GE RSEN-LG Installation Instructions Manual

Catalog Number: RSEN-LG
Total Lighting Control
Two-way Occupancy Sensor for large rooms
DESCRIPTION AND FEATURES
The RSEN-LG is an ultrasonic motion sensor with built­in timing and load control relay driving circuitry. It is designed to control lighting in a room approximately 900 to 2100 square feet. It is for use with the GE RTPACK switchpack only, and is not for use with other relays or transformers.
The sensor produces a low intensity, inaudible sound and detects changes in the sound waves caused by motion, such as walking into a room, reaching for a telephone, turning in a chair, etc. The sensor does not respond to audible sound.
When the sensor detects motion, the pre-set time delay period is started and the blue wire is electronically connected to the black wire. This energizes the relay in the RTPACK switchpack which turns on the load. At the end of the pre-set time period, the blue wire is disconnected from the black,
causing the relay to open which turns off the load. The red lead is a +15 VDC supply, the black lead is common and the blue lead is the relay control.
• Full coverage with no gaps for rooms up to 2100 square feet
• Minor motion coverage up to 1350 square feet
• Not for use in corridors or warehouses
• Separate time delay and sensitivity adjustments
• Manual override should a unit fail (Failed board can be replaced without removing unit or wiring)
• For indoor use
Before proceeding, read the enclosed installation instructions. For GE TLC Service, call: 1-877-584-2685 (USA) and (Canada)
Installation Instructions
IMRSEN-LG
Catalog Number: RSEN-LG
CAUTION: Do not run the sensor wire in the same conduit as power conductors. Install in accordance with local codes.
INSTALLATION
Basic Installation Steps
1. Locate and mount the sensor.
2. Mount the switchpack.
3. Wire the sensor to the switchpack.
4. Adjust settings and test.
Locating Sensor
Choose the sensor location carefully. The sensor must have a clear view of the area to be controlled. The line of sight must be through air; the sensor will not “see” through glass or high partitions. A mounting height of 12 feet or less is desirable. Avoid pointing directly into hallways. To prevent false activation, do not mount where forced air will blow directly at or by the sensor. For typical placement, refer to the Sensor Location diagrams.
If partitions between 49" and 71" are present, see the Sensor Coverage diagram. For greater partition heights, each partitioned area should be treated as an individual space with floor-to-ceiling walls. Note: For large open areas, scheduling may be a more effective solution than multiple occupancy sensors. Call 1-877-584-2685 for application assistance.
Mounting Sensor
Pass the control wires through the threaded mounting post and interlock to the back plate. The sensor mounts to normal ceiling tile through a single sensor’s slotted grills must point along the path where motion is to be detected. CAUTION: Finger-tighten the nut to
avoid stripping the mounting post.
3
4” hole. When mounted, the
Sensor Coverage
1/2 STEP
WALK
COVERAGE
NO PARTITIONS OR PARTITIONS NOT TO EXCEED 48" HIGH A = 56' B = 60' C = 24' D = 36' PARTITION HEIGHTS 49" TO 71" A = 38' B = 41' C = 17' D = 25'
SENSOR
A B
MOTION-
S
AT-DESK COVERAGE
Sensor Location
S
30' x 40
' CLASSROOM
40' x 100' DIVIDED CLASSROOM
Sensor Mounting
NUT
WASHER
SS S
' BOARD ROOM
30' x 50
ELECTRICAL BOX
CD
S
On hard ceilings an adapter plate is available to allow mounting to a standard fixture ring and junction box. The threaded mounting post may be cut down if it is too long to fit into the junction box.
Mounting Switchpack
The switchpack is generally mounted above the ceiling on the outside of the junction box that contains a hot line, neutral and the existing switch leg from which the lighting is controlled. If additional switchpacks are required, they are mounted on the outside of the boxes containing the appropriate switch legs. In installations where there are no existing switch legs, the switchpack may be mounted on the outside of any standard junction box, with or without an extension ring.
When mounted, the line connections are inside the box and the Class 2 wiring exits via the rear of the switchpack housing. In areas where Class 2 wiring is not permitted, the switchpack can be mounted internally to any standard electrical box.
SENSOR
UNIT
Switchpack Mounting
SWITCHPACK J BOX
COVERPLATE
ADAPTER
PLATE
LOCKNUT
Loading...
+ 2 hidden pages