1 GETTING STARTED 1.1IMPORTANT PROCEDURES1.1.1 CAUTIONS AND WARNINGS
To help ensure years of trouble free operation, please read through the following chapter for information to help guide you
through the initial installation procedures of your new relay.
BEFORE ATTEMPTING TO INSTALL OR USE THE RELAY, IT IS IMPERATIVE THAT ALL WARNINGS AND CAUTIONS
IN THIS MANUAL ARE REVIEWED TO HELP PREVENT PERSONAL INJURY, EQUIPMENT DAMAGE, AND/OR
DOWNTIME.
CAUTION: THE OPERATOR OF THIS INSTRUMENT IS ADVISED THAT IF THE EQUIPMENT IS USED IN A MANNER
NOT SPECIFIED IN THIS MANUAL, THE PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED.
1.1.1.1 COMMUNICATION BOARDS WITHDRAWAL / INSERTION
1
WARNING: MODULE WITHDRAWAL AND INSERTION SHALL ONLY BE PERFORMED BY DULY QUALIFIED
SERVICE PERSONNEL. FOR PERSONAL SECURITY PURPOSES, BEFORE ACCOMPLISHING ANY
WITHDRAWAL OR INSERTION OPERATION, THE RELAY MUST BE POWERED OFF AND ALL THE REAR
TERMINALS MUST BE POTENTIAL FREE. THE RELAY MUST BE GROUNDED USING THE REAR GROUNDING
SCREW.
The modular design of the relay allows for the withdra wal and insertion of the communication module.
Figure 1–2: shows the location of communication module s on the rear part of the relay. Qualified personnel must carry out
the insertion or extraction of the communication boards only after interrupting the relay auxiliary voltage and ensuring that
all the rear terminals are potential free.
Communication boards are installed on the rear of the unit, the upper port being reserved for the asynchronous
communications board and CAN, and the lower port for the ETHERNET board in any of its configurations.
Before performing any of these actions, control power must be removed fro m the relay and all the r ear terminalsmust be potential free. A grounded anti static wristband must be u sed when manipul ating the mo dule in or der to avoid
electrostatic discharges that may cause damage to the electronic components.
WITHDRAWAL: Loosen the small screws that keep the faceplate in place and extract the module.
INSERTION: Insert the module and press it firmly in the case, until it is completely fixed. After this, bolt the facep late
screws and replace the control power. Check that the relay is fully operative.
Figure 1–2: MODULE WITHDRAWAL/INSERTION
GE Multilin will not be responsible for any damage of the re la y, connected equipment or personnel whenever
The transformer module for the VTs and CTs is already connected to a female connector screwed to the case. The
current inputs incorporate shorting bars, so that the module can be extracted without the need to short-circuit the
currents externally. It is very important, for safety reasons not to change or switch the terminals for CTs and VTs.
AC Input Terminals
1
GE Multilin
Figure 1–3: REAR VIEW OF W650 UNIT
will not be responsible for any damage of the relay, connected equipment or personnel
For product information, instruction manual updates, and the latest software updates, please visit the GE Multilin Home
Page www.geindustrial.com/multilin.
Note: If there is any physical damage detected on the relay, or any of the contents listed are missing, please
contact GE Multilin immediately at:
EUROPE, MIDDLE EAST AND AFRICA:
GE MULTILIN
Av. Pinoa, 10
48170 Zamudio, Vizcaya (SPAIN)
Tel.: (34) 94-485 88 54, Fax: (34) 94-485 88 38
E-mail: multilin.tech.euro@ge.com
AMERICA, ASIA AND AUSTRALIA:
GE MULTILIN
215, Anderson Avenue
L6E 1B3 Markham, ON (CANADA)
Tel.: +1 905 294 6222, Fax: +1 905 201 2098
E-mail: multilin.tech@ge.com
1
The information provided herein is not intended to cover all the details of the variations of the equipment, nor does
it take into account the circumstances that may be present in your installation, operating or maintenance
activities.
Should you wish to receive additional information, or for any particular problem that cannot be solved by referring
to the information contained herein, please contact GENERAL ELECTRIC MULTILIN.
The W650 ground screw shown in Figure 1–5: must be correctly grounded.
Figure 1–5: LOCATION OF GROUNDING SCREW
Before communicating with a W650 unit through the front serial port, please ensure that the computer is grounded.
In case of using a laptop, it is recommended not to have it connected to its power supply. In many cases it might not be
correctly grounded either due to the power supply or to the connector cables used.
This is required not only for personal protection, bu t also to avoid a potential voltage difference between the
relay’s serial port and the computer’s port, which could produce permanent damage to the computer or the relay.
GE Multilin will not be responsible for any damage to the relay or connected equipment whenever this elemental
safety rule is not followed.
1.2OVERVIEW1.2.1 INTRODUCTION TO 650 FAMILY OF RELAYS
Historically, substation protection, control and metering functions were performed with electromechanical equipment. This
first generation of equipment was gradually replaced by analog electronic equipment (called static devices), most of which
emulated the single-function approach of their electromechanical precursors. Both of these technologies required
expensive cabling and auxiliary equipment to produce functioning systems.
Recently, digital electronic equipment has begun to provide protection, control and metering functions. Initially, this
equipment was either single function or had very limited multi-function capability, and did not significantly reduce the
cabling and auxiliary equipment required. However, recent digital relays have become quite multi-functional, reducing
cabling and auxiliaries significantly. These devices also transfer data to central control facilities and Human Machine
Interfaces using electronic communications. The functions pe rformed by these produ cts have become so broad that many
users prefer the term IED (Intelligent Electronic Device).
It is obvious to station designers that the amount of cabling and auxiliary equipment installed in stations can be even further
reduced, to 20% to 70% of the levels common in 1990, to achieve large cost r eductions. This requires placi ng even more
functions within the IEDs.
Users of power equipment are also interested in reducing cost by improving power quality and perso nnel productivity, and
as always, in increasing system reliability and efficiency. These objectives are realized through software which is used to
perform functions at both the station and supervisory levels. The use of these systems is growing rapidly.
High speed communications are required to meet the data transfer rates required by modern automatic control and
monitoring systems. In the near future, very high speed communications will be required to perform protection signalling.
This has been established by the IEC 61850 standard.
IEDs with capabilities outlined above will also provided significantly more power system data than is presently available,
enhance operations and maintenance, and permit the use of adaptative system configuration for protection and co ntrol
systems. This new generation of equipment must also be easily incorporated into automation systems, at both the station
and enterprise levels.
1
1.2.2 HARDWARE ARCHITECTURE
650 family of relays has been designed to meet the goals described above that are appearing nowadays in the environment
of new substations.
The 650 is a digital-based device containing a central processing unit (CPU) that handles multiple types of input and output
signals. The 650 family can communicate over a local area netwo rk (LAN) with an operator interface, a programming
device, or another 650 or UR device.
The CPU module contains firmware that provides protection elements in the form of logic algorithms, as well as
programming logic gates, timers, and latches for contro l features. It incorporates two internal processors, one for ge neric
use and a second one dedicated for communications.
Input Elements accept a variety of analog or digital signals from the field. The 650 isolates and converts these signals into
logic signals used by the relay.
Output Elements convert and isolate the logic signals generated by the relay into digital signals that can be used to control
field devices.
Contact Inputs/Outputs are signals associated to the physical input/output contacts in the relay
CT and VT inputs are signals coming from the inputs of current and voltage transformers, used for monitoring the power
system signals.
CAN Bus Inputs/Outputs: are signals associated to physical input/output contacts from independent modules connected
to the 650 unit via a CAN Bus.
PLC: Programmable Logic Controller. Control module that enables the unit configuration (assignment of inputs/outputs)
and the implementation of logic circuits.
Protection Elements: Relay protection elements, for example: Overcurrent, overvoltage, etc.
Remote inputs and outputs provide a means of sharing digital point state information between remote devices using IEC
61850 GSSE messages.
Analog Inputs are signals associated with transducers.
The firmware (software embedded in the relay) has been designed usin g object oriented progra mming techniques (OOP).
These techniques are based on the use of objects and classes, and provide the software architecture with the same
characteristics as the hardware architecture, i.e., modularity, scalability and flexibility.
1.2.4 COMMUNICATIONS ARCHITECTURE
The main processor performs protection, control, and communication functions, incorporating two internal processors, one
for generic use and a second one dedicated for communications.
A dedicated serial port is used for communication between the main processor and the human-machine interface . The
serial connection provides great immunity against electromagnetic disturbances, thus increasing system safety.
All W650 units incorporate an RS232 serial port on the front of the relay. There is also a possibility to incorporate up to two
additional communication modules on the rear.
One of the modules provides asynchronous serial communications, using different physical media (RS485, plastic or glass
fiber optic) depending on the selected model. The module incorporates two id entical po rts, COM1 and COM2. The C OM2
port is multiplexed with the front port.
Available options are:
Table 1–1: REAR SERIAL COMMUNICATIONS BOARD 1
BOARD CODEFUNCTIONALITY
FNone
ARedundant RS 485
pRedundant plastic fiber optic
GRedundant glass fiber optic
XRedundant RS485 + Can port (CANopen)
YRedundant plastic fiber optic + Can port (CANopen)
ZRedundant glass fiber optic + Can port (CANopen)
CCAN port (CANopen)
MRS485 + CAN port (CANopen)
1
The other module provides Ethernet communications (COM3 port), using 10/100BaseTX (self-negotiable speed) or
100BaseFX connectors, depending on the selected model. The most complete models include a double redundant
100BaseFX fiber optic port. Redundancy is provided at the physical level; the unit incorporates internally du plicated and
independent controllers for extended system reliability and accessibility.
Available Options are:
Table 1–2: REAR ETHERNET COMMUNICATIONS BOARD 2
BOARD
CODE
BOne 10/100BaseTX port (self-negotiable speed)
COne 10/100BaseTX port and one 100BaseFX port.
DOne 10/100BaseTX port and redundant 100BaseFX ports
ERedundant 10/100BaseTX ports
FUNCTIONALITY
For options C and D it is required to select the active physical media, by means of an intern al selector inside the module.
The factory configuration for this selection is the 10/100BaseTX port.
Finally, internal communication with input and output modules is performed via an internal CAN bus. This fa ct provides
increased communication speed, as well as the possibility of acknowledgement of modules, abnormalitie s, etc. As this is a
serial port supporting a communications protocol, it provides extraordinary immunity against external or internal
disturbances.
1.3ENERVISTA 650 SETUP SOFTWARE1.3.1 SYSTEM REQUIREMENTS
The EnerVista 650 Setup software interface is the preferred method to edit settings and view actual values because the PC
monitor can display more information in a simple comprehensible format.
The following minimum requirements must be met for the EnerVista 650 Setup software to properly operate on a PC:
•Pentium® class or higher processor (Pentium® II 300 MHz or higher recommended)
•Windows® NT 4.0 (Service Pack 3 or higher), Windows® 2000, Windows® XP
•Internet Explorer® 5.0 or higher
•64 MB of RAM (128 MB recommended)
•40 MB of available space on system drive and 40 MB of available space on installation drive
•RS232C serial and/or Ethernet port for communications to the relay
1.3.2 INSTALLATION
After ensuring the minimum requirements for using EnerVista 650 Setup are met (see previous section), use the following
procedure to install the EnerVista 650 Setup from the GE EnerVista CD.
1.Insert the GE EnerVista CD into your CD-ROM drive.
2.Click the Install Now button and follow the installation instructions to install the no-charge EnerVista software.
3.When installation is complete, start the EnerVista Launchpad application.
4.Click the IED Setup section of the Launch Pad window.
5.In the EnerVista Launch Pad window, click the Add Product button and select the “W650 Wind Generator Protection
1
System” relay from the Install Software window as shown below. Select the “Web” option to ensure the most recent
software release, or select “CD” if you do not have a web connection , then click the Add Now button to list software
items for the W650.
Figure 1–9: ADD PRODUCT WINDOW
6.If “Web” option is selected, chose the W650 software program and release notes (if desired) from the list and cl ick the
Download Now button to obtain the installation program.
7.EnerVista Launchpad will obtain the installation program from the Web or CD. Once the download is complete, double-
click the installation program to install the EnerVista 650 Setup software.
8.Select the complete path, including the new directory name, where the EnerVista 650 Setup will be installed.
9.Click on Next to begin the installation. The files will be installed in the directory indicated and the in stallation program
will automatically create icons and add EnerVista 650 Setup to the Windows start menu.
10. Follow the on-screen instructions to install the EnerVista 650 Setup software. When the Welcome window appears,
click on Next to continue with the installation procedure.
1
Figure 1–11: ENERVISTA 650 SETUP INSTALLATION
11. When the Choose Destination Location window appears, and if the software is not to be located in the default
directory, click Change… and type in the comple te path name including the new directory name and click Next to
continue with the installation procedure.
12. The default program group where the application will be added to is shown in the Sele cted Program F older window.
Click Next to begin the installation process, and all the necessary program files will be copied into the chosen directory.
1
Figure 1–13: SELECT PROGRAM FOLDER
13. To finish with the installation proce ss, select the desired language for startup.
This section is intended as a quick start guide to using the EnerVista 650 Setup software. Please refer to section 4.1 in this
manual for more information about the EnerVista 650 Setup software interface.
a) CONFIGURING AN ETHERNET CONNECTION
Before starting, verify that the Ethernet network cable is properly connected to the Ethernet port on the back of the relay.
1. Install and start the latest version of the EnerVista 650 Setup software (available from the GE EnerVista CD or online
from http://www.GEindustrial.com/multilin (see previous section fo r installation instructions).
2. Go to “Communication>Computer” and enter the following data refering to communications:
3. Select Control Type as MODBUS TCP/IP from the drop-down list. This option will display a number of interface
parameters that must be entered for proper Ethernet communications.
4. Enter the relay IP address (from “Setpoint>Product Setup >Communication Settings>Network>IP ADDRESS”) in
the IP Address field in MODBUS TCP/IP SETUP.
5. Enter the relay ModBus address (from “Setpoint>Product Setup >Communication Settings>ModBus
Protocol>ModBus Address COM1/COM2 setting”) in the Unit Identifier (Sl ave Address) fi eld.
6. Enter the ModBus port address (from “Setpoint>Product Setup >Communication Settings>ModBus
Protocol>ModBus Port Number” setting) in the ModBus Port field.
7.The Device has now been configured for Ethernet communications. Proceed to press the ON button to begin
communicating.
b) CONFIGURING AN RS232 CONNECTION
Before starting, verify that the RS232 serial cable is properly connected to the RS232 port on the front panel of the relay.
1. Install and start the latest version of the EnerVista 650 Setup software (available from the GE EnerVista CD or online
from http://www.GEindustrial.com/multilin (see previous section fo r installation instructions).
2. Go to “Communication>Computer” and enter the following data referred to communications:
3. Select Control Type as No Control Type from the drop-down list. This option will display a number of interface
parameters that must be entered for proper serial communications.
4. Enter the relay Slave Address (“Setpoint>Product Setup >Communication Settings>ModBus Pro tocol” menu) in the
Slave Address field.
5. Enter the physical communications parameters (Baudrate and parity settings) from “Setpoint>Product Setup
>Communication Settings>Serial Ports” menu, in their respective fields.
6.The Device has now been configured for RS232 communications. Proceed to press the ON button to begin
Please refer to Chapter 3. Hardware for detailed mounting and wiring instructions.
1.4.2 W650 COMMUNICATIONS
The Enervista 650 Setup software communicates to the relay via the fa ceplate RS232 port or the rear RS485/Ethernet
ports. To communicate via the faceplate RS232 port, a standard “straight-through” serial cable is used. The DB-9 male end
is connected to the relay and the DB-9 or DB-25 female en d is connected to the PC COM1 or COM2 po rt as described in
Figure 1–16:.
To communicate through the W650 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is
required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shi elded
twisted-pair (20, 22 or 24 AWG according to American standards; 0.25, 0.34 or 0.5 mm2 according to European standards)
connects the F485 converter to the W650 rear communication port.
In order to minimize communication errors that could be caus ed by external noise, it is recommended to use a shi elded
twist pair. In order to avoid loops where external currents could flow, the cabl e shield must be grounded only at one end.
The converter box (-, +, GND) terminals are connected to the relay (SDA, SDB, GND) terminals respectively. For long
communications cables (longer than 1 km), the RS485 circuit must be terminated in an RC network (i.e. 120 ohm, 1 nF).
This circuit is shown on Figure 1–17: RS485 CONNECTION FOR 650 UNITS, associated to text Zt(*).
1
Figure 1–16: RELAY- PC CONNECTION FOR RS232 FRONT PORT
To minimize errors from noise, th e use of shielded twisted pair wire is recommended. For correct operation, po larity must
be respected, although a different polarity will not damage the unit. For instance, the relays must be connected with all
RS485 SDA terminals connected together, and all SDB terminals connected together. This may result confusing
sometimes, as the RS485 standard refers only to terminals named “A” and “B”, although many devices use terminals
named “+” and “-“.
As a general rule, terminals “A” should be connected to terminals “-“, and terminals “B” to “+”. The GND terminal should be
connected to the common wire inside the shield, when provi ded. Otherwise, it should be connected to the shield. Each
relay should also be daisy chained to the next one in the link. A maximum of 32 relays can be connected in thi s manner
without exceeding driver capability. For larger systems, additional serial channels must be added. It is also possible to use
commercially available repeaters to increase the number of relays on a single channel to more th an 32. Do not use other
connection configurations different to the recommended.
Lightning strikes and ground surge currents can cause large mo mentary voltage differences between remote ends of the
communication link. For this reason, surge protection devices are internally provided. To ensure maximum reliability, all
1
equipment should have similar transient protection devices installed.
Figure 1–17: RS485 CONNECTION FOR 650 UNITS
To comunícate through theW650 rear Ethernet port from a PC a crossover cable is required. If the connection is
performedthrough a hub or a switch, a direct Ethernet cable is required.
1.4.3 FACEPLATE DISPLAY
All messages are displayed on a 20x4 character LCD display. An optional graphic display is also available. Messages are
displayed in different languages according to selected model.
W650 requires a minimum amount of maintenance when it is commissioned into service.W650 is a microprocessor based
relay and its characteristics do not change over time. As such no further functional tests are required. However, it is
recommended that maintenance on theW650 be scheduled with other system maintenance. The maintenance may involve
the following:
In-service maintenance:
1.Visual verification of the analog values integrity such as voltage and current (in comparison to other devices on the
corresponding system).
2.Visual verification of active alarms, relay display messages and LED indications.
3.Visual inspection for any damage, corrosion, dust or loose wires.
4.Event recorder file download with further event analysis.
Out-of-service maintenance:
1.Check wiring connections for firmness.
2.Analog values (current, voltages, analog inputs) injection test and metering accuracy verification. Calibrated test
equipment is required.
3.Protection elements setpoints verification (analog values injection or visua l verification of setting file entries against
relay settings schedule).
4.Contact inputs and outputs verification. This test can be conducted by direct change of state forcing or as part of the
system functional testing.
5.Visual inspection for any damage, corrosion or dust.
6.Event recorder file download with further events analysis.
1
Unscheduled maintenance such as during a disturbance causing system interruption:
1.View the event recorder and oscillography or fault report for correct operation of inputs, outputs and elements.
If it is concluded that the relay or one of its modules is of concern, contact GE Multilin or one of its representative for prompt
The modular W650 unit has been designed as a comprehensive generator controller specially adapted to wind turbine
generators. Based on the state of the art 650 family, it utilizes modern 32 bit processor platform to provide a complete
solution not only for the needs of present systems but also ready for the future. W650 simplifies the design of systems in
wind turbine generation due to the complete set of protection, measurement, control and recording functions. Maintenance
is eased thanks to the modular design wherea s cost is scalabl e de pending on th e options to allow a cost effective solution
from medium to large size generators.
The main features of W650 devices include:
•Directional overcurrent protection for phases, neutral, ground and sensitive ground
•High Speed Under and overvoltage protection
•Neutral Overvoltage
•Voltage Unbalance
•Under and overfrequency protection
•Autorecloser
•Metering
•Oscillography registers, fault reports, data logger
27P (4)Phase Undervoltage
27X (3)Auxiliary Undervoltage
32 (4)Directional Power
46 (3)Negative Sequence Time Overcurrent
50G (3)
50N (3)Neutral Instantaneous Overcurrent (calculated from the phase currents)
50P (6)Phase Instantaneous Overcurrent (two elements, High and Low)
50SG (3)
51G (3)
51N (3)Neutral Time Overcurrent (calculated from the phase currents)
51P (6)Phase Time Overcurrent with Voltage Restraint (two elements, High and Low)
51SG (3)
9 Analog Inputs: 5 current inputs (3 for phases,
1 for ground, 1 for sensitive ground), 4 voltage
inputs (3 for phases, 1 for auxiliary voltage)
Digital Programmable Contact Inputs (up to
64)
Digital Programmable Contact Outputs (up to
2
16)
32 Latched Virtual Inputs
32 Self-Reset Virtual Inputs
Virtual Outputs (up to 512)FrequencyModBus User Map
Tripping and closing circuit supervisionSequence components of currents and
W650 units are supplied as ½ 19” rack, 6 units high, containing the followi ng modules: power supply, CPU, I/O modules,
communication modules. The required information to completely define an W650 model is shown on Table 2–1:
(1) The digit selected for option G must be equal or higher than the digit selected for option F:
W650***F1G5*****: is a valid selectionW650***F5G1*****: is an invalid selection
As exceptions to this rule, 0 is always available for option G, and F2G1 is also a valid selection.
NOTE: TECHNICAL SPECIFICA TIONS ARE SUBJECT T O CHANGE WITHOUT NOTICE
2.4.1 PROTECTION ELEMENTS
Phase and ground units use as operation magnitude the current value received by the unit in current inputs, while the
neutral unit uses the calculated current value fro m the three ph ase currents.
2
The isolated ground unit will be used only fo r those applications where the neutral is comp letely isolated, and it uses the
fifth CT of the unit. This CT has a sensitivity that is 10 times higher than the universal model (connected to 1A or 5A
transformers). Therefore, it does not admit such a high permanent overload.
2.4.1.1 PHASE TIME OVERCURRENT (51PH/51PL)
Current InputPhasor (without harmonics) or RMS
Rated currentFor connection to 1 or 5 A CTs.
Pickup level0.05 to 160.00 A in steps of 0.01 A
Dropout level98% of the pickup level
Level Accuracy
Curve ShapesIEEE extremely / very / moderately inverse
Curve Multiplier (Time Dial)0.00 to 900.00 s in steps of 0.01 s
Reset typeInstantaneous or time delayed according to IEEE
Timing accuracyOperate at > 1.03 times the pickup ±3% of operate time or
Voltage restraintSelectable by setting
Saturation Level48 times the pickup level
Snapshot EventsSelectable by setting
±0.5% of the reading ± 10 mA from 0.05 to 10 A
±1.5% of the reading for higher values.
IEC A/B/C/long-time inverse/short time inverse curve
IAC extremely / very / normally / moderately inverse
ANSI extremely / very / normally / moderately inverse
2
t
I
Definite time
Rectifier curve
FlexCurve™ A/B/C/D user curve
30 ms. (whichever is greater)
2.4.1.2 GROUND TIME OVERCURRENT (51G)
Current InputPhasor (without harmonics) or RMS
Rated currentFor connection to 1 or 5 A CTs.
Pickup level0.05 to 160.00 A in steps of 0.01 A
Dropout level98% of the pickup level
Level Accuracy
±0.5% of the reading ± 10 mA from 0.05 to 10 A
±1.5% of the reading for higher values.
Page 37
2 PRODUCT DESCRIPTION2.4 TECHNICAL SPECIFICATIONS
Curve ShapesIEEE extremely / very / moderately inverse
IEC A/B/C/long-time inverse/short time inverse curve
IAC extremely / very / normally / moderately inverse
ANSI extremely / very / normally / moderately inverse
2
I
t
Definite time
Rectifier curve
FlexCurve™ A/B/C/D user curve
Curve Multiplier (Time Dial)0.00 to 900.00 s in steps of 0.01 s
Reset typeInstantaneous or time delayed according to IEEE
Timing accuracyOperate at > 1.03 times the pickup ±3% of operate time or
30 ms. (whichever is greater)
Saturation Level48 times the pickup level
Snapshot EventsSelectable by setting
2.4.1.3 NEUTRAL TIME OVERCURRENT (51N)
Current InputFundamental Phasor (without harmonics)
Pickup level0.05 to 160.00 A in steps of 0.01 A
Dropout level98% of the pickup level
Level Accuracy
Curve ShapesIEEE extremely / very / moderately inverse
Curve Multiplier (Time Dial)0.00 to 900.00 s in steps of 0.01 s
Reset typeInstantaneous or time delayed according to IEEE
Timing accuracyOperate at > 1.03 times the pickup ±3% of operate time
Saturation Level48 times the pickup level
Snapshot EventsSelectable by setting
±0.5% of the reading ± 10 mA from 0.05 to 10 A
±1.5% of the reading for higher values.
IEC A/B/C/long-time inverse/short time inverse curve
IAC extremely / very / normally / moderately inverse
ANSI extremely / very / normally / moderately inverse
2
I
t
Definite time
Rectifier curve
FlexCurve™ A/B/C/D user curve
Current InputPhasor (without harmonics) or RMS
Rated currentFor connection to 1 or 5 A CTs.
Pickup level0.005 to 16.000 A in steps of 0.001 A
Dropout level98% of the pickup level
Level Accuracy
2
Curve ShapesIEEE extremely / very / moderately inverse
Curve Multiplier (Time Dial)0.00 to 900.00 s in steps of 0.01 s
Reset typeInstantaneous or time delayed according to IEEE
Timing accuracyOperate at > 1.03 times the pickup ±3% of operate time
Saturation Level48 times the pickup level
Snapshot EventsSelectable by setting
±1.5% of the reading ± 1 mA from 0.005 to 16 A
IEC A/B/C/long-time inverse/short time inverse curve
IAC extremely / very / normally / moderately inverse
ANSI extremely / very / normally / moderately inverse
2
I
t
Definite time
Rectifier curve
FlexCurve™ A/B/C/D user curve
or 30 ms. (whichever is greater)
2.4.1.5 PHASE AND GROUND INSTANTANEOUS OVERCURRENT (50PH/50PL/50G)
Current InputPhasor (without harmonics) or RMS
Rated currentFor connection to 1 or 5 A CTs.
Pickup level0.05 to 160.00 A in steps of 0.01 A
Dropout level97% of the pickup level
Level Accuracy
Overreach< 2%
Trip delay0.00 to 900.00 s. in steps of 0.01 s.
Reset delay0.00 to 900.00 s. in steps of 0.01 s.
Operate time20 ms at 3 x Pickup at 50 Hz, typically
Timing accuracy±3% of operate time or 30 ms. (whichever is greater)
Snapshot EventsSelectable by setting
±0.5% of the reading ± 10 mA from 0.05 to 10 A
±1.5% of the reading for higher values
Current InputFundamental Phasor (without harmonics)
Pickup level0.05 to 160.00 A in steps of 0.01 A
Dropout level97% of the pickup level
Level Accuracy
Overreach< 2%
Trip delay0.00 to 900.00 s. in steps of 0.01 s.
Reset delay0.00 to 900.00 s. in steps of 0.01 s.
Operate time20 ms at 3 x Pickup at 50 Hz, typically
Timing accuracy±3% of operate time or 30 ms. (whichever is greater)
Snapshot EventsSelectable by setting
Current InputPhasor (without harmonics) or RMS
Rated currentFor connection to 1 or 5 A CTs.
Pickup level0.005 to 16.000 A in steps of 0.001 A
Dropout level97% of the pickup level
Level Accuracy
Overreach< 2%
Trip delay0.00 to 900.00 s. in steps of 0.01 s.
Reset delay0.00 to 900.00 s. in steps of 0.01 s.
Operate time20 ms at 3 x Pickup at 50 Hz
Timing accuracy±3% of operate time or 30 ms. (whichever is greater)
Snapshot EventsSelectable by setting
±0.5% of the reading ± 10 mA from 0.05 to 10 A
±1.5% of the reading for higher values
Current InputFundamental Phasor (without harmonics)
Pickup level0.05 to 160.0 A in steps of 0.01 A
Dropout level98% of the pickup level
Level Accuracy
2
Curve ShapesIEEE extremely / very / moderately inverse
Curve Multiplier (Time Dial)0.00 to 900.00 s in steps of 0.01 s
Reset typeInstantaneous or time delayed according to IEEE
Timing accuracyOperate at > 1.03 times the pickup ±3% of operate time
Saturation Level48 times the pickup level
Snapshot EventsSelectable by setting
±0.5% of the reading ± 10 mA from 0.05 to 10 A
±1.5% of the reading for higher values
IEC A/B/C/long-time inverse/short time inverse curve
IAC extremely / very / normally / moderately inverse
ANSI extremely / very / normally / moderately inverse
2
I
t
Definite time
Rectifier curve
FlexCurve™ A/B/C/D user curve
or 30 ms. (whichever is greater)
2.4.1.9 PHASE DIRECTIONAL (67P)
DirectionalityForward and reverse selectable by setting
PolarizingQuadrature Voltage:
ABC seq: Phase A (VBC), Phase B (VCA), Phase C
(VAB)
ACB seq: Phase A (VCB), Phase B (VAC), Phase C
(VBA)
Polarizing voltage threshold0 to 850 V ac in steps of 1 V
Characteristic angle-90º to +90º in steps of 1º
Block LogicPermission or Block selectable by setting
Angle accuracy
Operate time<30ms, typically
2.4.1.10 GROUND DIRECTIONAL (67G)
DirectionalityForward and reverse selectable by setting
PolarizingVoltage, current, dual
Polarizing V o ltageVN (measured or calculated, selected by setting)
Polarizing Current
Operating Current
Polarizing Voltage threshold0 to 500 Vac in steps of 1 V
Characteristic angle-90º to +90º in steps of 1º
Block LogicPermission or Block selectable by setting
Angle accuracy
Operate time<30ms, typically
±2º for I>0.1 A and V>5 Vac
2.4.1.11 NEUTRAL DIRECTIONAL (67N)
DirectionalityForward and reverse selectable by setting
PolarizingVoltage, current, dual
Polarizing V o ltageV
Polarizing Current
Operating CurrentI
Polarizing Voltage threshold0 to 500 Vac in steps of 1 V
Polarizing Current threshold0.005 A
Characteristic angle-90º to +90º in steps of 1º
Block LogicPermission or Block selectable by setting
Angle accuracy
Operate time<30ms, typically
2.4.1.12 SENSITIVE GROUND DIRECTIONAL (67SG)
DirectionalityForward and reverse selectable by setting
PolarizingVoltage
Polarizing V o ltageV
Operating Current
Polarizing Voltage threshold0 to 500 Vac in steps of 1 V
Characteristic angle-90º to +90º in steps of 1º
Block LogicPermission or Block selectable by setting
Angle accuracy
Operate time<30ms, typically
(measured or calculated, selected by setting)
N
th
Isg (measured from 5
N
±2º for I>0.1 A and V>5 Vac
(measured or calculated, selected by setting)
N
Isg (measured from 5
±2º for I>0.1 A and V>5 Vac
current transformer)
th
current transformer)
2
2.4.1.13 PHASE OVERVOLTAGE (59P)
Voltage InputFundamental Phasor (without harmonics) of phase-to-
phase voltages
Pickup level3 to 850 in steps of 1 V
Dropout level97% of the pickup level
Level Accuracy
Trip delay0.00 to 900.00 s. in steps of 0.01 s.
Reset delay0.00 to 900.00 s. in steps of 0.01 s.
Timing accuracy±3.5% of op erate time or 30 ms. (whichever is greater)
LogicAny/Two/All phases logic selectable by setting
Voltage InputFundamental Phasor of phase-to-ground or phase-to-
2
Pickup level3 to 850 in steps of 1 V
Dropout level103% of the pickup leve l
Level accuracy
Curve ShapesFixed time or inverse curve
Reset typeInstantaneous
Curve Multiplier (Time Dial)0.00 to 900.00 s. in steps of 0.01 s.
Timing accuracy±3.5% of operate time or 30 ms. (whichever is greater)
Minimum Voltage Threshold0 to 850 in steps of 1 V
LogicAny/Two/All phases logic selectable by setting
Supervised by BreakerSelectable by setting
Snapshot EventsSelectable by setting
phase voltages (selectable by setting)
±1% reading ±0.1% Full Scale from 10 to 500 V
2.4.1.15 NEUTRAL OVERVOLTAGE (59NH/59NL)
Voltage InputFundamental Phasor of the neutral voltage
Pickup level3 to 500 in steps of 1 V
Dropout level97% of the pickup level
Level accuracy
Trip delay0.00 to 900.00 s. in steps of 0.01 s
Reset delay0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy±3.5% of operate time or 30 ms. (whichever is greater)
Snapshot EventsSelectable by setting
2.4.1.16 AUXILIARY OVERVOLTAGE (59X)
Voltage InputFundamental Phasor
Pickup level3 to 500 in steps of 1 V
Dropout level97% of the pickup level
Level accuracy
Trip delay0.00 to 900.00 s. in steps of 0.01 s
Reset delay0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy±3.5% of operate time or 30 ms. (whichever is greater)
Snapshot EventsSelectable by setting
Voltage InputFundamental Phasor
Pickup level3 to 500 V in steps of 1 V
Dropout level97% of the pickup level
Level accuracy
Curve ShapesFixed time or inverse curve
Reset typeInstantaneous
Curve Multiplier (Time Dial)0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy±3.5% of operate time or 30 ms. (whichever is greater)
Snapshot EventsSelectable by setting
2.4.1.18 UNDERFREQUENCY (81U)
Pickup level20.00 to 65.00 Hz in steps of 0.01 Hz
Dropout levelPickup + 0.03 Hz
Level accuracy
Trip delay0.00 to 900.00 s. in steps of 0.01 s
Reset delay0.00 to 900.00 s. in steps of 0.01 s
Minimum voltage threshold30 to 500V in steps of 1 V
Timing accuracy±3.5% of operate time or 100 ms. (whichever is greater)
Snapshot EventsSelectable by setting
±1% reading ±0.1% Full Scale from 10 to 500 V
±0.01 Hz of the reading
2
2.4.1.19 OVERFREQUENCY (81O)
Pickup level20.00 to 65.00 Hz in steps of 0.01 Hz
Dropout levelPickup - 0.03 Hz
Level accuracy
Trip delay0.00 to 900.00 s. in steps of 0.01 s
Reset delay0.00 to 900.00 s. in steps of 0.01 s
Minimum voltage threshold30 to 500V in steps of 1 V
Timing accuracy±3.5% of operate time or 100 ms. (whichever is greater)
Snapshot EventsSelectable by setting
2.4.1.20 DIRECTIONAL POWER (32)
Current, VoltageFundamental Phasor (primary values)
Number of stages2
Pickup level (two stages)-10000.00 to 10000.00 MW (primary values) in steps of
Characteristic Angle (two stages)0.00 to 359.99 in steps of 0.01
Dropout level97% of the pickup level
Accuracy for primary magnitudes±3% complete range
Trip delay (two stages)0.00 to 900.00 s in steps of 0.01 s
Timing accuracy±3.5% of operate time or 30 ms. (whichever is greater)
Block Time after close0.00 to 900.00 s in steps of 0.01 s
Snapshot EventsSelectable by setting
2.4.1.21 VOLTAGE UNBALANCE (60V)
2
Pickup level 0.00-500.00% (V2/V1 ratio) in steps of 0.01%
Reset delay0.00 to 900.00 s in steps of 0.01 s
Trip delay0.00 to 900.00 s in steps of 0.01 s
Timing accuracy±3.5% of operate time or 30 ms. (whichever is greater)
Snapshot EventsSelectable by setting
2.4.2.1 AUTORECLOSE (79)
SchemesThree-pole tripping schemes
Number of shotsUp to 4 reclose attempts before lockout
Dead timeIndependent dead time setting before each shot
adjustable between 0 and 900 s in steps of 0.01 s
Reclaim time0.0 0 to 900.00 s in steps of 0.01 s
Condition permissionSelectable by setting
Hold time0.00 to 900.00 s in steps of 0.01 s
Reset time0.00 to 900.00 s in steps of 0.01 s
Snapshot EventsSelectable by setting
Possibility to modify protection settings after each shot programmable through PLC (block signals available after each
shot)
2.4.2 CONTROL
2.4.2.2 FUSE FAILURE
Algorithm based on positive sequence of voltage and current
Activation by V
2.4.2.3 BREAKER FAILURE (50BF)
Current InputFundamental Phasor (without harmonics)
Rated currentFor connection to 1 or 5 A CTs.
Pickup level for supervision0.05 to 160.00 A in steps of 0.01 A
Pickup level for high level0.05 to 160.00 A in steps of 0.01 A
Pickup level for low level0.05 to 160.00 A in steps of 0.01 A
Pickup level for internal arcing0.05 to 160.00 A in steps of 0.01 A
Reset level97% of the pickup level
Timing accuracy±3.5% of operate time or 30 ms. (whichever is greater)
Snapshot EventsSelectable by setting
2.4.2.4 BREAKER SETTINGS
Number of Switchgear1 to 16 (selection of switchgear for breaker control)
Maximum KI2t 0.00 to 9999.99 in steps of 0.01 (kA)2 s
KI2t integration Time
Maximum openings0 to 9999 in steps of 1
Maximum Openings in one hour1 to 60 in steps of 1
Snapshot EventsSelectable by setting
2.4.2.5 BREAKER MAINTENANCE
KI2t Breaker Counters for Phases A, B, C0.00 to 9999.99 in steps of 0.01 (kA)2 s
Breaker Openings Counter0 to 9999 in steps of 1
Breaker Closings Counter0 to 9999 in steps of 1
±0.5% of the reading ± 10 mA from 0.05 to 10 A
±1.5% of the reading for higher values.
0.03 to 0.25 s in steps of 0.01 s
2
2.4.2.6 SWITCHGEAR
Switchgear1 to16 (configurable in “relay configuration” screen).
Snapshot EventsSelectable by setting (for each switchgear in “system
setup”)
2.4.3 MONITORING
2.4.3.1 OSCILLOGRAPHY
Maximum Records:Up to 20 Oscillography records.
Sampling rate:Programmable to 4, 8, 16, 32 or 64 samples per power cycle
Capacity per record:
No of Oscillos * No of samples/cycle
Trigger position:
Trigger:Programmable via PLC
Data:5 current channels and 4 voltage channels
Data Storage:In non volatile memory (flash) without battery
Format:International Standard COMTRADE ASCII - IEEE C37.111-1999.
Automatic Overwrite:Selectable by setting. (Oscillography records can be concatenated)
Snapshot Events:Selectable by setting
5% to 95% of total length
Up to 16 digital channels programmable through PLC
Method:Single-ended
Positive Sequence Module:0.01 to 250.00 Ohm in steps of 0.01 Ohms
Positive Sequence Angle:25 to 90º in steps of 1º
2
Zero Sequence Module:0.01 to 750.00 Ohms in steps of 0.01 Ohm
Zero Sequence Angle:25 a 90º in steps of 1º
Line Length:0.0 to 2000.0 in steps of 0.1 (miles or km)
Accuracy:5% (typical)
Show Fault on HMI:Selectable by setting
Snapshot Events:Selectable by setting
Maximum Records:Up to 10 fault report records.
Data:Fault date and time, pre-fault currents and voltages, fault currents and voltages,
fault type, distance to the fault (fault location), line parameters, recloser and
breaker status information.
Data Storage:In non volatile memory (flash) without battery available through communications
In volatile memory (ram) available through HMI (if selectable by setting)
Format:Text in ASCII format
2.4.3.3 SNAPSHOT EVENTS
Capacity:479 scrolling events
Time-tag
Timing Accuracy:1 ms (using the IRIG-B synchronization input)
Triggers:
Data Storage
The snapshot event recording procedure can be enabled or disabled by setting for each protection function
2.4.3.4 CONTROL EVENTS
Capacity:128 events programmable through PLC
Time-tag:
Timing Accuracy:1 ms (using the IRIG-B synchronization input)
Triggers:By any digital signal programmable through PLC
AlarmPossibility to display the event as an alarm on the alarms panel.
Data Storage: In non volatile memory (flash) without battery
Control events are also displayed in the snapshot events recording
1 ms using an internal clock of 100 μs
Any element pickup, dropout
Digital input /output change of state
By virtual inputs and control events
In non volatile memory (flash) without battery
1 ms using an internal clock of 100 μs
Information available always through Communications for all models and also in
HMI for models with graphical display (M in ordering code).
Channels:9
Parameters:Ia (kA RMS), Ib (kA RMS), Ic (kA RMS), Ig (kA RMS), Isg (kA RMS), I2 (kA), P
(MW), Q (MVAr) and S (MVA)
Current and Power MethodThermal Exponential, Block Interval, Rolling Demand
Measurements:Each channel sho ws the present and maximum measu red value, with date and
time for the maximum recorded value.
Samples:5, 10, 15, 20, 30, 60 minutes.
Accuracy:
Trigger InputSelectable by setting (operation mode selection for the Block Interval calculation
Snapshot Events:Selectable by setting
2.4.3.6 DATA LOGGER
±1%
method)
2
Number of Channels:
ParametersAny available analog actual value
2 inputs default gates, from 3 to 8 inputs provided in library format.
be distributed as a single object.
Number:4 (A through D)
Reset points:40 (0 through 1 of pickup)
Operate points:80 (1 through 20 of pickup)
Time delay:0 to 65535 ms in steps of 1
Saturation Level20 times the pickup level
Number:15 configurable LEDs plus a ready non configurable LED
Programmability:from any logical variable, contact, or virtual input
Reset mode:Self-reset or Latched.
The first 5 LED’s are latched by hardware (red color ones), usually configured for
2
Reset Signal:The LED’s can be reset by hardware, pressing the front “esc” key during more
2.4.4.4 USER-DEFINABLE DISPLAYS
Number of configurable displays:1 (one line diagram fully configurable). In graphical displays only
Number of fixed displays:6, Metering (in primary values), Snapshot events (all and new), Alarms, Inputs
Number of selectable displays:Logotype, metering or both in scrolling mode, can be selectable as default
trip signals.
The following 10 ones (yellow and green) are self-reset but can be latched
through PLC configuration.
than 3 seconds or using the LED reset signal through PLC configuration.
and outputs screen with test functionality for inputs and outputs. In graphical
displays only
screen in text display for all models (basic and mimic). The metering screen
contains current and voltages for phases and ground in primary values.
2.4.4.5 USER-PROGRAMMABLE FRONT KEYS
Number of configurable Keys:5
Operation:drive PLC operands
2.4.5.1 CURRENT
Accuracy:
2.4.5.2 VOLTAGE
Accuracy:
2.4.5.3 REAL POWER (WATTS)
Accuracy:
±0.5% of the reading ± 10 mA from 0.05 to 10 A (for phases and ground)
±1.5% of the reading ± 1 mA from 0.005 to 5 A (for sensitive ground)
VT Ratio1.0 to 1500.0 in steps of 0.1
Rated Voltages500 Vac
Metering range:From 2 to 500 Vac
Relay Burden:0.05 VA at 120 Vac (50 or 60 Hz)
Voltage Withstand:Continuous at 500 V to neutral
2
VAC inputs do not need varistors, as the impulse test is applied to 100% of the transformers
2.4.6.3 CONTACT INPUTS
Input Activation Voltage Threshold:1 to 230 Vdc in steps of 1 V (selectable by setting)
Impedance:> 100 kOhm
Maximum error:
Load for voltage supervision inputs:2 mA + V/100 kOhm
Voltage threshold for voltage
supervision inputs
Debounce Time:1 to 50 in steps of 1 ms
Recognition time:< 1ms
Timing resolution:1 ms
1 min/hr at 800 to neutral
±10% setting ± 2.5 V
< 10 V (fixed)
For Input Activation Voltage Threshold and Debounce Time there is a single setting for all inputs in the same
group (inputs sharing the same common).
Input Type and Delay Input Time are not grouped; there is a different setting for each input.
Input TypePositive-Edge / Negative-Edge / Positive/ Negative
Delay Input Time0 to 60000 ms in steps of 1 ms (Input signal time delay)
2.4.6.4 REMOTE INPUTS
Number of input points:32, configured from 64 incoming bit points
Number of remote devices:
Default states on loss of comms:On, Off, Latest/on, Latest/off
2.4.6.5 ANALOG INPUTS
Current Input (mADC):0 to -1; 0 to +1; -1 to +1; 0 to 5; 0 to 10; 0 to 20; 4 to 20 (programmable)
Amplitude modulation:DC SHIFT = Demodulated input (no carrier)
Input Voltage:
Input Burden:1.5 mA
Input Impedance:3.3 kOhm
Minimum Input Voltage:2.4 V
Maximum Input Voltage:+/- 24 V
Formats:B000 (*) B001, B002 and B003 (*)
Isolation:2 kV
TTL
(*) Signal combinations recognized in accordance with IRIG Standard 200-95
2.4.7 REAL TIME CLOCK
2
Accuracy:
Backup energy:More than 1 week
Carry continuous:16 A
Make and Carry for 1 sec60 A
Break at L/R of 40 ms:0.3 A DC max. at 125 Vdc
Operate Time:< 8 ms
Contact material:Silver Alloy
Output Logic Type, Output Type and Pulse Ou tput Time are selectable by setting for each output
Output Logic TypePositive / Negative
Output TypeNormal / Pulse / Latch (Selectable by setting for each output)
Pulse Output Time0 to 60000 ms in steps of 1 ms (applicable only to signals set as pulse type)
Separate operate and reset signal can be configured by any digital signal programmable through PLC
Typical ±20 ppm
2.4.8 OUTPUTS
0.25 A DC max. at 250 Vdc
Contact Outputs (F31-F33, F34F36) for board type 2 (supervision)
in slot F:
The current seal-in circuit is used for verifying the current condition in a circuit
during the time that the tripping contact remains closed. If the current in the
tripping circuit is maintained over 100 mA, the function is sealed independently of
the status of the function that caused the trip.
Page 52
2.4 TECHNICAL SPECIFICATIONS2 PRODUCT DESCRIPTION
2.4.9 CONTROL POWER SUPPLY
LOW RANGE (LO)
Nominal DC Voltage:24 to 48 V
Min/Max DC Voltage19.2 / 57.6 V
Note:Low range is DC only
2
HIGH RANGE (HI)
Nominal DC Voltage:110 to 250 V
Min/Max DC Voltage88 / 300 V
Nominal AC Voltage:120 to 230 V
Min/Max AC Voltage102 / 250 V
ALL RANGES
Voltage Loss hold-up time200 ms typical, worst case 100 ms without unit reset
Power consumptionTypical =25 VA, Maximum =45 VA
Display backlight auto power-off mode after 15 minutes without touching any key, in order to ensure long life and minimum
Model ARedundant RS485
Model XRedundant RS485 + fiber CAN port (CANopen)
Model PRedundant 1mm-plastic F.O.
Model YRedundant 1mm-plastic F.O. + fiber CAN port (CANopen)
Model GRedundant multimode glass F.O.
Model ZRedundant multimode glass F.O. + fiber CAN port (CANopen)
Model CCable CAN port (CANopen)
Model MCa ble CAN port (CANopen) + RS485 (ModBus RTU)
Optic Features for ST connectors
Typical distance:1 200 m
Isolation:dc kV1
CAN PORT:
Rear port:
ModBus® RTU / DNP 3.0
Fiber CAN port in models X, Y, Z and cable CAN port in models C and M for
rear board 1
Physical Layer:ISO11898, High speed
Baud rate:125 / 500 kbaud
Fiber Type:Multimode glass F.O. port with ST connectors
Fiber Wave length:1300 nm
Fiber type:
Maximum recommended length1km (fiber); 500m (cable)
Isolation:2 kV
ETHERNET PORT:
Rear port:COM3
Type (depending on model):
Model B:10/100BaseTX self-negotiable
Model C:10/100BaseTX + 100Base FX
Model D:10/100BaseTX + redundant 100BaseFX (Physical media redundancy)
Model E:Redundant 10/100BaseT X self-ne gotiable ports
10/100BaseTXRJ45 connector
100BaseFXST connectors
Wave length:1300 nm
Fiber type:
Protocols available:ModBus® TCP/IP
Typical distance:1.65 km
Response time to ModBus commands: 10 ms Typical
Isolation:2 kV
In Models C and D, the 10/100BaseTX port is selected by an internal switch (see 3.3.3)
Two witness LED’s for transmission and reception are included
multimode 62.5/125 μm or 50/125 μm
multimode 62.5/125 μm or 50/125 μm
DNP over TCP/IP and UDP/IP
IEC 61850
Http, ftp, tftp (allow the use of a standard Internet browser)
Wave length: 1300nm
Connector types: ST package style
Fiber type: multimode 62.5/125 μm or 50/125 μm
2
TRANSMITTER CHARACTERISTICS
ParameterMin.Typ.Max.UnitReference
Output Optical Power BOL
62.5/125 μm, NA = 0.275 Fiber EOL
Output Optical Power BOL
50/125 μm, NA = 0.275 Fiber EOL
Output Optical Power at
Logic “0” State
RECEIVER CHARACTERISTICS
ParameterMin.Typ.Max.UnitReference
Input Optical Power
Minimum at Window Edge
Input Optical Power
Minimum at Eye Center
Input Optical Power Maximum-14dBm avg.Note 3
-19
-20
-22.5
-23.5
-33.9-31dBm avg.Note 3
-35.2-31.8dBm avg.Note 4
-14dBm avg.Note 1
-14dBm avg.Note 1
-45dBm avg.Note 2
Notes:
1.These optical power values are measured with the following conditions:
The Beginning of Live (BOL) to the End of Life (EOL) optical power degradation is typically 1.5 dB per industry
convention for long wavelength LEDs. The actual degration observed in Agilent’s 1300nm LED products is <1 dB, as
specified in this data sheet.
Over the specified operating voltage and temperature ranges.
With HALT Line State, (12.5 MHz square-wave), input signal.
At the end of one meter of noted optical fiber with cladding modes removed.
The average power value can be converted to a peak power value by adding 3 dB. Higher output optical power
transmitters are available on special request.
2.The transmitter provides compliance with the need for Transmit_Disable commands from the FDDI SMT layer by
providing an Output Optical Power level of <-45 dBm average in response to a logic “0” input. This specification applies
to either 62.5/125 μm or 50/125 μm fiber cables.
3.This specification is intended to indicate the performance of the receiver section of the transceiver when Input Optical
Power signal characteristics are present per the following definitions. The Input Optical Power dynamic range from the
minimum level (with a window time-width) to the maximum level is the range over which the receiver is guaranteed to
provide output data with a Bit Error Ratio (BER) better than or equal to 2.5e-10.
At the Beginning of Life (BOL).
Over the specified operating temperature and voltage ranges.
4.All conditions for Note 3 apply except that the measurement is made at the center of the symbol with no window timewidth.
IEC 61000-4-2 IEC 60255-22-2IVElectrostatic discharge immunity test
IEC 61000-4-3 IEC 60255-22-3IIIRadiated electromagnetic field disturbance test
IEC 61000-4-4 IEC 60255-22-4IVElectrical fast transient
IEC 61000-4-5 IEC 60255-22-5IVSurge immunity test
IEC 61000-4-6 IEC 60255-22-6IIIConducted electromagnetic field disturbance test
IEC 61000-4-8 EN 61000-4-8IVPower frequency magnetic field immunity
ENV50204IIIRadiated electromagnetic field disturbance test –
EMC EmisivityIEC 60255-25 EN 61000-6-4AConducted and radiated emissions
ProductIEC 60255-52 kVInsulation resistance – dielectric test
IEC 60255-56kV .5JImpulse test
IEC 60255-11100 msPower supply Voltage dips/interruptions/variations:
MechanicalIEC 60255-21-1IVibration test (sinusoidal)
IEC 60255-21-2
IEC 60255-21-3
I
II
1890 MHz.
Shock and bump
Seismic
2
Type test report available upon request.
W650 has been designed to comply with the highest existing requirements. More specifically, UNIPEDE recommendations
for high voltage substations are followed, even if for most applications such high classes are not required.
The relay complies with ANSI C37.90 standards, and has been designed to comply with international standards.
2.4.15 APPROVALS
ISO9001 Registered system.
CE marking: Meets the CE standards relevant for protections.
•Power supply, which can be simple or redundant, depending on the selected model
•Front module with alphanumerical (4 x 20) or optional graphical (16 x 40 characters)display. It includes the bus
on its rear, which communicates with the rest of modules via a high speed CAN bus.
•Transformers module with 5 current transformers and 4 voltage transformers
•CPU including a powerful DSP for measure processing as well as synchronous and as ynchronous communication
accessories.
W650 can incorporate a simple or redundant power supply.
The power supply module is fixed to the base plate using 4 screws, and the main and backup modules are identical.
These modules work in parallel continuously, distributing the 50% of the load for each of them, thus ensuring greater
reliability, and an instantaneous load transfer from the failed power supply to the other one, without loss of time or module
reset.
A relay connected to the low voltage side of the power supply monitors this voltage. The three contact terminals, normally
open, common, and normally closed, are available at the external connector te rminals. This rel ay monitors only the power
supply integrity and it is not controlled by the main microprocessor. This way, if we want a relay to monitor whether the unit
is ready to protect (READY), we should program one of the auxiliary relays in the unit.
This is a “fly-back” type power supply, providing high efficiency, stability and reliability thanks to the maturity of this
technology. There are two available ranges, Hi and Low, in order to optimize efficiency and general performance, including
3
the capability to tolerate auxiliary voltage interruptions (dips).
Oversized components highly resistant to temperature are used. For example, all capacitors are specified to stand up to
105ºC, transformer components are specially designed to stand up to 180ºC, the used MOSFET transistor is of very low
resistance, supports high voltage and is refrigerated by an oversized heat sink. This allows to support temperatures over
the 60ºC shown in the Technical Characteristics section, and prolonged overloads such as the ones occurring at batteries
in deep charge mode (much higher than +15% voltage shown in the Technical Characteristics section).
High capacitance capacitors are also used, providing high tolerance to prolonged dips, 100ms, even in the most
unfavorable consumption conditions. This allows the relay to continue with normal operation without undesired resets,
which would cause a long time of protection unavailability
Figure 3–2: shows the location of communications modules over the CPU. These modules have been designed in
accordance with the “plug and play” philosophy, so that units can be easily updated after their purchase, allowing for a
simple and economical migration of the application.
The model number and electrical characteristics of the unit are indica ted on the label loca ted on the right side of the re lay
case.
The metallic case of the unit is highly resistant to corrosion. It is made of stainless steel (AISI 304), coated with an epoxy
layer, and the rest of the metallic pieces are covered with a high quality resistive coating that has successfully passed at
least 96 hours in the salt spray chamber (S/N ASTM B-117).
The front of the relay is made of a conductor thermoplastic, flame retardant (V0), highly resistive material, which
guarantees the unit’s immunity to all kinds of EMI/RFI/ESD interferences. As well, an IP51 (IEC 529) protection degree
against dust and water through the front and with the relay mounted in the panel.
In order to guarantee safety and preventing access to the unit by unauthorized personne l, the front part of the relay has a
sealable cover to protect the RS 232 front port and the operation mode key.
3.3.1 MOUNTING
The unit is designed for semi-flush mounting. The relay is secured to the panel with the 4 M6 screws provided with the unit.
The user has access to the front keypad, display and communication port. The wiring is at the rear of the un it. The dr illing
dimensions are shown on Figure 3–4:.
3
Figure 3–3: PANEL MOUNTING
The relay width allows the mounting of two units on a standard 19’’ panel, 6 units high.
Figure 3–5: DIMENSIONS OF THE 19” RACKS 6U HIGH FOR TWO RELAYS
3.3.2 REAR DESCRIPTION
WARNING
Module withdrawal and insertion may only be performed when control power has been removed from the unit.
Proper electrostatic discharge protection (i.e. a static wrap) must be used when coming in contact with
products while the relay is energized.
The relay is wired through the terminal blocks located at the rear of the unit. The magnetic module, which receives the CT
secondary currents and the metering voltages, incorporates a very robust terminal board (columns A and B). Current inputs
provide automatic shorting of external CT circuits. The maximum recommended cable section for this terminal board, with
the appropriate terminal, is 6 mm
The rest of the terminal blocks, F and G for I/O and H for power supply, incorporate high quality connectors with the
capacity to withstand a rated current of 15 A at 300 V. These terminal blocks admit a cable section of up to 2.54 mm
12).
The communication boards have a different type of connector depending on the selected media: RS485, glass or plastic
fiber optic.
Glass fiber optic (100BaseFX)ST
Ethernet 100 FX (100BaseFX)ST
CAN FiberST
Figure 3–7: COMMUNICATIONS MEDIA SELECTOR GUIDE
Communication boards are installed at the rear part of the unit, the upper port being reserved for the asynchronous
communications board and CAN, and the lower port for the ETHERNET board in any of its configurations.
3
Figure 3–8: DETAIL OF INSERTION/EXTRACTION OF COMMUNICATION MODULES
The transformers module with the VTs and CTs is already con nected to a female connector screwed to the case
that incorporates shorting bars in the current inputs, so that it can be extracted without the need to short-circuit
the currents externally . It is very import ant, for safety reasons not to change or swi f t the terminals for CTs and VTs.
A grounded antistatic wristband must be used when manipulating the module in order to avoid electrostatic discharges that
may cause damage to the electronic components.
W650 units can hold different options for F module:
Option 1:Board with 16 digital inputs and 8 outputs.
Option 2: Board with 8 digital inputs, 4 circuit supervision inputs, 6 conventional outputs, and two current sensing
outputs
Option 4:Board with 32 digital inputs.
Option 5: Board with 16 digital inputs and 8 analog inputs.
For slot G there are four different options:
Option 0: No board
Option 1:Board with 16 digital inputs and 8 outputs.
Option 4:Board with 32 digital inputs.
Option 5: Board with 16 digital inputs and 8 analog inputs.
The number selected for slot G must be equal or higher than the number selected for option F for models includ ing bo ards
4 and 5.
3.4.2 DIGITAL INPUTS WITH TRIP CIRCUIT SUPERVISION
The Option 2 I/O board includes two groups of 4 inputs with one common, in terminals F9 to F10. It also includes 6 auxiliary
outputs, in terminals F19 to F30 with normally open contacts and two current sensing (latching) outputs (F31-F33 and F34F36).
Besides, there are 2 groups of inputs for trip circuit supervision. The first group includes two isolated digital inputs, terminals
F1-F2 and F3-F4. The second group, symmetrical an d identical to the first, is formed by isolated voltage inputs F15-F16
and F17-F18.
Using voltage detectors and current sensing, it is possible to implement several trip or close circuit supervision schemes, as
well as protection of the unit outpu t co ntact.
In order to implement these schemes, it is not necessary to perform any setting in the unit. Internal functions are
always operative. The detailed description of trip circuit supervision is included in chapter 5 in this manual.
3
3.4.3 CABLE/FIBER ETHERNET BOARD
The Ethernet board is the communication board 2 (COM3) sh own in Fig ure 3 –2:. It is located in the bottom at the rear part
of the relay.
In Models C and D, the 10/100BaseTX port is selected by an internal switch. To select between fiber and cable it is
necessary to extract the board, switch the jumper to the selected position, as indicated on Figure 3–10: F IBER/CABLE
SELECTION and insert the board again. As with any other relay manipulation, the relay power supply must be removed
and the operation must be performed only by skilled personnel.
The default port selected by switch is 10/100 TX in factory configuration. The switch selects between cable (10/100 TX)
and the first fiber port (100 FX). In Ethernet board type D (double fiber port) the backup channel is always fiber.
3 HARDWARE3.5 TRANSCEIVER OPTICAL POWER BUDGET VERSUS LINK LENGTH
3.5TRANSCEIVER OPTICAL POWER BUDGET VERSUS LINK LENGTH
Optical Power Budget (OPB) is the available optical power for a fiber op tic link to accommodate fiber cable losses plus
losses due to in-line connectors, splices, optical switches, and to provide margin for link aging and unplanned losses due to
cable plant reconfiguration and repair.
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
4 HUMAN INTERFACES. 4.1ENERVISTA 650 SETUP SOFTWARE INTERFACE4.1.1 INTRODUCTION
The EnerVista 650 Setup software provides a graphical user interface (GUI) as one of two human interfaces to a UR
device. The alternate human interface is implemented via the device’s faceplate keypad and display (see Human Machine
Interface section in this chapter).
The EnerVista 650 Setup software provides a single facility to configure, monitor, maintain, and trouble-shoot the operation
of relay functions, connected over local or wide area commu nication networks. It can be used while disconnected (i.e.
offline) or connected (i.e. on-line) to a 650 device. In off-line mode, settings files can be created for eventual downloading to
the device. In on-line mode, you can communicate with the device in real-time.
The EnerVista 650 Setup software, provided with every W650 relay, can be run from any computer supporting Microsoft
Windows
interface features. The EnerVista 650 Setup Help File provides details for getting started and using the EnerVista 650
Setup software interface.
This software package uses ModBus protocol, and it is designed to communicate with a single relay at a time. GE offers
different communication software packages, such as GE-POWER, which can be used to communicate simultaneously with
several relays.
EnerVista 650 Setup software provides an easy way to configure, monitor and manage all W650 features.
4.1.2.1 ENGAGING A DEVICE
The EnerVista 650 Setup software may be used in on-line mode (relay connected) to directly communicate with a 650
device.
® 95, 98, NT, 2000, ME, a nd XP. This chapter provides a summary of the basic EnerVista 650 Setup software
4.1.2 ENERVISTA 650 SETUP SOFTWARE OVERVIEW
4
4.1.2.2 USING SETTINGS FILES
The EnerVista 650 Setup software interface supports three ways of handling changes to relay settings:
1.In off-line mode (relay disconnected) to create or edit relay settings files for later download to communicating relays.
2.While connected to a communicating relay to directly modify any rel ay settings via relay data view windows, and th en
save the settings to the relay.
3.You can create/edit settings files and then write them to the relay while the interface is connected to the relay.
Settings files are organized on the basis of file names assigned by the user. A settings file contains data pertaining to the
following types of relay settings:
• Product Setup
• System Setup
• P rotection Elements
• Control Elements
• Inputs/Outputs
• Relay Configuration
• Logic Configuration
4.1.2.3 VIEWING ACTUAL VALUES
You can view real-time relay data such as input/output status and measured parameters.
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
4.1.2.4 VIEWING TRIGGERED EVENTS
While the interface is in either on-line or off-line mode, you can view and analyze data generated by triggered specified
parameters, via one of the following:
•Event Recorder facility: The event recorder captures contextual data associated with the last 479 events, listed in
chronological order from most recent to oldest.
•Oscillography facility: The oscillography waveform traces and digital states are used to provide a visual display of
power system and relay operation data captured during specific triggered events.
4.1.2.5 FIRMWARE UPGRADES
The firmware of a W650 device can be upgraded, locally or remotely, via the EnerVista 650 Setup software. The
corresponding instructions are provided by the EnerVista 650 Setup Help file under the topic “Upgrading Firmware”.
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (i.e. default
values, minimum/maximum values, data type, and item size) may change slightly from version to version of firmware.
The addresses are rearranged when new features are added or existing features are enhanced or modified.
4
4.1.2.6 ONE LINE DIAGRAMS
You can configure an one line diagram (bay mimic) to be used in relays with graphical display.
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
4.1.4 COMMUNICATION MENU
To start communicating with the relay go to “Communication>Computer>Computer settings” section in the main
EnerVista 650 Setup menu.
Safety instructions must be followed before connecting the computer to the relay. Safety instructions are detailed in section
1.1.3. Connect the relay ground terminal and the communicating computer to a good grounding. Otherwise, communication
may not be viable, or even, in worst cases, the relay and/or the computer could result damaged by overvoltages.
For on-line working, previously ensure that all relay communication parameters, such as baudrate, slave ModBus address,
etc, match the computer settings.
4
Figure 4–2: COMMUNICATION PARAMETERS MENU
The “Communication > computer” screen is divided in several subsections:
•Computer settings: Main communication parameters for serial communication and control type selection.
•ModBus/TCP Setup (if ModBus /TCP is selected as control type): Communication parameters for ModBus TCP
communication.
•Communication control: Device communication status (communicating or not communicating).
•Communication optimization: allows optimizing the communication time outs and failure establishing.
4.1.4.1 COMPUTER SETTINGS:
Shows the communication parameters necessary in order to establish communication with the unit. Such as slave address,
communication port, baud rate, parity, control type and startup mode.
Baud rate, parity, data bits, stop bits and ModBus slave address for com2 (RS232 front port and second serial p ort in the
rear communication board) are displayed in the default text logotype main screen.
ModBus Slave Address: ModBus addresses used for serial and Ethernet communication.
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
Communication ports: port used in the computer for serial communication.
Baud Rate: Baud rate for serial communication (from 1200 up to 115200 bauds in EnerVista 650 Setup, from 300 to
115200 in relay).
Parity: parity for serial communication. None, odd or even can be selected.
Control Type: The available control modes are:
•No Control Type, this option selects the serial communication mode, for use with serial communication ports (front
port, RS485, or plastic or glass fiber optic).
•MODBUS/TCP, this option selects ModBus TCP/IP communication mode, for communica tion through the Ethernet
port. In this case, the top right window will show the typical parameters to be programmed; IP address, port address
and unit identifier in the MODBUS TCP SETUP section.
•MODEM, this option displays the parameter to set in case of using a modem for the communication, such as Phone
number, Time out (sec), init. command, type of dialing (tones or pulses).
4.1.4.2 COMMUNICATION CONTROL:
Located at the bottom of the screen, it shows the status of the communication with the relay . W ith rel ay no t co mmunica tin g,
a message “650 Setup is not talking to a W650” will be shown and ON button wi ll be enable. Pressing this button, 650
Setup start communicating with the relay.
With relay communicating a message “650 Setup is now talking to a W650” will be shown and OFF will be enable. Pressing
this button, communications between relay and PC will be closed.
4
4.1.4.3 COMMUNICATION OPTIMIZATION:
The parameters shown on the bottom right window (Communica tion optimization) can improve co mmunication , although it
is recommended to leave the default values indicated by the EnerVista 650 Setup. These parameters are the maximum
time to wait for a response in the relay (in ms) and the maximum attempts to perform before assuming communications
failure.
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
T able 4–1: TYPES OF FILES GENERATED BY ENERVISTA 650 SETUP SOFTWARE OPERATION MODE OFF-LINE:
SETTINGS & CONFIGURATION FILE *.650
DescriptionProtection Settings and Configuration Section
Created byEnerVista 650 Setup
Relay configuration file containing all protection
elements Settings, input/output and LEDs configuration,
graphic display configuration, etc.
Equations corresponding to the logic created and
compiled in the PLC Editor
EnerVista 650 Setup:
“File>Save *”
EnerVista 650 Setup:
“File>Open *”
Connect with the relay
(“Communications>Computer”)
Open the created file (“File>Open *”)
Send to relay from the menu: “File>Send info to relay”
Note that texts used in the configuration of inputs,
outputs, etc. are not sent to the relay. The only texts
sent to relay are operations, events, and LEDs.
PLC project file
containing the
necessary
information
relative to the
relay model,
logic libraries
included in the
project (*.lib),
graphic file
name (*.aut),
etc.
PLC Editor:
“File>Save
Project”
PLC Editor:
“File>Open
Project”
Connect with the relay (“Communications>Computer”)
LaunchLogic equations Editor (“Setpoint>Logic Configuration”)
Open the created PLC project (“File>Open Project”)
Compile the project (“Run>Compile”)
Now the logic (virtual outputs) can be sent directly to relay
(“Run>Send Equations to Relay ”). Texts of virtual outputs are
not stored in the relay, only in the logic configuration files to be
edited.
container. Logic
equations (Virtual
Outputs) in FDB
format.
Logic configuration
graphic editor (PLC
Editor)
PLC Project file
containing all the
drawings used by the
logic, required by 650
relay based on IEC
61131-3 standard.
Functional block
diagram (FDB).
PLC Editor:
“File>Save Project”
PLC Editor:
“File>Open Project”
User programmable
logic objects
Logic configuration
graphic editor (PLC
Editor)
Library file to be
included as an object
in a PLC project.
Logic packages that
can be stored into
libraries and be
distributed in different
PLC projects.
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
In case of using element libraries (either existing (“File Library>Open Library”) or created by the user (“File Library>New
Library”)), the program will create and manage the corresponding files (*.lib) in a folder named FDB (Functional Block
Diagram). These files are used for the PLC project compilation. It is necessary to store them with the other logic
configuration files that built the PLC project (*.pep, *.aut, *.lib).
Besides sending basic information to the relay (Settings + configuration) in *.650 format, it is recommended to store *.650,
*.pep, *.aut and *.lib files inside the relay (“Communication>Upload info files to relay”), to ensure that logic configuration
files will be available in the future for further logic modification s; either if these files are not used by the relay, they are
required for connecting to a relay and analyzing its configuration. The program manages the logic configuration files
globally, so that when the user selects to save file *.pep in the relay, the associated *.aut and *.lib files are also stored.
File storage inside the relay
(RECOMMENDED)
Retrieval of files stored in the relay
(RECOMMENDED)
“Communication > Upload info files to relay” through Ethernet
“Communication > Download info files from relay” through Ethernet
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
Table 4–2: TYPES OF FILES CREATED BY ENERVISTA 650 SETUP– ONLINE OPERATION MODE
SETTINGS & CONFIGURATION FILE *.650
DescriptionProtection Settings and Configuration Section
Created byEnerVista 650 Setup
Relay configuration file containing all protection
ontents
How to
transfer to
relay
elements, settings, input/output and LEDs configuration,
graphic display configuration, etc.
Equations corresponding to the logic created and
compiled in the PLC Editor
Connect with the relay (“Communications>Computer”) Connect with the relay (“Communications>Computer”)
PLC project file
containing the
necessary
information relative
to the relay model,
logic libraries
included in the
project (*.lib),
graphic file name
(*.aut), etc.
Open the created PLC project (“File>Open Project”)
Compile the project (“Run>Compile”)
Now the logic (virtual outputs) can be sent directly to relay
(“Run>Send Equations to Relay”). Texts of virtual outputs are
not stored in the relay, only in the logic configuration files to be
edited.
container. Logic
equations (Virtual
Outputs) in FDB
format.
Logic configuration
graphic editor (PLC
Editor)
PLC Project file
containing all the
drawings used by
the logic, required
by 650 relay based
on IEC 61131-3
standard.
Functional block
diagram (FDB).
User programmable
logic objects
Logic configuration
graphic editor (PLC
Editor)
Library file to be
included as an object
in a PLC project.
Logic packages that
can be stored into
libraries and be
distributed in different
PLC projects.
4
Modify settings and configuration directly in the relay:
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
4.1.6 ENERVISTA 650 SETUP MENUS STRUCTURE
The EnerVista 650 Setup menus structure is shown in Table 4–3: .
Unless specified, options are available in both On-line and Off-line mode.
Options enabled only in On-line mode are marked as (*)
Options enabled only in Off-line mode are marked as (**)
The “View > Language ” submenu allows the user to change the default language for the EnerVista 650 Setup program and
it is only enabled when the relay is not communicating and no file has been opened.
Table 4–3: ENERVISTA 650 SETUP MENUS STRUCTURE
OPERATIONS
(*)
NA
NA
NA
NA
COMMUNICATION SECURITYVIEWHELP
ModBus
Memory
Map
Languages
(**)
Upgrade firmware
version (*)
Upgrade operating
system (*)
Upgrade 650 Web
Server
Upload info files to
relay
Download info files
from relay
Change
Password
User
Management
4
FILESETPOINTACTUAL
Open (**)Product SetupFront PanelNAComputerLogin userTraces
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
4.1.7 FILE MENU OVERVIEW
Table 4–4: GENERAL OVERVIEW OF FILE MENU:
FILE
Open (**)Open a settings and configuration file for off-line working.
Save As (**)Save *.650 settings and configuration file.
Close (**)Close the opened *.650 file in EnerVista 650 Setup.
Config File (*.650)
Converter
Properties (**)File properties for *.650.
Get info from relay (*)
Send info to relay (*)Send and write the *.650 settings and configuration to the relay.
Print Setup (**)To configure printer settings.
Print Preview (**)Preview of settings and configuration file printing format.
Print (**)Launch the *.650 file to be printed.
Print to file (*.xls) (**)*.650 printed to file in excel format.
ExitQuit the application closing all the open windows.
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (**)
Tool to convert the *.650 files from one version to another
Retrieve the *.650 settings and relay configuration compiled equations
from the relay.
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
4.1.7.1 OPEN, SAVE AS AND CLOSE
In these options, the program opens a dialog box (with default path to Files> Config program fold er) where the setting and
configuration files can be selected for their “off-line” edition. For enabling access to this menu, there must be no
communication between the PC program and the relay.
4
Figure 4–5: OPEN FILE MENU
Once the *.650 file with the appropriated relay model (FXGX) is selected, the program will enable the off-line options to fully
program the unit. The enabled menus in the EnerVista 650 Setup program are: File, Setpoint, Actual, Communication, View
and Help.
The off-line mode displays the File, Setpoint, Actual, Communica tion, Security, View and Help submenus to program the
unit.
The Actual values submenus are for structure purposes only Values are not refreshed while the relay is not communicating.
The “Save as” and ”Close” submenus are used to save the *.650 file into the computer and to close the current file. To work
in off line mode for settings and configuration edition it is not necessary to use th e ”Close” option, a new *.650 can be
opened without closing the previous one. The ”Close” option is used to clear all data in EnerVista 650 Setup program,
enabling “Language”, ”Upgrade firmware version” and “Upgrade Operating system” options.
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
4.1.7.2 CONFIG FILE (*650) CONVERTER
Figure 4–6: CONFIG FILE (*650)CONVERTER MENU
This tool provides automatic conversion of configuration files from a firmware version to a previous or later version.
Open the source *.650 file and select the version and model to be converted to.
It is possible to change the model type (FXGX) using the conversion tool. It must be taken into account that part of the logic
can be readjusted to fit the new input and output boards selection. Notice also that the external wiring of inputs and outputs
board are different for type 1, 2, 4 and 5.
4.1.7.3 PROPERTIES
When this option is selected, the program will show a screen including the relay model information, firmware version, etc. of
the file being edited, as shown on Figure 4–7:
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
4.1.7.4 PRINTING OPTIONS (PRINT SETUP/PRINT PREVIEW/PRINT/PRINT TO FILE)
The printing options are active only in off-line mode, in “File edition”, and not in on-line mode, connected with the relay.
a) PRINT SETUP
Option to configure the printing options and settings for the printing device.
b) PRINT PREVIEW
Option to preview the whole settings and configuration file (*.650) in paper format to be printed as shown in Figure 4–8:.
4
Figure 4–8: PRINT PREVIEW OF SETTINGS FILE
c) PRINT
In this option, the program will print the relay configuratio n using the PC default (active) printer on port COMx or LPT. This
option is active only in off-line mode, in file edition, an d not in on-line mode, connected with the relay.
d) PRINT TO FILE (*XLS)
Possibility to export the configuration file to an Excel file using the “Print to file (*.xls)” option.
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
4.1.8 SETPOINT MENU OVERVIEW
Table 4–5: GENERAL OVERVIEW OF SETPOINT MENU IN ENERVISTA 650 SETUP:
SETPOINT
Product Setup
System Setup
Protection Elements
Control Elements
Inputs/OutputsContact I/O settings for all boards available in device, Remote Comms.
Relay Configuration
Logic Configuration
Clock (*)
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (**)
Communications settings for all protocols and physical mediums.
ModBus user map definition, fault report, oscillography, data logger and
demand settings.
General Settings, Flex Curves Definition, Breaker settings and
maintenance, and switchgear snapshot events management.
Phase, Neutral, Ground, Sensitive Ground and Negative Sequence
Current Settings. Voltage Elements settings and Power Settings
management.
Setting groups, under and overfrequency settings, autoreclose, breaker
failure and VT fuse failure.
Configuration of Outputs, LEDs, Operations, Protection Elements,
Oscillography, Control Events, Switchgear, Inputs, Virtual Inputs,
Operations and HMI. Whole relay configuration with internal relay signals
or user-definable ones as logic (virtual outputs).
Logic configuration graphic editor (PLC Editor). It is a PLC Project file
editor that contains all the internal drawings used to make the logic
(virtual outputs) based on IEC 61131-3 standard. Functional block
diagram (FDB).
Relay synchronization to computer clock or to user-definable date and
time. On-line mode only.
4
4.1.8.1 PRODUCT SETUP
Table 4–6: GENERAL OVERVIEW OF PRODUCT SETUP MENU:
PRODUCT
SETUP
Communication
Settings
ModBus User Map
Fault ReportFault report settings. Possibility to show fault reports on HMI screen.
Oscillography
Data LoggerData logger configuration
Demand
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (**)
Serial Ports, Network (Ethernet), ModBus Protocol, DNP Slave, IEC 8705-104, CAN Open and SNTP settings.
ModBus user map definition. The ModBus user map is formed by 256
records, selectable from the complete relay ModBus map.
Oscillography settings (trigger position, samples per cycle, etc). The
trigger and digital channels (up to 16) must be configured in
“Setpoint>Relay configuration”.
Demand settings. The demand trigger and demand reset signals must be
configured in “Setpoint>Relay configuration”
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
e) COMMUNICATION SETTINGS
This section details the settings related to communication parameters for the different protocols available in the W650.
Table 4–7: GENERAL OVERVIEW OF COMMUNICATION SETTINGS MENU:
COMMUNICATION
SETTINGS
Serial PortsBaud rate and parity for COM1 and COM2 serial communication ports.
Ethernet communication parameters for COM3 (IP Address, Netmask,
Gateway IP)
NOTE: The ModBus Slave address used by Ethernet ports is the one set
for COM2.EnerVista 650 Setup software allows programming two
different Ethernet addresses, but the first IP has always to be set as the
second IP Address is an Alias.
ModBus Slave Addresses for serial and Ethernet communication and the
ModBus port number used for ModBus TCP/IP
Physical port, Slave Address for DNP, IP Addresses for Masters, TCP/
UDP Port, Unsolicited Response parameters, Analog scale factors and
deadbands, message fragment size, Binary input block.
TCP Port, Common Addr of ASDU, Cyclic Meter Period and,
Synchronization Event settings.
4
Network (Ethernet)
ModBus Protocol
DNP3 Slave
IEC 870-5-104,
SNTP (*)Sinchronization over Ethernet settings
CAN OpenNode ID and Baud for CANopen protocol
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode ar e marked as (** )
4.1.8.2 SYSTEM SETUP
This section shows the settings related to the system setup definition such as shown in the following table.
Table 4–8: GENERAL OVERVIEW OF SYSTEM SETUP MENU:
SYSTEM
SETUP
This screen describes and enables the settings of the power system
where the relay will operate. Some of these settings will be used only for
General Settings
Flex Curves
Breaker settings
Breaker maintenance
SwitchgearConfiguration of snapshot events for each switchgear (enable or disable)
metering values presentation purposes; however, some of them apply
directly to the sampling and analog-digital conversion process (rated
frequency setting). Therefore, these settings need to be adjusted so that
they fit the system settings.
Flex Curves – Programmable user curves: The relay incorporates 4 user
curves called Flex Curve A, B, C and D. The points for these curves are
defined by the user in “Setpoint>System Setup>Flex Curves>Edit Curve” menu in EnerVista 650 Setup. User defined flex curves can be
selected as an operation curve in all the time overcurrent functions in the
relay.
Breaker settings, maintenance and switchgear selection of the device
configured as breaker in the W650. The selected switchgear will be used
in recloser, breaker failure and synchronism functions. The settings are
Number of Switchgear, Maximum KI
Openings, Max.Openings 1 hour and Snapshot Events.
These settings correspond to the initialization of (KI)
counting of number of openings and closings of the switchgear
configured as breaker. These Counters allow the breaker Maintenance.
They are used to cumulate the breaker ageing produced by a trip or a
breaker opening. In order to incorporate the breaker historic, in case of
existing breakers, the system allows assigning an initial value to
accumulated amperes, and to the number of opening and closing
operations.
2
t, KI2t Integ. Time, Maximum
2
t counters, and the
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (**)
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
4.1.8.3 PROTECTION ELEMENTS
This option shows all the protection-grouped elements available in the rel ay as shown in Table 4–9:. Each of these groups
includes the specific protection units of the same type. For example phase currents group includes TOC, IOC, directional
units, etc. There are three groups available, so there are three protection units of each function that can work in grouped
mode or ungrouped (altogether).
Table 4–9: GENERAL OVERVIEW OF PROTECTION ELEMENTS MENU:
PROTECTION
ELEMENTS
Phase CurrentAll overcurrent grouped functions for phase current.
Neutral Current
Ground Current
Sensitive Ground
Current
Negative Sequence
Current
Voltage Elements
PowerDirectional power grouped protection functions.
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (**)
All overcurrent grouped functions for neutral current. (Calculated from
phases, not measured)
All overcurrent grouped functions for ground current. (Measured from 4
current input)
All overcurrent grouped functions for sensitive ground current.
(Measured from 5
Negative sequence time overcurrent function
All under and overvoltage grouped functions for phases, neutral,
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
Table 4–10: PROTECTION ELEMENTS INCLUDED
PHASE
CURRENT
Phase TOC HighPhase time overcurrent, high level (51PH)
Phase TOC LowPhase time overcurrent, low level (51PL)
Phase IOC HighPhase instantaneous overcurrent, high level (50PH)
Phase IOC LowPhase instantaneous overcurrent, low level (50PL)
Phase DirectionalPhase directional unit (67P). Quadrature Voltage for polarization
NEUTRAL
CURRENT
Neutral TOCNeutral time overcurrent (51N)
Neutral IOCNeutral instantaneous overcurrent (50N)
Neutral DirectionalNeutral directional unit (67N). Voltage, current and dual polarization.
GROUND
CURRENT
Ground TOCGround time overcurrent (51G)
4
SENSITIVE
GROUND
CURRENT
NEGATIVE
SEQUENCE
CURRENT
VOLTAGE
ELEMENTS
POWER
Ground IOCGround instantaneous overcurrent (50G)
Ground DirectionalGround directional unit (67G). Voltage, current and dual polarization.
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
4.1.8.4 CONTROL ELEMENTS
This option shows all the control elements available in the relay as shown in Table 4–11:. Some of the elements are
grouped ones such as underfrequency, overfrequency and broken conductor.
Table 4–11: GENERAL OVERVIEW OF CONTROL ELEMENTS MENU:
CONTROL
ELEMENTS
W650 units incorporate a flexible grouping capability for protection units.
This means that protection units can be used in either single setting
group (default mode-all units can operate simultaneously) or four setting
groups (in this mode, protection units are grouped in four independent
Setting Group
UnderfrequencyUnderfrequency unit (81U). Grouped element
OverfrequencyOverfrequency unit (81O). Grouped element
AutorecloseRecloser (79). Not grouped, a single unit provided
Breaker FailureBreaker failure (50BF). Not grouped, a single unit provided
VT Fuse FailureFuse Failure (VTFF). Not grouped, a single unit provided
tables, with only one of them active at a given time).
Protection element grouping involves only Protection elements together
with broken conductor detection and over and under frequency, which
are usually considered as control elements. The rest of control elements
such as recloser, fuse failure, breaker failure, synchronism, and breaker
settings are not involved in the tabled groups concept.
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
4.1.8.5 INPUT/OUTPUTS
Section that contains the settings for all input and output boards and the Force Outputs and Virtual inputs activation tools.
Table 4–12: GENERAL OVERVIEW OF “INPUTS/OUTPUTS” SETTINGS MENU.
INPUTS/
OUTPUTS
Contact I/O
Force Outputs (*)
Virtual Inputs (*)
Remote Comms.
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (** )
Inputs and outputs settings for all boards in W650. The I/O settings
configuration can only be performed through EnerVista 650 Setup, not
HMI available.
This menu allows activating each contact output in the relay, to facilitate
maintenance testing. On line mode only.
This menu allows operating virtual inputs. These variables are used as
inputs to logic schemes configured in the relay. Virtual inputs can be
operated in a latched mode (32 latched virtual inputs) or in Self-reset
mode (32 self reset virtual inputs).
This menu allows configuring remote inputs coming from other devices
through GSSE messages.
This section shows the settings related to inputs and outputs for the different boards available in W650 (F , G).
4
Table 4–13: GENERAL OVERVIEW OF “INPUTS/OUTPUTS>CONTACT I/O” SETTINGS MENU.
CONTACT I/O
Board FBoard locate d in first slot, always connected.
Board G
Board located in second slot, depends on model definition. If model is
type G0 there is no board in second slot.
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
4.1.8.6 RELAY CONFIGURATION
This is the relay configuration section in which the relay can be configured using internal states or already compiled
equation on PLC Editor.
Table 4–14: GENERAL OVERVIEW OF RELAY CONFIGURATION MENU:
RELAY CONFIG
OutputsConfiguration of contact output operate and reset signals for all boards.
LEDs
Operations
Protection Elements
Oscillography
Control Events
Switchgear
Remote outputs
Inputs
Virtual Inputs
MMI (HMI-Human
Machine Interface)
15 LEDs fully configurable from any logical variable, contact or virtual
input. First 5
can be latched through PLC configuration. From the LED configuration
screen, it is possible to print the vertical LED label for the relay
Configurable operations up to 24. Operation texts, interlocks, final states,
frontal keys, time outs and masters.
This tab allows assigning operands (logic signals) as inputs to different
protection elements. To block, reset, initiate the different protection
elements inputs.
Trigger and up to 16 digital channels to be included in oscillography
records, are programmable from any logical variable, contact or virtual
input. Text configuration is only for off-line mode.
NOTE: This screen is used for the configuration of digital channels and
oscillography trigger. The rest of parameters, such as function enabling/
disabling, sampling rate, number of oscillography files, etc. must be set
on the Setpoint>Product Setup>Oscillography menu.
Up to 128 user programmable events from any logical variable, contact
or virtual input. Possibility to display the event as an alarm on the alarms
panel. Control events are also displayed in the snapshot events
recording. 1 ms time tagging.
A control event is a logic signal associated to an operand or combination
of operands, that allows following the status of that signal.
Up to 16 configurable switchgear elements. A switchgear element can be
a breaker, a line selector switch, a grounding selector switch, a busbar
selector switch, etc. This screen allows configuration of type of contacts,
opening and closing time, contact assignation and text for events related
to switchgear. There are 64 pre-established events for switchgear, which
correspond to opening, closing, Error01 and Error11 of the 16
programmable switchgear elements.
Up to 32 DNA bits and 64 userSt bits to be transmitted to remote devices
over CAN using GSSE messages
Text configuration for off-line mode file management for all the contact
inputs available in device.
Text configuration for off-line mode file management. 32 latched and 32
self reset virtual inputs.
Screen for one line diagram configuration. This menu shows a scenario
to draw a simplified one-line diagram of a bay in a feeder, line,
transformer, etc. The menu includes a library for power elements,
metering elements, text and drawings. See an example in Figure 4–10:
LEDs are latched by hardware, the rest are self-reset but
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
4.1.8.7 LOGIC CONFIGURATION
This logic configuration allows creating more complex con figurations, using the graphical PLC, than using the tables from
Relay Configuration. For file management detailed information go to section 4.1.5.
File description:
*.pep:
*.aut:PLC Project file containing all the drawings used by the logic, required by 650 relay based on IEC 61131-3 standard. Functional
*.lib:User programmable logic objects: Library file to be included as an object in a PLC project. Logic packages that can be stored
Header for Logic project: PLC project file containing the necessary information relative to the relay model, logic libraries
included in the project (*.lib), graphic file name (*.aut), etc.
block diagram (FDB).
into libraries and be distributed in different PLC projects.
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
4.1.8.8 CLOCK
This menu allows to update the date and time of the relay, either synchronizing them with the PC clock, or entering the
information manually.
4
Figure 4–11: CLOCK
4.1.9 ACTUAL VALUES MENU OVERVIEW
The menu bar in the main screen of EnerVista 650 Setup software shows the ACTUAL menu option. This option
concentrates and displays all the status of protection, control elements, metering, counters information, oscillography,
events, fault locator, etc. This section shows only the structure of menus in EnerVista 650 Setup.
Table 4–15: GENERAL OVERVIEW OF ACTUAL VALUES MAIN MENU:
ACTUAL
Front PanelThe relay fron t LEDs status is shown on this menu.
Status
Metering
Inputs/Outputs
Records
Protection and control status signals for all available protection functions
in device.
All metering values available in device. Primary and secondary values,
frequency and phasor diagram provided.
All input and output status provided. For contact inputs and contact
outputs as well as virtual input and virtual output signals.
Only enabled in on line mode, retrieval of all the available records in
device. Snapshot events, control events, oscillography and fault reports.
4.1.9.1 FRONT PANEL
The front panel menu shows only the LEDs submenu where all the front LEDs can be monitored.
4.1.9.2 STATUS
The following menu includes all the available protection status in the device.
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
Table 4–16: GENERAL OVERVIEW OF STATUS MENU:
STATUS
Operation bits
Breaker
ProtectionStatus of all the protection units in the device.
Control ElementsStatus of all the control units available in the device.
Protection Summary
Snapshots events
summary
ModBus User Map
Switchgear Status
Calibration
Flex Curves
System Info
Records Status
SNTP-IRIG-BInformation related to synchronization via IRIG_B or SNTP
CAN OpenInformation related to OPENcan protocol
Up to 24 elements. OPERATION BIT XX is (0) when the configured time
out for the operation XX expires or when success conditions are met.
And it is (1) if operation XX is executed and interlocks are fulfilled.
Breaker status (open, closed or undefined). The rest of the status signals
corresponding to the switchgear XX configured as breaker are in the
“Status>Switchgear Status>Switchgear XX” menu.
This screen shows a complete list of all protection and control elements
in the relay, showing their status (enabled or not).
Summary of the snapshot events status (enabled or disabled) for
protection, control, inputs and outputs boards and switchgear.
Up to 256 elements. Value in SIGNED INT 16 BIT format of the reading
for the selected address configured in “Setpoint>Product Setup>ModBus User Map”
Up to 16 blocks of switchgear status signals for the 16 configurable
devices. Status signals such as inputs for A and B contacts, status for A
and B, open and close status, error 00 and error 11, open init and close
init, fail to open and fail to close signals.
Internal states for calibration. Factory calibration and calibration error
signals.
Flex curve status for A, B, C and D user curves. (0) if it is not configured,
(1) if it is configured. To configure a flex curve go to “Setpoint>System Setup>Flex Curves” menu.
This screen can monitor the system parameters and the internal status of
the Relay operative system. Not enabled by default, password required
Information related to the different records stored in the Relay, such as:
Fault reports, control events, oscillography , data logger , demand, energy,
and breaker maintenance.
4
Table 4–17: DIFFERENT CONTROL ACTUAL VALUES INCLUDED IN THE CONTROL ELEMENTS MENU
CONTROL
ELEMENTS
FrequencyStatus signals (pickups and operations) for under and overfrequency
AutorecloseS tatus signals for autoreclose function (79). Close signal, recloser status
Breaker FailureStatus signals for breaker failure function (50BF).
VT Fuse FailureFuse failure detection signal.
Setting GroupsStatus signals (activations and blocks) for the relay setting group change.
units.
(ready, lockout, etc), block signals after each shot.
By default the “setting group” setting is disabled and all the grouped
elements can be enabled at the same time.
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
T able 4–18: ACTUAL VALUES INCLUDED IN THE PROTECTION MENU
PROTECTION
4
Protection BlocksThis screen shows all the protection element blocks available. Protection
Phase CurrentProtection status signals (pickups and operations) for time overcurrent,
Neutral CurrentProtection status signals (pickups and operations) for time overcurrent,
Ground CurrentProtection status signals (pickups and operations) for time overcurrent,
Sensitive Ground
Current
Negative Sequence
Current
VoltageProtection status signals (pickups and operations) for all voltage
PowerProtection status signals (pickups and operations) for directional power
elements block signals can be configured at “Setpoint>Relay Configuration > Protection Elements”.
instantaneous overcurrent and directional protection functions for phase
current.
instantaneous overcurrent and directional protection functions for neutral
current (calculated from phases).
instantaneous overcurrent and directional protection functions for ground
current (measured from 4
Protection status signals (pickups and operations) for time overcurrent,
instantaneous overcurrent, isolated and directional protection functions
for ground current (measured from 5
Protection status signals (pickups and operations) for negative sequence
time overcurrent function.
functions, undervoltage, overvoltage, neutral overvoltage, and auxiliary
under and over voltage.
units.
th
current input).
th
current input).
T able 4–19: ACTUAL VALUES RELATED TO RECORDING FUNCTIONS IN THE RECORDS STATUS MENU:
RECORD
STATUS
Fault ReportsThis menu shows the fault repor t status signals, as fault report trigger,
Control EventsStatus of the control events (if the signal configured to launch the control
OscillographyStatus of signals related to oscillography recording, such as status or
Data LoggerData logger information about oldest and newest sample time stamp,
DemandDemand trigger and reset inputs status.
EnergyFreeze, unfreeze and reset input signals for energy counters.
Breaker MaintenanceAll signals related to breaker maintenance, such as number of openings,
fault date, fault type and location, besides the fault report number.
event is active or not).
digital channels, oscillography trigger, number of records available, etc.
and number of channels and days configured in data logger settings.
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
4.1.9.3 METERING
The Metering menu includes all the measurements available in the device. Primary and secon dary values, and also the
data related to the recording functions in the relay.
Table 4–20: GENERAL OVERVIEW OF METERING MENU:
METERING
Primary ValuesPrimary values measurements for currents, voltages, power, energy and
Secondary ValuesSecondary values measurements for currents, voltages and power.
Phasor DiagramCurrent, voltage and sequence components.
FrequencyLine and Bus frequencies.
demand
4.1.9.4 INPUTS/OUTPUTS
The Inputs/Outputs menu includes all the inputs and outputs signals available in the device. Contact and virtual type.
Table 4–21: GENERAL OVERVIEW OF INPUTS/OUTPUTS MENU:
INPUTS/
OUTPUTS
Contact InputsStatus of digital inputs in the Relay for each board according to the relay
Contact Output StatusStatus of digital outputs in the Relay for each board according to the relay
Contact Outputs
Operates
Contact Outputs
Resets
IO Board StatusStatus of I/O boards. This status provides if the hardware it is OK (boards
Virtual InputsStatus of Virtual inputs latched (32) and self-reset (32).
Virtual OutputsStatus of virtual outputs (configured in PLC Editor). Up to 512.
Remote OutputsStates of remote outputs
Remote InputsStatus of remote device and remote inputs
Analog Inputs (*)Measurements coming from analog inputs (DCMA)
model.
model.
Status (activated or not) of the variables used to operate a contact
output. To configure these signals go to “Setpoint>Relay
Configuration>Outputs” menu.
Status (activated or not) of the variables used to reset a contact output.
T o configure these signals go to “Setpoint>Relay Configuration>Outputs”
menu. This output reset Command will only be effective if the “latch”
option has been Selected for the “Output Type” setting on the I/O board,
thus when the contact output has been configured to emulate function 86
(latching relay).
matching relay model, correctly inserted in their tracks, in good state and
communicating through the internal CAN Bus).
4
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (** )
4.1.9.5 RECORDS
The Records menu is only available in on line mode and includes the possibili ty to retrieve all the records availabl e in the
device. By serial or Ethernet.
Table 4–22: GENERAL OVERVIEW OF RECORDS MENU:
RECORDS (*)
Event recorder (*)Retrieval and visualization of snapshot event (all and new), control
Waveform capture (*)Retrieval of oscillography files, by serial or Ethernet.
Fault Report (*)Retrieval and visualization of fault report files, by serial or Ethernet.
Data logger (*)Retrieval and visualization of data logger files. Only by Ethernet.
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (** )
events and alarm panel. By serial or Ethernet (ModBus RTU or TCP/IP)
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
4.1.10 OPERATIONS MENU OVERVIEW
Option only available in on line mode, showing all the operations previously configured in the relay with their corresponding
texts.
Table 4–23: GENERAL OVERVIEW OF OPERATIONS MENU:
OPERATIONS
Operation 1 (*)Entry to first operation (with its corresponding text)
......
Operation 24 (*)
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (** )
Entry to 24
th
operation (with its corresponding text)
4.1.11 COMMUNICATION MENU OVERVIEW
The communication menu includes the computer screen to start communicating with the relay, the different update
procedures available in device: firmware, operative system, web server and other file storing capabilities (upload and
4
download info files to/from relay).
For more detail information go to section 4.1.4 for co mmunication menus description and to section 5 for flash memory
update procedures.
Table 4–24: GENERAL OVERVIEW OF COMMUNICATION MENU:
COMMUNICATION
ComputerMenu to start communication with the relay.
Modem (**)Menu to set modem communication parameters (only available if control
Troubleshooting (*)Menu that Lets the user to perform reading or writing in ModBus
Calibration (*)Retrieval and store calibration settings from/to relay.
Upgrade firmware
version (**)
Upgrade operating
system (**)
Upgrade 650 web
server
Upload info files to
relay
Download info files
from relay
Options enabled only in On-line mode are marked as (*). Options enabled only in Off-line mode are marked as (** )
type is set to modem in computer menu).
addresses, for verifying communications and access to different
positions in the ModBus memory map.
Menu to update the relay firmware version through Ethernet
Menu to update the relay boot code (front RS323 and Ethernet
connection)
Menu to update the web server application (if available)
Hard disk storage of settings and configuration files on the relay.
Retrieval of settings and configuration files that had been previously
stored in the relay hard disk.
The rest of options available in the Communication menu in EnerVista 650 Setup are:
•Modem: Allows configuring the unit for remote communications via modem, using telephonic l ine. It i s o nly avail able if
the relay is not communicating and if modem has been select on Communication>compu te r control type selection. Go
to “Communication>Modem”
•Troubleshooting (Serial or Ethernet connection): Lets the user to perform reading or writing in ModBus a ddresses, for
verifying communications and access to different positions in the ModBus memory map. Only available if the
communication has already been established. Go to “Communication>Troubleshooting”. An example is provided in
Figure 4–12:
Figure 4–12: COMMUNICATION TROUBLESHOOTING SCREEN
•Calibration (Serial or Ethernet connection): Allows retrieving the unit calibration settings and storing them in a file (with
extension *.cal). For reading or storing the calibration settings in the relay go to “Communications>Calibration>Get
4 HUMAN INTERFACES.4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
or Set calibration settings” and select the intended calibration file. The calibration retrieval process is necessary to
be performed before updating the unit operative system, when the operating system is updated all the data in the relay
is deleted, including the factory calibration settings. When only the firmware is updated (for versions higher than 1.50),
the calibration settings are automatically saved in the relay.
•Upgrade firmware version (Ethernet connection): Go to “Communications>Upgrade firmwa re version”, this menu
allows the user to update the firmware version of the relay through Ethernet communication. Firmware is related to the
relay internal program, designed by GE Multilin, which performs the protection and control functions, and which is run
by the relay main microprocessor.
•Upgrade operating system (Serial and Ethernet connection): Go to “Communications>Upgrade operating system”.
This option allows the user to update the relay operative system. The operative system or OS is the program that
supports the firmware and provides auxiliary services for access to electronic devices included in the relay.
IMPORTANT NOTE:
READ CAREFULLY THE FLASH MEMORY UPDATE PROCED URE DESCRIBED IN
SECTION 9 AND CLOSE ALL THE RUNNING APPLICATIONS BEFORE
PERFORMING FIRMWARE AND OPERATIVE SYSTEM UPDATING PROCCESS
Before updating firmware check that the firmware version that is going to be updated
match the operative system version of the relay. Otherwise it is necessary to update the
operative system before proceeding to update the firmware. Other combinations of
firmware and operative system different from the listed below will not be operative
The operative system version is available in the logotype main screen in HMI; it is the
number between brackets in the first line, e.g. W6501.70 (2.35). The operative system
version is 2.35
4
Firmware version up to 1.5X must be used with Boot Code 2.30 (or 2.20 and 2.35)
Firmware version from 1.6X up to 1.8X must be used with Boot Code 2.35
Firmware version 2.00 must be used with Boot Code 3.00
Thanks to the use of a double flash memory, one with the Bootcode startup program and the operative system, and a
second one with the application program (firmware), a high reliability is guaranteed when updating the unit firmware, as
even if the case of a communication breakdown during the firmware upg rade process, we can retry the process for an
unlimited number of times.
•Upgrade 650 web server (Ethernet connection): Go to “Communications> Upgrade 650 web server”. The relay web
server application can be updated to further versions (if available) using this menu without modifying the relay
operative system.
•Upload info files to relay (Ethernet connection): Go to “Communications>Upload info files to relay”. This
functionality is used to store setting files (*.650) inside the relay, as well as auxiliary files used by the programmable
logic graphical editor (*.pep, *.aut, *.lib).
•Download info files from relay (Ethernet connection): Go to “Communications>Download info files from relay”.
This functionality is used for retrieving the files (*.650 and *.pep, *.aut, *.lib) th at have been previously stored in the
relay flash memory.
Important Note:
*.650 files contain protection, control settings, relay configuration and compiled logic
equations. This file can be retrieved from the relay, using the “File>Get info from
relay” option in EnerVista 650 Setup (through serial or Ethernet communication).
“File>Send info to relay” option stores this *.650 file in the relay.
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE4 HUMAN INTERFACES.
*.pep, *.aut and *.lib files contain the logic configuration projects necessary to modify the
logic (virtual outputs) in the relay. These files can be stored in the relay, using the
“Communication>Upload info files to relay” option in EnerVista 650 Setup (through
Ethernet communication). They can be retrieved using “Communication>Downloadinfo files to relay” option in EnerVista 650 Setup program (Ethernet communication).
Take into account tha t the *.pep, *.aut and lib rary files are necessary to modify the PLC
logic (virtual outputs). Without these files setting and configuration can be modified but
not logic equations (virtual outputs). It is advisable to use the
“Communication>Upload info files to relay” option to store these logic configuration
files into the relay.
It is important to distinguish between “Send / Get info to relay” and “Upload /Download info files to/from relay”. “File>Send/Get info to relay”sends/gets
settings and configuration and compiled logic equation to/from the relay (*.65 0 format),
and the relay automatically starts working with the new settings once they a re stored.
“Communications>Upload/Download info files to relay“, stores/retrieves in the
relay hard disk: settings, configuration and compiled logic equations (*.650) besid es the
PLC files (*.pep, *.aut, *.lib). This is only a physical storage (file backup).