GE Multilin 3 Series Manual

LISTED
GE
Grid Solutions
Multilin
from M & MII Family, 239, 735/737, MLJ, & TOV relays
3 Series Retrofits
TM
Retrofit Guide
3 Series version: 2.3x
*1601-0380-A2*
Copyright © 2017 GE Multilin Inc. All rights reserved.
3 Series Retrofit Guide.
3 Series Retrofit is a registered trademark of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin Inc. The content of this manual is for informational use only and is subject to change without notice.
Part numbers contained in this manual are subject to change without notice, and should therefore be verified by GE Multilin Inc. before ordering.
Part number: 1601-0380-A2 (September 2017)
For further assistance
For product support, contact the information and call center as follows:
GE Grid Solutions
650 Markland Street Markham, Ontario Canada L6C 0M1 Worldwide telephone: +1 905 927 7070 Europe/Middle East/Africa telephone: +34 94 485 88 54 North America toll-free: 1 800 547 8629 Fax: +1 905 927 5098 Worldwide e-mail: multilin.tech@ge.com Europe e-mail: multilin.tech.euro@ge.com Website: http://www.gegridsolutions.com/multilin
ii
Safety words and definitions
NOTE
The following symbols used in this document indicate the following conditions:
Note
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Note
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Note
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Note
Indicates practices not related to personal injury.
Indicates general information and practices, including operational information and practices, that are not related to personal injury.
General Cautions and Warnings
The following general safety precautions and warnings apply.
Note
Note
Disassembly of this unit will void the warranty. Do not attempt to open or repair the retrofit enclosure. All repairs are to be conducted by the factory.
Before attempting to use the equipment, it is important that all danger and caution indicators are reviewed.
If the equipment is used in a manner not specified by the manufacturer or functions abnormally, proceed with caution. Otherwise, the protection provided by the equipment may be impaired and can result in impaired operation and injury.
Note
Note
Hazardous voltages can cause shock, burns or death.
Installation/service personnel must be familiar with general device test practices, electrical awareness and safety precautions must be followed.
Before performing visual inspections, tests, or periodic maintenance on this device or associated circuits, isolate or disconnect all hazardous live circuits and sources of electric power.
Failure to shut equipment off prior to removing the power connections could expose you to dangerous voltages causing injury or death.
Ensure that all connections to the product are correct to avoid accidental risk of shock and/or fire, for example from high voltage connected to low voltage terminals.
Follow the requirements of this manual, including adequate wiring size and type, terminal torque settings, voltage, current magnitudes applied, and adequate isolation/ clearance in external wiring from high to low voltage circuits.
Use the device only for its intended purpose and application.
iii
Ensure that all ground paths are un-compromised for safety purposes during device operation and service.
All recommended equipment should be grounded and must have a reliable and un­compromised grounding path for safety purposes, protection against electromagnetic interference and proper device operation.
Equipment grounds should be bonded together and connected to the facility’s main ground system for primary power.
Keep all ground leads as short as possible.
In addition to the safety precautions mentioned all electrical connections made must respect the applicable local jurisdiction electrical code.
It is recommended that a field external switch, circuit breaker be connected near the equipment as a means of power disconnect. The external switch or circuit breaker is selected in accordance with the power rating.
Ensure that the control power applied to the device, the AC current, and voltage input match the ratings specified on the relay nameplate. Do not apply current or voltage in excess of the specified limits.
Only qualified personnel are able to operate the device. Such personnel must be thoroughly familiar with all safety cautions and warnings in this manual and with applicable country, regional, utility, and plant safety regulations.
Hazardous voltages can exist in the power supply and at the device connection to current transformers, voltage transformers, control, and test circuit terminals. Make sure all sources of such voltages are isolated prior to attempting work on the device.
Hazardous voltages can exist when opening the secondary circuits of live current transformers. Make sure that current transformer secondary circuits are shorted out before making or removing any connection to the current transformer (CT) input terminals of the device.
For tests with secondary test equipment, ensure that no other sources of voltages or currents are connected to such equipment and that trip and close commands to the circuit breakers or other switching apparatus are isolated, unless this is required by the test procedure and is specified by appropriate utility/plant procedure.
When the device is used to control primary equipment, such as circuit breakers, isolators, and other switching apparatus, all control circuits from the device to the primary equipment must be isolated while personnel are working on or around this primary equipment to prevent any inadvertent command from this device.
Use external disconnect equipment to isolate the mains voltage supply.
Note
To ensure the settings file inside the relay is updated, wait 30 seconds after a setpoint change before cycling power.
Note
This product is rated to Class A emissions levels and is to be used in Utility, Substation Industrial environments. Not to be used near electronic devices rated for Class B levels.
iv
Table of Contents
1: OVERVIEW INTRODUCTION ................................................................................................................................ 1
MIF AND MIF II RELAYS .................................................................................................................. 3
MIV AND MIV II RELAYS ................................................................................................................. 5
MIG AND MIG II RELAYS ................................................................................................................ 7
MIN AND MIN II RELAYS ................................................................................................................ 11
MIW AND MIW II RELAYS .............................................................................................................. 13
239 RELAYS ........................................................................................................................................15
735/737 RELAYS ............................................................................................................................... 17
MLJ AND TOV RELAYS .................................................................................................................... 19
FINDING YOUR M AND MII FAMILY RELAY ORDER CODE ............................................... 21
2: CONVERTING SETTINGS FILES
3: INSTALLING THE 3 SERIES RELAY
4: ELECTRICAL INSTALLATION
DOWNLOADING AND SAVING MIF II OR MIV II SETPOINT FILES ................................. 24
CONVERTING A SAVED MIF II OR MIV II SETPOINT FILE .................................................. 25
CONVERSION REPORT ................................................................................................................... 27
LOADING SETPOINTS FROM A FILE .......................................................................................... 28
CONVERTING MIN II 67IG1 TO 350 32N ................................................................................ 29
3 SERIES DIMENSIONS AND MOUNTING ............................................................................... 34
M AND MII FAMILY RELAYS .......................................................................................................... 36
239 DIMENSIONS ............................................................................................................................. 43
735/737 DIMENSIONS AND 350 RETROFIT MOUNT ......................................................... 44
MLJ AND TOV DIMENSIONS AND MOUNTING .................................................................... 46
P40 AGILE DIMENSIONS ............................................................................................................... 49
350 WIRING ........................................................................................................................................ 52
345 WIRING ........................................................................................................................................ 53
339 WIRING ........................................................................................................................................ 54
MIF II WIRING ..................................................................................................................................... 56
MIV II WIRING .................................................................................................................................... 57
MIF II/MIV II TO 350 RETROFIT WIRING .................................................................................. 58
239 WIRING ........................................................................................................................................ 62
735/737 WIRING .............................................................................................................................. 65
A: APPENDIX WARRANTY ......................................................................................................................................... 67
CHANGE NOTES ................................................................................................................................ 67
3 SERIES RETROFIT – INSTRUCTION MANUAL v
3 SERIES RETROFIT – INSTRUCTION MANUAL vi
GE
Grid Solutions
3 Series Retrofit
Chapter 1: Overview
Overview
1.1 Introduction
As the Multilin MII Family, Multilin 239, and Multilin 735/737 digital relays age, the Multilin
Series (SR3) family of protection relays provide updated functional and economical
3 protection solutions for feeders, motors and transformers. The 3 the 350, 345, and 339, provide extensive diagnostic information allowing users to troubleshoot and minimize downtime. 3 simplify engineering tasks such as configuration, wiring, testing, commissioning, and maintenance.
The MultilinTM 3 Series Retrofit Instruction Manual offers a solution to upgrade previously installed Multilin relays, providing detailed order code equivalencies, mechanical details, and wiring diagrams. For common MII Family Digital relays a software conversion tool provides conversion of existing settings files and Modbus Maps. This manual also provides retrofit suggestions for Multilin M Family, MLJ, and TOV relays in less detail.
Series relays streamline work flow processes and
Series family, including
3 SERIES RETROFIT – INSTRUCTION MANUAL 1
INTRODUCTION CHAPTER 1: OVERVIEW
The MultilinTM 3 Series Retrofit takes place in four general steps, as follows.
1. Select a replacement relay - see the summary tables and the specific order code comparisons for the MII Family relays shown in this chapter. If you need to determine your MII relay order code, refer to section
1.10 Finding your M and MII Family relay
order code.
2. Convert the existing settings file if applicable; MIF II, and MIV II file conversion is currently supported for most models - see Chapter 2:
Converting Settings F iles.
3. Install the new 3 Series Retrofit - see Chapter 3: Installing the 3 Series Relay.
4. Wire the new 3 Series Retrofit - see Chapter 4: Electrical Installation.
3 Series relays have an IP54 rating, superior to that of the MII Family relays which have an IP52 rating. In addition, vibration tests for 3
Series relays have been passed for both the 4­screw mount (as used in the MII Family retrofit) and 8-screw mount (as used for new installations).
2 3 SERIES RETROFIT – INSTRUCTION MANUAL
CHAPTER 1: OVERVIEW MIF AND MIF II RELAYS
NOTE
1.2 MIF and MIF II relays
Installed Relay Retrofit Relay
MIFII Digital Feeder Relay MIF Digital Feeder Relay
MIF and MIF II features are available in 350 relays as described in the table below:
Feature MIF MIF II
Protection &
Control
Monitoring &
Metering
Oscillography 8 samples/cycle
Communications Serial (RS232, RS485)
Hardware 2 digital inputs
1. For additional features, refer to the 350 Instruction Manual.
Thermal Overload: 49, IOC: 50PH, 50PL, 50GH, 50GL, 50NH, 50NL TOC: 51G, 51N, 51P
Cold Load Pickup: CLP Breaker Failure: 50BF
Breaker Health Event Recording
maximum length 24 cycles
protocols: Modbus RTU
6 relay outputs Configurable I/O Configurable Logic 4 configurable LEDs 2 fixed LEDs
Thermal Overload: 49(1) IOC: 50P (2), 50G(2)
TOC: 51G(1), 51P(1)
Autoreclose: 79 Cold Load Pickup: CLP Breaker Failure to Open
Breaker Health Event Recording
8 samples/cycle maximum length 24 cycles
Serial (RS232, RS485) protocols: Modbus RTU, IEC 60870-5­103
2 digital inputs 6 digital outputs Configurable I/O Configurable Logic 4 configurable LEDs 2 fixed LEDs
350 Feeder Protection System
350
Thermal Overload: 49 IOC: 50P(2), 50N(2), 50_2, 50G/SG(2)
TOC: 51P, 51N, 51_2, 51G/SG Other protection: 67G/SG, 32N, VTFF, 27_1, 27X, 59X, 67P, 67N, 46BC, 32, 27P, 59P, 59_2, 59N, 81U(2), 81O(2), Arc Flash
Autoreclose: 79 Cold Load Pickup: CLP Breaker Failure: 50BF
Other control: 60CTS, 86, 25
Breaker Health Event Recording
up to 32 samples per cycle (user-selectable) maximum length 192 cycles
USB Serial (RS485) protocols: Modbus RTU, DNP 3.0, IEC 60870-5-103 Ethernet protocols: Modbus TCP/IP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE, IEC 61850, OPC-UA
10 inputs 7 outputs (2 Form A, 5 Form C) Configurable I/O Configurable Logic 10 LEDs (non-programmable LEDs) 12 LEDs (programmable LEDs)
1
The following table describes MIF and MIF II options, and the equivalent 350 options and order codes. In some cases the 350 options have changed from those available for MIF and MIF II relays, so read the descriptions carefully.
Note
Order codes are subject to change without notice. See the GE Multilin website at: http://
www.gegridsolutions.com/multilin for up-to-date order codes.
3 SERIES RETROFIT – INSTRUCTION MANUAL 3
MIF AND MIF II RELAYS CHAPTER 1: OVERVIEW
Feature MIF order code options MIF II order code options 350 order code options
Application MIF-P-A11E100F00C
MIFII-P-A11E00HI00
All 350 relays come with 3 phase
and ground standard. P: 3 Phase and Ground N: Single Phase
Curves MIFP-A-11E100F00C
P: 3 Phase and Ground N: Single Phase
MIFIIP-A-11E00HI00
All 350 relays come with ANSI, IEC,
and IAC curves standard. A: ANSI Curves I: IEC Curves U: IAC Curves C: EPTAR-C Curves (single phase only)
Phase CT Range MIFPA-1-1100F00C
A: ANSI Curves I: IEC Curves U: IAC Curves C: EPTAR-C Curves (single phase only)
MIFIIPA-1-1E00HI00
350E-P0-G0HEENNSNNN
Ground CT
0: N models (single phase) 1: Phase CT = 1 A (0.1 - 2.4 A) 5: Phase CT = 5 A (0.5 - 12 A)
MIFPA1-1-E100F00C
0: Phase CT = 1/5 A 1: Phase CT = 1 A 5: Phase CT = 5 A
MIFIIPA1-1-E00HI00
Range
1: Ground CT In = 1 A (0.1 - 2.4 A) 5: Ground CT In = 5 A (0.5 - 12 A) N: Sensitive Ground (0.005 - 0.12 A)
1: Ground CT In = 1 A (0.1 - 2.4 A) 5: Ground CT In = 5 A (0.5 - 12 A) L: Extremely Sensitive Ground In = 1 A (0.002 - 0.048 A) N: Sensitive Ground (0.005 - 0.12 A)
Language All MIF relays come with English
MIFIIPA11-E-00HI00
standard.
E: English F: French T: Turkish
Options MIFPA11E-1-00F00C
0: Basic Model () 1: Option 1 (Configurable I/O, Event Recording, and Oscillography) 2: Option 2 (Option 1 and Cold Load Pickup, Breaker Failure Protection, Breaker Health, and Configurable Logic)
MIFIIPA11E-0-0HI00
0: Basic Model () 1: Option 1 (Event Recording, Oscillography, Configurable I/O and LEDs) 2: Option 2 (Option 1 and Cold Load Pickup, Breaker Failure Protection, Breaker Health, Configurable Logic, and Circuit Breaker Control)
Recloser n/a MIFIIPA11E0-0-HI00
0: without Recloser R: with Recloser
Power Supply MIFPA11E100-F-00C
MIFIIPA11E00-HI-00
P0: user selectable 1/5 A three-
phase current inputs (0.02 - 20 × CT)
350EP0-G0-HEENNSNNN
G0: user selectable 1/5 A Ground
current input (0.02 - 20 × CT)
S0: user selectable 1/5 A Sensitive
Ground current input (0.002 - 3 × CT)
All 350 relays come with English
standard.
350EP0G0HEE-N-NSNNN
N: CLP, Lockout (86)
C: CLP, 50BF, Autoreclose (79)
All 350 relays come with Event
Recording, Oscillography,
Configurable I/O and LEDs,
Configurable Logic (up to 16),
Breaker Health, and Circuit Breaker
Control standard.
1
350EP0G0HEE-N-NSNNN
N: CLP, Lockout (86)
C: CLP, 50BF, Autoreclose (79)
350EP0G0-H-EENNSNNN
H: 110 - 250 VDC (Range: 88~300 VDC) 110 - 230 VAC (Range: 88~264 VAC) F: 24 - 48 VDC (Range: 19~58 VDC)
Protocol All MIF relays come with Modbus
RTU standard.
Environmental
n/a MIFIIPA11E00HI0-0
Option
1. Some features are implemented or configured somewhat differently in the 350 relay. See the 350 Instruction Manual for details.
2. For details of 350 communications implementation, see the 3 Series Communications Guide.
4 3 SERIES RETROFIT – INSTRUCTION MANUAL
HI: 110 - 250 VDC (Range: 88~300 VDC) 110 - 230 VAC (Range: 88~264 VAC) LO: 28 - 48 VDC (Range: 19~58 VDC)
MIFIIPA11E00HI-0-0
0: Standard model (Modbus RTU) C: IEC60870-5-103 with 2 Comms ports
0: None H: Conformal Coating
H: 110 - 250 VDC
110 - 230 VAC
L: 28 - 48 VDC
350EP0G0HEENN-SN-NN
SN: Standard: Front USB, Rear
RS485: Modbus RTU, DNP3.0,
IEC60870-5-103
2
350EP0G0HEENNSNN-N
N: None
H: Harsh Environment Conformal
Coating
CHAPTER 1: OVERVIEW MIV AND MIV II RELAYS
1.3 MIV and MIV II relays
Installed Relay Retrofit Relay
MIV II Voltage/Frequency Relay MIV Voltage/Frequency Relay
MIV and MIV II features are available in 350 relays as described in the table below:
350 Feeder Protection System
Feature MIV MIV II
Protection &
Control
Oscillography 8 samples/cycle
CommunicationsSerial (RS232, RS485)
Hardware 2 digital outputs
1. For additional features, refer to the 350 Instruction Manual.
UV: 27(2) OV: 59(2), 59N(2) Underfrequency: 81U(2) Overfrequency: 81O(2) Phase reversal: 47(1)
maximum length 24 cycles
protocols: Modbus RTU
6 relay outputs Configurable I/O Configurable Logic 2 fixed LEDs 4 configurable LEDs
UV: 27P(4) OV: 59P(4), 59N(4) Underfrequency: 81U(4) Overfrequency: 81O(4) Phase reversal: 47(1)
Note: the number of elements differs for different MIV II options. Maximum numbers are shown.
MIV 1000 & 3000: 8 samples/cycle maximum length 24 cycles
MIV 2000: 2 samples per cycle maximum length 432 cycles
Serial (RS232, RS485) protocols: Modbus RTU
2 digital inputs 6 digital outputs Configurable I/O Configurable Logic 2 fixed LEDs 4 configurable LEDs
1
350
UV: 27P(4), 27X(1), 27P_1(1) OV: 59P(4), 59N(4), 59X(1), 59_2(2) Underfrequency: 81U(4) Overfrequency: 81O(4)
Other Protection: 25(1), VTFF(1),
Volt/Hz
24(1)
up to 32 samples per cycle (user-selectable) maximum length 192 cycles
USB Serial (RS485) protocols: Modbus RTU, DNP 3.0, IEC 60870-5-103 Ethernet protocols: Modbus TCP/IP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE, IEC 61850, OPC-UA
10 inputs 7 outputs (2 Form A, 5 Form C) Configurable I/O Configurable Logic 10 LEDs (non-programmable LEDs) 12 LEDs (programmable LEDs)
3 SERIES RETROFIT – INSTRUCTION MANUAL 5
MIV AND MIV II RELAYS CHAPTER 1: OVERVIEW
The following table describes MIV II options, and the equivalent 350 options and order codes. In some cases the 350 options have changed from those available for MIV II relays, so read the descriptions carefully.
Feature MIV order code options MIV II order code options 350 order code options
Function MIV-1-000E000F00C
MIVII-1-010E00HI00
350E-PXGX-HE-N-N-V-SNNN
1: Voltage Functions 2: Frequency Functions 3: Voltage and Frequency Function
Voltage Range MIV10-0-0E000F00C
0: 10 - 250 V Setting Range 1: 2 - 60 V Setting Range
Language All MIV relays come with English
standard.
Power Supply MIV1000E000-F-00C
H: 110 - 250 VDC (Range: 88~300 VDC) 110 - 230 VAC (Range: 88~264 VAC) F: 24 - 48 VDC (Range: 19~58 VDC)
Environmental
n/a MIVII1010E00HI-00
Option
Note
Order codes are subject to change without notice. See the GE Multilin website at: http://
www.gegridsolutions.com/multilin for up-to-date order codes.
1: Voltage Functions 2: Frequency Functions 3: Voltage and Frequency Function
MIVII10-1-0E00HI00
0: 10 - 250 V Setting Range 1: 2 - 60 V Setting Range
MIVII1010-E-00HI00
E: English F: French T: Turkish
MIVII1010E00-HI-00
HI: 110 - 250 VDC (Range: 88~300 VDC) 110 - 230 VAC (Range: 88~264 VAC) LO: 28 - 48 VDC (Range: 19~58 VDC)
00: None 0H: Conformal Coating
V: Voltage Metering - 27P(4), 27X(1),
27P_1(1), 59P(4), 59N(4), 59X(1),
59_2(2), 81O(4), 81U(4), 25(1), VTFF(1)
All 350 models with the VT module:
Primary VT range: 0.15 to 550kV
VT Secondary range: 50 to 220V
All 350 relays come with English
standard.
350EPXGX-H-ENNVSNNN
H: 110 - 250 VDC
110 - 230 VAC
L: 28 - 48 VDC
350EPXGXHENNVSNN-N
N: None
H: Harsh Environment Conformal
Coating
6 3 SERIES RETROFIT – INSTRUCTION MANUAL
CHAPTER 1: OVERVIEW MIG AND MIG II RELAYS
NOTE
1.4 MIG and MIG II relays
Installed Relay
MIG II Generator Protection System MIG Machine Protection Relay
Retrofit Relay
350 Feeder Protection System, 345 Transformer Protection System, 339 Motor Protection System, 850 Feeder Protection System, or P40 Agile P14D Relay
Most MIG and MIG II features are available in 350, 345, or 339 relays as described in the tables below. In some cases an 8 Series or P40 Agile relay may be required to replace full functionality. For additional information, refer to the P40 Technical Manual or
850
Instruction Manual.
1.4.1 MIG and MIG II P to 350 or 345
For the MIG II P being used as a transformer, when 87R is not required, the 350 relay is an option. When 87R is required, the 345 relay with 87G is an option.
For the MIG II P being used as a generator, the 350 relay is an option.
Note
Feature MIG MIG II P
Protection &
Control
Current Unbalance: 46
Thermal Protection: 49 IOC: 50P, 50G, 51G TOC: 51P Undercurrent: 37 66 Restricted Ground Differential: 87R
The 350 Feeder Protection System does not support Restricted Ground Differential 87R. To replace MIG and MIG II P relays when Restricted Ground Fault protection is required, the 345 relay with 87G can be used. a P40 Agile P14D relay or 850 Feeder Protection System can also be used.
Current Unbalance: 46
Thermal Protection: 49 IOC: 50N, 50P, 50G TOC: 51G, 51N, 51P
Restricted Ground Differential: 87R
1
350
Current unbalance: 51_2 or 46(1), 50_2 (1) or 46(1) Thermal Protection: 49 IOC: 50P(2), 50G/SG(2), 50N(2), TOC: 51P(1), 51G/SG(1), 51N(1),
Other Protection: I1/I2(46BC)
2
345
Current unbalance: 51_2 or 46(1), 50_2 (1) or 46(1) Thermal Protection: 49 IOC: 50P(2), 50G/SG(2), 50N(2), TOC: 51P(1), 51G/SG(1), 51N(1),
Restricted Ground Fault: 87G/RGF(2)
3 SERIES RETROFIT – INSTRUCTION MANUAL 7
MIG AND MIG II RELAYS CHAPTER 1: OVERVIEW
Feature MIG MIG II P
Metering & Monitoring
Oscillography 8 samples/cycle
Communications Serial (RS232, RS485)
Hardware 2 digital outputs
1. For additional features, refer to the 350 Instruction Manual.
2. For additional features, refer to the 345 Instruction Manual.
Metering Event Recording
maximum length 24 cycles
protocols: Modbus RTU
6 relay outputs Configurable I/O Configurable Logic 2 fixed LEDs 4 configurable LEDs
Metering Event Recording
8 samples/cycle maximum length 24 cycles
Serial (RS232, RS485) protocols: Modbus RTU
2 digital inputs 6 digital outputs Configurable I/O Configurable Logic 2 fixed LEDs 4 configurable LEDs
The following table describes MIG II P options, and the equivalent 350 and 345 options and order codes. In some cases the 350/345 options have changed from those available for MIG II relays, so read the descriptions carefully.
1
350
Metering Event Recording
up to 32 samples per cycle (user-selectable) maximum length 192 cycles
USB Serial (RS485) protocols: Modbus RTU, DNP 3.0, IEC 60870-5-103 Ethernet protocols: Modbus TCP/IP, DNP 3.0, IEC 60870-5­104, IEC 61850 GOOSE, IEC 61850, OPC-UA
10 inputs 7 outputs (2 Form A, 5 Form C) Configurable I/O Configurable Logic 10 LEDs (non-programmable LEDs) 12 LEDs (programmable LEDs)
2
345
Metering Event Recording
up to 32 samples per cycle (user-selectable) maximum length 192 cycles
USB Serial (RS485) protocols: Modbus RTU, DNP 3.0, IEC 60870-5-103 Ethernet protocols: Modbus TCP/IP, DNP 3.0, IEC 60870-5­104, IEC 61850 GOOSE, IEC 61850, OPC-UA
10 inputs 7 outputs (2 Form A, 5 Form C) Configurable I/O Configurable Logic 10 LEDs (non-programmable LEDs) 12 LEDs (programmable LEDs)
Feature MIG order code options MIG II P order code options 350/345 order code options
Application n/a MIGII-P-A11E00HI00
P: Generator Protection Elements
350EP0G0HE-M-NNSNNN
M: Advanced configuration: User
selectable 49, 50P(2), 50G/SG(2),
50N(2), 51P(1), 51G/SG(1), 51N(1),
51_2 or 46(1), 50_2 (1) or 46(1), I1/
I2(46BC)
345EP0G0HE-M-NNSNNN
M: Advanced configuration: 87T,
87T-50, 51P(2), 51N(2), 51G(2),
50P(2), 50G(2), 50N(2), 49P, 46 (51_2/
50_2)(2), 86, 50BF(2), 87G/RGF(2)
Curves MIGP-A-11E000F00C
MIGIIP-A-11E00HI00
All 350 and 345 relays come with
ANSI, IEC, and IAC curves standard. A: ANSI Curves I: IEC Curves
Phase CT Range MIGPA-1-1E000F00C
1: Phase CT = 1 A (0.1 - 2.4 A) 5: Phase CT = 5 A (0.5 - 12 A)
A: ANSI Curves I: IEC Curves
MIFIIPA-1-1E00HI00
0: Phase CT = 1/5 A 1: Phase CT = 1 A
3xxE-P0-G0HEMNNSNNN
P0: P0 user selectable 1/5 A three-
phase current inputs
5: Phase CT = 5 A
Ground CT
MIGPA1-1-E000F00C
MIGIIPA1-1-E00HI00
3xxEP0-G0-HEMNNSNNN
Range
1: Ground CT In = 1 A (0.1 - 2.4 A) 5: Ground CT In = 5 A (0.5 - 12 A) N: Sensitive Ground CT In = 1 A (0.005 - 0.12 A)
1: Ground CT In = 1 A (0.1 - 2.4 A) 5: Ground CT In = 5 A (0.5 - 12 A) N: Sensitive Ground (0.005 - 0.12 A)
G0: user selectable 1/5 A Ground
current input (0.02 - 20 × CT)
S0: user selectable 1/5 A Sensitive
Ground current input (0.002 - 3 × CT)
8 3 SERIES RETROFIT – INSTRUCTION MANUAL
CHAPTER 1: OVERVIEW MIG AND MIG II RELAYS
NOTE
Feature MIG order code options MIG II P order code options 350/345 order code options
Power Supply MIGPA11E000-F-00C
MIGIIPA11E00-HI-00
3xxEP0G0-H-EENNSNNN
H: 110 - 250 VDC (Range: 88~300 VDC) 110 - 230 VAC (Range: 88~264 VAC) F: 24 - 48 VDC (Range: 19~58 VDC)
Note
Order codes are subject to change without notice. See the GE Multilin website at: http://
HI: 110 - 250 VDC (Range: 88~300 VDC) 110 - 230 VAC (Range: 88~264 VAC) LO: 28 - 48 VDC (Range: 19~58 VDC)
www.gegridsolutions.com/multilin for up-to-date order codes.
1.4.2 MIG and MIG II Q to 339
Feature MIG MIG II Q
Protection &
Control
Metering & Monitoring
Oscillography 8 samples/cycle maximum length
Communications Serial (RS232, RS485)
Hardware 2 digital outputs
1. For additional features, refer to the 339 Instruction Manual.
Current Unbalance: 46
Thermal Protection: 49 IOC: 50P, 50G, 51G TOC: 51P Undercurrent: 37 66 Restricted Ground Differential: 87R
24 cycles
protocols: Modbus RTU
6 relay outputs Configurable I/O Configurable Logic 2 fixed LEDs 4 configurable LEDs
Current Unbalance: 46 Acceleration Time: 48 Thermal Protection: 49 IOC: 50N, 50P, 50G TOC: 51G, 51N, 51P Undercurrent: 37 66
Metering Event Recording
8 samples/cycle maximum length 24 cycles
Serial (RS232, RS485) protocols: Modbus RTU
2 digital inputs 6 digital outputs Configurable I/O Configurable Logic 2 fixed LEDs 4 configurable LEDs
H: 110 - 250 VDC 110 - 230 VAC L: 28 - 48 VDC
1
339
Current Unbalance: 46 Acceleration Time: 48 Thermal Protection: 49 IOC: 50G/SG(1), 50L, 50N(1), 50P(1) TOC: 51N(1), 51P(1), 51R Undercurrent: 37 66
Other Protection: 86, 50BF
Metering Event Recording
up to 32 samples per cycle (user-selectable) maximum length 192 cycles
USB Serial (RS485) protocols: Modbus RTU, DNP 3.0, IEC 60870-5-103 Ethernet protocols: Modbus TCP/IP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE, IEC 61850
10 inputs 7 outputs (2 Form A, 5 Form C) Configurable I/O Configurable Logic 10 LEDs (non-programmable LEDs) 12 LEDs (programmable LEDs)
3 SERIES RETROFIT – INSTRUCTION MANUAL 9
MIG AND MIG II RELAYS CHAPTER 1: OVERVIEW
NOTE
The following table describes MIG and MIG II Q options, and the equivalent 339 options and order codes. In some cases the 339 options have changed from those available for MIG and MIG II relays, so read the descriptions carefully.
Feature MIG order code options MIG II Q order code options 339 order code options
Application n/a MIGII-Q-A11E00HI00
339EP0G0HE-S-NNSNNN
Curves MIGP-A-11E000F00C
A: ANSI Curves I: IEC Curves
Phase CT Range MIGPA-1-1E000F00C
1: Phase CT = 1 A (0.1 - 2.4 A) 5: Phase CT = 5 A (0.5 - 12 A)
Ground CT
MIGPA1-1-E000F00C
Range
1: Ground CT In = 1 A (0.1 - 2.4 A) 5: Ground CT In = 5 A (0.5 - 12 A) N: Sensitive Ground CT In = 1 A (0.005 - 0.12 A)
Power Supply MIFPA111-F-C
H: 110 - 250 VDC (Range: 88~300 VDC) 110 - 230 VAC (Range: 88~264 VAC) F: 24 - 48 VDC (Range: 19~58 VDC)
Note
Order codes are subject to change without notice. See the GE Multilin website at: http://
www.gegridsolutions.com/multilin for up-to-date order codes.
Q: Motor Protection Elements
MIGIIQ-A-11E00HI00
A: ANSI Curves I: IEC Curves
MIGIIQA-1-1E00HI00
1: Phase CT = 1 A (0.1 - 2.4 A) 5: Phase CT = 5 A (0.5 - 12 A)
MIGIIQA1-1-E00HI00
1: Ground CT In = 1 A (0.1 - 2.4 A) 5: Ground CT In = 5 A (0.5 - 12 A) N: Sensitive Ground CT In = 1 A (0.005 - 0.12 A)
MIFIIQA11E00-HI-00
HI: 110 - 250 VDC (Range: 88~300 VDC) 110 - 230 VAC (Range: 88~264 VAC) LO: 28 - 48 VDC (Range: 19~58 VDC)
S: Standard configuration: 37, 46,
48, 49, 50P(1), 50G/SG(1), 50N(1),
50L,51R, 66, 86, 51N(1), 51P(1), 50BF
All 339 relays come with ANSI, IEC,
and IAC curves standard.
339E-P0-G0HESNNSNNN
P0: user selectable 1/5 A three-
phase current inputs (0.02 - 20 × CT)
339EP0-G0-HESNNSNNN
G0: user selectable 1/5 A Ground
current input (0.02 - 20 × CT)
All 339 relays come with CBCT
(50:0.025) standard.
339EP1G1-H-ESNNSNNN
H: 110 - 250 VDC
110 - 230 VAC
L: 28 - 48 VDC
10 3 SERIES RETROFIT – INSTRUCTION MANUAL
CHAPTER 1: OVERVIEW MIN AND MIN II RELAYS
1.5 MIN and MIN II relays
Installed Relay Retrofit Relay
MIN II Ground Protection System MIN Digital Ground Protection
Most MIN and MIN II features are available in 350 relays as described in the table below:
350 Feeder Protection System, or P40 Agile Relay
Feature MIN
Protection &
Control
Metering & Monitoring
Oscillography 8 samples/cycle
Communications Serial (RS232, RS485)
Hardware 2 digital outputs
1. For a detailed example of converting the MIN II Option "S" 67IG1 function to the 350 32N function, see Converting MIN II 67IG1 to 350 32N on page 29.
2. For additional features, refer to the 350 Instruction Manual.
Directional: 67N1, 67N2 IOC: 50GH, 50GL TOC: 51GH, 51GL Cold Load Pickup: CLP Breaker Failure: 50BF
Metering Breaker Health Event Recording
maximum length 24 cycles
protocols: Modbus RTU
6 relay outputs Configurable I/O Configurable Logic 2 fixed LEDs 4 configurable LEDs
67G1, 67G2, 67PC1, 67PC2 50G1, 50G2 51G1, 51G2
Metering
Event Recorder
8 samples/cycle maximum length 24 cycles
Serial (RS232, RS485) protocols: Modbus RTU
2 digital inputs 6 digital outputs Configurable I/O Configurable Logic 2 fixed LEDs 4 configurable LEDs
MIN II
1
Directional: 67P(1), 67N(1), 67G/SG(1) IOC: 50P(2), 50N(2), 50_2, 50G/SG(2) TOC: 51P(1), 51G/SG(1), 51N(1) Cold Load Pickup: CLP Breaker Failure: 50BF
Other: 49, 32N(2), VTFF + Voltage, Power, and Energy Metering, 60CTS
Metering Breaker Health Event Recording
up to 32 samples per cycle (user-selectable) maximum length 192 cycles
USB Serial (RS485) protocols: Modbus RTU, DNP 3.0, IEC 60870-5-103 Ethernet protocols: Modbus TCP/IP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE, IEC 61850, OPC-UA
10 inputs 7 outputs (2 Form A, 5 Form C) Configurable I/O Configurable Logic 10 LEDs (non-programmable LEDs) 12 LEDs (programmable LEDs)
350
2
3 SERIES RETROFIT – INSTRUCTION MANUAL 11
MIN AND MIN II RELAYS CHAPTER 1: OVERVIEW
NOTE
The following table describes MIN and MIN II options, and the equivalent 350 options and order codes. In some cases the 350 options have changed from those available for MIN and MIN II relays, so read the descriptions carefully.
Feature MIN order code options MIN II order code options 350 order code options
Function MIN-N-A0E000H00C
MINII-N-A0EE00HI00
350EP0G0HE-E-N-R-SNNN
N: Ground directional relay L1: Ground directional relay for teleprotection schemes
N: Ground directional relay L: Ground directional relay for teleprotection schemes
Current Protection E: Extended configuration: User selectable 49, 50P(2), 50G/SG(2), 50N(2), 51P(1), 51G/SG(1), 51N(1)
Other Options R: Phase, Neutral, and Ground Directional Overcurrent Protection: 67P(1), 67N(1), 67G/SG(1), 32N(2), VTFF + Voltage, Power, and Energy Metering, 60CTS
Curves MINN-A-0E000H00C
A: ANSI Curves I: IEC Curves
MINIIN-A-0EE00HI00
A: ANSI Curves
All 350 relays come with ANSI, IEC, and IAC curves standard.
I: IEC Curves
Ground CT
MINNA0-E-000H00C
MINIINA0-E-E00HI00
350EP0-G0-HEENRSNNN
Range
E: Ground CT In = 1 A or 5 A (10­240% of CT rating) S2: Isolated ground and Peterson coil
Power Supply MINNA0E000-H-00C
H: 110 - 250 VDC (Range: 88~300 VDC) 110 - 230 VAC (Range: 88~264 VAC) F: 24 - 48 VDC (Range: 19~58 VDC)
Environmental
n/a MINIINA0EE00HI-00
E: Ground CT In = 1 A or 5 A (10­240% of CT rating) S2: Isolated ground3 and Peterson coil
MINIINA0EE00-HI-00
HI: 110 - 250 VDC (Range: 88~300 VDC) 110 - 230 VAC (Range: 88~264 VAC) LO: 28 - 48 VDC (Range: 19~58 VDC)
G0: user selectable 1/5 A Ground current input (0.02 - 20 × CT) S0: user selectable 1/5 A Sensitive Ground current input (0.002 - 3 × CT)
350EP0G0-H-EENRSNNN
H: 110 - 250 VDC 110 - 230 VAC L: 28 - 48 VDC
350EP0G0HEENRSNN-N
Option
00: None 0H: Conformal Coating
N: None H: Harsh Environment Conformal Coating
1. Option L is not available in the 3 Series.
2. Option S is not directly replaced in the 350 Feeder Protection System, however the Wattmetric Ground Fault element (32N) is a substitute for MINII option S and detects feeder/line ground faults in solidly grounded, ungrounded, resistance grounded and res onance grounded networks. It provides equivalent functionality to the Isolated Ground and Petersen Coil elements of the MIN II relay. Option S directional ground fault for Isolated or Peterson Coil grounded networks may also be replaced by P40 Agile P14D relays. The P40 Agile P14D relay uses different algorithms to achieve more accurate High Impedance Fault detection; refer to the
P14D
Technical Manual, Chapter 6, Section 18.
3. For a detailed example of converting the MIN II Option "S" 67IG1 Isolated Ground function to the 350 32N function, see Converting MIN II 67IG1 to 350 32N on page 29.
-
Note
Order codes are subject to change without notice. See the GE Multilin website at: http://
www.gegridsolutions.com/multilin for up-to-date order codes.
12 3 SERIES RETROFIT – INSTRUCTION MANUAL
CHAPTER 1: OVERVIEW MIW AND MIW II RELAYS
1.6 MIW and MIW II relays
Installed Relay Retrofit Relay
MIW II Directional Power Protection System 350 Feeder Protection System or 889 Generator Protection System
Most MIW and MIW II features are available in 350 relays as described in the table below. In some cases an 8 Series relay may be required to replace full functionality.
Feature MIW MIW II
Protection &
Control
Metering & Monitoring
Oscillography 8 samples/cycle
Communications Serial (RS232, RS485)
Hardware 2 digital outputs
1. For additional features, refer to the 350 Instruction Manual.
Directional Power: 32RP, 32FP, 32LF 40 60
maximum length 24 cycles
protocols: Modbus RTU
6 relay outputs Configurable I/O Configurable Logic 2 fixed LEDs 4 configurable LEDs
Directional Power: 32(4) 40 60
Metering Event Recording Configurable IO and LEDs Configurable Logic
8 samples/cycle maximum length 24 cycles
Serial (RS232, RS485) protocols: Modbus RTU
2 digital inputs 6 digital outputs Configurable I/O Configurable Logic 2 fixed LEDs 4 configurable LEDs
1
350
Directional Power: 32(2)
Other Protection: 27P(2), 27X(1), 27P_1 (1), 59P(2), 59N(1), 59X(1), 59_2(1), 81O(2), 81U(2), 67P(1), 67N(1), 67G/SG(1), VTFF(1), 25(1), 60CTS
Metering Breaker Health Event Recording Programmable Logic Elements ...
up to 32 samples per cycle (user-selectable) maximum length 192 cycles
USB Serial (RS485) protocols: Modbus RTU, DNP 3.0, IEC 60870-5-103 Ethernet protocols: Modbus TCP/IP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE, IEC 61850, OPC-UA
10 inputs 7 outputs (2 Form A, 5 Form C) Configurable I/O Configurable Logic 10 LEDs (non-programmable LEDs) 12 LEDs (programmable LEDs)
3 SERIES RETROFIT – INSTRUCTION MANUAL 13
MIW AND MIW II RELAYS CHAPTER 1: OVERVIEW
NOTE
The following table describes MIW and MIW II options, and the equivalent 350 options and order codes. In some cases the 350 options have changed from those available for MIW and MIW II relays, so read the descriptions carefully.
Feature MIW order code options MIW II order code options 350 order code options
Function n/a MIWII-1-000E00HI00
350EP0G0HEEN-W-SNNN
11: 3x Directional Power, 1x Loss of Field, 1x Fuse Failure 2: 4x Directional Power
W: Advanced Protection: 27P(2), 27X(1), 27P_1 (1), 59P(2), 59N(1), 59X(1), 59_2(1), 81O(2), 81U(2), 67P(1), 67N(1), 67G/SG(1), VTFF(1), 25(1), 60CTS, 32(2)
Power Supply MIW1000E000-F-00C
H: 110 - 250 VDC (Range: 88~300 VDC) 110 - 230 VAC (Range: 88~264 VAC) F: 24 - 48 VDC (Range: 19~58 VDC)
1. To replace model MIW II 1000 and the Loss of Excitation protection function, refer to the 889 Instruction Manual.
Note
Order codes are subject to change without notice. See the GE Multilin website at: http://
MIWII1000E00-HI-00
HI: 110 - 250 VDC (Range: 88~300 VDC) 110 - 230 VAC (Range: 88~264 VAC) LO: 28 - 48 VDC (Range: 19~58 VDC)
350EP0G0-H-EENWSNNN
H: 110 - 250 VDC 110 - 230 VAC L: 28 - 48 VDC
www.gegridsolutions.com/multilin for up-to-date order codes.
14 3 SERIES RETROFIT – INSTRUCTION MANUAL
CHAPTER 1: OVERVIEW 239 RELAYS
1.7 239 relays
Installed Relay Retrofit Relay
239 Motor Protection Relay 339 Motor Protection System
239 features are available in 339 relays as described in the table below:
Feature
Protection &
Control
Monitoring &
Metering
Communications RS485 port USB
Hardware 2 inputs and 3 fixed inputs.
1. The 239 relay with MOD 509 is designed to provide ground directional protection. Similar pro­tection can be obtained using the 339 relay neutral instantaneous protection using either the current, voltage, or both.
2. For additional features, refer to the 339 Instruction Manual.
Undercurrent/minimum load: 37 Motor/load bearing, Overtemperature: 38 Mechanical jam:39 Current unbalance: 46
Stator winding overtemperature: 49 Phase short circuit: 50 Timed overload: 51 Ground fault instantaneous or definite time: 50G/50N
Alarm relay: 74 Lockout and trip relay: 86/94
Metering Event Recording
4 Form C contacts 6 Fixed LEDs
239
1
Undercurrent: 37
Current Unbalance: 46 Acceleration Time: 48 Thermal Protection: 49 IOC: 50G/SG(1), 50L, 50N(1), 50P(1) TOC: 51N(1), 51P(1), 51R
Other Protection: 66, 86, 50BF
Metering Event Recording
Serial (RS485) protocols: Modbus RTU, DNP 3.0, IEC 60870-5-103 Ethernet protocols: Modbus TCP/IP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE, IEC 61850
10 inputs 7 outputs (2 Form A, 5 Form C) Configurable I/O Configurable Logic 8 configurable and 4 fixed LEDs 10 fixed LED (drawout unit) 12 fixed LEDs (non-drawout unit)
339
2
3 SERIES RETROFIT – INSTRUCTION MANUAL 15
239 RELAYS CHAPTER 1: OVERVIEW
NOTE
The following table describes 239 options, and the equivalent 339 options and order codes. In some cases the 339 options have changed from those available for 239 relays, so read the descriptions carefully.
Note
Order codes are subject to change without notice. See the GE Multilin website at: http://
www.gegridsolutions.com/multilin for up-to-date order codes.
Feature 239 order code options 339 order code options
Application 239RTD-AN-H
AN: Single isolated, analog output: 0 – 1, 0 – 20, 4 – 20 mA Programmable output parameters: thermal capacity,% full load, phase current, RTD1, RTD2, RTD3 temperature
Phase CT
239 standard phase CT Input:
Range
1 A and 5 A secondary Range: 0.1 to 11 x phase CT primary
Ground CT
239 standard ground CT input:
Range
5 A secondary and 50:0.025 Range:
0.03 to 1.4 x CT primary (5 A CT)
0.05 to 16.0 A (50:0.025 CT)
Power
Supply
239 standard power supply: 90 – 300 VDC or 70 – 265 VAC, 50 / 60 Hz
Harsh
239RTDAN-H
Environment
H: Harsh Environment Conformal Coating
RTDs 239-RTD-ANH
3 RTDs: stator/bearing; programmable type: platinum, nickel, copper
339EP0G0HE-S-NNSNNH
S: Standard configuration: 37, 46, 48, 49, 50P(1), 50G/SG(1), 50N(1), 50L,51R, 66, 86, 51N(1), 51P(1), 50BF
339E-P0-G0HESNNSNNH
P0: user selectable 1/5 A three-phase current inputs (0.02 - 20 × CT)
339EP0-G0-HESNNSNNH
G0: user selectable 1/5 A Ground current input (0.02 - 20 × CT)
All 339 relays come with CBCT (50:0.025) standard.
339EP1G1-H-ESNNSNNH
H: 110 - 250 VDC 110 - 230 VAC L: 28 - 48 VDC
339EP1G1HESNNSNN-H
H: Harsh Environment Conformal Coating
The 339 can support 3 - 100 ohm Pt RTDs. The RMIO module supports up to 12 - 100 ohm Pt RTDs.
16 3 SERIES RETROFIT – INSTRUCTION MANUAL
CHAPTER 1: OVERVIEW 735/737 RELAYS
1.8 735/737 relays
Installed Relay Retrofit Relay
735/737Feeder Protection System 350 Feeder Protection System
735 and 737 features are available in 350 relays as described in the table below.
Feature 735/737
Protection &
Control
Metering & Monitoring
Communications RS485 2-wire communications
Hardware 8 LED trip indicators
1. For additional features, refer to the 350 Instruction Manual.
50/51, 50G/51G 50P(2), 50G/SG(2), 50N(2), 51P(1),
Current Metering shown in % Metering
or RS422 4-wire communications
4 LED status indicators 3 standard outputs
737 has 8 additional output relays to provide separate dry contact outputs for each overcurrent protection element.
1
350
51G/SG(1), 51N(1)
User selectable 49, 86
Breaker Health Event Recording Programmable Logic Elements ...
USB Serial (RS485) protocols: Modbus RTU, DNP 3.0, IEC 60870-5-103 Ethernet protocols: Modbus TCP/IP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE, IEC 61850, OPC-UA
10 inputs 7 outputs (2 Form A, 5 Form C) Configurable I/O Configurable Logic 8 configurable and 4 fixed LEDs 10 fixed LED (drawout unit) 12 fixed LEDs (non-drawout unit)
3 SERIES RETROFIT – INSTRUCTION MANUAL 17
Loading...
+ 51 hidden pages