1Chapter Overview313
2Introduction to the Scheme Logic314
3Fixed Scheme Logic316
3.1Any Start Logic317
3.2VTS Acceleration Indication Logic318
3.3CB Fail SEF Protection Logic318
3.4CB Fail Non Current Protection Logic319
3.5Composite Earth Fault Start Logic320
3.6Any Trip Logic320
3.7SEF Any Start Logic320
4Programmable Scheme Logic321
viiiP747-TM-EN-1
MiCOM P747Contents
P747-TM-EN-1.1
4.1Viewing and Printing PSL Diagrams321
4.2Trip Output Mappings322
4.3Opto-Input Mappings323
4.4Output Relay Mappings324
4.5LED Mappings325
4.6Control Input Mappings325
4.7Function Key Mappings325
4.8Circuit Breaker Mapping326
4.9Fault Record Trigger Mapping326
4.10Check Synchronisation and Voltage Monitor Mappings326
4.11Settings326
Chapter 13Installation329
1Chapter Overview331
2Handling the Goods332
2.1Receipt of the Goods332
2.2Unpacking the Goods332
2.3Storing the Goods332
2.4Dismantling the Goods332
3Mounting the Device333
3.1Flush Panel Mounting333
3.2Rack Mounting334
4Cables and Connectors336
4.1Terminal Blocks336
4.2Power Supply Connections337
4.3Earth Connnection337
4.4Current Transformers337
4.5Voltage Transformer Connections338
4.6Watchdog Connections338
4.7EIA(RS)485 and K-Bus Connections338
4.8IRIG-B Connection338
4.9Opto-input Connections338
4.10Output Relay Connections338
4.11Ethernet Metallic Connections339
4.12Ethernet Fibre Connections339
4.13RS232 connection339
4.14Download/Monitor Port339
4.15GPS Fibre Connection339
4.16Fibre Communication Connections339
5Case Dimensions340
5.1Case Dimensions 80TE340
Chapter 14Commissioning Instructions341
1Chapter Overview343
2General Guidelines344
3Commissioning Test Menu345
3.1Opto I/P Status Cell (Opto-input Status)345
3.2Relay O/P Status Cell (Relay Output Status)345
3.3Test Mode Cell345
3.4Test Pattern Cell346
3.5Contact Test Cell346
3.6Test LEDs Cell346
3.7Red and Green LED Status Cells346
3.8PSL Verificiation346
3.8.1Test Port Status Cell346
P747-TM-EN-1ix
ContentsMiCOM P747
P747-TM-EN-1.1
3.8.2Monitor Bit 1 to 8 Cells346
3.8.3Using a Monitor Port Test Box347
4Commissioning Equipment348
4.1Minimum Equipment Required348
4.2Optional Equipment Required348
5Product Checks349
5.1Product Checks with the IED De-energised349
5.1.1Visual Inspection350
5.1.2Current Transformer Shorting Contacts350
5.1.3Insulation350
5.1.4External Wiring351
5.1.5Watchdog Contacts351
5.1.6Power Supply351
5.2Product Checks with the IED Energised351
5.2.1Watchdog Contacts352
5.2.2Test LCD352
5.2.3Date and Time352
5.2.4Test LEDs353
5.2.5Test Alarm and Out-of-Service LEDs353
5.2.6Test Trip LED353
5.2.7Test User-programmable LEDs353
5.2.8Test Opto-inputs353
5.2.9Test Output Relays354
5.2.10Test Serial Communication Port RP1354
5.2.11Test Serial Communication Port RP2356
5.2.12Test Ethernet Communication356
5.2.13Test Current Inputs356
5.2.14Test Voltage Inputs357
6Setting Checks358
6.1Apply Application-specific Settings358
6.1.1Transferring Settings from a Settings File358
6.1.2Entering settings using the HMI358
7Busbar Protection Checks360
7.1Busbar Differential Protection Checks360
7.2Connecting the Test Circuit360
7.3Performing the Test360
7.4Check the Operating Time361
8Onload Checks362
8.1Confirm Current Connections362
8.2Confirm Voltage Connections362
8.3On-Load Busbar Differential Test363
9Final Checks364
10Commissioning Test Settings365
Chapter 15Maintenance and Troubleshooting367
1Chapter Overview369
2Maintenance370
2.1Maintenance Checks370
2.1.1Alarms370
2.1.2Opto-isolators370
2.1.3Output Relays370
2.1.4Measurement Accuracy370
2.2Replacing the Device371
2.3Repairing the Device372
2.4Removing the front panel373
2.5Replacing PCBs373
2.5.1Replacing the main processor board374
xP747-TM-EN-1
MiCOM P747Contents
P747-TM-EN-1.1
2.5.2Replacement of communications boards374
2.5.3Replacement of the input module375
2.5.4Replacement of the power supply board376
2.5.5Replacement of the I/O boards376
2.6Recalibration376
2.7Changing the battery377
2.7.1Post Modification Tests377
2.7.2Battery Disposal377
2.8Cleaning377
3Troubleshooting378
3.1Self-Diagnostic Software378
3.2Power-up Errors378
3.3Error Message or Code on Power-up378
3.4Out of Service LED on at power-up379
3.5Error Code during Operation380
3.5.1Backup Battery380
3.6Mal-operation during testing380
3.6.1Failure of Output Contacts380
3.6.2Failure of Opto-inputs380
3.6.3Incorrect Analogue Signals381
3.7PSL Editor Troubleshooting381
3.7.1Diagram Reconstruction381
3.7.2PSL Version Check381
4Repair and Modification Procedure382
Chapter 16Technical Specifications383
1Chapter Overview385
2Interfaces386
2.1Front Serial Port386
2.2Download/Monitor Port386
2.3Rear Serial Port 1386
2.4Fibre Rear Serial Port 1386
2.5Rear Serial Port 2387
2.6Redundant Ethernet Ports387
2.7IRIG-B (Demodulated)387
2.8IRIG-B (Modulated)387
2.9Rear Ethernet Port Copper388
2.10Rear Ethernet Port Fibre388
2.10.1100 Base FX Receiver Characteristics388
2.10.2100 Base FX Transmitter Characteristics389
3Busbar Protection Functions390
3.1Busbar Circuitry Fault Protection390
3.2Busbar Circuitry Fault Protection390
3.3Busbar Dead Zone Protection390
3.4Three-phase Overcurrent Protection390
3.5Earth Fault Protection391
3.6Transient Overreach and Overshoot391
4Performance of Monitoring and Control Functions392
4.1Voltage Transformer Supervision392
4.2PSL Timers392
5Measurements and Recording393
5.1General393
5.2Disturbance Records393
5.3Event, Fault and Maintenance Records393
5.4Fault Locator393
6Standards Compliance394
P747-TM-EN-1xi
ContentsMiCOM P747
P747-TM-EN-1.1
6.1EMC Compliance: 2004/108/EC394
6.2Product Safety: 2006/95/EC394
6.3R&TTE Compliance394
6.4UL/CUL Compliance394
7Mechanical Specifications395
7.1Physical Parameters395
7.2Enclosure Protection395
7.3Mechanical Robustness395
7.4Transit Packaging Performance395
8Ratings396
8.1AC Measuring Inputs396
8.2Current Transformer Inputs396
8.3Voltage Transformer Inputs396
8.4Auxiliary Supply Voltage396
8.5Nominal Burden397
8.6Power Supply Interruption397
8.7Standard Output Contacts398
8.8Watchdog Contacts398
8.9Isolated Digital Inputs399
8.9.1Nominal Pickup and Reset Thresholds399
9Environmental Conditions400
9.1Ambient Temperature Range400
9.2Ambient Humidity Range400
9.3Corrosive Environments400
10Type Tests401
10.1Insulation401
10.2Creepage Distances and Clearances401
10.3High Voltage (Dielectric) Withstand401
10.4Impulse Voltage Withstand Test401
11Electromagnetic Compatibility402
11.11 MHz Burst High Frequency Disturbance Test402
11.2Damped Oscillatory Test402
11.3Immunity to Electrostatic Discharge402
11.4Electrical Fast Transient or Burst Requirements402
11.5Surge Withstand Capability402
11.6Surge Immunity Test403
11.7Immunity to Radiated Electromagnetic Energy403
11.8Radiated Immunity from Digital Communications403
11.9Radiated Immunity from Digital Radio Telephones403
11.10Immunity to Conducted Disturbances Induced by Radio Frequency Fields403
11.11Magnetic Field Immunity404
11.12Conducted Emissions404
11.13Radiated Emissions404
11.14Power Frequency404
Appendix A Symbols and Glossary405
1Chapter Overview407
2Acronyms and Abbreviations408
3Units for Digital Communications414
4American Vs British English Terminology415
5Logic Symbols and Terms416
6Logic Timers420
7Logic Gates422
Figure 39:Fault recorder stop conditions155
Figure 40:Trip LED logic170
Figure 41:TCS Scheme 1188
Figure 42:PSL for TCS Scheme 1189
Figure 43:TCS Scheme 2189
Figure 44:PSL for TCS Scheme 2190
Figure 45:TCS Scheme 3190
Figure 46:PSL for TCS Scheme 3190
Figure 47:RS485 biasing circuit196
Figure 48:Remote communication using K-Bus197
Figure 49:Control input behaviour208
Figure 50:Manual selection of a disturbance record215
Figure 51:Automatic selection of disturbance record - method 1216
Figure 52:Automatic selection of disturbance record - method 2217
Figure 53:Configuration file extraction218
Figure 54:Data file extraction219
Figure 55:Data model layers in IEC61850224
Figure 56:GPS Satellite timing signal232
Figure 57:Board connectors243
Figure 58:Example PRP redundant network245
Figure 59:Application of PRP at substation level246
Figure 60:IED attached to redundant Ethernet star or ring circuit247
Figure 61:IED, bay computer and Ethernet switch with self healing ring facilities247
Figure 62:Internal architecture of IED, C264 bay computer and H36x Ethernet switch248
Figure 63:Redundant Ethernet ring architecture with IED, bay computer and Ethernet
249
switches
Figure 64:Redundant Ethernet ring architecture with IED, bay computer and Ethernet
249
switches after failure
Figure 65:Dual homing mechanism250
Figure 66:Application of Dual Homing Star at substation level251
Figure 67:SNMP MIB tree253
Figure 68:IED and REB IP address configuration258
Figure 69:Connection using (a) an Ethernet switch and (b) a media converter262
Figure 70:Connection using (a) an Ethernet switch and (b) a media converter265
Figure 71:Default display navigation282
Figure 72:Flowchart showing how S1 Agile can be used to set up and save a protection
Figure 77:CB Fail Non Current Protection Logic320
Figure 78:Composite Earth Fault Start Logic320
Figure 79:Any Trip Logic320
Figure 80:SEF Any Start Logic320
Figure 81:Trip Output Mappings322
Figure 82:Opto-Input Mappings323
Figure 83:Output Relay Mappings324
Figure 84:LED Mappings325
Figure 85:Control Input Mappings325
Figure 86:Function Key Mappings325
Figure 87:Circuit Breaker mapping326
Figure 88:Fault Record Trigger mapping326
Figure 89:Check Synchronisation and Voltage Monitor mappings326
Figure 90:Location of battery isolation strip333
Figure 91:Rack mounting of products335
Figure 92:Terminal block types336
Figure 93:80TE case dimensions340
Figure 94:RP1 physical connection355
Figure 95:Remote communication using K-bus355
Figure 96:Possible terminal block types372
Figure 97:Front panel assembly374
Figure 98:Logic Gates422
Figure 99:P747 busbar protection, 3 box solution432
Figure 100:P747 busbar protection with 40 inputs, 24 outputs and coprocessor433
Figure 101:P747 busbar protection with 32 inputs, 32 outputs and coprocessor434
Figure 102:P747 busbar protection with 32 inputs, 24 outputs and standard coprocessor435
P747-TM-EN-1xvii
Table of FiguresMiCOM P747
P747-TM-EN-1.1
xviiiP747-TM-EN-1
INTRODUCTION
CHAPTER 1
Chapter 1 - IntroductionMiCOM P747
P747-TM-EN-1.1
2P747-TM-EN-1
MiCOM P747Chapter 1 - Introduction
P747-TM-EN-1.1
1CHAPTER OVERVIEW
This chapter contains the following sections:
Chapter Overview3
Foreword4
Features and Functions6
Compliance8
Functional Overview9
Ordering Options10
P747-TM-EN-13
Chapter 1 - IntroductionMiCOM P747
P747-TM-EN-1.1
2FOREWORD
This technical manual provides a functional and technical description of Alstom Grid's MiCOM P747, as well
as a comprehensive set of instructions for using the device.
We have attempted to make this manual as accurate, comprehensive and user-friendly as possible.
However we cannot guarantee that it is free from errors. Nor can we state that it cannot be improved. We
would therefore be very pleased to hear from you if you discover any errors, or have any suggestions for
improvement. All feedback should be sent to our contact centre via the following URL:
http://www.alstom.com/grid/contactcentre/
2.1TARGET AUDIENCE
This manual is aimed towards all professionals charged with installing, commissioning, maintaining,
troubleshooting, or operating any of the products within the specified product range. This includes installation
and commissioning personnel as well as engineers who will be responsible for operating the product.
The level at which this manual is written assumes that installation and commissioning engineers have
knowledge of handling electronic equipment. Also, system and protection engineers have a thorough
knowledge of protection systems and associated equipment.
2.2TYPOGRAPHICAL CONVENTIONS
The following typographical conventions are used throughout this manual.
● The names for special keys and function keys appear in capital letters.
For example: ENTER
● When describing software applications, menu items, buttons, labels etc as they appear on the screen
are written in bold type.
For example: Select Save from the file menu.
● Filenames and paths use the courier font
For example: Example\File.text
● Special terminology is written with leading capitals
For example: Sensitive Earth Fault
● If reference is made to the IED's internal settings and signals database, the menu group heading
(column) text is written in upper case italics
For example: The SYSTEM DATA
● If reference is made to the IED's internal settings and signals database, the setting cells and DDB
signals are written in bold italics
For example: The Language cell in the SYSTEM DATA column
● If reference is made to the IED's internal settings and signals database, the value of a cell's content is
written in the Courier font
For example: The Language cell in the SYSTEM DATA column contains the value English
column
2.3NOMENCLATURE
Due to the technical nature of this manual, many special terms, abbreviations and acronyms are used
throughout the manual. Some of these terms are well-known industry-specific terms while others may be
special product-specific terms used by Alstom Grid. A glossary at the back of this manual provides a
complete description of all special terms used throughout the manual.
4P747-TM-EN-1
MiCOM P747Chapter 1 - Introduction
P747-TM-EN-1.1
We would like to highlight the following changes of nomenclature however:
● The word 'relay' is no longer used for the device itself. Instead, the device is referred to as an 'IED'
(Intelligent Electronic Device), the 'device', the 'product', or the 'unit'. The word 'relay' is used purely to
describe the electromechanical components within the device, i.e. the output relays.
● British English is used throughout this manual.
● The British term 'Earth' is used in favour of the American term 'Ground'.
2.4PRODUCT SCOPE
This product protects busbars with up to 4 zones plus a check zone. It can be applied at any voltage level.
One device is used to protect each phase (3-box solution). A further device can be used to protect the
neutral line (4-box solution). The device is suitable for applications on solidly grounded systems, or where a
centralised scheme is needed.
Each device can manage a maximum of:
● 4 Voltage transformers (VTs) (1 VT per zone),
● 18 Current transformers (CTs)
● 18 Circuit breakers (CBs)
● 72 isolators
● Up to 40 Digital Inputs and 128 Virtual Inputs (128 digital inputs via communications) for each
protected phase
● Up to 32 Digital Outputs and 128 Virtual Outputs (128 digital outputs via communications) for each
protected phase
The P747 consists of the following main components.
Main protection
This uses low impedance biased current differential protection. The typical operating time is less than one
cycle. If a fault occurs and more than one zone needs to be tripped, you might need to trip zones
sequentially. You can do this by setting different time delays on each of the zone differential elements.
Backup protection
This consists of:
● phase overcurrent
● dead zone
● circuit breaker failure
Settings application software
This allows you to create a scheme and display the measured data. The scheme editor allows you to quickly
draw schemes from a library of elements, then validate the scheme. It can also display the status of DDBs
and measured data on the scheme in real time.
Inputs and outputs
The device has many hard-wired digital inputs and outputs. For applications that demand more, virtual inputs
and outputs can be used between the products protecting the different phases. 128 virtual inputs and outputs
can be shared between products using communications links. Use hard-wired inputs and outputs to connect
the most time-critical signals between devices. Use Virtual inputs and outputs to communicate less timecritical information signals between devices.
P747-TM-EN-15
Chapter 1 - IntroductionMiCOM P747
P747-TM-EN-1.1
3FEATURES AND FUNCTIONS
3.1PROTECTION FUNCTIONS
The P747 provides the following protection functions:
Protection FunctionIEC 61850ANSI
Phase segregated biased current differential high speed busbar protectionPhsPDIF87BB/P
Check Zone segregated biased phase current differential high speed busbar protectionCzPPDIF87CZ/P
Definite Time overcurrent protection (2 stages)OcpPTOC50/P
IDMT overcurrent protection (2 stages)OcpPTOC51/P
Dead zone phase protection (short zone between CTs and open CBs)DzpPhsPTOC 50DZ
CB Failure (auxiliary contacts or fast undercurrent)RBRF50BF
CB Failure and isolator state monitoring
LockoutRBRF89
Undervoltage control27
VT blocking scheme based on V<VTS
3.2CONTROL FUNCTIONS
FeatureIEC 61850ANSI
Watchdog contacts
Read-only mode
NERC compliant cyber-security
Function keys (up to 10)FnkGGIO
Programmable LEDs (up to 18)LedGGIO
Programmable hotkeys (2)
Programmable allocation of digital inputs and outputs
Fully customizable menu texts
Circuit breaker control, status & condition monitoringXCBR52
Trip circuit and coil supervision
Control inputsPloGGIO1
Power-up diagnostics and continuous self-monitoring
Dual rated 1A and 5A CT inputs
Alternative setting groups (4)
Graphical programmable scheme logic (PSL)
Fault locatorRFLO
3.3MEASUREMENT FUNCTIONS
Measurement of all instantaneous & integrated values
(Exact range of measurements depend on the device model)
Disturbance recorder for waveform capture – specified in samples per
cycle
Fault Records
6P747-TM-EN-1
Measurement FunctionIEC 61850ANSI
MET
RDREDFR
MiCOM P747Chapter 1 - Introduction
P747-TM-EN-1.1
Measurement FunctionIEC 61850ANSI
Maintenance Records
Event Records / Event loggingEvent records
Time Stamping of Opto-inputsYesYes
3.4COMMUNICATION FUNCTIONS
The device offers the following communication functions:
FeatureANSI
NERC compliant cyber-security
Front RS232 serial communication port for configuration16S
Rear serial RS485 communication port for SCADA control16S
2 Additional rear serial communication ports for SCADA control and
teleprotection (fibre and copper) (optional)
Ethernet communication (optional)16E
Redundant Ethernet communication (optional)16E
Courier16S
IEC 61850 (optional)16E
IEC 60870-5-103 (optional)16S
DNP3.0 over serial link (optional)16S
DNP3.0 over Ethernet (optional)16E
IRIG-B time synchronisation (optional)CLK
16S
P747-TM-EN-17
Chapter 1 - IntroductionMiCOM P747
P747-TM-EN-1.1
4COMPLIANCE
The device has undergone a range of extensive testing and certification processes to ensure and prove
compatibility with all target markets. Below is a list of standards with which the device is compliant. A detailed
description of these criteria can be found in the Technical Specifications chapter.
Compliance Standards
ConditionCompliance
EMC compliance (compulsory)2004/108/EC (demonstrated by EN60255-26:2009)
Product safety (compulsory)2006/95/EC (demonstrated by EN60255-27:2005)
R&TTE Compliance (compulsory)99/5/EC
EMCEN50263, IEC 60255-22-1/2/3/4/5/6/7, IEC 61000-4-5/6/8/9/10/16
K-Bus/Courier1
Modbus2
IEC60870-5-1033
DNP3.04
IEC 61850 over Ethernet and Courier via rear K-Bus/RS4856
DNP3 over Ethernet with Courier rear port K-Bus/RS485 protocol8
Mounting Options:
Panel mounting M
Rack mounting N
Langua ge Options:
English, French, German, Spanish0
English, French, German, Russian5
Chinese, English or French via HMI, with English or French only via communications portC
Software Version Options:
Unless specified the latest version will be delivered**
Settings File s Options:
Default0
Customer specificA
Design Suffix:
Extended CPUK
Order Number
E00036
Chapter 1 - IntroductionMiCOM P747
P747-TM-EN-1.1
6ORDERING OPTIONS
10P747-TM-EN-1
Loading...
+ 428 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.