GE Entelliguard TU Conversion Kit, MicroVersaTrip Plus Conversion Kit, PM Conversion Kit Installation Instructions Manual

INTRODUCTION
GE Conversion Kits are designed for upgrading existing Allis
Chalmers®, Siemens/Allis®, and Siemens® low-voltage
power circuit breakers, rather than replacing the entire breaker.
The Conversion Kits include Entelliguard TU™,
the latest technological advance in GE trip systems. Entelliguard, MicroVersaTrip Plus and MicroVersaTrip P
Conversion Kits are designed and tested to conform to ANSI Standard C37.59, allowing the retrofitter to properly install the kit and acceptance test the breaker.
This publication covers installation of Entelliguard, MicroVersaTrip Plus and MicroVersaTrip PM Conversion Kits on Allis Chalmers®, Siemens/Allis®, and Siemens® LA-4000 low-voltage power circuit breakers. Each Conversion Kit contains all the components needed to convert from the existing trip system.
DEH40015
Installation Instructions .
R01
Entelliguard TU™, MicroVersaTrip Plus™ and PM™ Conversion Kits
for Allis Chalmers®, Siemens/Allis® LA-4000-Blue Low-Voltage Power Circuit Breakers
1
TABLE OF CONTENTS
Section 1. General Information ............................................................................................................ Page 3
Section 2. Before Installation ................................................................................................................ Page 3
Section 3. Breaker Preparation ............................................................................................................ Page 4
Section 4. Installing the Conversion Kit .............................................................................................. Page 5
Installing Flux Shifter Reset Bracket ............................................................................................................ Page 6
Installing ththe Trip Unit Wiring Harness ..................................................................................................... Page 7
Installing the Trip Unit Mounting Bracket .................................................................................................... Page 9
Installing the Current Sensors ..................................................................................................................... Page 10
Installing the Communications Harness ...................................................................................................... Page 11
Section 5. Installing the Trip Unit ...................................................................................................... Page 11
Section 6. Four-Wire Ground Fault Option ...................................................................................... Page 12
Section 7. Testing and Trouble-shooting ........................................................................................... Page 13
Testing ........................................................................................................................................................ Pages 13
Trouble-Shooting ........................................................................................................................................ Page 14
Nuisance Tripping on Ground Fault-Equipped Breakers .............................................................. Page 14
2
LIST OF FIGURES
1. Primary disconnects removed from the bottom studs. ............................................................................................. Page 4
2. Components supplied with the conversion kit. ........................................................................................................ Page 5
3. Old and New Reset Assembly. ................................................................................................................................ Page 6
4. Installed Reset Assembly. ........................................................................................................................................ Page 6
5. Flux shifter mounting location. ................................................................................................................................ Page 6
6. Flux shifter mounting.. ............................................................................................................................................. Page 6
7. Flux shifter mounting. .............................................................................................................................................. Page 6
8. Installing Reset Link. ............................................................................................................................................... Page 6
9. 36-pin trip unit connector ......................................................................................................................................... Page 7
10. 36-pin connector adapter bracket ............................................................................................................................. Page 7
11. Adapter bracket locking tabs.................................................................................................................................... Page 8
12. Installing the push nuts ono the guide pins. ............................................................................................................. Page 8
13. Locking tabs on mounting plate.. ............................................................................................................................. Page 8
14. Trip unit bracket mounting. ..................................................................................................................................... Page 9
15. Securing trip unit bracket. ........................................................................................................................................ Page 9
16. Position of current sensors. .................................................................................................................................... Page 10
17. Installing current sensors ....................................................................................................................................... Page 10
18. Installing wire harness. .......................................................................................................................................... Page 10
19. Caution label to be applied to the breaker and compartment door... ...................................................................... Page 11
20. Trip unit installed on the breaker. .......................................................................................................................... Page 11
21. Neutral sensor outline for 3000A through 4000A breakers ................................................................................... Page 13
3
SECTION 1. GENERAL INFORMATION
GE Conversion Kit installation is straightforward, but does require careful workmanship and attention to these instructions. Familiarity with the breaker is highly desirable. The general approach is to first remove the existing trip devices from the breaker, then install the Entelliguard, MicroVersaTrip Plus and MicroVersaTrip PM kit components. Following this procedure, the converted breaker is performance tested before it is returned to service.
The majority of trip unit kit installations do not require any customized assembly work. However, some conversions may involve unusual mounting conditions or accessory combinations that require minor modifications and/or relocation of components. In most instances, this supplementary work can be done on site.
In preparation for the conversion, the installer should verify that the appropriate current sensors and trip unit have been furnished. Whenever a ground-fault trip element is installed on a breaker with a four-wire system, an associated neutral sensor (CT) is required for separate mounting in the equipment.
Ensure that retrofitted breakers are applied within their short­circuit ratings. For example, when the trip elements of the breaker are to be changed from long-time instantaneous to long-time short-time, the short-time rating will govern the application.
As a service-related consideration, the installation of a Entelliguard, MicroVersaTrip Plus and MicroVersaTrip PM kit provides an excellent opportunity to perform normal maintenance on the breaker. Such procedures are described in the installation and maintenance manuals supplied with the breaker and equipment.
SECTION 2. BEFORE INSTALLATION
Before starting any work, turn off and lock out all power sources leading to the breaker, both primary and secondary. Remove the breaker to a clean, well-lighted work area.
WARNING: Low-voltage power circuit breakers use high­speed, stored-energy spring operating mechanisms. The breakers and their enclosures contain interlocks and safety features intended to provide safe, proper operating sequences. For maximum personnel protection during installation, operation, and maintenance of these breakers, the following procedures must be followed. Failure to follow these procedures may result in personal injury or property damage.
Only qualified persons, as defined in the National Electrical Code, who are familiar with the installation and maintenance of low-voltage power circuit breakers and switchgear assemblies, should perform any work on these breakers.
Completely read and understand all instructions before attempting any breaker installation, operation, maintenance, or modification.
Turn off and lock out the power source feeding the breaker before attempting any installation, maintenance, or modification. Follow all lock-out and tag-out rules of the National Electrical Code and all other applicable codes.
Do not work on a closed breaker or a breaker with the closing springs charged. Trip the breaker OPEN and be sure the stored-energy springs are discharged, thus eliminating the possibility that the breaker may trip open or the closing springs discharge and cause injury.
Trip the breaker OPEN, then remove the breaker to a well-lighted work area before beginning work.
Do not perform any maintenance that includes breaker charging, closing, tripping, or any other function that could cause significant movement of a draw-out breaker while it is on the draw-out extension rails.
Do not leave the breaker in an intermediate position in the switchgear compartment. Always leave it in the CONNECTED, TEST, or DISCONNECTED position. Failure to do so could lead to improper positioning of the breaker and flashback.
Refer to DEH-4567 for supplementary instructions of settings of the Entelliguard Electronic Trip Unit.
Refer to DEH-3456 for supplementary instructions for wiring the RELT circuit.
Refer to DEH-6273 for supplementary instructions of settings of the MicroVersaTrip Plus and MicroVersaTrip PM.
4
SECTION 3. BREAKER PREPARATION
The following steps are performed to prepare the breaker for installation of the new conversion kit. Unless otherwise indicated, the procedure is the same for LA-3000 Gold, LA­4000 Gold, RL-3200 and RL-4000 breakers.
WARNING: Before installing the conversion kit, turn the breaker OFF, disconnect it from all voltage sources, and discharge the closing springs.
1. Open the breaker and remove it from its enclosure.
Carefully place the breaker on a suitable work surface so that the rear of the breaker is initially accessible.
2. If the conversion kit is to be installed on a fused breaker
(LAF series), remove the fuse structure from the upper (line) studs to allow easier access to the load studs. Additional work may be required to install kit into fused breaker.
3. Loosen the three Allen-head screws securing each of the
primary disconnects to the line (upper) and load (lower) studs and remove the primary disconnects.
4. Remove the wires from the original current sensors (CTs),
if present, and slide off the CTs.
5. Remove manual charging handle. Remove the two bolts
holding the escutcheon to the breaker frame and lift off the escutcheon.
6. Remove old flux shifter and mounting bracket. Also
remove old trip unit and its mounting bracket along with its wire harness.
Figure 1: Primary disconnects removed from bottom studs
Loading...
+ 11 hidden pages