P40 Agile P14D, P14N, P94V Version History
P40Agile-VH-EN-9 3
Major Minor
50 H A
April-13
· Original Issue
TG8612C
·
Agile Relay issue follow ing a failure: Error/Lockout 7104:2000/reboot
· IEC 61850 - Connection / Dis connection issues
· DNP3oE Versions - Courier Tunnelling doesnot work (AGP 140-46)
· Company name is still AREV A in DNP3 build.
·
Ethernet application (IEC61850 + DNP3oe) crashes if a Courier tunnel is continuously opened/closed
· Object 0 variations: 219, 222, 245 and 247 are incorrect.
· QNX kernel can delay user threads for up to 10ms.
·
IEC61850 Select Before Operate Incorrect Behaviour
· With e-ter ra scada system, the P40 Agi le data model extraction stops at Measurments/PriFouMMX U 1$CF
· Unextracted events are lost on RP1, following relay reboot, using a DNPOE build.
·
Incorrect response to Object 2 Variation 3 request for Binary Input Event with R elative Time
· IEEE Floats are wrong at modbus interface.
·
Downloading a settings fi le reverts settings temporarly to setting gr oup 1
P14D-B/G/L/Z-TM-EN-1
· The map of IEC61850 data model for P34x has er rors in Function.
P14N-B/Z-TM-EN-1
· P94V operation on UF
P94V-B/P-TM-EN-1
· DNP3OE Versions - Command management during IED disconnection / connection
· CB Fail trip may fail to operate under faults with DC transient offsets
· IEC 61850 Client disass ociation while reading PloGGI O 1$C O block in P14D IEDs
· IEC61850 Measurements negative values rounding error
·
Agile latch reset when setting group is changed
· What to do with Pending Reports when BufTm>0? Ed1
· Undervoltage programmable curve not using standard template used by other Px4x relays
· The VCO Status, cell [3582], for the Voltage Controlled Overcurrent isn't updated after a change. The change
takes effect after a power cycle or change to V Dep OC V<1 S et.
· ISEF, IEF and anything related are not scaled properly when the CT r atio is 5A.
· EF directional function fail to trip
P14DH 53A IEC61850-8-1 Level B Conformanc e Failure/Issue
50 K A April-2016
DNP Over Ethernet Application Crash after many days of Polling
DNPOE after operated some DI and AI events at the same time ,the relay Ethernet board seems locked and after a while the relay reboot.
FA Steady Fault - Incorrect Assertion
P14DZ HiZ Function asserting incorrectly (CHA HiF)
Incorrect Burst Count - HiF Det ec tion
High Impedance Fault Maloperation
HIF CHA Hysteresis is not correctly set
HIF Burst Threshold is not reset after the adaptive threshold is disabled
50 June-15AJ
Relay type: Agile P14N, P14D and P94V
Software
Version
Hardware
Suffix
Original Date of
Issue
Description of Changes Technical Documentation
Page 4
Version History P40 Agile P14D, P14N, P94V
4 P40Agile-VH-EN-9
Major Minor
Relay type: Agile P14N, P14D and P94V
Software
Version
Hardware
Suffix
Original Date of
Issue
Description of Changes Technical Documentation
50 L A April-2017
Permanent ethernet communication loss in P40 A gil e r elays
Maintenance Record Generated Everytime Gateway is configured in DNP configuration
CS1 and CS2 does not work independently whey CB Comp enabled for CS2
51 A A Sep-13
· Ethernet Enhancements for the P94V
· New model P14DA
· Neutral Admittance Protection for the P14DL and P14DZ
· Selectable Measured/Derived NVD.
Undervoltage programmable curve not using standard template used by other Px4x relaysThe map of IE C 61850 data model for P34x has errors in FunctionWith e-terra scada system, the P40 Agile data model extraction stops at Measurments/PriFouMMXU1$CFWhen using SBOns control m odel for the data 'Control/XC BR 1$C O $Lock' and both Check Conditions are set the
Agile relay is dropping the connection to the client.
DNP ALSTOM rebranding in dnpev_devattr.hQNX kernel can delay user threads for up to 10ms.Unextracted events are lost on RP1, fol lowing relay reboot, using a DNPOE build.Incorrect response to Object 2 V ariation 3 request for Binary Input Event with Relative Tim eISEF, IEF and anything related are not sc aled properly when the CT ratio is 5A. IEEE Floats are wrong at modbus interface. Ethernet application (IEC61850 + DNP3oe) crashes if a Courier t unnel is continuously opened/c losed (as done by
S1 Agile Measurements viewer ).
P14D-TM-EN-1 P14N-TM-EN-1 P94V-TM-EN-1
51 B A Nov-13
EF directional function fail to trip
The VCO Status, cell [3582], for the Voltage Controlled Overcurrent isn't updated after a change. The change
takes effect after a power cycle or change to V Dep
Object 0 variations: 219, 222, 245 & 247 are incorrect.
P14D-TM-EN-1 P14N-TM-EN-1 P94V-TM-EN-1
51 C A June-14
ZR0006 FCT fails; High current drain to opto transformer drive circuit
· Chinese HMI Added
· The DDB 1599-1798 display ”PSL internal 001-200“, but DDB 923-1022 still display "PSL internal 001- 100". Have
duplicate content. The VCO Status isn't updated after a change. The edited change does take eff ect after a power-cycle or a change to "V Dep OC V<1 Set" cell 3583.
Object 0 variations: 219, 222, 245 and 247 are incorrect.
52 B A
P14D-TM-EN-1 P14N-TM-EN-1 P94V-TM-EN-1
Nov-13
Page 5
P40 Agile P14D, P14N, P94V Version History
P40Agile-VH-EN-9 5
Major Minor
Relay type: Agile P14N, P14D and P94V
Software
Version
Hardware
Suffix
Original Date of
Issue
Description of Changes Technical Documentation
· Add P14DH variant with Wattmetric Directional Earthfault pr otection
The .lng files generated by building and t he .LNG files used by S1 Agile are inconsistent.
Incorrect russian translations for DDB_CONTROL_TRIP & DDB_CONTROL_CLOSE
P14DH 53A IEC61850-8-1 Level B Conformanc e Failure/Issue
Inconsistent language text strings between P40Agile and P14x.
B A Apr-14
CB Fai l trip may fail to operate under faults with DC transient offsets
· Integrate new FPGA version to fix transistor issue
C A Apr-15
Agile Relay failure: Error/Lockout 7104:2000/reboot
The LCD display year is 2080 but in t he disturbance and event records it is 1980.
Us ing S1 Agile changing values to the Voltage Transformer does not c hange the corresponding vaues in Residual
O/V NVD column
Line length mismatch between value sent from S1 Agile and the value r eceived in the relay
DNP3oE Setting Files - GoEna i s visible
Values under High impedance menu do not show values in primary when relay is set to primary in S1.
53 D A Aug-2015
Very sharp pick current level lead relay trippi ng on IREF
53 E A April-2017
IEC 61850 - Connection / Disconnection issues
DNP3oE Versions - Courier Tunnelling doesnot work
DNPOE after operated some DI and AI events at the same time ,the relay Ethernet board seems l ocked and after a while the relay reboot.
DNP Over Ethernet Application Crash after many days of Polling
Permanent ethernet communic ation loss in P40 Agile rel ays
TCP disrupts after around 206 days of continuous use
P14DZ HiZ Function assert ing incorrectly (CHA H iF)
Incorrect Burst Count - HiF Detection
FA Steady Fault - Incorrect Assertion
HIF CHA Hysteresis is not correctly s et
HIF Burst Threshold is not reset after the adaptive threshold is disabled
Maintenance Record Generated Ever ytime Gateway is configured in DNP configuration
CS1 and CS2 does not work independently whey CB C om p enabled for CS2
New opto threshold for Russian requirement New reduced I/O option (3I/4O in 20TE and 6I/8O in 30TE)
IEC 61850 Client disassociat ion while reading PloGGIO1$CO block in P14D IEDs
IEC 61850: incorrect Courier cell mapping to TotWh and TotVArh in MMTR LNs
IEC 61850 m easurements negative values rounding error
54 A
P14D-TM-EN-3 P14N-TM-EN-3 P94V-TM-EN-3
A A Apr-14
53
P14D-TM-EN-3 P14N-TM-EN-3 P94V-TM-EN-3
P14D-TM-EN-4.1 P14N-TM-EN-4.1 P94V-TM-EN-4.1
Dec-14A
Page 6
Version History P40 Agile P14D, P14N, P94V
6 P40Agile-VH-EN-9
Major Minor
Relay type: Agile P14N, P14D and P94V
Software
Version
Hardware
Suffix
Original Date of
Issue
Description of Changes Technical Documentation
B A Apr-15
Agile Relay failure: Error/Lockout 7104:2000/reboot
The LCD display year is 2080 but in t he disturbance and event records it is 1980.
Using S1 Agile changing values to the Voltage Transformer does not change the corresponding vaues in Residual
O/V NVD column
Line length mismatch between value sent from S1 Agile and the value r eceived in the relay
DNP3oE Setting Files - GoEna i s visible
Values under High impedance menu do not show values in primary when relay is set to primary in S1.
P14D-TM-EN-4.1 P14N-TM-EN-4.1 P94V-TM-EN-4.1
54 C A April-2017
IEC 61850 - Connection / Disconnection issues
DNP3oE Versions - Courier Tunnelling does not work
DNPOE after operated some DI and AI events at the same time, the relay Ethernet board seems l ocked and after a while the relay reboot.
Permanent Ethernet communication loss in P40 Agile relays
TCP disrupts after around 206 days of continuous use
P14DZ HiZ Function assert ing incorrectly (CHA H iF)
Incorrect Burst Count - HiF Detection
FA Steady Fault - Incorrect Assertion
HIF CHA Hysteresis is not correctly s et
HIF Burst Threshold is not reset after the adaptive threshold is disabled
Maintenance Record Generated Ever ytime Gateway is configured in DNP configuration
55 A A
November-15
CS1 and CS2 does not work independently whey CB C om p enabled for CS2
· To retrofit legacy pr oducts KAVR100, KAVS and KVTR
· Pin to pin retrofit solution for KMPC130
· Compliance to CEI 0-16 requi rements in P14D/P94V
·
New communication protocol options - 1)IEC61850 over Ethernet + Modbus via RS485, 2)IEC61850 over
Ethernet + DNP3.0 via RS485
· Settable k factor i n T hermal overload
· Fault locator sett ing improvements
·
Earth Fault (EF1) sett ing 10mA minimum threshold
· DNP3.0 Unsolicited message reporting
·
PSL timer setting
· New extra shorting link ordering option – for capacitor cone NVD application & alarm on IED removal
· Compliance to Russian Rosseti requirements
· NCIT column visibil ity incorrect.
· Write 'AAAA ' into cell 0x0002 failed with a r eply code 05(CS103_GRC_SETTING_OUT_OF_RANGE)
·
Generated MICS document for I E C 61850 protocol contains 'I EC 61850' instead of 'IEC 61850".
· Can not extract Disturbance records from a P545 DNP3 OE us ing DNP3 commands
· P145 reboots periodicall y w hen IEC 61850 comms active and SNTP active
· Status report over IEC61850 not in line with DDB signals
P14D-TM-EN-5 P14N-TM-EN-5 P94V-TM-EN-5
Page 7
P40 Agile P14D, P14N, P94V Version History
P40Agile-VH-EN-9 7
Major Minor
Relay type: Agile P14N, P14D and P94V
Software
Version
Hardware
Suffix
Original Date of
Issue
Description of Changes Technical Documentation
· actVal Data Attribute now finalised as INT32 requi rement in SCL (Edition 1 Only)
·
Values under High impedance menu do not s how values in primary when relay is set to primary in S1.
· Pending Reports when BufTm>0? Ed1
· Agile latch reset when setting group is changed
· Connection / Disconnec tion issues
· Class 0 should be configurable to select either C ounter or corresponding Frozen Counter
· DNP3oE Versions - Courier Tunnelling doesnot work
·
For DNPOE build, the frozen counter always keeps the same val ue w ith the static counter without accepting a
Freeze command.
· The behaviour of frozen counter i s different between DNP3 and DNPOE before the freeze command is sent
·
DNPOE after operated some DI and AI events at the same time ,the relay Ethernet board seems l ocked and after
a while the relay reboot.
·
IEC 61850 Interoperability problem when a client writes to any/all unsupported Trigger Options
· Problems with ICD fi les for P140 50A
·
8.333Hz is displayed in the first generated Fault Recor d after relay reboot.
· P145 Underfrequency issue i n Russia
· SecRmsMMXU1 showing values in primary, not secondary
· IEC 61850: incorrect C ourier cell mapping to TotWh and TotVArh in MMTR LNs
· CB Fail trip may fail to operate under faults with DC transient offsets
· "FUNCTION KEYS" column is visible for 20TE devices i n P 14 Agile data model.
· Default GOOSE “Min Cycl e T ime” is wrong.
·
Visibility of setting "I>1 TMS" and "I>1 Time Dial" is wrong in Group 2
· EPATR-B curve
·
High Impedance Fault issue
· DNP3OE Versions - Command management during IED disconnection / connection
· Freq Avg Cycles & df/dt Avg Cycles should use power cycle instead of PCON calls cycles
· The unit of Records/RFLO1/CF/FltDiskm is incorrect
· Very sharp pick cur rent level lead relay trippi ng on IREF
·
The error message" Runtime Error C991:3011" appear on P14N relay when glance over the cells in overcurrent
column from HMI
· Column [4E00] PSL TIMERS is i nvisible from relay
· Default Setting of Relay i s in-consistent t o Look & Feel
·
P94VR Look & Feel consistency check issues via courier interface
· “Ethernet failover” option displays in IED Confi gurator
· New settings Moving average cells ([42 41] -> [42 2D]) are not working in Modbus.
·
When download the soft w are to the P14DZ relay and power cycle,the error message - "Runt ime Error
2e0b:0101" appear and relay reboot
· The sequence number should not inc rease when relay send retry unsolicited message
Page 8
Version History P40 Agile P14D, P14N, P94V
8 P40Agile-VH-EN-9
Major Minor
Relay type: Agile P14N, P14D and P94V
Software
Version
Hardware
Suffix
Original Date of
Issue
Description of Changes Technical Documentation
· Language translations of al l new DDBs and settings are in E nglish apart from French.
·
The display of the cell[0341][0345][0347][0343] misses a sign minus on Modbus protocol, and the value of new
adding cells can't be t aken.
·
SecAvgMSTA.Volts4.rang. m ax.f is not configurable.
· The IEC61850 communication disconnect when BRCB with special configuration is Enabled
· Trip elements 5 is mi ssing in fault record of DNP protocol.
· CTS operations when [4609] CTS VN< Inhibit is not satisfied.
· Command "Reset Total Autoreclosures" is missing for P94VR DNP Object 10.
· DNP Binary Input 42 and Binary Input 299 could not be set when DDB 167 "UV Block " is ON.
· Wrong DDB mapping for DA VtpAvgPTOV2.Str.PhsC.
·
When browsing Fault R ecord from HMI, Avg O/V Start operates unexpectedly when AVG OVER VOLT pr otection
is disabled.
·
FUN number should be 164 instead of 162 for DDB #549 "dv/dt2 StartA/AB" in L & F " IEC60870-5-103" spread
sheet.
· Modbus address of all DDBs in "Alarm status 2" and "Alarm status 3" are incorrect.
· Some menu text mistake in 55A version.
·
Look & Feel Start Elements, Trip Elements available opt ions, "Fault Record" spr ead sheet need update.
·
Data Group Modbus missing, Modbus Number of steps shi ft from cell [420D] V<3 Function to [4211] V<3
Poledead Inh in Look & Feel.
· Max value 10Hz could not be set to cells f+Df/Dt x Dfreq(x=1 to 9) via M odbus protocol.
· The mapping "Measurements/Sec M ST A1$MX$AvVAr3$mag$f" was wrong, it should map to the cell [0342]("+3P h
VAr Fix Dem").
· The new Average voltage protections keep running even if 091D is dis abeled
· FAULT RECORD Start CN and Trip CN are missing from UI when tw o stages of average voltage protec tions are
both enabled in case of three phase faults.
· BRCB - Wrong response when client sets an unknow EntryID value before enable it
· DO sequence error in ICD file
· Modbus Start, Data Group Modbus, Modbus Number of steps, M odbus registers are incorrect for Frequency
Protection Stage 9 cells in L&F.
·
In Unsolicited mode, t he m easured unsolicited response time is 5s greater than the setting [1B 04] - "Unso
Response" value
· The cell text of these cel ls[4201][4220][4240][4250] ar e not consistent with l ook&feel file.
· The cell [30 11] Dir Char Setting exist in P94VR.
·
Modbus address error in L& F for cell [03 28] ~ [03 2D]
· Inconsistency between L& F and sw.
· There is no translation for these DDB(ordinal:1799-1842) in look & feel file.
· The "ASDU Type" in "Fault Record" t hat's extracted by Px40VDEW is not consistent wi th look & feel file.
· The format of Build Date&Tim e is not correct.
Page 9
P40 Agile P14D, P14N, P94V Version History
P40Agile-VH-EN-9 9
Major Minor
Relay type: Agile P14N, P14D and P94V
Software
Version
Hardware
Suffix
Original Date of
Issue
Description of Changes Technical Documentation
55 B A October-16
The values of DDBs (1717~1720) read via IEC61850 can not be updated after downloading t he new PS L
The fault record can't be extracted via CS103 protocol if the previous fault recor d terminated by "Reset CU".
DNP Over Ethernet Application Crash after many days of Polling
Permanent ethernet communic ation loss in P40 Agile rel ays in MICHELIN Site (ACT 160622 – 45574)
After enabling the BRCB, the f irst integrity report comes out around 10s when the integrity time is set to be 3s under certain pre-st eps
P14DZ HiZ Function assert ing incorrectly (CHA H iF)
Incorrect Burst Count - HiF Detection
FA Steady Fault - Incorrect Assertion
HIF CHA Hysteresis is not correctly s et
HIF Burst Threshold is not reset after the adaptive threshold is disabled
56 A A February-16
· PRP / HSR / FailOver redundancy (new hardware boards) Configurable Fail-over in DNP3
· DDB 781/782 doesn't show the r eal status when the alarm “Port A Link Fail” or "Port B Link Fail" show in HMI
· The status of DDB 783 is “OFF” issue
P14D-TM-EN-6.1 P14N-TM-EN-6.1
P94V-TM-EN-6.1
57 A A May-15
· RSTP redundancy (new hardware boards)
· PCCN/Electre features
· CEI 0-16 2nd round
· DNP3 memory leak correction (AGPL-49)
P14D-TM-EN-7 P14N-TM-EN-7 P94V-TM-EN-7
· The values of DDBs (1717~1720) read via IEC61850 can not be updated after downloadi ng the new PSL
· The fault record can' t be extracted via CS103 protocol if the previous fault record terminated by "Reset CU".
· DNP Over Ethernet Applic ation Crash after many days of Polling
· DDB #146 "Prot'n Disabled" events are read as "test mode" vi a C S 103 protocol.
· The new under voltage Average voltage prot ections doesn't use POLEDEAD similar to the standar d under voltage
· Ext AR SEF Trip could not block AR when [493F] SEF Ext Prot is set to "Block AR".
· The VTS Fast Block can not block the AVG undervoltage;AVG over voltage;AVG ZERO SEQ O/V;AVG POS SEQ O/V and AVG NEG SEQ O/V
· DDB #167 UV Block should not be visible on P14DA.
· After enabling the BRCB, t he first integrity report comes out around 10s when the integrity time is s et to be 3s under certain pre-st eps
· IEC 61850 client sets unsupported TrgOps must have response+ (Tissue 780)
· P14DZ HiZ Function asser ting incorrectly ( CH A HiF)
· Incorrect Burst Count - HiF Detection
· FA Steady Fault - Incorrect Assertion
· HIF CHA Hysteresis is not correctly set
· HIF Burst Threshold is not reset after the adaptive threshold is disabled
57 B A April-2017
Permanent ethernet communic ation loss in P40 Agile rel ays in MICHELIN Site
Maintenance Record Generated Ever ytime Gateway is configured in DNP configuration
Page 10
Version History P40 Agile P14D, P14N, P94V
10 P40Agile-VH-EN-9
Major Minor
Relay type: Agile P14N, P14D and P94V
Software
Version
Hardware
Suffix
Original Date of
Issue
Description of Changes Technical Documentation
CLONE - CS1 and CS2 does not work independent ly whey CB Comp enabled for CS2
60 A A Dec-2016
· Voltage vector shift
· Switch Status and control
· IEC61850 Fault Records
· Code Review Report - Bad task priority change in DSP DTC tr ansmit task
· Permanent ethernet communi cation loss in P40 Agile r elays
· DDB #146 ""Prot'n Disabled" " events are read as ""test mode"" via CS103 protocol.
. No events read from CS103 protocol for DDB #441 ""Test Mode"", D DB #771 " " G O O SE IED Absent"", DDB #780 ""IP Addr Conflict"", DDB #1200 ""Monitor bit 1"" to DDB #1207 "" M onitor bit 8"".
. IED reboot during the Enduranc e T est (Stress Test) at 69Hz
. Agile RSTP is non-responsive at 10Mbps
. Relay contact 1 doesn’t persist data on P14DH model after reboot
61 A A April 2017
· TEFD new algorithm
· Vn input implementation c hange
· New In RMS measurement
. 64 Virtual Inputs
. Editable user alarms
. Maintenance Record Generated E verytime Gateway is configured in DNP configuration
. CS1 and CS2 does not work independently w hey C B C omp enabled for CS2
P14D-TM-EN-9 P14N-TM-EN-9 P94V-TM-EN-9
P14D-TM-EN-8 P14N-TM-EN-8 P94V-TM-EN-8
Page 11
Page 12
Imagination at work
Grid Solutions St Leonards Building Redhill Business Park Stafford, ST16 1WT, UK +44 (0) 1785 250 070 www.gegridsolutions.com/contact
© 2017 General Electric. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is compl
ete or correct or will apply to any particular project.
This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change wit
hout notice.
Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
P40Agile-VH-EN-9
Loading...