EPM 2200 Power Meter Instruction Manual for product revision 1.0x.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The manual is for informational use only and is subject to change without
notice.
Part number: 1601-9111-A5 (June 2016)
ii
Note
GENERAL SAFETY PRECAUTIONS - EPM 2200
• Failure to observe and follow the instructions provided in the equipment manual(s)
could cause irreversible damage to the equipment and could lead to property
damage, personal injury and/or death.
• Before attempting to use the equipment, it is important that all danger and
caution indicators are reviewed.
• If the equipment is used in a manner not specified by the manufacturer or
functions abnormally, proceed with caution. Otherwise, the protection provided by
the equipment may be impaired and can result in Impaired operation and injury.
• Caution: Hazardous voltages can cause shock, burns or death.
• Installation/service personnel must be familiar with general device test practices,
electrical awareness and safety precautions must be followed.
• Before performing visual inspections, tests, or periodic maintenance on this device
or associated circuits, isolate or disconnect all hazardous live circuits and sources
of electric power.
• Failure to shut equipment off prior to removing the power connections could
expose you to dangerous voltages causing injury or death.
• All recommended equipment that should be grounded and must have a reliable
and un-compromised grounding path for safety purposes, protection against
electromagnetic interference and proper device operation.
• Equipment grounds should be bonded together and connected to the facility’s
main ground system for primary power.
• Keep all ground leads as short as possible.
• At all times, equipment ground terminal must be grounded during device
operation and service.
• In addition to the safety precautions mentioned all electrical connections made
must respect the applicable local jurisdiction electrical code.
• Before working on CTs, they must be short-circuited.
• To be certified for revenue metering, power providers and utility companies must
verify that the billing energy meter performs to the stated accuracy. To confirm the
meter’s performance and calibration, power providers use field test standards to
ensure that the unit’s energy measurements are correct.
This product cannot be disposed of as unsorted municipal waste in the European
Union. For proper recycling return this product to your supplier or a designated
collection point. For more information go to www.recyclethis.info.
iii
Safety words and definitions
NOTE
The following symbols used in this document indicate the following conditions
Note
Indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
Note
Indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
Note
Indicates a hazardous situation which, if not avoided, could result in minor or
moderate injury.
Note
Note
Indicates practices not related to personal injury.
Indicates general information and practices, including operational information, that
are not related to personal injury.
For further assistance
For product support, contact the information and call center as follows:
GE Solutions
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Worldwide telephone: +1 905 927 7070
Europe/Middle East/Africa telephone: +34 94 485 88 54
North America toll-free: 1 800 547 8629
Fax: +1 905 927 5098
Worldwide e-mail: multilin.tech@ge.com
Europe e-mail: multilin.tech.euro@ge.com
Website: http://www.gegridsolutions.com/multilin
Warranty
For products shipped as of 1 October 2013, GE warrants most of its GE manufactured
products for 10 years. For warranty details including any limitations and disclaimers, see
our Terms and Conditions at
This introduction to three-phase power and power measurement is intended to
provide only a brief overview of the subject. The professional meter engineer or meter
technician should refer to more advanced documents such as the EEI Handbook for
Electricity Metering and the application standards for more in-depth and technical
coverage of the subject.
1.1Three Phase System Configurations
Three-phase power is most commonly used in situations where large amounts of
power will be used because it is a more effective way to transmit the power and
because it provides a smoother delivery of power to the end load. There are two
commonly used connections for three-phase power, a wye connection or a delta
connection. Each connection has several different manifestations in actual use.
When attempting to determine the type of connection in use, it is a good practice to
follow the circuit back to the transformer that is serving the circuit. It is often not
possible to conclusively determine the correct circuit connection simply by counting
the wires in the service or checking voltages. Checking the transformer connection will
provide conclusive evidence of the circuit connection and the relationships between
the phase voltages and ground.
1.2Wye Connection
The wye connection is so called because when you look at the phase relationships and
the winding relationships between the phases it looks like a Y. Figure 1.1 depicts the
winding relationships for a wye-connected service. In a wye service the neutral (or
center point of the wye) is typically grounded. This leads to common voltages of 208/
120 and 480/277 (where the first number represents the phase-to-phase voltage and
the second number represents the phase-to-ground voltage).
EPM 2200 POWER METER – INSTRUCTION MANUAL1–1
WYE CONNECTIONCHAPTER 1: THREE-PHASE POWER MEASUREMENT
Phase 2
V
A
V
B
V
C
Phase 3
Figure 1-1: Three-phase Wye Winding
The three voltages are separated by 120o electrically. Under balanced load conditions
the currents are also separated by 120
conditions can cause the currents to depart from the ideal 120
phase voltages and currents are usually represented with a phasor diagram. A phasor
diagram for the typical connected voltages and currents is shown in Figure 1.2.
N
Phase 1
o
. However, unbalanced loads and other
o
separation. Three-
The phasor diagram shows the 120o angular separation between the phase voltages.
The phase-to-phase voltage in a balanced three-phase wye system is 1.732 times the
phase-to-neutral voltage. The center point of the wye is tied together and is typically
grounded. Table 1.1 shows the common voltages used in the United States for wyeconnected systems.
1–2EPM 2200 POWER METER – INSTRUCTION MANUAL
Figure 1-2: Phasor Diagram Showing Three-phase Voltages and Currents
CHAPTER 1: THREE-PHASE POWER MEASUREMENTDELTA CONNECTION
V
A
V
B
Table 1.1: Common Phase Voltages on Wye Services
Phase to Ground VoltagePhase to Phase Voltage
7,620 volts13,200 volts
Usually a wye-connected service will have four wires: three wires for the phases and
one for the neutral. The three-phase wires connect to the three phases (as shown in
Figure 1.1). The neutral wire is typically tied to the ground or center point of the wye.
In many industrial applications the facility will be fed with a four-wire wye service but
only three wires will be run to individual loads. The load is then often referred to as a
delta-connected load but the service to the facility is still a wye service; it contains
four wires if you trace the circuit back to its source (usually a transformer). In this type
of connection the phase to ground voltage will be the phase-to-ground voltage
indicated in Table 1, even though a neutral or ground wire is not physically present at
the load. The transformer is the best place to determine the circuit connection type
because this is a location where the voltage reference to ground can be conclusively
identified.
1.3Delta Connection
Delta-connected services may be fed with either three wires or four wires. In a threephase delta service the load windings are connected from phase-to-phase rather
than from phase-to-ground. Figure 1.3 shows the physical load connections for a
delta service.
In this example of a delta service, three wires will transmit the power to the load. In a
true delta service, the phase-to-ground voltage will usually not be balanced because
the ground is not at the center of the delta.
Phase 3
Figure 1.4 shows the phasor relationships between voltage and current on a threephase delta circuit.
In many delta services, one corner of the delta is grounded. This means the phase to
ground voltage will be zero for one phase and will be full phase-to-phase voltage for
the other two phases. This is done for protective purposes.
EPM 2200 POWER METER – INSTRUCTION MANUAL1–3
BLONDEL’S THEOREM AND THREE PHASE MEASUREMENTCHAPTER 1: THREE-PHASE POWER MEASUREMENT
V
A
V
BC
Figure 1-4: Phasor Diagram, Three-Phase Voltages and Currents, Delta-Connected
Another common delta connection is the four-wire, grounded delta used for lighting
loads. In this connection the center point of one winding is grounded. On a 120/240
volt, four-wire, grounded delta service the phase-to-ground voltage would be 120
volts on two phases and 208 volts on the third phase. Figure 1.5 shows the phasor
diagram for the voltages in a three-phase, four-wire delta system.
V
BC
N
V
I
C
I
B
V
AB
C
V
CA
I
A
V
CA
Figure 1-5: Phasor Diagram Showing Three-phase Four-Wire Delta-Connected System
1.4Blondel’s Theorem and Three Phase Measurement
1–4EPM 2200 POWER METER – INSTRUCTION MANUAL
In 1893 an engineer and mathematician named Andre E. Blondel set forth the first
scientific basis for polyphase metering. His theorem states:
If energy is supplied to any system of conductors through N wires, the total power in
the system is given by the algebraic sum of the readings of N wattmeters so arranged
that each of the N wires contains one current coil, the corresponding potential coil
being connected between that wire and some common point. If this common point is
on one of the N wires, the measurement may be made by the use of N-1 Wattmeters.
V
V
AB
B
CHAPTER 1: THREE-PHASE POWER MEASUREMENTBLONDEL’S THEOREM AND THREE PHASE MEASUREMENT
The theorem may be stated more simply, in modern language:
In a system of N conductors, N-1 meter elements will measure the power or energy
taken provided that all the potential coils have a common tie to the conductor in
which there is no current coil.
Three-phase power measurement is accomplished by measuring the three individual
phases and adding them together to obtain the total three phase value. In older
analog meters, this measurement was accomplished using up to three separate
elements. Each element combined the single-phase voltage and current to produce a
torque on the meter disk. All three elements were arranged around the disk so that the
disk was subjected to the combined torque of the three elements. As a result the disk
would turn at a higher speed and register power supplied by each of the three wires.
According to Blondel's Theorem, it was possible to reduce the number of elements
under certain conditions. For example, a three-phase, three-wire delta system could
be correctly measured with two elements (two potential coils and two current coils) if
the potential coils were connected between the three phases with one phase in
common.
In a three-phase, four-wire wye system it is necessary to use three elements. Three
voltage coils are connected between the three phases and the common neutral
conductor. A current coil is required in each of the three phases.
In modern digital meters, Blondel's Theorem is still applied to obtain proper
metering. The difference in modern meters is that the digital meter measures each
phase voltage and current and calculates the single-phase power for each phase. The
meter then sums the three phase powers to a single three-phase reading.
Some digital meters measure the individual phase power values one phase at a time.
This means the meter samples the voltage and current on one phase and calculates a
power value. Then it samples the second phase and calculates the power for the
second phase. Finally, it samples the third phase and calculates that phase power.
After sampling all three phases, the meter adds the three readings to create the
equivalent three-phase power value. Using mathematical averaging techniques, this
method can derive a quite accurate measurement of three-phase power.
More advanced meters actually sample all three phases of voltage and current
simultaneously and calculate the individual phase and three-phase power values. The
advantage of simultaneous sampling is the reduction of error introduced due to the
difference in time when the samples were taken.
EPM 2200 POWER METER – INSTRUCTION MANUAL1–5
POWER, ENERGY AND DEMANDCHAPTER 1: THREE-PHASE POWER MEASUREMENT
Phase B
Phase C
Phase A
A
B
C
N
Node "n"
Figure 1-6: Three-Phase Wye Load Illustrating Kirchoff’s Law and Blondel’s Theorem
Blondel's Theorem is a derivation that results from Kirchoff's Law. Kirchoff's Law states
that the sum of the currents into a node is zero. Another way of stating the same thing
is that the current into a node (connection point) must equal the current out of the
node. The law can be applied to measuring three-phase loads. Figure 1.6 shows a
typical connection of a three-phase load applied to a three-phase, four-wire service.
Kirchoff's Law holds that the sum of currents A, B, C and N must equal zero or that the
sum of currents into Node "n" must equal zero.
If we measure the currents in wires A, B and C, we then know the current in wire N by
Kirchoff's Law and it is not necessary to measure it. This fact leads us to the
conclusion of Blondel's Theorem- that we only need to measure the power in three of
the four wires if they are connected by a common node. In the circuit of Figure 1.6 we
must measure the power flow in three wires. This will require three voltage coils and
three current coils (a three-element meter). Similar figures and conclusions could be
reached for other circuit configurations involving Delta-connected loads.
1.5Power, Energy and Demand
It is quite common to exchange power, energy and demand without differentiating
between the three. Because this practice can lead to confusion, the differences
between these three measurements will be discussed.
Power is an instantaneous reading. The power reading provided by a meter is the
present flow of watts. Power is measured immediately just like current. In many digital
meters, the power value is actually measured and calculated over a one second
interval because it takes some amount of time to calculate the RMS values of voltage
and current. But this time interval is kept small to preserve the instantaneous nature
of power.
Energy is always based on some time increment; it is the integration of power over a
defined time increment. Energy is an important value because almost all electric bills
are based, in part, on the amount of energy used.
1–6EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 1: THREE-PHASE POWER MEASUREMENTPOWER, ENERGY AND DEMAND
0
10
20
30
40
50
60
70
80
123456789 10 11 12 13 14 15
Time (minutes)
sttawolik
Typically, electrical energy is measured in units of kilowatt-hours (kWh). A kilowatthour represents a constant load of one thousand watts (one kilowatt) for one hour.
Stated another way, if the power delivered (instantaneous watts) is measured as 1,000
watts and the load was served for a one hour time interval then the load would have
absorbed one kilowatt-hour of energy. A different load may have a constant power
requirement of 4,000 watts. If the load were served for one hour it would absorb four
kWh. If the load were served for 15 minutes it would absorb ¼ of that total or one
kWh.
Figure 1.7 shows a graph of power and the resulting energy that would be transmitted
as a result of the illustrated power values. For this illustration, it is assumed that the
power level is held constant for each minute when a measurement is taken. Each bar
in the graph will represent the power load for the one-minute increment of time. In
real life the power value moves almost constantly.
The data from Figure 1.7 is reproduced in Table 1.2 to illustrate the calculation of
energy. Since the time increment of the measurement is one minute and since we
specified that the load is constant over that minute, we can convert the power
reading to an equivalent consumed energy reading by multiplying the power reading
times 1/60 (converting the time base from minutes to hours).
Time Interval
EPM 2200 POWER METER – INSTRUCTION MANUAL1–7
(minute)
Figure 1-7: Power Use over Time
Table 1.2: Power and Energy Relationship over Time
Power (kW)Energy (kWh)Accumulated Energy
(kWh)
1300.500.50
2500.831.33
3400.672.00
4550.922.92
5601.003.92
6601.004.92
POWER, ENERGY AND DEMANDCHAPTER 1: THREE-PHASE POWER MEASUREMENT
Table 1.2: Power and Energy Relationship over Time
As in Table 1.2, the accumulated energy for the power load profile of Figure 1.7 is
14.92 kWh.
Demand is also a time-based value. The demand is the average rate of energy use
over time. The actual label for demand is kilowatt-hours/hour but this is normally
reduced to kilowatts. This makes it easy to confuse demand with power, but demand
is not an instantaneous value. To calculate demand it is necessary to accumulate the
energy readings (as illustrated in Figure 1.7) and adjust the energy reading to an
hourly value that constitutes the demand.
In the example, the accumulated energy is 14.92 kWh. But this measurement was
made over a 15-minute interval. To convert the reading to a demand value, it must be
normalized to a 60-minute interval. If the pattern were repeated for an additional
three 15-minute intervals the total energy would be four times the measured value or
59.68 kWh. The same process is applied to calculate the 15-minute demand value.
The demand value associated with the example load is 59.68 kWh/hr or 59.68 kWd.
Note that the peak instantaneous value of power is 80 kW, significantly more than the
demand value.
Figure 1.8 shows another example of energy and demand. In this case, each bar
represents the energy consumed in a 15-minute interval. The energy use in each
interval typically falls between 50 and 70 kWh. However, during two intervals the
energy rises sharply and peaks at 100 kWh in interval number 7. This peak of usage
will result in setting a high demand reading. For each interval shown the demand
value would be four times the indicated energy reading. So interval 1 would have an
associated demand of 240 kWh/hr. Interval 7 will have a demand value of 400 kWh/
hr. In the data shown, this is the peak demand value and would be the number that
would set the demand charge on the utility bill.
1–8EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 1: THREE-PHASE POWER MEASUREMENTREACTIVE ENERGY AND POWER FACTOR
0
20
40
60
80
100
12345678
Intervals (15 mins.)
sruoh-ttawolik
Figure 1-8: Energy Use and Demand
As can be seen from this example, it is important to recognize the relationships
between power, energy and demand in order to control loads effectively or to monitor
use correctly.
1.6Reactive Energy and Power Factor
The real power and energy measurements discussed in the previous section relate to
the quantities that are most used in electrical systems. But it is often not sufficient to
only measure real power and energy. Reactive power is a critical component of the
total power picture because almost all real-life applications have an impact on
reactive power. Reactive power and power factor concepts relate to both load and
generation applications. However, this discussion will be limited to analysis of reactive
power and power factor as they relate to loads. To simplify the discussion, generation
will not be considered.
Real power (and energy) is the component of power that is the combination of the
voltage and the value of corresponding current that is directly in phase with the
voltage. However, in actual practice the total current is almost never in phase with the
voltage. Since the current is not in phase with the voltage, it is necessary to consider
both the inphase component and the component that is at quadrature (angularly
rotated 90o or perpendicular) to the voltage. Figure 1.9 shows a single-phase voltage
and current and breaks the current into its in-phase and quadrature components.
EPM 2200 POWER METER – INSTRUCTION MANUAL1–9
REACTIVE ENERGY AND POWER FACTORCHAPTER 1: THREE-PHASE POWER MEASUREMENT
V
I
I
R
I
X
0
Figure 1-9: Voltage and Complex Current
The voltage (V) and the total current (I) can be combined to calculate the apparent
power or VA. The voltage and the in-phase current (IR) are combined to produce the
real power or watts. The voltage and the quadrature current (IX) are combined to
calculate the reactive power.
The quadrature current may be lagging the voltage (as shown in Figure 1.9) or it may
lead the voltage. When the quadrature current lags the voltage the load is requiring
both real power (watts) and reactive power (VARs). When the quadrature current leads
the voltage the load is requiring real power (watts) but is delivering reactive power
(VARs) back into the system; that is VARs are flowing in the opposite direction of the
real power flow.
Reactive power (VARs) is required in all power systems. Any equipment that uses
magnetization to operate requires VARs. Usually the magnitude of VARs is relatively
low compared to the real power quantities. Utilities have an interest in maintaining
VAR requirements at the customer to a low value in order to maximize the return on
plant invested to deliver energy. When lines are carrying VARs, they cannot carry as
many watts. So keeping the VAR content low allows a line to carry its full capacity of
watts. In order to encourage customers to keep VAR requirements low, some utilities
impose a penalty if the VAR content of the load rises above a specified value.
A common method of measuring reactive power requirements is power factor. Power
factor can be defined in two different ways. The more common method of calculating
power factor is the ratio of the real power to the apparent power. This relationship is
expressed in the following formula:
Total PF = real power / apparent power = watts/VA
This formula calculates a power factor quantity known as Total Power Factor. It is
called Total PF because it is based on the ratios of the power delivered. The delivered
power quantities will include the impacts of any existing harmonic content. If the
voltage or current includes high levels of harmonic distortion the power values will be
affected. By calculating power factor from the power values, the power factor will
include the impact of harmonic distortion. In many cases this is the preferred method
of calculation because the entire impact of the actual voltage and current are
included.
1–10EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 1: THREE-PHASE POWER MEASUREMENTHARMONIC DISTORTION
Displacement PFθcos=
Time
Amps
– 1000
– 500
0
500
1000
A second type of power factor is Displacement Power Factor. Displacement PF is
based on the angular relationship between the voltage and current. Displacement
power factor does not consider the magnitudes of voltage, current or power. It is solely
based on the phase angle differences. As a result, it does not include the impact of
harmonic distortion. Displacement power factor is calculated using the following
equation:
where
θ is the angle between the voltage and the current (see Fig. 1.9).
In applications where the voltage and current are not distorted, the Total Power
Factor will equal the Displacement Power Factor. But if harmonic distortion is present,
the two power factors will not be equal.
1.7Harmonic Distortion
Harmonic distortion is primarily the result of high concentrations of non-linear loads.
Devices such as computer power supplies, variable speed drives and fluorescent light
ballasts make current demands that do not match the sinusoidal waveform of AC
electricity. As a result, the current waveform feeding these loads is periodic but not
sinusoidal. Figure 1.10 shows a normal, sinusoidal current waveform. This example
has no distortion.
Figure 1.11 shows a current waveform with a slight amount of harmonic distortion.
The waveform is still periodic and is fluctuating at the normal 60 Hz frequency.
However, the waveform is not a smooth sinusoidal form as seen in Figure 1.10.
EPM 2200 POWER METER – INSTRUCTION MANUAL1–11
Figure 1-10: Nondistorted Current Waveform
HARMONIC DISTORTIONCHAPTER 1: THREE-PHASE POWER MEASUREMENT
–1000
–500
0
500
1000
t
)s
p
m
a(
tner
r
u
C
a
2a
–1500
1500
Time
Amps
3rd harmonic
5th harmonic
7th harmonic
Total
fundamental
– 500
0
500
1000
Figure 1-11: Distorted Current Waveform
The distortion observed in Figure 1.11 can be modeled as the sum of several
sinusoidal waveforms of frequencies that are multiples of the fundamental 60 Hz
frequency. This modeling is performed by mathematically disassembling the distorted
waveform into a collection of higher frequency waveforms.
These higher frequency waveforms are referred to as harmonics. Figure 1.12 shows
the content of the harmonic frequencies that make up the distortion portion of the
waveform in Figure 1.11.
The waveforms shown in Figure 1.12 are not smoothed but do provide an indication of
1–12EPM 2200 POWER METER – INSTRUCTION MANUAL
the impact of combining multiple harmonic frequencies together.
When harmonics are present it is important to remember that these quantities are
operating at higher frequencies. Therefore, they do not always respond in the same
manner as 60 Hz values.
Figure 1-12: Waveforms of the Harmonics
CHAPTER 1: THREE-PHASE POWER MEASUREMENTPOWER QUALITY
Inductive and capacitive impedance are present in all power systems. We are
accustomed to thinking about these impedances as they perform at 60 Hz. However,
these impedances are subject to frequency variation.
XL = jwL and
XC = 1/jwC
At 60 Hz, w = 377; but at 300 Hz (5th harmonic) w = 1,885. As frequency changes
impedance changes and system impedance characteristics that are normal at 60 Hz
may behave entirely differently in the presence of higher order harmonic waveforms.
Traditionally, the most common harmonics have been the low order, odd frequencies,
such as the 3rd, 5th, 7th, and 9th. However newer, non-linear loads are introducing
significant quantities of higher order harmonics.
Since much voltage monitoring and almost all current monitoring is performed using
instrument transformers, the higher order harmonics are often not visible. Instrument
transformers are designed to pass 60 Hz quantities with high accuracy. These devices,
when designed for accuracy at low frequency, do not pass high frequencies with high
accuracy; at frequencies above about 1200 Hz they pass almost no information. So
when instrument transformers are used, they effectively filter out higher frequency
harmonic distortion making it impossible to see.
1.8Power Quality
However, when monitors can be connected directly to the measured circuit (such as
direct connection to a 480 volt bus) the user may often see higher order harmonic
distortion. An important rule in any harmonics study is to evaluate the type of
equipment and connections before drawing a conclusion. Not being able to see
harmonic distortion is not the same as not having harmonic distortion.
It is common in advanced meters to perform a function commonly referred to as
waveform capture. Waveform capture is the ability of a meter to capture a present
picture of the voltage or current waveform for viewing and harmonic analysis.
Typically a waveform capture will be one or two cycles in duration and can be viewed
as the actual waveform, as a spectral view of the harmonic content, or a tabular view
showing the magnitude and phase shift of each harmonic value. Data collected with
waveform capture is typically not saved to memory. Waveform capture is a real-time
data collection event.
Waveform capture should not be confused with waveform recording that is used to
record multiple cycles of all voltage and current waveforms in response to a transient
condition.
Power quality can mean several different things. The terms “power quality” and
“power quality problem” have been applied to all types of conditions. A simple
definition of “power quality problem” is any voltage, current or frequency deviation
that results in mis-operation or failure of customer equipment or systems. The causes
of power quality problems vary widely and may originate in the customer equipment,
in an adjacent customer facility or with the utility.
EPM 2200 POWER METER – INSTRUCTION MANUAL1–13
POWER QUALITYCHAPTER 1: THREE-PHASE POWER MEASUREMENT
In his book Power Quality Primer, Barry Kennedy provided information on different
types of power quality problems. Some of that information is summarized in Table 1.3.
Table 1.3: Typical Power Quality Problems and Sources
CauseDisturbance TypeSource
Impulse transientTransient voltage disturbance,
sub-cycle duration
Oscillatory
transient with decay
Sag/swellRMS voltage, multiple cycle
InterruptionsRMS voltage, multiple
Under voltage/over
voltage
Voltage flickerRMS voltage, steady state,
Harmonic distortionSteady state current or voltage,
Transient voltage, sub-cycle
duration
duration
seconds or longer duration
RMS voltage, steady state, multiple
seconds or longer
duration
System protection
Circuit breakers
Fuses
Maintenance
Motor starting
Load variations
Load dropping
Intermittent loads
Motor starting
Arc furnaces
Non-linear loads
System resonance
It is often assumed that power quality problems originate with the utility. While it is
true that power quality problems can originate with the utility system, many problems
originate with customer equipment. Customer-caused problems may manifest
themselves inside the customer location or they may be transported by the utility
system to another adjacent customer. Often, equipment that is sensitive to power
quality problems may in fact also be the cause of the problem.
If a power quality problem is suspected, it is generally wise to consult a power quality
professional for assistance in defining the cause and possible solutions to the
problem.
1–14EPM 2200 POWER METER – INSTRUCTION MANUAL
GE
Grid Solutions
Note
EPM 2200 Power Meter
Chapter 2: Overview and
Specifications
Overview and Specifications
In European Union member state countries, this meter is NOT certified for revenue
metering. See the Safety Precautions section for meter certification details.
2.1Hardware Overview
The EPM 2200 multifunction power meters is designed for use with and/or within Industrial
Control Panels in electrical substations, panel boards, and as a power meter for OEM
equipment. EPM 2200 meters provide multifunction measurement of all electrical
parameters.
The EPM 2200 monitor is a 0.5% class electrical panel meter. Using bright and large 0.56”
LED displays, it is designed to be used in electrical panels and switchgear. The meter has a
unique anti-dither algorithm to improve reading stability. The EPM 2200 meter uses highspeed DSP technology with high-resolution A/D conversion to provide stable and reliable
measurements. UL 61010-1 does not address performance criteria for revenue generating
watt-hour meters for use in metering of utilities and/or communicating directly with
utilities, or use within a substation. Use in revenue metering, communicating with utilities,
and use in substations was verified according to the ANSI and IEC standards listed in the
Compliance Section (2.3).
The EPM 2200 meter is a meter and transducer in one compact unit. Featuring an optional
RS485 port, it can be programmed using the faceplate of the meter or through software.
ANSI or DIN mounting may be used.
EPM 2200 meter features that are detailed in this manual are as follows:
•0.5% Class Accuracy
•Multifunction Measurement including Voltage, Current, Power, Frequency, Energy, etc.
•Percentage of Load Bar for Analog Meter Perception
•Easy to Use Faceplate Programming
•One Communication Option:
• RS485 Modbus/KYZ output (Option S)
EPM 2200 POWER METER – INSTRUCTION MANUAL2–1
HARDWARE OVERVIEWCHAPTER 2: OVERVIEW AND SPECIFICATIONS
• BACnet MS/TP Serial Multifunction Meter with Modbus TCP/IP Internet (Option B)
2.1.1Voltage and Current Inputs
Universal Voltage Inputs
Voltage Inputs allow measurement to 416 Volts Line-to-Neutral and 721 Volts Line-to-Line.
One unit will perform to specification when directly connected to 69 Volt, 120 Volt, 230
Volt, 277 Volt, 277 Volt and 347 Volt power systems.
Current Inputs
The EPM 2200 meter Current Inputs use a unique dual input method:
Method 1: CT Pass Through
The CT passes directly through the meter without any physical termination on the meter.
This insures that the meter cannot be a point of failure on the CT circuit. This is preferable
for utility users when sharing relay class CTs.
Method 2: Current “Gills”
This unit additionally provides ultra-rugged Termination Pass Through Bars that allow CT
leads to be terminated on the meter. This, too, eliminates any possible point of failure at
the meter. This is a preferred technique for insuring that relay class CT integrity is not
compromised (the CT will not open in a fault condition).
2.1.2Order Codes
The order codes for the EPM 2200 are indicated below.
Table 2–1: EPM 2200 Order Codes
PL2200
Base UnitPL2200
Enclosure OptionENC120||NEMA1 Rated - Indoor, Single Meter Enclosure, 120V
Software Option*
Communications Option
–*– * – *
|||
EPM 2200 Meter
ENC277||NEMA1 Rated - Indoor, Single Meter Enclosure, 277V
A1|
B1|
C1|
BN|
Volts and Amps Meter
Volts, Amps, Power and Frequency Meter
Volts, Amps, Power, Frequency and Energy Counters Meter
BACnet Volts, Amps, Power, Frequency and Energy Counters
meter
RS485 Serial/KYZ Pulse
S
None
X
BACnet MS/TP Serial and Modbus TCP/IP Internet
B
* Software Options are only available with Communications Option S.
For example, to order an EPM 2200 to measure Volts, Amps, Power & Frequency, with
Modbus/KYZ output communications, use PL2200-XXXXXX-B1-S.
Accessories available for the EPM 2200 are indicated below.
2–2EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 2: OVERVIEW AND SPECIFICATIONSHARDWARE OVERVIEW
Table 2–2: EPM 2200 Accessory Order Codes
PL2200–
DIN BracketPL2200–
*
ACC
–
*
–
EPM 2200 Meter DIN Mounting Bracket
DIN
2.1.3Measured Values
The following table lists the measured values available in real time, average, maximum,
and minimum.
Table 2–3: EPM 2200 Measured Values
Measured ValuesReal TimeAverageMaximumMinimum
Voltage L-NXXX
Voltage L-LXXX
Current per phaseXXXX
Current NeutralX
WattsXXXX
VARsXXXX
VAXXXX
Power Factor (PF)XXXX
Positive watt-hoursX
Negative watt-hoursX
Net watt-hoursX
Positive VAR-hoursX
Negative VAR-hoursX
Net VAR-hoursX
VA-hoursX
FrequencyXXX
Voltage anglesX
Current anglesX
% of load barX
2.1.4Utility Peak Demand
The EPM 2200 provides user-configured Block (fixed) window, or Rolling window demand.
This feature allows you to set up a customized demand profile. Block window demand is
demand used over a user-configured demand period (usually 5, 15, or 30 minutes). Rolling
EPM 2200 POWER METER – INSTRUCTION MANUAL2–3
SPECIFICATIONSCHAPTER 2: OVERVIEW AND SPECIFICATIONS
window demand is a fixed window demand that moves for a user-specified subinterval
period. For example, a 15-minute demand using 3 subintervals and providing a new
demand reading every 5 minutes, based on the last 15 minutes.
Utility demand features can be used to calculate kW, kVAR, kVA and PF readings. All other
parameters offer maximum and minimum capability over the user-selectable averaging
period. Voltage provides an instantaneous maximum and minimum reading which
displays the highest surge and lowest sag seen by the meter.
2.2Specifications
POWER SUPPLY
Range:.................................................Universal, (90 to 265) VAC @50/60Hz
Power consumption: ....................5 VA, 3.5 W
VOLTAGE INPUTS (MEASUREMENT CATEGORY III)
Range:.................................................Universal, Auto-ranging up to 416 V AC L-N, 721 V AC L-L
CHAPTER 2: OVERVIEW AND SPECIFICATIONSSPECIFICATIONS
Figure 2-2: Output Timing
EPM 2200 POWER METER – INSTRUCTION MANUAL2–7
COMPLIANCECHAPTER 2: OVERVIEW AND SPECIFICATIONS
2.3Compliance
TestReference Standard
IEC62053-22 (0.5% Accuracy)
ANSI C12.20 (0.5% Accuracy)
CE Compliant
REACH Compliant
RoHS Compliant
Surge WithstandANSI (IEEE) C37.90.1
BurstANSI C62.41
Electrostatic DischargeIEC61000-4-2
RF ImmunityIEC61000-4-3
Fast TransientIEC61000-4-4
Surge ImmunityIEC61000-4-5
Conducted Disturbance ImmunityIEC61000-4-6
Magnetic Field ImmunityIEC61000-4-8
Voltage Dips and Sags ImmunityIEC61000-4-11
Immunity for Industrial EnvironmentsEN61000-6-2
Emission Standards for Industrial
EN61000-6-4
Environments
EMC RequirementsEN61326-1
APPROVALS
Applicable Council DirectiveAccording to:
North AmericaUL Recognized
ISOManufactured under a registered
quality program
UL61010-1
C22.2. No 61010-1 (PICQ7)
File e200431
ISO9001
2–8EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 2: OVERVIEW AND SPECIFICATIONSACCURACY
NOTE
2.4Accuracy
For 23 °C, 3 Phase balanced Wye or Delta load.
ParameterAccuracyAccuracy Input Range
Voltage L-N [V]0.2% of reading
Voltage L-L [V]0.4% of reading(120 to 600)V
Current Phase [A]0.2% of reading
Current Neutral (calculated)
2% of Full Scale
[A]
Active Power Total [W]0.5% of reading
Active Energy Total [Wh]0.5% of reading
Reactive Power Total [VAR]1.0% of reading
Reactive Energy Total [VARh]1.0% of reading
Apparent Power Total [VA]1.0% of reading
Apparent Energy Total [VAh]1.0% of reading
Power Factor1.0% of reading
Frequency+/- 0.01Hz(45 to 65)Hz
Load Bar+/- 1 segment
1
For 2.5 element programmed units, degrade accuracy by an additional 0.5% of reading.
2
For unbalanced voltage inputs where at least one crosses the 150V auto-scale threshold
(for example, 120V/120V/208V system), degrade accuracy by additional 0.4%.
2
(69 to 480)V
1
(0.15 to 5)A
1
(0.15 to 5)A @ (45 to 65)Hz
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0 to 0.8) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0 to 0.8) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1
(0.005 to 6)A
EPM 2200 accuracy meets the IEC62053-22 Accuracy Standards for 0.5% Class Meters.
This standard is shown in the table below.
Value of CurrentPower FactorPercentage Error Limits for
0.01 I
n≤I < 0. 05 In1±1.0
0.05 I
n≤I≤Imax1±0.5
0.02 I
n≤I < 0.1 In0.5 inductive
0.8 capacitive
0.1 I
n≤I≤Imax0.5 inductive
0.8 capacitive
When specially requested by the
user, from:
0.1 I
n≤I≤Imax
Note
In the table above:
I
n = Nominal (5A)
max = Full Scale
I
0.25 inductive
0.8 capacitive
Meters of Class 0.5 S
±1.0
±1.0
±0.6
±0.6
±1.0
±1.0
EPM 2200 POWER METER – INSTRUCTION MANUAL2–9
ACCURACYCHAPTER 2: OVERVIEW AND SPECIFICATIONS
2–10EPM 2200 POWER METER – INSTRUCTION MANUAL
Loading...
+ 86 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.