GE Multilin EPM 2200 Instruction Manual

GE
LISTED
Grid Solutions
Multilin™ EPM 2200
Power Meter
Instruction Manual
Software Revision: 1.0x Manual P/N: 1601- 9111-A5 Manual Order Code: GEK-113575D
*1601-911-A5*
Copyright © 2016 GE Multilin Inc. All rights reserved.
EPM 2200 Power Meter Instruction Manual for product revision 1.0x.
The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The manual is for informational use only and is subject to change without notice.
Part number: 1601-9111-A5 (June 2016)
ii
Note
GENERAL SAFETY PRECAUTIONS - EPM 2200
• Failure to observe and follow the instructions provided in the equipment manual(s) could cause irreversible damage to the equipment and could lead to property damage, personal injury and/or death.
• Before attempting to use the equipment, it is important that all danger and caution indicators are reviewed.
• If the equipment is used in a manner not specified by the manufacturer or functions abnormally, proceed with caution. Otherwise, the protection provided by the equipment may be impaired and can result in Impaired operation and injury.
• Caution: Hazardous voltages can cause shock, burns or death.
• Installation/service personnel must be familiar with general device test practices, electrical awareness and safety precautions must be followed.
• Before performing visual inspections, tests, or periodic maintenance on this device or associated circuits, isolate or disconnect all hazardous live circuits and sources of electric power.
• Failure to shut equipment off prior to removing the power connections could expose you to dangerous voltages causing injury or death.
• All recommended equipment that should be grounded and must have a reliable and un-compromised grounding path for safety purposes, protection against electromagnetic interference and proper device operation.
• Equipment grounds should be bonded together and connected to the facility’s main ground system for primary power.
• Keep all ground leads as short as possible.
• At all times, equipment ground terminal must be grounded during device operation and service.
• In addition to the safety precautions mentioned all electrical connections made must respect the applicable local jurisdiction electrical code.
• Before working on CTs, they must be short-circuited.
• To be certified for revenue metering, power providers and utility companies must verify that the billing energy meter performs to the stated accuracy. To confirm the meter’s performance and calibration, power providers use field test standards to ensure that the unit’s energy measurements are correct.
This product cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling return this product to your supplier or a designated collection point. For more information go to www.recyclethis.info.
iii
Safety words and definitions
NOTE
The following symbols used in this document indicate the following conditions
Note
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Note
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Note
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Note
Note
Indicates practices not related to personal injury.
Indicates general information and practices, including operational information, that are not related to personal injury.
For further assistance
For product support, contact the information and call center as follows:
GE Solutions 650 Markland Street Markham, Ontario Canada L6C 0M1 Worldwide telephone: +1 905 927 7070 Europe/Middle East/Africa telephone: +34 94 485 88 54 North America toll-free: 1 800 547 8629 Fax: +1 905 927 5098 Worldwide e-mail: multilin.tech@ge.com Europe e-mail: multilin.tech.euro@ge.com Website: http://www.gegridsolutions.com/multilin
Warranty
For products shipped as of 1 October 2013, GE warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see our Terms and Conditions at
https://www.gegridsolutions.com/multilin/warranty.htm
For products shipped before 1 October 2013, the standard 24-month warranty applies.
iv
Table of Contents
1: THREE-PHASE POWER MEASUREMENT
2: OVERVIEW AND SPECIFICATIONS
3: MECHANICAL INSTALLATION
THREE PHASE SYSTEM CONFIGURATIONS ........................................................................... 1-1
WYE CONNECTION ..........................................................................................................................1-1
DELTA CONNECTION ......................................................................................................................1-3
BLONDEL’S THEOREM AND THREE PHASE MEASUREMENT ......................................... 1-4
POWER, ENERGY AND DEMAND ............................................................................................... 1-6
REACTIVE ENERGY AND POWER FACTOR ............................................................................. 1-9
HARMONIC DISTORTION ..............................................................................................................1-11
POWER QUALITY .............................................................................................................................. 1-13
HARDWARE OVERVIEW ................................................................................................................. 2-1
V
OLTAGE AND CURRENT INPUTS ...................................................................................... 2-2
O
RDER CODES ..................................................................................................................... 2-2
M
EASURED VALUES ............................................................................................................ 2-3
U
TILITY PEAK DEMAND .......................................................................................................2-3
SPECIFICATIONS ............................................................................................................................... 2-4
COMPLIANCE ..................................................................................................................................... 2-8
ACCURACY .......................................................................................................................................... 2-9
INTRODUCTION ................................................................................................................................ 3-1
ANSI INSTALLATION STEPS .......................................................................................................... 3-2
DIN INSTALLATION STEPS ...........................................................................................................3-3
4: ELECTRICAL INSTALLATION
5: COM OPTION S: MODBUS/KYZ OUTPUT
CONSIDERATIONS WHEN INSTALLING METERS ................................................................. 4-1
CT L
EADS TERMINATED TO METER ...................................................................................4-2
CT L
EADS PASS-THROUGH (NO METER TERMINATION) ................................................ 4-3
Q
UICK CONNECT CRIMP CT TERMINATIONS ................................................................... 4-5
V
OLTAGE AND POWER SUPPLY CONNECTIONS .............................................................. 4-6
G
ROUND CONNECTIONS ....................................................................................................4-6
V
OLTAGE FUSES .................................................................................................................. 4-6
ELECTRICAL CONNECTION DIAGRAMS ..................................................................................4-7
D
ESCRIPTION ........................................................................................................................ 4-7
(1) W
YE, 4-WIRE WITH NO PTS AND 3 CTS, NO PTS, 3 ELEMENT ............................ 4-8
(2) W
YE, 4-WIRE WITH NO PTS AND 3 CTS, 2.5 ELEMENT ........................................ 4-11
(3) W
YE, 4-WIRE WITH 3 PTS AND 3 CTS, 3 ELEMENT .............................................. 4-12
(4) W
YE, 4-WIRE WITH 2 PTS AND 3 CTS, 2.5 ELEMENT ...........................................4-13
(5) D
ELTA, 3-WIRE WITH NO PTS, 2 CTS ....................................................................... 4-14
(6) D
ELTA, 3-WIRE WITH 2 PTS, 2 CTS ......................................................................... 4-15
(7) D
ELTA, 3-WIRE WITH 2 PTS, 3 CTS ......................................................................... 4-16
(8) C
URRENT-ONLY MEASUREMENT (THREE-PHASE) .................................................... 4-17
(9) C
URRENT-ONLY MEASUREMENT (DUAL-PHASE) ...................................................... 4-18
(10) C
URRENT-ONLY MEASUREMENT (SINGLE-PHASE) ................................................ 4-19
CONNECTING TO THE RS485/KYZ OUTPUT PORT ............................................................. 5-1
EPM 2200 POWER METER – INSTRUCTION MANUAL TOC–1
6: USING THE METER PROGRAMMING USING THE FACEPLATE ...............................................................................6-1
M
ETER FACE ELEMENTS ..................................................................................................... 6-2
M
ETER FACE BUTTONS ....................................................................................................... 6-2
S
TART UP .............................................................................................................................. 6-3
M
AIN MENU ........................................................................................................................6-4
R
ESET MODE .......................................................................................................................6-4
E
NTER PASSWORD (IF ENABLED) .......................................................................................6-5
C
ONFIGURATION MODE ......................................................................................................6-6
C
ONFIGURING THE SCROLL FEATURE ............................................................................... 6-8
C
ONFIGURING THE CT SETTING ........................................................................................6-9
C
ONFIGURING THE PT SETTING ........................................................................................6-10
C
ONFIGURING THE CONNECTION (CNCT) SETTING ......................................................... 6-11
C
ONFIGURING THE COMMUNICATION PORT SETTINGS .................................................. 6-12
O
PERATING MODE ...............................................................................................................6-14
% OF LOAD BAR ...............................................................................................................................6-15
WATT-HOUR ACCURACY TESTING (VERIFICATION) ...........................................................6-15
I
NFRARED & KYZ PULSE CONSTANTS FOR ACCURACY TESTING ................................. 6-16
GE COMMUNICATOR PROGRAMMING OVERVIEW ............................................................ 6-17
F
ACTORY INITIAL DEFAULT SETTINGS ............................................................................... 6-17
H
OW TO CONNECT USING GE COMMUNICATOR SOFTWARE ......................................6-17
D
EVICE PROFILE SETTINGS ................................................................................................. 6-20
7: COM OPTION B: BACNET MS/TP WITH MODBUS TCP/IP
A: EPM 2200 NAVIGATION MAPS
B: MODBUS MAPPING FOR EPM 2200
BACNET MS/TP .................................................................................................................................. 7-1
EPM 2200 METER BACNET OBJECTS ....................................................................................... 7-2
CONFIGURING COM OPTION B: BACNET MS/TP WITH MODBUS TCP/IP ................. 7-4
R
ESETTING THE ETHERNET CARD ...................................................................................... 7-11
USING THE EPM 2200 METER’S WEB INTERFACE ..............................................................7-11
H
OME WEB PAGE ................................................................................................................. 7-11
BAC
NET OBJECTS STATUS WEB PAGE ............................................................................. 7-13
C
HANGE PASSWORD WEB PAGE ....................................................................................... 7-14
S
TATISTICS WEB PAGE ......................................................................................................... 7-14
R
ESET CONFIGURATION WEB PAGE ...................................................................................7-15
USING THE EPM 2200 IN A BACNET APPLICATION ........................................................... 7-15
INTRODUCTION ................................................................................................................................ A-1
NAVIGATION MAPS (SHEETS 1 TO 4) ........................................................................................ A-1
EPM 2200 N
AVIGATION MAP TITLES: ............................................................................A-1
INTRODUCTION ................................................................................................................................ B-1
MODBUS REGISTER MAP SECTIONS ........................................................................................ B-1
DATA FORMATS ............................................................................................................................... B-2
FLOATING POINT VALUES ........................................................................................................... B-2
MODBUS REGISTER MAP .............................................................................................................. B-3
C: MANUAL REVISION
RELEASE NOTES ................................................................................................................................C-1
HISTORY
TOC–2 EPM 2200 POWER METER – INSTRUCTION MANUAL
GE
Grid Solutions
EPM 2200 Power Meter
Chapter 1: Three-Phase Power
Measurement
Three-Phase Power Measurement
This introduction to three-phase power and power measurement is intended to provide only a brief overview of the subject. The professional meter engineer or meter technician should refer to more advanced documents such as the EEI Handbook for Electricity Metering and the application standards for more in-depth and technical coverage of the subject.
1.1 Three Phase System Configurations
Three-phase power is most commonly used in situations where large amounts of power will be used because it is a more effective way to transmit the power and because it provides a smoother delivery of power to the end load. There are two commonly used connections for three-phase power, a wye connection or a delta connection. Each connection has several different manifestations in actual use.
When attempting to determine the type of connection in use, it is a good practice to follow the circuit back to the transformer that is serving the circuit. It is often not possible to conclusively determine the correct circuit connection simply by counting the wires in the service or checking voltages. Checking the transformer connection will provide conclusive evidence of the circuit connection and the relationships between the phase voltages and ground.
1.2 Wye Connection
The wye connection is so called because when you look at the phase relationships and the winding relationships between the phases it looks like a Y. Figure 1.1 depicts the winding relationships for a wye-connected service. In a wye service the neutral (or center point of the wye) is typically grounded. This leads to common voltages of 208/ 120 and 480/277 (where the first number represents the phase-to-phase voltage and the second number represents the phase-to-ground voltage).
EPM 2200 POWER METER – INSTRUCTION MANUAL 1–1
WYE CONNECTION CHAPTER 1: THREE-PHASE POWER MEASUREMENT
Phase 2
V
A
V
B
V
C
Phase 3
Figure 1-1: Three-phase Wye Winding
The three voltages are separated by 120o electrically. Under balanced load conditions the currents are also separated by 120 conditions can cause the currents to depart from the ideal 120 phase voltages and currents are usually represented with a phasor diagram. A phasor diagram for the typical connected voltages and currents is shown in Figure 1.2.
N
Phase 1
o
. However, unbalanced loads and other
o
separation. Three-
The phasor diagram shows the 120o angular separation between the phase voltages. The phase-to-phase voltage in a balanced three-phase wye system is 1.732 times the phase-to-neutral voltage. The center point of the wye is tied together and is typically grounded. Table 1.1 shows the common voltages used in the United States for wye­connected systems.
1–2 EPM 2200 POWER METER – INSTRUCTION MANUAL
Figure 1-2: Phasor Diagram Showing Three-phase Voltages and Currents
Table 1.1: Common Phase Voltages on Wye Services
Phase to Ground Voltage Phase to Phase Voltage
120 volts 208 volts 277 volts 480 volts 2,400 volts 4,160 volts 7,200 volts 12,470 volts
CHAPTER 1: THREE-PHASE POWER MEASUREMENT DELTA CONNECTION
V
A
V
B
Table 1.1: Common Phase Voltages on Wye Services
Phase to Ground Voltage Phase to Phase Voltage
7,620 volts 13,200 volts
Usually a wye-connected service will have four wires: three wires for the phases and one for the neutral. The three-phase wires connect to the three phases (as shown in Figure 1.1). The neutral wire is typically tied to the ground or center point of the wye.
In many industrial applications the facility will be fed with a four-wire wye service but only three wires will be run to individual loads. The load is then often referred to as a delta-connected load but the service to the facility is still a wye service; it contains four wires if you trace the circuit back to its source (usually a transformer). In this type of connection the phase to ground voltage will be the phase-to-ground voltage indicated in Table 1, even though a neutral or ground wire is not physically present at the load. The transformer is the best place to determine the circuit connection type because this is a location where the voltage reference to ground can be conclusively identified.
1.3 Delta Connection
Delta-connected services may be fed with either three wires or four wires. In a three­phase delta service the load windings are connected from phase-to-phase rather than from phase-to-ground. Figure 1.3 shows the physical load connections for a delta service.
V
C
Phase 2
Phase 1
Figure 1-3: Three-phase Delta Winding Relationship
In this example of a delta service, three wires will transmit the power to the load. In a true delta service, the phase-to-ground voltage will usually not be balanced because the ground is not at the center of the delta.
Phase 3
Figure 1.4 shows the phasor relationships between voltage and current on a three­phase delta circuit.
In many delta services, one corner of the delta is grounded. This means the phase to ground voltage will be zero for one phase and will be full phase-to-phase voltage for the other two phases. This is done for protective purposes.
EPM 2200 POWER METER – INSTRUCTION MANUAL 1–3
BLONDEL’S THEOREM AND THREE PHASE MEASUREMENT CHAPTER 1: THREE-PHASE POWER MEASUREMENT
V
A
V
BC
Figure 1-4: Phasor Diagram, Three-Phase Voltages and Currents, Delta-Connected
Another common delta connection is the four-wire, grounded delta used for lighting loads. In this connection the center point of one winding is grounded. On a 120/240 volt, four-wire, grounded delta service the phase-to-ground voltage would be 120 volts on two phases and 208 volts on the third phase. Figure 1.5 shows the phasor diagram for the voltages in a three-phase, four-wire delta system.
V
BC
N
V
I
C
I
B
V
AB
C
V
CA
I
A
V
CA
Figure 1-5: Phasor Diagram Showing Three-phase Four-Wire Delta-Connected System
1.4 Blondel’s Theorem and Three Phase Measurement
1–4 EPM 2200 POWER METER – INSTRUCTION MANUAL
In 1893 an engineer and mathematician named Andre E. Blondel set forth the first scientific basis for polyphase metering. His theorem states:
If energy is supplied to any system of conductors through N wires, the total power in the system is given by the algebraic sum of the readings of N wattmeters so arranged that each of the N wires contains one current coil, the corresponding potential coil being connected between that wire and some common point. If this common point is on one of the N wires, the measurement may be made by the use of N-1 Wattmeters.
V
V
AB
B
CHAPTER 1: THREE-PHASE POWER MEASUREMENT BLONDEL’S THEOREM AND THREE PHASE MEASUREMENT
The theorem may be stated more simply, in modern language:
In a system of N conductors, N-1 meter elements will measure the power or energy taken provided that all the potential coils have a common tie to the conductor in which there is no current coil.
Three-phase power measurement is accomplished by measuring the three individual phases and adding them together to obtain the total three phase value. In older analog meters, this measurement was accomplished using up to three separate elements. Each element combined the single-phase voltage and current to produce a torque on the meter disk. All three elements were arranged around the disk so that the disk was subjected to the combined torque of the three elements. As a result the disk would turn at a higher speed and register power supplied by each of the three wires.
According to Blondel's Theorem, it was possible to reduce the number of elements under certain conditions. For example, a three-phase, three-wire delta system could be correctly measured with two elements (two potential coils and two current coils) if the potential coils were connected between the three phases with one phase in common.
In a three-phase, four-wire wye system it is necessary to use three elements. Three voltage coils are connected between the three phases and the common neutral conductor. A current coil is required in each of the three phases.
In modern digital meters, Blondel's Theorem is still applied to obtain proper metering. The difference in modern meters is that the digital meter measures each phase voltage and current and calculates the single-phase power for each phase. The meter then sums the three phase powers to a single three-phase reading.
Some digital meters measure the individual phase power values one phase at a time. This means the meter samples the voltage and current on one phase and calculates a power value. Then it samples the second phase and calculates the power for the second phase. Finally, it samples the third phase and calculates that phase power. After sampling all three phases, the meter adds the three readings to create the equivalent three-phase power value. Using mathematical averaging techniques, this method can derive a quite accurate measurement of three-phase power.
More advanced meters actually sample all three phases of voltage and current simultaneously and calculate the individual phase and three-phase power values. The advantage of simultaneous sampling is the reduction of error introduced due to the difference in time when the samples were taken.
EPM 2200 POWER METER – INSTRUCTION MANUAL 1–5
POWER, ENERGY AND DEMAND CHAPTER 1: THREE-PHASE POWER MEASUREMENT
Phase B
Phase C
Phase A
A
B
C
N
Node "n"
Figure 1-6: Three-Phase Wye Load Illustrating Kirchoff’s Law and Blondel’s Theorem
Blondel's Theorem is a derivation that results from Kirchoff's Law. Kirchoff's Law states that the sum of the currents into a node is zero. Another way of stating the same thing is that the current into a node (connection point) must equal the current out of the node. The law can be applied to measuring three-phase loads. Figure 1.6 shows a typical connection of a three-phase load applied to a three-phase, four-wire service. Kirchoff's Law holds that the sum of currents A, B, C and N must equal zero or that the sum of currents into Node "n" must equal zero.
If we measure the currents in wires A, B and C, we then know the current in wire N by Kirchoff's Law and it is not necessary to measure it. This fact leads us to the conclusion of Blondel's Theorem- that we only need to measure the power in three of the four wires if they are connected by a common node. In the circuit of Figure 1.6 we must measure the power flow in three wires. This will require three voltage coils and three current coils (a three-element meter). Similar figures and conclusions could be reached for other circuit configurations involving Delta-connected loads.
1.5 Power, Energy and Demand
It is quite common to exchange power, energy and demand without differentiating between the three. Because this practice can lead to confusion, the differences between these three measurements will be discussed.
Power is an instantaneous reading. The power reading provided by a meter is the present flow of watts. Power is measured immediately just like current. In many digital meters, the power value is actually measured and calculated over a one second interval because it takes some amount of time to calculate the RMS values of voltage and current. But this time interval is kept small to preserve the instantaneous nature of power.
Energy is always based on some time increment; it is the integration of power over a defined time increment. Energy is an important value because almost all electric bills are based, in part, on the amount of energy used.
1–6 EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 1: THREE-PHASE POWER MEASUREMENT POWER, ENERGY AND DEMAND
0
10
20
30
40
50
60
70
80
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Time (minutes)
sttawolik
Typically, electrical energy is measured in units of kilowatt-hours (kWh). A kilowatt­hour represents a constant load of one thousand watts (one kilowatt) for one hour. Stated another way, if the power delivered (instantaneous watts) is measured as 1,000 watts and the load was served for a one hour time interval then the load would have absorbed one kilowatt-hour of energy. A different load may have a constant power requirement of 4,000 watts. If the load were served for one hour it would absorb four kWh. If the load were served for 15 minutes it would absorb ¼ of that total or one kWh.
Figure 1.7 shows a graph of power and the resulting energy that would be transmitted as a result of the illustrated power values. For this illustration, it is assumed that the power level is held constant for each minute when a measurement is taken. Each bar in the graph will represent the power load for the one-minute increment of time. In real life the power value moves almost constantly.
The data from Figure 1.7 is reproduced in Table 1.2 to illustrate the calculation of energy. Since the time increment of the measurement is one minute and since we specified that the load is constant over that minute, we can convert the power reading to an equivalent consumed energy reading by multiplying the power reading times 1/60 (converting the time base from minutes to hours).
Time Interval
EPM 2200 POWER METER – INSTRUCTION MANUAL 1–7
(minute)
Figure 1-7: Power Use over Time
Table 1.2: Power and Energy Relationship over Time
Power (kW) Energy (kWh) Accumulated Energy
(kWh)
1300.500.50
2500.831.33
3400.672.00
4550.922.92
5601.003.92
6601.004.92
POWER, ENERGY AND DEMAND CHAPTER 1: THREE-PHASE POWER MEASUREMENT
Table 1.2: Power and Energy Relationship over Time
Time Interval (minute)
7701.176.09
8701.177.26
9601.008.26 10 70 1.17 9.43 11 80 1.33 10.76 12 50 0.83 12.42 13 50 0.83 12.42 14 70 1.17 13.59 15 80 1.33 14.92
Power (kW) Energy (kWh) Accumulated Energy
(kWh)
As in Table 1.2, the accumulated energy for the power load profile of Figure 1.7 is
14.92 kWh.
Demand is also a time-based value. The demand is the average rate of energy use over time. The actual label for demand is kilowatt-hours/hour but this is normally reduced to kilowatts. This makes it easy to confuse demand with power, but demand is not an instantaneous value. To calculate demand it is necessary to accumulate the energy readings (as illustrated in Figure 1.7) and adjust the energy reading to an hourly value that constitutes the demand.
In the example, the accumulated energy is 14.92 kWh. But this measurement was made over a 15-minute interval. To convert the reading to a demand value, it must be normalized to a 60-minute interval. If the pattern were repeated for an additional three 15-minute intervals the total energy would be four times the measured value or
59.68 kWh. The same process is applied to calculate the 15-minute demand value. The demand value associated with the example load is 59.68 kWh/hr or 59.68 kWd. Note that the peak instantaneous value of power is 80 kW, significantly more than the demand value.
Figure 1.8 shows another example of energy and demand. In this case, each bar represents the energy consumed in a 15-minute interval. The energy use in each interval typically falls between 50 and 70 kWh. However, during two intervals the energy rises sharply and peaks at 100 kWh in interval number 7. This peak of usage will result in setting a high demand reading. For each interval shown the demand value would be four times the indicated energy reading. So interval 1 would have an associated demand of 240 kWh/hr. Interval 7 will have a demand value of 400 kWh/ hr. In the data shown, this is the peak demand value and would be the number that would set the demand charge on the utility bill.
1–8 EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 1: THREE-PHASE POWER MEASUREMENT REACTIVE ENERGY AND POWER FACTOR
0
20
40
60
80
100
12345678
Intervals (15 mins.)
sruoh-ttawolik
Figure 1-8: Energy Use and Demand
As can be seen from this example, it is important to recognize the relationships between power, energy and demand in order to control loads effectively or to monitor use correctly.
1.6 Reactive Energy and Power Factor
The real power and energy measurements discussed in the previous section relate to the quantities that are most used in electrical systems. But it is often not sufficient to only measure real power and energy. Reactive power is a critical component of the total power picture because almost all real-life applications have an impact on reactive power. Reactive power and power factor concepts relate to both load and generation applications. However, this discussion will be limited to analysis of reactive power and power factor as they relate to loads. To simplify the discussion, generation will not be considered.
Real power (and energy) is the component of power that is the combination of the voltage and the value of corresponding current that is directly in phase with the voltage. However, in actual practice the total current is almost never in phase with the voltage. Since the current is not in phase with the voltage, it is necessary to consider both the inphase component and the component that is at quadrature (angularly rotated 90o or perpendicular) to the voltage. Figure 1.9 shows a single-phase voltage and current and breaks the current into its in-phase and quadrature components.
EPM 2200 POWER METER – INSTRUCTION MANUAL 1–9
REACTIVE ENERGY AND POWER FACTOR CHAPTER 1: THREE-PHASE POWER MEASUREMENT
V
I
I
R
I
X
0
Figure 1-9: Voltage and Complex Current
The voltage (V) and the total current (I) can be combined to calculate the apparent power or VA. The voltage and the in-phase current (IR) are combined to produce the real power or watts. The voltage and the quadrature current (IX) are combined to calculate the reactive power.
The quadrature current may be lagging the voltage (as shown in Figure 1.9) or it may lead the voltage. When the quadrature current lags the voltage the load is requiring both real power (watts) and reactive power (VARs). When the quadrature current leads the voltage the load is requiring real power (watts) but is delivering reactive power (VARs) back into the system; that is VARs are flowing in the opposite direction of the real power flow.
Reactive power (VARs) is required in all power systems. Any equipment that uses magnetization to operate requires VARs. Usually the magnitude of VARs is relatively low compared to the real power quantities. Utilities have an interest in maintaining VAR requirements at the customer to a low value in order to maximize the return on plant invested to deliver energy. When lines are carrying VARs, they cannot carry as many watts. So keeping the VAR content low allows a line to carry its full capacity of watts. In order to encourage customers to keep VAR requirements low, some utilities impose a penalty if the VAR content of the load rises above a specified value.
A common method of measuring reactive power requirements is power factor. Power factor can be defined in two different ways. The more common method of calculating power factor is the ratio of the real power to the apparent power. This relationship is expressed in the following formula:
Total PF = real power / apparent power = watts/VA
This formula calculates a power factor quantity known as Total Power Factor. It is called Total PF because it is based on the ratios of the power delivered. The delivered power quantities will include the impacts of any existing harmonic content. If the voltage or current includes high levels of harmonic distortion the power values will be affected. By calculating power factor from the power values, the power factor will include the impact of harmonic distortion. In many cases this is the preferred method of calculation because the entire impact of the actual voltage and current are included.
1–10 EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 1: THREE-PHASE POWER MEASUREMENT HARMONIC DISTORTION
Displacement PF θcos=
Time
Amps
– 1000
– 500
0
500
1000
A second type of power factor is Displacement Power Factor. Displacement PF is based on the angular relationship between the voltage and current. Displacement power factor does not consider the magnitudes of voltage, current or power. It is solely based on the phase angle differences. As a result, it does not include the impact of harmonic distortion. Displacement power factor is calculated using the following equation:
where
θ is the angle between the voltage and the current (see Fig. 1.9).
In applications where the voltage and current are not distorted, the Total Power Factor will equal the Displacement Power Factor. But if harmonic distortion is present, the two power factors will not be equal.
1.7 Harmonic Distortion
Harmonic distortion is primarily the result of high concentrations of non-linear loads. Devices such as computer power supplies, variable speed drives and fluorescent light ballasts make current demands that do not match the sinusoidal waveform of AC electricity. As a result, the current waveform feeding these loads is periodic but not sinusoidal. Figure 1.10 shows a normal, sinusoidal current waveform. This example has no distortion.
Figure 1.11 shows a current waveform with a slight amount of harmonic distortion. The waveform is still periodic and is fluctuating at the normal 60 Hz frequency. However, the waveform is not a smooth sinusoidal form as seen in Figure 1.10.
EPM 2200 POWER METER – INSTRUCTION MANUAL 1–11
Figure 1-10: Nondistorted Current Waveform
HARMONIC DISTORTION CHAPTER 1: THREE-PHASE POWER MEASUREMENT
1000
500
0
500
1000
t
)s
p
m a(
tner
r u C
a
2a
–1500
1500
Time
Amps
3rd harmonic
5th harmonic
7th harmonic
Total
fundamental
– 500
0
500
1000
Figure 1-11: Distorted Current Waveform
The distortion observed in Figure 1.11 can be modeled as the sum of several sinusoidal waveforms of frequencies that are multiples of the fundamental 60 Hz frequency. This modeling is performed by mathematically disassembling the distorted waveform into a collection of higher frequency waveforms.
These higher frequency waveforms are referred to as harmonics. Figure 1.12 shows the content of the harmonic frequencies that make up the distortion portion of the waveform in Figure 1.11.
The waveforms shown in Figure 1.12 are not smoothed but do provide an indication of
1–12 EPM 2200 POWER METER – INSTRUCTION MANUAL
the impact of combining multiple harmonic frequencies together.
When harmonics are present it is important to remember that these quantities are operating at higher frequencies. Therefore, they do not always respond in the same manner as 60 Hz values.
Figure 1-12: Waveforms of the Harmonics
CHAPTER 1: THREE-PHASE POWER MEASUREMENT POWER QUALITY
Inductive and capacitive impedance are present in all power systems. We are accustomed to thinking about these impedances as they perform at 60 Hz. However, these impedances are subject to frequency variation.
XL = jwL and
XC = 1/jwC
At 60 Hz, w = 377; but at 300 Hz (5th harmonic) w = 1,885. As frequency changes impedance changes and system impedance characteristics that are normal at 60 Hz may behave entirely differently in the presence of higher order harmonic waveforms.
Traditionally, the most common harmonics have been the low order, odd frequencies, such as the 3rd, 5th, 7th, and 9th. However newer, non-linear loads are introducing significant quantities of higher order harmonics.
Since much voltage monitoring and almost all current monitoring is performed using instrument transformers, the higher order harmonics are often not visible. Instrument transformers are designed to pass 60 Hz quantities with high accuracy. These devices, when designed for accuracy at low frequency, do not pass high frequencies with high accuracy; at frequencies above about 1200 Hz they pass almost no information. So when instrument transformers are used, they effectively filter out higher frequency harmonic distortion making it impossible to see.
1.8 Power Quality
However, when monitors can be connected directly to the measured circuit (such as direct connection to a 480 volt bus) the user may often see higher order harmonic distortion. An important rule in any harmonics study is to evaluate the type of equipment and connections before drawing a conclusion. Not being able to see harmonic distortion is not the same as not having harmonic distortion.
It is common in advanced meters to perform a function commonly referred to as waveform capture. Waveform capture is the ability of a meter to capture a present picture of the voltage or current waveform for viewing and harmonic analysis. Typically a waveform capture will be one or two cycles in duration and can be viewed as the actual waveform, as a spectral view of the harmonic content, or a tabular view showing the magnitude and phase shift of each harmonic value. Data collected with waveform capture is typically not saved to memory. Waveform capture is a real-time data collection event.
Waveform capture should not be confused with waveform recording that is used to record multiple cycles of all voltage and current waveforms in response to a transient condition.
Power quality can mean several different things. The terms “power quality” and “power quality problem” have been applied to all types of conditions. A simple definition of “power quality problem” is any voltage, current or frequency deviation that results in mis-operation or failure of customer equipment or systems. The causes of power quality problems vary widely and may originate in the customer equipment, in an adjacent customer facility or with the utility.
EPM 2200 POWER METER – INSTRUCTION MANUAL 1–13
POWER QUALITY CHAPTER 1: THREE-PHASE POWER MEASUREMENT
In his book Power Quality Primer, Barry Kennedy provided information on different types of power quality problems. Some of that information is summarized in Table 1.3.
Table 1.3: Typical Power Quality Problems and Sources
Cause Disturbance Type Source
Impulse transient Transient voltage disturbance,
sub-cycle duration
Oscillatory transient with decay
Sag/swell RMS voltage, multiple cycle
Interruptions RMS voltage, multiple
Under voltage/over voltage
Voltage flicker RMS voltage, steady state,
Harmonic distortion Steady state current or voltage,
Transient voltage, sub-cycle duration
duration
seconds or longer duration
RMS voltage, steady state, multiple seconds or longer duration
repetitive condition
long-term duration
Lightning Electrostatic discharge Load switching Capacitor switching
Line/cable switching Capacitor switching Load switching
Remote system faults
System protection Circuit breakers Fuses Maintenance
Motor starting Load variations Load dropping
Intermittent loads Motor starting Arc furnaces
Non-linear loads System resonance
It is often assumed that power quality problems originate with the utility. While it is true that power quality problems can originate with the utility system, many problems originate with customer equipment. Customer-caused problems may manifest themselves inside the customer location or they may be transported by the utility system to another adjacent customer. Often, equipment that is sensitive to power quality problems may in fact also be the cause of the problem.
If a power quality problem is suspected, it is generally wise to consult a power quality professional for assistance in defining the cause and possible solutions to the problem.
1–14 EPM 2200 POWER METER – INSTRUCTION MANUAL
GE
Grid Solutions
Note
EPM 2200 Power Meter
Chapter 2: Overview and
Specifications
Overview and Specifications
In European Union member state countries, this meter is NOT certified for revenue metering. See the Safety Precautions section for meter certification details.
2.1 Hardware Overview
The EPM 2200 multifunction power meters is designed for use with and/or within Industrial Control Panels in electrical substations, panel boards, and as a power meter for OEM equipment. EPM 2200 meters provide multifunction measurement of all electrical parameters.
The EPM 2200 monitor is a 0.5% class electrical panel meter. Using bright and large 0.56” LED displays, it is designed to be used in electrical panels and switchgear. The meter has a unique anti-dither algorithm to improve reading stability. The EPM 2200 meter uses high­speed DSP technology with high-resolution A/D conversion to provide stable and reliable measurements. UL 61010-1 does not address performance criteria for revenue generating watt-hour meters for use in metering of utilities and/or communicating directly with utilities, or use within a substation. Use in revenue metering, communicating with utilities, and use in substations was verified according to the ANSI and IEC standards listed in the Compliance Section (2.3).
The EPM 2200 meter is a meter and transducer in one compact unit. Featuring an optional RS485 port, it can be programmed using the faceplate of the meter or through software. ANSI or DIN mounting may be used.
EPM 2200 meter features that are detailed in this manual are as follows:
0.5% Class Accuracy
Multifunction Measurement including Voltage, Current, Power, Frequency, Energy, etc.
Percentage of Load Bar for Analog Meter Perception
Easy to Use Faceplate Programming
One Communication Option:
• RS485 Modbus/KYZ output (Option S)
EPM 2200 POWER METER – INSTRUCTION MANUAL 2–1
HARDWARE OVERVIEW CHAPTER 2: OVERVIEW AND SPECIFICATIONS
• BACnet MS/TP Serial Multifunction Meter with Modbus TCP/IP Internet (Option B)
2.1.1 Voltage and Current Inputs
Universal Voltage Inputs
Voltage Inputs allow measurement to 416 Volts Line-to-Neutral and 721 Volts Line-to-Line. One unit will perform to specification when directly connected to 69 Volt, 120 Volt, 230 Volt, 277 Volt, 277 Volt and 347 Volt power systems.
Current Inputs
The EPM 2200 meter Current Inputs use a unique dual input method:
Method 1: CT Pass Through
The CT passes directly through the meter without any physical termination on the meter. This insures that the meter cannot be a point of failure on the CT circuit. This is preferable for utility users when sharing relay class CTs.
Method 2: Current “Gills”
This unit additionally provides ultra-rugged Termination Pass Through Bars that allow CT leads to be terminated on the meter. This, too, eliminates any possible point of failure at the meter. This is a preferred technique for insuring that relay class CT integrity is not compromised (the CT will not open in a fault condition).
2.1.2 Order Codes
The order codes for the EPM 2200 are indicated below.
Table 2–1: EPM 2200 Order Codes
PL2200
Base Unit PL2200 Enclosure Option ENC120 | | NEMA1 Rated - Indoor, Single Meter Enclosure, 120V
Software Option*
Communications Option
* – * – *
|||
EPM 2200 Meter
ENC277 | | NEMA1 Rated - Indoor, Single Meter Enclosure, 277V
A1 | B1 | C1 |
BN |
Volts and Amps Meter Volts, Amps, Power and Frequency Meter Volts, Amps, Power, Frequency and Energy Counters Meter BACnet Volts, Amps, Power, Frequency and Energy Counters
meter RS485 Serial/KYZ Pulse
S
None
X
BACnet MS/TP Serial and Modbus TCP/IP Internet
B
* Software Options are only available with Communications Option S.
For example, to order an EPM 2200 to measure Volts, Amps, Power & Frequency, with Modbus/KYZ output communications, use PL2200-XXXXXX-B1-S.
Accessories available for the EPM 2200 are indicated below.
2–2 EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 2: OVERVIEW AND SPECIFICATIONS HARDWARE OVERVIEW
Table 2–2: EPM 2200 Accessory Order Codes
PL2200
DIN Bracket PL2200
*
ACC
*
EPM 2200 Meter DIN Mounting Bracket
DIN
2.1.3 Measured Values
The following table lists the measured values available in real time, average, maximum, and minimum.
Table 2–3: EPM 2200 Measured Values
Measured Values Real Time Average Maximum Minimum
Voltage L-N XXX
Voltage L-L XXX
Current per phase XXXX
Current Neutral X
Watts XXXX
VARs XXXX
VA XXXX
Power Factor (PF) XXXX
Positive watt-hours X
Negative watt-hours X
Net watt-hours X
Positive VAR-hours X
Negative VAR-hours X
Net VAR-hours X
VA-hours X
Frequency XXX
Voltage angles X
Current angles X
% of load bar X
2.1.4 Utility Peak Demand
The EPM 2200 provides user-configured Block (fixed) window, or Rolling window demand. This feature allows you to set up a customized demand profile. Block window demand is demand used over a user-configured demand period (usually 5, 15, or 30 minutes). Rolling
EPM 2200 POWER METER – INSTRUCTION MANUAL 2–3
SPECIFICATIONS CHAPTER 2: OVERVIEW AND SPECIFICATIONS
window demand is a fixed window demand that moves for a user-specified subinterval period. For example, a 15-minute demand using 3 subintervals and providing a new demand reading every 5 minutes, based on the last 15 minutes.
Utility demand features can be used to calculate kW, kVAR, kVA and PF readings. All other parameters offer maximum and minimum capability over the user-selectable averaging period. Voltage provides an instantaneous maximum and minimum reading which displays the highest surge and lowest sag seen by the meter.
2.2 Specifications
POWER SUPPLY
Range:.................................................Universal, (90 to 265) VAC @50/60Hz
Power consumption: ....................5 VA, 3.5 W
VOLTAGE INPUTS (MEASUREMENT CATEGORY III)
Range:.................................................Universal, Auto-ranging up to 416 V AC L-N, 721 V AC L-L
Supported hookups:.....................3-element Wye, 2.5-element Wye,
2-element Delta, 4-wire Delta
Input impedance: ..........................1 MOhm/phase
Burden:...............................................0.0144 VA/phase at 120 Volts
Pickup voltage:................................10 V AC
Connection: ......................................Screw terminal
Maximum input wire gauge: ...AWG #12 / 2.5 mm
Fault withstand:..............................Meets IEEE C37.90.1
Reading:.............................................Programmable full-scale to any PT ratio
CURRENT INPUTS
Class 10:.............................................5 A nominal, 10 A maximum
Burden:...............................................0.005 VA per phase maximum at 11 A
Pickup current:................................0.1% of nominal
Connections:....................................O or U lug;
Pass-through wire, 0.177" / 4.5 mm maximum diameter
Quick connect, 0.25" male tab
Fault Withstand (at 23°C):..........100 A / 10 seconds, 300 A / 3 seconds, 500 A / 1 second
Reading:.............................................Programmable full-scale to any CT ratio
ISOLATION
All Inputs and Outputs are galvanically isolated to 2500 V AC
ENVIRONMENTAL
Storage:..............................................–20 to 70°C
Operating: .........................................-20 to 70°C
Humidity:...........................................up to 95% RH, non-condensing
Faceplate rating:............................NEMA 12 (water resistant), mounting gasket included
METER ENCLOSURE ENVIRONMENTAL
Storage:..............................................–20 to 70°C
Operating: .........................................-10 to 50°C
Humidity:...........................................up to 95% RH, non-condensing
Faceplate rating:............................NEMA 1 (Indoor Use)
Pollution degree.............................II
Overvoltage Category.................III (this product is designed for indoor use only)
MEASUREMENT METHODS
Voltage and current: ....................True RMS
Power: .................................................Sampling at 400+ samples/cycle on all channels measured; readings
simultaneously
A/D conversion: ..............................6 simultaneous 24-bit analog-to-digital converters
2
2–4 EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 2: OVERVIEW AND SPECIFICATIONS SPECIFICATIONS
UPDATE RATE
All parameters:...............................Up to 1 second
COMMUNICATIONS FORMAT
Types: ................................................. RS485 port through back plate plus KYZ Pulse (Com Option S)
RS485 serial port and RJ45 Ethernet port through backplate (Com Option B)
COMMUNICATIONS PORTS
Protocols:.......................................... Modbus RTU, Modbus ASCII (Com Option S)
Modbus TCP/IP, BACnet MS/TP Serial (Com Option B)
Baud rate:.........................................9600 to 57600 bps
Port address:................................... 001 to 247
Data format:....................................8 bits, no parity
MECHANICAL PARAMETERS
Dimensions:..................................... 4.25" × 4.85" × 4.85" (L × W × H)
105.4 mm × 123.2 mm × 123.2 mm (L × W × H)
Mounting:.......................................... mounts in 92 mm square DIN or ANSI C39.1, 4-inch round cut-out
Weight:............................................... 2 pounds / 0.907 kg
METER ENCLOSURE MECHANICAL PARAMETERS
Dimensions:..................................... 8.08" × 11.06" × 13.50" (L × W × H)
205.23 mm × 280.92 mm × 342.9 mm (L × W × H)
Weight:............................................... 25 pounds / 11.4 kg
KYZ/RS485 PORT SPECIFICATIONS
RS485 Transceiver; meets or exceeds EIA/TIA-485 Standard:
Type: .................................................. Two-wire, half duplex
Min. Input Impedance: ............... 96k
Max. Output Current: .................. ±60mA
EPM 2200 POWER METER – INSTRUCTION MANUAL 2–5
SPECIFICATIONS CHAPTER 2: OVERVIEW AND SPECIFICATIONS
WH PULSE
KYZ output contacts (and infrared LED light pulses through face plate):
Pulse Width: ....................................40ms
Full Scale Frequency: ..................6Hz
Contact type: ..................................Solid State – SPDT (NO – C – NC)
Relay type: .......................................Solid state
Peak switching voltage: .............DC ±350V
Continuous load current: ..........120mA
Peak load current: ........................350mA for 10ms
On resistance, max.: ....................35
Leakage current: ...........................1μA@350V
Isolation: ...........................................AC 3750V
Reset State: ......................................(NC - C) Closed; (NO - C) Open
Infrared LED:
Peak Spectral Wavelength: ......940nm
Reset State: ......................................Off
Figure 2-1: Internal Schematic (De-energized State)
2–6 EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 2: OVERVIEW AND SPECIFICATIONS SPECIFICATIONS
Figure 2-2: Output Timing
EPM 2200 POWER METER – INSTRUCTION MANUAL 2–7
COMPLIANCE CHAPTER 2: OVERVIEW AND SPECIFICATIONS
2.3 Compliance
Test Reference Standard
IEC62053-22 (0.5% Accuracy)
ANSI C12.20 (0.5% Accuracy)
CE Compliant
REACH Compliant
RoHS Compliant
Surge Withstand ANSI (IEEE) C37.90.1
Burst ANSI C62.41
Electrostatic Discharge IEC61000-4-2
RF Immunity IEC61000-4-3
Fast Transient IEC61000-4-4
Surge Immunity IEC61000-4-5
Conducted Disturbance Immunity IEC61000-4-6
Magnetic Field Immunity IEC61000-4-8
Voltage Dips and Sags Immunity IEC61000-4-11
Immunity for Industrial Environments EN61000-6-2
Emission Standards for Industrial
EN61000-6-4
Environments
EMC Requirements EN61326-1
APPROVALS
Applicable Council Directive According to:
North America UL Recognized
ISO Manufactured under a registered
quality program
UL61010-1 C22.2. No 61010-1 (PICQ7) File e200431
ISO9001
2–8 EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 2: OVERVIEW AND SPECIFICATIONS ACCURACY
NOTE
2.4 Accuracy
For 23 °C, 3 Phase balanced Wye or Delta load.
Parameter Accuracy Accuracy Input Range
Voltage L-N [V] 0.2% of reading Voltage L-L [V] 0.4% of reading (120 to 600)V Current Phase [A] 0.2% of reading Current Neutral (calculated)
2% of Full Scale
[A] Active Power Total [W] 0.5% of reading Active Energy Total [Wh] 0.5% of reading Reactive Power Total [VAR] 1.0% of reading Reactive Energy Total [VARh] 1.0% of reading Apparent Power Total [VA] 1.0% of reading Apparent Energy Total [VAh] 1.0% of reading Power Factor 1.0% of reading Frequency +/- 0.01Hz (45 to 65)Hz Load Bar +/- 1 segment
1
For 2.5 element programmed units, degrade accuracy by an additional 0.5% of reading.
2
For unbalanced voltage inputs where at least one crosses the 150V auto-scale threshold
(for example, 120V/120V/208V system), degrade accuracy by additional 0.4%.
2
(69 to 480)V
1
(0.15 to 5)A
1
(0.15 to 5)A @ (45 to 65)Hz
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0 to 0.8) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0 to 0.8) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
1
(0.005 to 6)A
EPM 2200 accuracy meets the IEC62053-22 Accuracy Standards for 0.5% Class Meters. This standard is shown in the table below.
Value of Current Power Factor Percentage Error Limits for
0.01 I
n I < 0. 05 In 1 ±1.0
0.05 I
n I Imax 1 ±0.5
0.02 I
n I < 0.1 In 0.5 inductive
0.8 capacitive
0.1 I
n I Imax 0.5 inductive
0.8 capacitive
When specially requested by the user, from:
0.1 I
n I Imax
Note
In the table above:
I
n = Nominal (5A) max = Full Scale
I
0.25 inductive
0.8 capacitive
Meters of Class 0.5 S
±1.0 ±1.0
±0.6 ±0.6
±1.0 ±1.0
EPM 2200 POWER METER – INSTRUCTION MANUAL 2–9
ACCURACY CHAPTER 2: OVERVIEW AND SPECIFICATIONS
2–10 EPM 2200 POWER METER – INSTRUCTION MANUAL
Loading...
+ 86 hidden pages