points
0-265 VAC (47-63 Hz),
120/240 VAC nominal
0.2 A for 31-125 VDC
VersaMax Discrete Output Module,
Relay 2.0 A per point Isolated
Form A, 16 points
0-125 VDC, 5/24/125 VDC nominal;
0-265 VAC (47-63 Hz), 120/240 VAC nominal
2.0 A for 5-265 VAC, 2.0 A for 5-30 VDC,
0.2 A for 31-125 VDC
Points per Common 2 groups of 16 Isolated points Isolated points
External Power Supply
Load Current
5V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
10.2-30 VDC, 12/24 VDC nominal 0-125 VDC, 5/24/125 VDC nominal; 0-265 VAC (47-63 Hz), 120/240 VAC nominal
0.5 A at 30 VDC maximum (resistive); 2.0 A inrush maximum for 100 ms
90 maximum 245 maximum 490 maximum
One LED per point shows individual
point ON/OFF state (logic side).
FLD PWR LED indicates field power is
present. OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
10 mA per point minimum; 2.0 A for 5-265
VAC maximum (resistive); 2.0 A for 5-30 VDC
maximum (resistive); 0.2 A for 31-125 VDC
maximum (resistive)
One LED per point shows individual
point ON/OFF state (logic side).
FLD PWR LED indicates field power is
present. OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
0-125 VDC, 5/24/125 VDC nominal; 0-265
VAC (47-63 Hz), 120/240 VAC nominal
10 mA per point minimum; 2.0 A for 5-265
VAC maximum (resistive); 2.0 A for 5-30 VDC
maximum (resistive); 0.2 A for 31-125 VDC
maximum (resistive)
One LED per point shows individual
point ON/OFF state (logic side).
FLD PWR LED indicates field power is
present. OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
www.geautomation.com
Automation & Control Systems
1.135
VersaMax Control
Process Automation Control Systems
Analog Input Modules
Analog input modules receive signals from current and voltage input devices. Modules require a carrier base (IC200CHSxxx).
IC200ALG230 IC200ALG240 IC200ALG260 IC200ALG261
VersaMax Analog Input Module,
Product Name
Lifecycle Status Active Active Active Active
Input Range ±10 VDC or 0-10 VDC ±10 VDC, 4-20 mA 4-20 mA, ±10 VDC or 0-10 VDC ±10 VDC
Number of Channels 4 8 Channel to channel isolated 8 8
External Power Supply
Resolution
Update Rate
Accuracy at 25°C
Input Impedance
Input Filter Response 5.0 ms N/A 5.0 ms N/A
5V Backplane Current Consumption (mA)
3.3V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
12 Bit Voltage/Current,
4 Channels
None Range: 19.5-30 VDC including
Bipolar mode: 2.5 mV = 8 counts,
Unipolar mode: 2.5 mV = 8 counts
0.4 ms Approximately 20 mS max. @
±0.3% typical of full scale,
±0.5% maximum of full scale
Voltage mode:
126 kOhms maximum,
Current mode:
200 Ohms maximum
125 maximum 15 maximum 130 maximum 200 maximum
N/A 120 maximum N/A N/A
INT PWR LED indicates
internally-generated field power
is present. OK LED indicates backplane power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in)
x 50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Analog Input Module, 16 Bit Voltage/Current Isolated,
8 Channel
ripple; Current consumption: 100
mA maximum plus load currents
Current mode: 381 nA nominal Voltage mode: 381 µV nominal
50 Hz filter frequency
Approximately 16.7 mS max. @
60 Hz filter frequency
±0.1% maximum of full scale ±0.3% typical of full scale,
N/A Voltage mode:
FLD PWR LED indicates the
presence of both logic power
and user power. OK LED
indicates module status.
110 mm (4.3 in) x 66.8 mm (2.63 in)
x 50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Analog Input Module,
12 Bit Voltage/Current,
8 Channel
None None
Current mode: 4 µA = 8 counts,
Bipolar mode: 2.5 mV = 8 counts,
Unipolar mode: 2.5 mV = 8 counts
0.4 ms 7.5 ms
±0.5% maximum of full scale
126 kOhms maximum,
Current mode:
200 Ohms maximum
INT PWR LED indicates
internally-generated field power
is present. OK LED indicates backplane power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in)
x 50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Analog Input Module,
15 Bit Differential Voltage,
8 Channel
Bipolar mode: 0.3125 mV =
1 counts
±0.3% typical of full scale,
±0.5% maximum of full scale
Voltage mode:
100 kOhms maximum
INT PWR LED indicates
internally-generated field power
is present. OK LED indicates backplane power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in)
x 50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
Automation & Control Systems
1.136
www.geautomation.com
Process Automation Control Systems
VersaMax Control
Analog Input Modules
Analog input modules receive signals from current and voltage input devices. Modules require a carrier base (IC200CHSxxx).
IC200ALG262 IC200ALG263 IC200ALG264
VersaMax Analog Input Module,
Product Name
Lifecycle Status Active Active Active
Input Range 0 to 20 mA or 4 to 20 mA ±10 VDC 0 to 20 mA or 4 to 20 mA
Number of Channels 8 15 15
External Power Supply
15 Bit Differential Current,
8 Channel
None None None
VersaMax Analog Input Module,
15 Bit Voltage,
15 Channel
VersaMax Analog Input Module,
15 Bit Current,
15 Channel
4 to 20 mA: 0.5micro Amp= 1 count;
Resolution
Update Rate
Accuracy at 25°C
Input Impedance
Input Filter Response N/A N/A 24 Hz ±20%
5V Backplane Current Consumption (mA)
3.3V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
0 to 20 mA: 0.625micro Amp = 1 count
7.5 ms 7.5 ms 7.5 ms
±0.3% typical of full scale,
±0.5% maximum of full scale
Current mode:
100 kOhms maximum
200 maximum 150 maximum 100 maximum
N/A N/A N/A
INT PWR LED indicates
internally-generated field power
is present. OK LED indicates backplane power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in) , not including the
height of the carrier or the
mating connectors
Bipolar mode: 0.3125 mV = 1 count 4 to 20 mA: 0.5micro Amp= 1 count;
0 to 20 mA: 0.625micro Amp = 1 count
±0.3% typical of full scale,
±0.5% maximum of full scale
Voltage mode:
100 kOhms maximum
INT PWR LED indicates
internally-generated field power
is present. OK LED indicates backplane power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in) , not including the
height of the carrier or the
mating connectors
±0.3% typical of full scale,
±0.5% maximum of full scale
Voltage mode:
100 kOhms maximum,
Current mode:
200 Ohms maximum
INT PWR LED indicates
internally-generated field power
is present. OK LED indicates backplane power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in) , not including the
height of the carrier or the
mating connectors
www.geautomation.com
Automation & Control Systems
1.137
VersaMax Control
Process Automation Control Systems
Analog Output Modules
Analog output modules provide voltage or current signals to analog output devices. Modules require a carrier base (IC200CHSxxx).
IC200ALG320 IC200ALG321 IC200ALG322
VersaMax Analog Output Module,
Product Name
Lifecycle Status Active Active Active
Output Range
Number of Channels 4 4 4
External Power Supply
12 Bit Current, 4 Channel
4-20 mA 0-10 VDC ±10 VDC
Range: 18-30 VDC
including ripple;
Current consumption:
160 mA maximum
including load current
VersaMax Analog Output Module,
12 Bit 0-10V Voltage, 4 Channel
Range: 18-30 VDC
including ripple;
Current consumption:
125 mA maximum
VersaMax Analog Output Module,
12 Bit ±10V Voltage, 4 Channel
Range: 18-30 VDC
including ripple;
Current consumption:
125 mA maximum
4 uA = 8 counts 2.5 mV = 8 counts 5 mV = 16 counts
Resolution
Update Rate 0.3 ms maximum 0.3 ms maximum 0.3 ms maximum
Accuracy at 25°C
5V Backplane Current Consumption (mA)
3.3V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
±0.3% typical of full scale,
±0.5% maximum of full scale
50 maximum 50 maximum 50 maximum
N/A N/A N/A
FLD PWR LED indicates
field power is present.
OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
±0.3% typical of full scale,
±0.5% maximum of full scale
FLD PWR LED indicates
field power is present.
OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
±0.3% typical of full scale,
±0.5% maximum of full scale
FLD PWR LED indicates
field power is present.
OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
Automation & Control Systems
1.138
www.geautomation.com
Process Automation Control Systems
VersaMax Control
Analog Output Modules
Analog output modules provide voltage or current signals to analog output devices. Modules require a carrier base (IC200CHSxxx).
IC200ALG325 IC200ALG326 IC200ALG327 IC200ALG328 IC200ALG331
VersaMax Analog Output
Product Name
Lifecycle Status Active Active Active Active Active
Output Range
Number of Channels 8 8 12 12 single ended, one group 4
External Power Supply
Resolution
Update Rate 15.0 ms maximum 15.0 ms maximum 10.0 ms maximum 15 ms maximum 7 ms maximum
Accuracy at 25¢XC
5V Backplane Current Consumption (mA)
3.3V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
Module, 13 Bit ±10 VDC or 0 to
10 VDC Voltage, 8 Channel
±10 VDC or 0 to 10 VDC 4 to 20 mA (default)
Range: 18-30 VDC
including ripple;
Current consumption:
102 mA maximum
1.25 mV = 4 counts 4-20 mA: 5 counts =
±0.3% typical of full scale,
±0.5% maximum of full scale
50 maximum 50 maximum 50 maximum 50 maximum 10 maximum
N/A N/A N/A N/A 115 maximum
FLD PWR LED indicates
field power is present.
OK LED indicates backplane
power is present.
110 mm (4.3 in) x
66.8 mm (2.63 in) x 50 mm
(1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Analog Output
Module, 13 Bit Current,
8 Channel
0 to 20 mA (configured
with jumper)
Range: 18-30 VDC
including ripple;
2A inrush maximum,
100 mA maximum
(no load), 185 mA
maximum (all 8
outputs at full scale)
2.5 uA (~12.7 bits) 0-20 mA: 4 counts = 2.5 uA (13 bits)
±0.3% of full scale (typical),
±0.5% of full scale (max.)
±1% of full scale (max.)
FLD PWR LED indicates
field power is present.
OK LED indicates backplane
power is present.
110 mm (4.3 in) x
66.8 mm (2.63 in) x 50 mm
(1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Analog Output
Module, 13 Bit ±10 VDC
or 0 to 10 VDC Voltage,
12 Channel
±10 VDC or 0 to 10 VDC 4 to 20 mA (default)
Range: 18-30 VDC
including ripple;
Current consumption:
112 mA maximum
1.25 mV = 4 counts 4-20 mA: 5 counts =
±0.3% typical of full scale,
±0.5% maximum of
full scale
FLD PWR LED indicates
field power is present.
OK LED indicates backplane
power is present.
110 mm (4.3 in) x
66.8 mm (2.63 in) x 50 mm
(1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Analog Output
Module, 13 Bit, 0 - 20
mA, 4-20 mA Current, 12
Channel
0 to 20 mA (configured
with jumper)
Range: 18-30 VDC
including ripple;
Current consumption:
2A inrush maximum
100 mA maximum (no load)
270 mA maximum
(all 12 outputs at full scale)
2.5 uA (~12.7 bits) 0-20 mA: 4 counts = 2.5 uA (13 bits)
+/- 0.3% of full scale
(typical),
+/- 0.5% of full scale (max.)
+/-1% of full scale (max.)
FLD PWR LED indicates
field power is present.
OK LED indicates backplane
power is present.
110 mm (4.3 in) x
66.8 mm (2.63 in) x 50 mm
(1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Analog Output
Module, 14 Bit Voltage/
Current 1500 VAC
Isolation, 4 Channel
±10 VDC, 4-20 mA
Range: 19.5-30 VDC
including ripple;
Current consumption:
100 mA maximum plus load currents
Current mode: 381 nA
nominal Voltage mode: 381
µV nominal
±0.1% maximum of
full scale
FLD PWR LED indicates
the presence of both logic
power and user power.
OK LED indicates
module status.
110 mm (4.3 in) x
66.8 mm (2.63 in) x 50 mm
(1.956 in), not including the
height of the carrier or the
mating connectors
www.geautomation.com
Automation & Control Systems
1.139
VersaMax Control
Process Automation Control Systems
Analog Mixed Modules
Analog mixed modules provide maximum flexibility by combining inputs and outputs in a single, compact module. Modules require a carrier base (IC200CHSxxx).
IC200ALG430 IC200ALG431 IC200ALG432
VersaMax Analog Mixed Module,
Product Name
Lifecycle Status Active Active Active
Input Range 4-20 mA 0-10 VDC -10 to +10 VDC
Output Range 4-20 mA 0-10 VDC -10 to +10 VDC
External Power Supply
Resolution
Update Rate 0.3 ms maximum 0.3 ms maximum 0.3 ms maximum
Accuracy at 25°C
Input Impedance 200 Ohms maximum 120 kOhms minimum 125 kOhms minimum
Input Filter Response 5.0 ms 5.0 ms 5.0 ms
LED Indicators
Dimensions (W x H x D)
12 Bit Input Current 4 Channel/Output
Current 2 Channel
Range: 18-30 VDC including ripple;
Current consumption: 125 mA maximum
4 uA = 8 counts 2.5 mV = 8 counts Input : 2.5 mV = 8 counts,
±0.3% typical of full scale,
±0.5% maximum of full scale
FLD PWR LED indicates field power
is present. OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Analog Mixed Module,
12 Bit 0-10V Input 4 Channel/Output
0-10V 2 Channel
Range: 18-30 VDC including ripple;
Current consumption: 125 mA maximum
±0.3% typical of full scale,
±0.5% maximum of full scale
FLD PWR LED indicates field power
is present. OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
VersaMax Analog Mixed Module,
12 Bit ±10V Input 4 Channel/Output
±10V 2 Channel
Range: 18-30 VDC including ripple;
Current consumption: 125 mA maximum
Output: 5 mV = 16 counts
±0.3% typical of full scale,
±0.5% maximum of full scale
FLD PWR LED indicates field power is present. OK LED indicates backplane
power is present.
110 mm (4.3 in) x 66.8 mm (2.63 in) x
50 mm (1.956 in), not including the
height of the carrier or the
mating connectors
Automation & Control Systems
1.140
www.geautomation.com
Process Automation Control Systems
VersaMax Control
RTD and Thermocouple Modules
Specialty modules are available for RTD and Thermocouple inputs. Modules require a carrier base (IC200CHSxxx).).
IC200ALG620 IC200ALG630
Product Name
Lifecycle Status Active Active
Input Range
Number of Channels 4 7
Resolution 15 bits plus sign 15 bits plus sign
Update Rate
Accuracy at 25°C
5 V Backplane Current Consumption (mA)
3.3 V Backplane Current Consumption (mA)
LED Indicators
Dimensions (W x H x D)
60 Hz: approximately 210 milliseconds per channel 50 Hz:
on voltage measurement: ±0.15% on resistance measurement
VersaMax Analog Input Module,
16 Bit RTD, 4 Channel
RTD types: 25, 100, and 1000 ohm platinum
10, 50, and 100 ohm copper 100 and
120 ohm nickel 604 ohms nickel/iron
60 Hz: approximately 60 milliseconds per channel 50 Hz:
approximately 230 milliseconds per channel
on temperature measurement: ±0.15% on RTD
(temperature) measurement
125 maximum 125 maximum
125 maximum 125 maximum
OK LED: green indicates backplane power is present.
Amber indicates module fault.
110 mm (4.3 in) x 66.8 mm (2.63 in) x 50 mm (1.956 in),
not including the height of the carrier or the
mating connectors
VersaMax Analog Input Module, 16 Bit Thermocouple, 7 Channel
Thermocouple types:
J, K, T, S, R, none (used for mV inputs)
approximately 70 milliseconds per channel
on voltage measurement: ±0.2%
on temperature measurement:±0.15%
OK LED: green indicates backplane power is present.
Amber indicates module fault.
110 mm (4.3 in) x 66.8 mm (2.63 in) x 50 mm (1.956 in),
not including the height of the carrier or
the mating connectors
www.geautomation.com
Automation & Control Systems
1.141
Loading...