Copyright 2000 Reuter-Stokes, Inc. All rights reserved. This manual may
not, in whole or part, be copied, photocopied, reproduced, translated or
reduced to any electronic medium or machine readable form without prior
consent, in writing, from Reuter-Stokes, Inc.
The illustrations shown in this manual are intended solely to illustrate the
text of this manual. Because of the many variables and requirements
associated with any particular installation, Reuter-Stokes, Inc. cannot
assume responsibility or liability for actual use based upon the illustrative
uses and applications.
Trademarks
LTC-MAP™, SAGE™, are trademarks of Reuter-Stokes, Inc.
Warranty
Reuter-Stokes, Inc. warrants each of our products to be free from defects in
material or workmanship. Our obligation under this warranty is to repair or
replace, at our discretion, any product or part of a product that proves to be
defective upon examination within 18 months of the date of shipment, or 12
months from the date of startup, whichever occurs first. No other warranty
is expressed or implied. Reuter-Stokes, Inc. does not warrant that your
monitoring system will operate as described in this manual in every
environment.
Reuter-Stokes, Inc. has thoroughly tested the equipment and reviewed the
documentation. However, Reuter-Stokes, Inc. does not warrant the
performance of the products for for any particular purpose. In no event is
Reuter-Stokes, Inc. liable for any damage resulting, directly or indirectly,
from the use of this product.
THE EXPRESS WARRANTY SET FORTH ABOVE IS EXCLUSIVE, AND NO
OTHER WARRANTY OF ANY KIND, WHETHER STATUTORY, WRITTEN,
ORAL, EXPRESS, OR IMPLIED (INCLUDING WARRANTIES OF FITNESS FOR
PARTICULAR PURPOSE OR MERCHANTABILITY), SHALL APPLY.
Revision History
Revision Release Date
1.0 November 14, 1997
1.1 January 26, 1998
B July 6, 1998, July 19,1999
C October 14, 1999
D February 3, 2000
Available Options......................................................................................................................................................1-6
Front Cover Layout....................................................................................................................................................2-2
Face Panel Layout....................................................................................................................................................2-3
Alarm Status & Settings Button.........................................................................................................................2-4
Serial Port ..............................................................................................................................................................2-5
Power Supply Board ............................................................................................................................................2-8
CPU Board .............................................................................................................................................................2-9
Selecting a Location................................................................................................................................................3-1
Mounting the Monitor..............................................................................................................................................3-2
Wiring the Sensors.............................................................................................................................................3-10
Wiring a Tap Position Indicator......................................................................................................................3-11
Wiring the AC Voltage Inputs...........................................................................................................................3-17
Wiring the AC Current Inputs...........................................................................................................................3-17
Wiring the Digital Inputs...................................................................................................................................3-17
Wiring the Annunciator Outputs.....................................................................................................................3-18
Wiring the Internal Heater................................................................................................................................3-19
Serial Port Communications.............................................................................................................................3-21
Calibrate Tap Position............................................................................................................................................3-24
Analog Channel Readings Screens...................................................................................................................4-2
Digital Channel Readings Screens....................................................................................................................4-2
Tap Change Summary Screen ............................................................................................................................4-3
Alarm Status & Settings Button.............................................................................................................................4-5
LTC-MAP Status Screen......................................................................................................................................4-5
Current Time and Date Screen............................................................................................................................4-6
The LTC-MAP 2130 Monitor (Figure 1-1) is an on-line maintenance
action planner (MAP) for load tap changers (LTC). It continuously
monitors performance data from various types of sensors, such as
temperature and current. It stores this data in non-volatile memory for
downloading to a personal computer.
Figure 1-1: LTC -MAP 2130 Monitor
70055MP Revision D February 3, 2000
1-2 Section 1: Introduction
LTC-MAP 2130 Monitor is a multi -input data storage and analysis
system. Each system features:
• Seventeen (17) analog input channels.
• Sixteen (16) digital input channels (via optional Control Isolator).
• One (1) serial port/modem line.
• Two annunciator relay outputs (form C contacts).
LTC-MAP 2130 uses state of the art technology to process, analyze,
and store data into a configurable profile. A built-in microprocessor
compares, computes, and relates stored data to set parameters.
Alarms are generated when data levels exceed the set parameters.
NOTE: Parameters are set via the SAGE host software package.
Refer to the SAGE Product Manual, Part No. 70057MP, for details
on parameter configuration and data retrieval and analysis.
Data profiles and alarm events are stored in non-volatile randomaccess memory. The stored information is then downloaded to a
personal computer, either directly through the serial port or via an
optional modem. The SAGE host software package allows data
retrieval and analysis.
February 3, 2000 70055MP Revision D
Section 1: Introduction 1-3
Specifications
Input
Analog
Digital
Seventeen (17) channels.
Channels 1 - 7
Input: 4 to 20 mA.
Sample rate: 150 Hz.
Channel 8
Input: ±10 VDC.
Sample rate: 150 Hz.
Channels 9-11
Configurable input:
• 4 to 20 mA with a sample rate of 150 Hz, or
• 5A AC (as monitored by a CT) with a sample rate of 1920
Hz.
Channel 12
Configurable input:
• 4 to 20 mA with a sample rate of 150 Hz, or
• 50A AC (as monitored by a CT) with a sample rate of
1920 Hz.
Channels 13-16
Configurable input:
• 4 to 20 mA with a sample rate of 150 Hz, or
• 120/240 VAC with a sample rate of 1920 Hz.
Channel 17
Configurable input:
• 4 to 20 mA with a sample rate of 150 Hz, or
• Signal conditioned with a sample rate of 1920 Hz.
Sixteen channels via two optional control isolators (eight
Two dry-contact relay outputs for alarm indication.
Three LEDs:
POWER: When lit, indicates that the monitor is receiving
power.
ALARM1: When lit, indicates that a software
configurable alarm has been activated; contact relay
driven.
ALARM2: When lit, indicates that a software
configurable alarm has been activated; contact relay
driven.
Front panel four line liquid crystal (LCD).
Resolution: 1 V, 1 A, 1 °C.
Standard: RS-232-C serial port; DB-9 connector.
Optional: 14.4k bps modem, installed on the back left side of
the monitor base.
Type: Non-volatile, solid state RAM.
Capacity: Up to 128 K, based on configuration.
Mode: Revolving loop.
Averaging Interval: Configurable from 1 to 60 minutes.
Three front panel push buttons:
Operating Conditions: Used to display present operating
conditions.
Alarm Status & Settings:
Used to display present alarm status.
Acknowledge Alarm:
Used to deactivate alarm relays.
One CPU Board mounted push button:
SETUP: Used to initiate setup procedure for tap position
calibrations.
III.
No regular maintenance is required.
No regular cleaning is required.
No specific limit; however, intermittent operation is
undesirable and should be corrected as soon as
possible.
February 3, 2000 70055MP Revision D
Section 1: Introduction 1-5
Electrical
Sensor Power Supply
(Electrical Rating)
Power Consumption
Environmental
Temperature Range
Pollution Degree
Maximum Relative
Maximum Altitude
Power Input
Protection
Power Input
Supply Voltage
Fluctuation
Operating
Humidity
24 VDC @ 0.65A.
Fused (F1)
Type: AGC3 instant blow.
Rating: 3A @ 250 V.
AC: Standard: 120 VAC +10/-15%AC, 50 - 60 Hz.
Optional (factory set): 240 VAC +10/-15%AC, 50 - 60 Hz.
DC: 125 VDC +15%DC.
NOTE: Monitors supplied with internal heater option must
have AC power input.
Less than 16VA.
Mains supply voltage must not exceed +10% of nominal
supply voltage.
Standard: 0°C to +60 °C (+32°F to +140 °F).
With Heater Option: -40°C to +60 °C (-40°F to +140 °F).
4.
80%.
2000m.
Physical Enclosure
Material
Standard
Dimensions
NOTE: Specifications subject to change without notice.
Weight
Stainless steel, weather-proof.
NEMA Type 4.
12” (305 mm) x 12” (305 mm) x 6” (152 mm).
18 lbs. (8.16 kg); additional weight for accessories.
70055MP Revision D February 3, 2000
1-6 Section 1: Introduction
Available Options
Available options for the LTC-MAP 2130 are listed in Table 1-1. Refer
to the applicable documentation for detailed information on the
available options.
Table 1-1: LTC -MAP 2130 Options
Option Part No. Description/Function
Magnetic Mount RTD
Temperature Sensor
RTD Transmitter T821028 Connects to an insertion-type temperature sensor and
Clamp-On AC Current
(CT) Sensor
Control Isolator 40041MP Optically isolates the monitoring system from the transformer
Combustible Gas Sensor 10384MP Measures hydrogen and hydrocarbon levels in the insulating
Moisture Sensor T801074 Measures moisture levels in the insulating oil.
Eight Line Phone
Multiplexer
Fifteen Line Phone
Multiplexer
14.4k bps Modem 20046MP Installed in the monitor; allows transfer of data and
SAGE Host Software
Package
30000MP Attaches magnetically to the transformer; has a built-in
4-20 ma transmitter.
Refer to Document No. 70063MP for more information.
transmits a 4-20 mA signal back to the monitor.
Refer to Document No. 70064MP for more information.
T821026 Clips onto a transformer lead and detects load current.
Refer to Document No. 70059MP for more information.
controls.
Refer to Document No. 70062MP for more information.
oil.
Refer to Document No. 70065MP for more information.
40047MPA Allows up to eight monitors (with installed modems) to be
connected to a single phone line for data transmission.
Refer to Document No. 70061MP for more information.
40047MPB Allows up to fifteen monitors (with installed modems) to be
connected to a single phone line for data transmission.
Refer to Document No. 70061MP for more information.
configuration parameters over a telephone line to an off-site
PC.
Refer to Document No. 70058MP for more information.
SAGE
Provides tools for parameter configuration, parameter
calibration, data retrieval, and data analysis.
Refer to Document No. 70057MP for more information.
February 3, 2000 70055MP Revision D
Section 1: Introduction 1-7
Typical Application
A transformer utilizing an LTC-MAP 2130 monitor is illustrated in Figure
1-2. The monitor is mounted on the transformer. Analog sensors
mounted on the transformer are connected to the monitor. Refer to the
example typical wiring diagram in Section 3 to determine specific
sensor input connections.
Figure 1-2: Typical LTC -MAP 2130 Application
70055MP Revision D February 3, 2000
1-8 Section 1: Introduction
A typical system may include several monitors, one for each
transformer at the site, multiplexed together. The multiplexer is
typically located at the on-site substation. (See Figure 1-3). Data from
all monitors on site may then be downloaded to a remote personal
computer (PC). SAGE host software installed on the PC allows for
data retrieval and analysis.
Figure 1-3: Typical System
February 3, 2000 70055MP Revision D
Section 1: Introduction 1-9
Manual Conventions
This manual provides the information you will need to install, operate,
and maintain the LTC-MAP 2130 Monitor.
Throughout this manual CAUTIONS,WARNINGS, and NOTES are
provided.
CAUTION: Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury.
WARNING: Indicates a potentially hazardous situation which, if not
avoided, may result in death or serious injury.
NOTE: Contains supplemental information.
70055MP Revision D February 3, 2000
Section 2: Getting Started
Receiving Inspection
On receipt of the LTC-MAP 2130 Monitor:
1. Carefully inspect the packing containers and contents for physical
damage.
2. Carefully unpack the monitor, checking that all items listed on the
packing slip are present and in good condition.
NOTE: If damage is evident, or any items are missing, contact
Support Services at (330-425-3755) for further instructions.
Customer Support/Service
For service or support for your LTC-MAP 2130 Monitor, contact:
Field Service/Customer Support Department
Reuter-Stokes, Inc.
Edison Park
8499 Darrow Rd.
Twinsburg, OH 44087
PH: 330-425-3755
FAX: 330-425-1812
www.gepower.com
GE Syprotec
179 Boulevard Brunswick
Pointe-Claire, Quebec H9R 5N2
Canada
PH: 514-694-3637
FAX: 514-694-9245
70055MP Revision D February 3, 2000
2-2 Section 2: Getting Started
Front Cover Layout
There are three indicator lights on the front cover of the LTC-MAP 2130
Monitor (see Figure 2-1):
• The yellow POWER indicator illuminates whenever the monitor is
receiving power.
• The red ALARM1 indicator illuminates whenever a configured
contact relay alarm is activated.
• The red ALARM2 indicator illuminates whenever a configured
contact relay alarm is activated.
The fasteners on the right side of the front cover allow access to the
inside face panel of the monitor.
Figure 2-1: LTC -MAP 2130 Monitor (Front Cover)
February 3, 2000 70055MP Revision D
Section 2: Getting Started 2-3
Face Panel Layout
The face panel is accessed by releasing the fasteners on the right side
of the front cover. The front panel features (see Figure 2-2):
• A four-line LCD display.
• Operating Conditions button.
• Alarm Status & Settings button.
• AcknowledgeAlarm button.
• A serial port.
Present operating conditions, alarm settings, and alarm status may be
viewed on the display by pressing the appropriate buttons.
The serial port allows direct connection, utilizing a null modem cable,
between the LTC-MAP 2130 and a portable computer for data transfer.
NOTE: A null modem cable is available from Reuter-Stokes (Part No.
10101MP).
The two thumb screws on the right side of the face panel provide
access to the CPU and I/O circuit boards.
Figure 2-2: LTC -MAP 2130 Monitor (Face Panel)
70055MP Revision D February 3, 2000
2-4 Section 2: Getting Started
Operating Conditions Button
The Operating Conditions button is located directly below and left
aligned with the display. Pressing the Operating Conditions button
displays the sensor value readings. Four channels are displayed
simultaneously. The display includes:
• Channel number.
• Channel name.
• Present reading.
• Units.
After all sensor screens are displaye d, pressing the Operating
Conditions button again displays the tap change summary screen.
During tap position calibration, the Operating Conditions button is used
to adjust settings.
Alarm Status & Settings Button
The Alarm Status & Settings button is located directly below and right
aligned with the display. Pressing Alarm Status & Settings displays
the monitor status and the date and time. If there are alarm conditions,
pressing Alarm Status & Settings scrolls through descriptions of alarm
conditions.
During tap position calibration, the Alarm Status & Settings button is
used to adjust settings.
Acknowledge Alarm Button
The Acknowledge Alarm button is located in the lower left corner of
the face panel. Pressing Acknowledge Alarm resets the alarm relay;
however, the indicator remains lit for the duration of the alarm
condition.
February 3, 2000 70055MP Revision D
Section 2: Getting Started 2-5
LCD Display
The LCD is a 20 character by 4 line display (Figure 2-3). It displays
operating and status conditions. Screens are scrolled through using
the Operating Conditions and Alarm Status & Settings buttons.
L T C - M A P 2 1 3 0
r e v 2 1 3 0 . x x . y y
c o p y r I g h t ( C ) 1 9 9 7
< <
Operating Alarm Status
Conditions & Settings
Figure 2-3: Display with Control Buttons
Serial Port
CAUTION: The serial port and the modem cannot function
simultaneously. When using the serial port for communications, the
internal modem (if installed) must be disconnected at JP8; otherwise
the serial port will not function.
The serial port is a 9-pin male DB-9 connector. This port allows direct
connection, utilizing a null modem cable, between the LTC-MAP 2130
and a portable computer for data transfer. Data transfer rate is
19.2 kbps.
The serial port does not support dumb terminal operation. In order for
communications to take place:
• A null modem cable must be installed between the monitor serial
port and personal computer serial port.
• SAGE host software must be installed on the personal computer.
NOTE: A null modem cable is available (Part No. 10101MP ).
70055MP Revision D February 3, 2000
2-6 Section 2: Getting Started
Circuit Board Location
The CPU and I/O circuit boards are accessed by loosening the two
thumb screws on the right side of the face panel (see Figure 2-4).
The CPU circuit board is mounted to the back side of the face panel.
The I/O Circuit board is mounted to the inside rear panel of the Monitor
cabinet. The Power Supply board is mounted on the I/O Circuit board.
A ribbon cable connects the CPU and I/O circuit boards.
Figure 2-4: LTC -MAP 2130 (Top View with Face Panel Open)
February 3, 2000 70055MP Revision D
Section 2: Getting Started 2-7
Alarm #1
Alarm #2
Power
I/O Board
The I/O Circuit board (Figure 2-5) contains sensor signal conditioning
circuitry and hardware to interface to the sensors mounted on the
transformer.
Sensor
Ground
Ribbon Cable
Connector
(To CPU Board)
Control
Isolator
InputsVoltage
Jumper
D10
R18
R17
R15
U6
TP1
C7
C9
U4
J4
C27
Sensor
Inputs
C11
RN6
U2
C8C10
U5
C16
R68
R67
U7
R70
R69
GT1 GT3 GT5 GT7
J15
C20
R71
Y
EN
R44
C
R38
B
Z9
A
Z13
R43
+12
Z8
REL
R37
A3
Z10
R41
A2
Z12
Y
EN
C
B
R39
R40
A
Z11
R42
COMCOM
+12
Z14
DIGITALANALOG 2ANALOG 1CURRENT
Jumper
J1
J7J6J3
JP13
J2
J17
17
J8
CHANNEL
1 16 14171513 12 11 10 9
A
B
JP7
JP5JP9
GT14 GT16
GT12GT6GT4GT2GT17
J14J16
COMMON
SENSOR
8
1ST CONTROL ISOLATOR2ND CONTROL ISOLATOR
7
SENSOR INPUTS
6
5
4
3
2
1
(24 VDC)
SENSOR
POWER
Current
Inputs
Jumper
C4
TP2
TP3TP4
RN1
U9
C12
A
TP9TP6
U12
B
JP1JP2JP3JP4JP6JP8
C17
GT10
GT8
C30
GT9GT11GT13GT15
J10
RJ1
GND
SENSOR
COMMON
J13
D1
COM
D2
RED GRN
R7
PHONE
16
15
14
13
12
11
10
9
SENSOR
POWER
COM
MOTOR
SENSOR INPUTS
CURRENT
C
B
A
(24 VDC)
R50
R53
R8
R12
R99
D25
R98
D24
R97
D12
R92
D16
Outside Phone
Line Connection
TP5
RN4
RN2
U1
C34
C31
C13
C32
TP7TP8
U11
C18
U14
D3
D4
D17
D18
D13
D14
MODEM VOLTS
OPEN = 12V
MOV1
T1
MOV5
T2
MOV6
T3
MOV7
T4
Figure 2-5: I/O Circuit Board
Q6
R101
Q5
C19
R100
C33
U13
D9
D8
R6
R64
C3
C2
R3
C14
Q2
R102
Q4
R24
C23
C24
R48
U10
C22
9V
6V
C1
Q1
R49
R16
C15
C21
R20
U3
Q8
Q7
R108
R109
J18R110
ANN1
K4
#2
ANNUNCIATOR
NC COM NO
C25
C26
C28
#4
INPUT
VOLTAGE
#1
#3
INPUT
VOLTAGE
#2
INPUT
VOLTAGE
HEATER
#1
INPUT
VOLTAGE
J20
VOLTAGE
Internal Modem
Connection
D31
D30
D11
D32
D29
Q3
R111
R112
NORMINV
R113
K1
NC COM NO
ANNUNCIATOR
F1
LINENEUT
D28
K3
K2
Q9
Q10
J19
ANN2
NORMINV
J12
Annunciator
U8
Inputs
C6
J5
C5
Inputs
J9
70055MP Revision D February 3, 2000
2-8 Section 2: Getting Started
Power Supply Board
The Power Supply circuit board (Figure 2-6) contains the low voltage
supplies, incoming power terminals, and the power fuse (F1) for the
monitor. F1 is a type AGC3 fuse, rated for 3 Amp at 250 V.
Figure 2-6: Power Supply Circuit Board
February 3, 2000 70055MP Revision D
Section 2: Getting Started 2-9
CPU Board
The CPU circuit board (Figure 2-7) contains the microprocessor (CPU),
LCD Display, front panel buttons, and serial port.
Figure 2-7: CPU Circuit Board
70055MP Revision D February 3, 2000
2-10 Section 2: Getting Started
Communications
The SAGE host software installed on a personal computer allows for
data retrieval and analysis. Communications with the LTC-MAP 2130
must be established in order to download data to the PC or upload
configuration information to the terminal. Communication between the
PC and the monitor can be established:
• Directly via the front panel serial port and a null modem cable
to a personal computer running the SAGE host software.
NOTE: SAGE host software must be installed on the PC for
proper communication to take place. The front panel serial
port does not support dumb terminal operation.
• Over phone lines using an optional modem installed inside the
monitor.
• Over phone lines via a phone multiplexer installed in the
control house and connected to several LTC-MAP 2130
monitors. Refer to Document No. 70061MP for detailed
information on the phone multiplexers available from ReuterStokes, Inc.
CAUTION: The serial port and the modem cannot function
simultaneously. When using the serial port for communications, the
internal modem (if installed) must be disconnected at J8; otherwise
the serial port will not function.
February 3, 2000 70055MP Revision D
Section 3: Installation
This Section includes procedures for installation, configuration, wiring,
setting up communications, and initial start-up of the LTC -MAP 2130
Monitor.
Selecting a Location
The LTC -MAP 2130 is enclosed in a weatherproof stainless steel box that
can be mounted indoors or outdoors. When selecting a mounting location
for the monitor, verify that:
• The mounting surface is able to support a minimum of 25 pounds (11.3
kg).
• The mounting surface allows ample space for mounting the stainless
steel box and allows for a 12-inch (305 mm) door clearance (see Figure
3-1).
• Sensors are located nearby to minimize cable length.
• Wiring and cables can access the monitor gland plate.
• The face panel display is at a readable level.
• An operating temperature of 0 ºC to +60 ºC (+32 ºF to +140 ºF) can be
maintained at the monitor location.
NOTE: With the heater option installed, an operating temperature of
-40 ºC to +º60 C (-40 ºF to +140 ºF) must be maintained at the
monitor location.
CAUTION: Select a mounting location that assures an operating
temperature of 0 ºC to +60 ºC (+32 ºF to +140 ºF), otherwise system operation
could be interrupted.
70055MP Revision D February 3, 2000
½"
3-2Section 3: Installation
Mounting the Monitor
Secure the monitor to the selected location using four ¼-20# stainless
steels bolts through the mounting holes (see Figure 3-1).
After securely mounting the LTC -MAP 2130 monitor, route the input and
output cables back to the gland plate.
CAUTION: Do not apply power to the LTC -MAP 2130 until all input and
output cables are connected.
The removable gland plate on the bottom of the LTC -MAP 2130 Monitor has
pre-punched conduit hol es (see Figure 3-2) and strain relief cable
connectors. Weep holes are provided to allow drainage of excess
moisture.
Additional holes can be drilled into the gland plate if required. Remove the
plate by removing the two nuts and washers securing it to the monitor. The
nuts are accessed from inside the monitor.
CAUTION: Do not drill additional holes into the gland plate while it is installed
on the monitor. Metal chips can damage the circuit boards.
4.194"
(106 mm)
1.25"
(31.8 mm)
Weep Holes
1"
(25.4 mm)
10.25" (260 mm)
Strain Relief Connector
Figure 3-2: Gland Plate
.875"
22.2 mm
70055MP Revision D February 3, 2000
Channel
3-4Section 3: Installation
I/O Board Configuration Jumpers
The I/O board configuration jumpers allow you to customize the LTC -MAP
2130 monitor to your application’s specific sensor (channel type input),
alarm, and modem requirements.
Channel Configuration
Channels 9 through 12 are configurable for a 4-20 mA sensor input or a
5A/50A current input (as monitored through a CT). Channels 13 through 16
are configurable for a 4-20 mA sensor input or a voltage input. Refer to
Table 3-1 for specific jumper numbers and positions for each channel.
Refer to Figure 3-3 for A and B jumper positions.
Table 3-1: Channel Configuration Jumpers and Positions
Jumper Position Selected Input
JP1 A
B
JP2 A
B
JP3 A
B
JP4 A
B
JP5 A
B
JP6 A
B
JP7 A
B
JP8 A
B
JP9 A
B
5A (CT) Current Input A.
4-20 mA Sensor Input #9.
5A (CT) Current Input B.
4-20 mA Sensor Input #10.
5A (CT) Current Input C.
4-20 mA Sensor Input #11.
50 A (CT) Motor Current.
4-20 mA Sensor Input #12.
Voltage Input 1.
4-20 mA Sensor Input #13.
Voltage Input 2.
4-20 mA Sensor Input #14.
Voltage Input 3.
4-20 mA Sensor Input #15.
Voltage Input 4.
4-20 mA Sensor Input #16.
Temperature Inside the monitor.
4-20 mA Sensor Input #1.
Modem Power Supply Configuration Jumper
Jumper JP12 sets the modem power supply. Refer to Table 3-2 for jumper
positions.
NOTE: Refer to the modem specifications to determine the modem power
supply requirements. Refer to Figure 3-3 for jumper location.
Table 3-2: Modem Power Supply Configuration (JP12)
JP12 Position Selected Modem Power Supply
1-2 6 VDC
2-3 9 VDC
No Jumper 12 VDC
70055MP Revision D February 3, 2000
3-6 Section 3: Installation
Alarm Configuration Jumpers
Jumpers JP18 and JP19 set the annunci ator relay outputs to normal or
inverted. Jumper JP13 configures the Acknowledge Alarm button. Refer to
Table 3-3 for jumper positions. Refer to Figure 3-3 for jumper locations.
NOTE: JP13 must always be installed.
Table 3-3: Alarm Configuration
Jumper Position Description
JP18 INV
NORM
JP19 INV
NORM
JP13 Installed
Removed
Annunciator 1 Output Inverted.
Annunciator 1 Output Normal.
Annunciator 2 Output Inverted.
Annunciator 2 Output Normal.
Configures the Alarm Acknowledge button for use.
Not applicable.
Ground Jumpers
Jumpers JP10 and JP14, when installed, are set to earth ground. These
jumpers must always be installed for accurate and safe operation.
WARNING: Jumpers JP10 and JP14 must always be installed for accurate
and safe monitor operation.
February 3, 2000 70055MP Revision D
Section 3: Installation 3-7
Wiring
Overview
Prior to starting any wiring procedures:
Pull the power fuse (F1) on the Power Supply board.
• Securely ground the LTC -MAP 2130 at the ground lug.
CAUTION: Pull the power board fuses or remove F1 on the I/O board before
making connections.
WARNING: The LTC -MAP 2130 Monitor must be properly grounded before
placing the unit in service. An improper or missing ground can create a
safety hazard.
Refer to Figure 3-4 for fuse and ground lug locations.
LTC-MAP 2130 wiring consists of:
• Wiring the sensors.
• Wiring a tap position indicator (if used).
• Wiring the AC current inputs.
• Wiring the AC voltage inputs.
• Wiring the digital inputs.
• Wiring the annunciator outputs.
• Wiring the internal heater.
• Wiring power.
Refer to Figure 3-4 for I/O Board Terminal Locations. Refer to Figure 3-5 for
an example of a typical wiring diagram.
70055MP Revision D February 3, 2000
Line Connection
3-8Section 3: Installation
Sensor Ground
1/4-20 Stud
First Control
Isolator Input
Second Control
Isolator Input
TP1
C7
C9
U4
J4
D10
R18
R17
R15
U6U5
C8C10
R67
R70
R69
GT1 GT3 GT5 GT7
C20
R71
C27
R44
R38
Z9
Z13
R43
Z8
R37
Z10
R41
Z12
R39
R40
Z11
R42
Z14
C16
R68
U2
C11
J15
J1
RN6
J2
J8
U7
1 16 14
1513 12 11 10 9
JP7
GT14 GT16
Y
COMMON
EN
SENSOR
C
B
A
8
1ST CONTROL ISOLATOR2ND CONTROL ISOLATOR
7
+12
SENSOR INPUTS
6
REL
5
A3
4
A2
3
Y
2
EN
1
C
(24 VDC)
B
SENSOR
POWER
A
COMCOM
+12
JP13
17
CHANNEL
A
B
JP5JP9
GT12GT6GT4GT2GT17
J14J16
C4
J7
J3
TP2
TP3
RN1
JP1JP2JP3JP4JP6JP8
GT8
GT9GT11GT13GT15
SENSOR
COMMONSENSOR INPUTS
POWER
SENSOR
(24 VDC)
J6
A
B
GND
COM
PHONE
COM
CURRENT
RED GRN
MOTOR
C
B
A
U9
C12
TP9TP6
C17
C30
J10
RJ1
J13
R50
R53
R99
D25
R98
D24
R97
D12
R92
D16
C1
+
C4
J1
U14
D3
D4
D17
D18
D13
D14
D1
D2
R7
R8
R12
MOV1
T1
MOV5
T2
MOV6
T3
MOV7
T4
J17
GT10
17
16
15
14
13
12
11
10
9
U1
J2 MOV1
LINE NEUT
MODEM VOLTS
9V
6V
OPEN = 12V
C1
C25
C26
C28
Z1
POWER
R108
J20DIGITALANALOG 2ANALOG 1CURRENTVOLTAGE
C3
+
C2
+
J.W.HARLEY INC.
ASSY NO.
U3
Q8
R109
J18R110
#2
ANNUNCIATOR
NC COM NO
#4
INPUT
VOLTAGE
#3
INPUT
VOLTAGE
#2
INPUT
VOLTAGE
#1
INPUT
VOLTAGE
20065MPA
20065MPB
Q7
ANN1
NORMINV
K4
ANNUNCIATOR
#1
HEATER
F1
NC COM NO
LINE NEUT
Power Fuse
Type ADC2
Rated for 3A @ 250 V
U2
Power
Input
Q9
R111
Q10
R112
J19
ANN2
R113
K1
J12
J9
NORMINV
U8
C6
J5
C5
Annunciator
Outputs
Voltage
Inputs
Heater Power
Input
Sensor
Inputs 1-8
Configurable
Sensor Inputs 9-16
Figure 3-4: Fuse, Input Terminals, and Ground Locations
Current
Inputs
External Phone
Ground Lug
Internal Modem
Connection
February 3, 2000 70055MP Revision D
Section 3: Installation 3-9
Figure 3-5: Example of a Typical Wiring Diagram for the LTC-MAP 2130
70055MP Revision D February 3, 2000
3-10 Section 3: Installation
Wiring the Sensors
Refer to Table 1-1 for a list of sensors available for use with the
LTC-MAP 2130 Monitor. Detailed installation information for each sensor is
provided in the referenced documentation.
Some general notes to consider during sensor selection and installation:
• Thermowell RTD sensors require a signal conditioning transmitter to
provide a 4-20 mA output to the monitor.
• Figure 3-4 provides Sensor and Input Connection locations on the I/O
board.
• We recommend using #18 AWG shielded, twisted pair wire for sensor
input connections to the I/O board, unless stated otherwise in the
documentation provided with the sensor. Use of shielded twisted pair
improves noise immunity; the shield should be grounded at one end
only.
February 3, 2000 70055MP Revision D
Section 3: Installation 3-11
Wiring a Tap Position Indicator
OEM Potentiometer s
The OEM potentiometer is a voltage divider containing a resistor string.
Each position on the string represents a tap position. In the examples in
this Section, the potentiometers have thirty three positions containing thirty
two 40-ohm resistors. The actual number of positions and number and
values of resistors may be different on your potentiometer.
The power supplied to the OEM potentiometer depends on the utility. The
variations include:
• -5 to +5 VDC or -10 to +10 VDC.
• 0 to +5 VDC or 0 to +10 VDC.
• No voltage (connect with LTC -MAP power).
Determine the voltage across your potentiometer and follow the
appropriate wiring instructions.
In general, two signals are utilized between the OEM potentiometer and the
LTC-MAP. The signal is a linearly varying DC voltage (+10 V maximum).
For proper tap position recording by the LTC -MAP, the linearly varying DC
voltage from the OEM potentiometer must have a uniform increment for
each tap position. For example, a potentiometer used for a 33 tap device
(16 lower, 16 raise, and neutral) with a 10 Volt drop across the entire bridge
must show a 10V/32 = 0.3125 V change per tap step on the potentiometer
wiper.
70055MP Revision D February 3, 2000
3-12 Section 3: Installation
0 to +5 VDC or 0 to +10 VDC Power
Connect the OEM potentiometer to the LTC -MAP Circuit Board, as follows
(refer to Figure 3-6):
1. Connect the OEM Potentiometer Wiper to Sensor Input #8.
2. Connect the OEM Potentiometer 0 VDC Common Point to Sensor
Common.
Figure 3-6: Typical OEM Potentiometer with 0 to +5 VDC Power
February 3, 2000 70055MP Revision D
Section 3: Installation 3-13
-5 to +5 VDC or -10 to +10 VDC Power
Connect the OEM potentiometer to the LTC -MAP Circuit Board, as follows
(refer to Figure 3-7):
1. Connect the OEM Potentiometer Wiper to Sensor Input #8.
2. Connect the OEM Potentiometer Center Point to the Sensor Common.
Figure 3-7: Typical OEM Potentiometer with -5 to +5 VDC Power
70055MP Revision D February 3, 2000
3-14 Section 3: Installation
LTC-MAP Power
OEM potentiometers that are not powered require power from the LTC MAP’s 24 VDC Sensor Power Supply. To use the LTC -MAP supply, you
must:
• Select a Voltage Drop Resistor (Rd).
• Connect the Power Supply wires to the OEM Potentiometer.
• Connect the wires at the Monitor Circuit board.
In order to use this power, you must first calculate the value of the required
voltage drop resistor (Rd). The voltage drop resistor limits the current and
voltage across the potentiometer (see Figure 3-8).
Figure 3-8: Typical OEM Potentiometer Powered by LTC-MAP
To calculate Rd:
1. Determine the value and number of resistors in the potentiometer.
NOTE: LTC -MAP can accommodate any value or number of tap
position resistors.
2. Calculate the String Resistance (Rs) where:
Rs = (Resistor Value) x (Number of Resistors).
February 3, 2000 70055MP Revision D
Section 3: Installation 3-15
3. Calculate the Voltage Drop Resistor value (Rd):
Rd = Rs x 1.4.
4. Select a voltage drop resistor as follows:
Resistance: first standard value greater than the Rd.
Power rating: 2 watts.
Tolerance: 5% or less
As an example, consider a potentiometer with thirty-two 40 ohm
resistors. The calculated string resistance would be:
Rs = (40 ohms) x (32 Resistors) - 1280 ohms.
And
Rd = Rs x 1.4 = 1280 x 1.4 = 1792 ohms.
The next standard resistor value greater than 1792 is 1800 ohms.
Therefore, the selected voltage drop resistor should be an 1800 ohm,
5%, 2 watt resistor.
Connect the wires to the OEM Potentiometer as follows:
1. Connect the designated positive point lead to the OEM Potentiometer
Positive Point.
2. Connect the designated common point lead to the OEM Potentiometer
Common Point.
3. Connect the designated wiper lead to the OEM Potentiometer Wiper.
Connect the wires to the circuit board as follows:
1. Connect one end of the Voltage Drop Resistor (Vd) to a sensor power
supply terminal.
2. Connect the positive point lead to the other end of the Voltage Drop
Resistor (Vd).
3. Connect the common point lead to the designated Sensor Common
terminal.
4. Connect the wiper lead to Sensor Input #8.
NOTE: Tap Position must be calibrated to operate correctly (see Calibrate
Tap Position).
CAUTION: The positive lead must be connected to Sensor Input #5 and the
negative lead to Sensor Common. Failure to comply can damage the LTC MAP.
70055MP Revision D February 3, 2000
3-16 Section 3: Installation
After-Market
Use the following procedure to wire an After-Market Tap Position Indicator.
1. Verify that the signal output is one of the following:
• - 5V to + +5 VDC
• -10 to + 10 VDC,
• 0 to +5 VDC, or
• 0 to +10 VDC.
2. Connect the signal output to Sensor Input #8.
3. Connect the signal reference to a Sensor Common Terminal.
NOTE: Tap Position must be calibrated to operate correctly (see Calibrate
Tap Position).
February 3, 2000 70055MP Revision D
Section 3: Installation 3-17
Wiring the AC Voltage Inputs
Connect voltage signals to the designated terminals (Voltage Input #1, #2,
#3, #4) on the wiring and installation diagrams. Refer to Figure 3-5 for
terminal location.
NOTE: The signal specification range for Voltage Inputs #1, #2, #3, and #4
are 0 to 300 Vrms. If your signal input is different, contact Support Services
as noted on back cover.
Wiring the AC Current Inputs
There are two types of current inputs - powered CT and unpowered CT
(e.g., Clamp On AC Current Transducer).
Connections for unpowered CT’s are not polarity sensitive. Connect the CT
between the A, B, or C Current terminals (refer to Figures 3-4 and 3-5).
Connections for powered (active) CT’s are polarity sensitive. Refer to
information on the active CT’s connection points for proper polarity.
Wiring the Digital Inputs
The LTC -MAP 2130 monitor collects output data from the Control Isolator at
the digital inputs. (See Figure 3-4 for Control Isolator Input terminal
locations.)
NOTE: Refer to Document No. 70062MP for specific information on
the Control Isolator, Part No. 40041MP.
1. Mount the Control Isolator(s) per the guidelines provided in the
documentation provided with the Control Isolator.
NOTE: The control Isolators are provided with a 10 foot cable;
therefore, when selecting a mounting location, be sure it is within 10
feet of the monitor.
2. Connect the output cable of the Control Isolator to the First Control
Isolator Input (digital channels 1-8) as designated on the wiring and
installation diagrams.
3. If there is a second Control isolator installed, connect the output cable
of the Control Isolator to the Second Control Isolator Input (digital
channels 9-16) as designated on the wiring and installation diagrams.
NOTE: If only one Control Isolator is installed, it must be connected to the
First Control Isolator input terminals on the I/O board.
70055MP Revision D February 3, 2000
3-18 Section 3: Installation
Wiring the Annunciator Outputs
Wire the alarms by connecting the alarm activation signal to the Alarm
normally opened or Alarm normally closed contacts. Refer to Figure 3-5 for
Alarm Contact (Annunciator Output) locations.
NOTE: The signal specification range for the Alarm Inputs are 120 VAC @ ¼
HP, 240 VAC @ 10 A, or 150 VDC @ 10 A. If your signal is different, contact
Support Services as noted on back cover.
Be sure to configure the alarm jumpers (JP18 and JP19) for either normal or
inverted output as required by your application.
Figure 3-9: I/O Board Terminal Locations
February 3, 2000 70055MP Revision D
Section 3: Installation 3-19
Wiring the Internal Heater
The monitor’s internal heater requires 110 VAC power input. Refer to Figure
3-9 for Heater Terminal locations.
WARNING: Do not bridge the heater power terminals to the monitor power
supply terminals if DC is used to supply the monitor. The heater is AC only.
Wiring Power
The LTC -MAP 2130 is factory configured for either 120 VAC or 240 VAC
operation per the customer order. Refer to Figure 3-9 for the location of the
Power Input Terminals.
1. Connect the “hot” phase of the 120 or 210 power line to the LINE Power
Input Terminal.
2. Connect the neutral line to the NEUT Power Input Terminal.
70055MP Revision D February 3, 2000
3-20 Section 3: Installation
Establishing Communications
The SAGE host software installed on a personal computer allows for
data retrieval and analysis. Communications with the LTC -MAP 2130 must
be established in order to download data to the PC or upload configuration
information to the LTC -MAP. Communication between the PC and the
monitor can be established:
• Directly via the front panel serial port and a null modem cable to a
personal computer running SAGE .
NOTE: The SAGE host software must be installed on the PC for
proper communication to take place. The front panel serial port
does not support dumb terminal operation.
• Over phone lines using an optional modem installed inside the
monitor.
• Over phone lines via a phone multiplexer installed in the control
house and connected to several LTC -MAP 2130 monitors. Refer to
Document No. 70061MP for detailed information on the phone
multiplexers available from Reuter-Stokes.
CAUTION: The serial port and the modem cannot function simultaneously.
When using the serial port for communications, the internal modem (if
installed) must be disconnected at J8; otherwise the serial port will not
function.
February 3, 2000 70055MP Revision D
Section 3: Installation 3-21
Serial Port Communications
To establish communications via the front panel serial port:
1. Be sure the modem, if installed, is disconnected at J8.
2. Be sure the SAGE host software is installed on the personal
computer.
3. Connect a null modem cable between the front panel serial port and the
serial port on the personal computer. See Figure 3-10 for serial port
location.
4. From within the SAGE host software, set the serial port rate to 19200
bps.
Figure 3-10: Serial Port Location
70055MP Revision D February 3, 2000
3-22 Section 3: Installation
Modem Communications
To establish communications via a modem:
1. If not already installed, mount the modem inside the monitor using the
supplied Velcroattachments.
2. Connect the modem per the instructions supplied with it.
See Figure 3-11 for modem mounting location and typical connections.
3. Set JP12 on the I/O board to select the modem power supply. Refer to
Modem Power Supply Configuration earlier in this section.
4. Be sure the serial port speed rate is set to 19200 bps (positions 3 and 4
on SW4 on the CPU board should be open).
Figure 3-11: Modem Location and Connections
February 3, 2000 70055MP Revision D
Section 3: Installation 3-23
Initial Start Up
1. Before applying power to the system, verify that:
• All sensors are mounted and connected properly.
• None of the wiring or cables are shorted.
• All connections follow the wiring and installation diagrams.
• All monitored input signals are within specified input ranges.
• Phone lines are properly connected to a phone multiplexer (if used).
WARNING: Check all wiring before applying power to the unit. Wiring
errors can damage the device and create a safety hazard.
2. Connect the power input wires to the 120 V AC/DC Power terminal.
3. Apply power to the monitor.
NOTE: Copyright information will be displayed for approximately
ten seconds. After that, the display will go blank.
L T C - M A P 2 1 3 0
r e v 2 1 3 0 . x x . y y
c o p y r I g h t ( C ) 1 9 9 7
4. Configure and set system parameters using the SAGE host software
package. (Refer to the SAGE documentation for specific
procedures.)
5. Upload the SAGE configuration files to the LTC-MAP, either through
the RS232 Serial port or via a modem. (Refer to the SAGE
documentation for specific procedures.)
6. Verify the current date and time.
• Press the Alarm Status & Settings button two times or until the
Current Time and Current Date screen is displayed:
C u r r e n t T i m e :
1 2 : 3 0 : 2 2
C u r r e n t D a t e :
W e d 0 9 / 1 7 / 1 9 9 7
• If the time and date are incorrect, reset them using the procedures
outlined in the SAGE documentation.
NOTE: The date and time must be set accurately to insure that LTC MAP 2130 properly acquires data.
70055MP Revision D February 3, 2000
3-24 Section 3: Installation
Once power is applied, and conf iguration parameters have been uploaded
to the monitor, the monitor enters normal operation and begins monitoring
sensor and voltage inputs.
Refer to Section 4 - Operation for further operation procedures.
Calibrate Tap Position
1. Press the Setup button to display the Tap Position Input Calibration
Low Point screen.
T A P P O S I T I O N I N P U T
C A L I B R A T I O N
L O W P O I N T :
5
â
The Setup button is located on the upper left corner of back side the
CPU board.
á
2. Observe and record the actual tap position of the LTC at the TAP
Position Indicator.
3. Adjust the value of the low tap position calibration point to the value
observed in Step 2 by pressing â or á until the correct value is
displayed
4. Press Setup to display the Tap Position High Point Calibration screen.
T A P P O S I T I O N I N P U T
C A L I B R A T I O N
H I G H P O I N T :
6
â
5. Manually move the tap up one position.
á
6. Adjust the value of the high tap position calibration point up one
position from the low calibration point by pressing â or á until the
correct value is displayed.
7. Press Setup to exit the Calibration and return to normal operation.
February 3, 2000 70055MP Revision D
Section 4: Operation
Overview
Once power is applied, the LTC -MAP starts monitoring sensor, voltage,
current, and relay timing inputs. Monitoring functions continue
uninterrupted while operating conditions and alarm status & settings are
viewed and during system setup procedures. Channel readings, alarm
status, and current time and date as set from the SAGE host software
package, can be viewed on the LTC -MAP Monitor display.
Refer to the SAGE documentation for detailed channel configuration,
parameter setting procedures, and monitoring capabilities.
CAUTION: To keep the enclosure weatherproof, close and latch the door
when not using the LTC -MAP. Failure to comply can result in equipment
damage.
Operating Conditions Button
Operating conditions, including current analog and digital channel
readings and a tap change summary, are displayed by pressing the
Operating Conditions button.
• Pressing Operating Conditions during normal operation displays the first
Analog Channels Screen.
• Pressing Operating Conditions repeatedly during normal operation
continuously scrolls through the following screens:
• Analog Channels 1 through 4 Readings.
• Analog Channels 5 through 8 Readings.
• Analog Channels 9 through 12 Readings.
• Analog Channels 13 through 16 Readings.
• Analog Channel 17 Reading.
• Digital Channels 1 through 4 Readings.
• Digital Channels 5 through 9 Readings.
• Digital Channels 10 through 12 Readings.
• Digital Channels 13 through 16 Readings.
• Tap Change Summary.
• If Alarm Status & Settings is pressed while any one of the operating
condition screens is displayed, the Status screen is displayed.
70055MP Revision D February 3, 2000
4-2 Section 4: Op eration
Analog Channel Readings Screens
The Analog Channel Readings screens di splay up to four channels each
(see Figure 4-1). There is one line of display (20 columns) available for each
channel:
• Columns 1 through 10 display the channel’s description as uploaded
from the SAGE configuration file.
• Columns 11through 16 display a numeric representation of the current
value being read at the channels input.
• Columns 17 through 20 display the units of the reading.
• If a channel is not connected, no information is displayed for the
channel; down arrows indicate that pressing Operating Conditions will
display more information (e.g., other configured analog channel
readings, or digital channel readings).
R M T E M P 3 7 . 5 d e g C
T o p O i l 4 5 . 3 d e g C
â
o a d C u r r e 6 8 9 A m p
L
ââ
â
Figure 4-1: Sample Analog Channel Display
Digital Channel Readings Screens
The Digital Channel Readings screens display up to four channels each
(see Figure 4-2). There is one line of display (20 columns) available for each
channel:
• Columns 1 through 17 display the channel’s description as uploaded
from the SAGE configuration file.
• Columns 18 through 20 display the channels status as ON or OFF.
C N T R L I S O 1 C H 1 O N
C N T R L I S O 1 C H 2 O N
C N T R L I S O 1 C H 3 O N
C N T R L I S O 1 C H 4 O F F
Figure 4-2: Sample Digital Channel Display
February 3, 2000 70055MP Revision D
Section 4: Operation 4-3
Tap Change Summary Screen
The Tap Change Summary screen (Figure 4-3) displays:
• Tap Changes in the last hour.
• Tap Changes so far this hour.
• Total number of tap changes since power up.
T a p C h a n g e S u m m a r y
L a s t H o u r = 3
T h i s H o u r = 3
T o t a l = 2 3 6
á
Figure 4-3. Tap Change Summary Screen
70055MP Revision D February 3, 2000
4-4 Section 4: Op eration
Alarm Status & Settings Button
Alarm Status & Settings screens are accessed by pressing the Alarm Status
& Settings button:
• Pressing Alarm Status & Settings during normal operation displays the
LTC-MAP Status screen.
• Pressing Alarm Status & Settings repeatedly during normal operation
continuously scrolls through the Alarm and Status screens, in the
following order:
• LTC-MAP Status Screens
• Current Date and Time Screen
• Pressing Operating Conditions, while an Alarm Status & Setting screen is
displayed, will display the first Analog Channels readings screen.
LTC-MAP Status Screen
The LTC -MAP status screen displays current alarm status. If there are no
alarm conditions, the Normal Status screen (Figure 4-4) is displayed.
If one or more alarms are present, each alarm will be displayed sequentially
and on a separate screen (see Figure 4-5). There are two lines of text
available to display the alarm description; also displayed is the present
value of the parameter triggering the alarm.
A l a r m S t a t u s :
N o r m a l
Figure 4-4: LTC-MAP Status Screen (No Alarms)
* * * A L A R M * * *
T a n k 2 D I f f T e m p
a b o v e s e t l i m i t
V a l u e N O W : 2 4 . 5 d e g C
Figure 4-5: LTC-MAP Alarms Screen
February 3, 2000 70055MP Revision D
Section 4: Operation 4-5
Current Time and Date Screen
The Current Time and Current Date screen (Figure 4-6) displays:
• The current time as read from the system clock and displayed in 24
hour format (HH/MM/SS).
• The current date as read from the system clock and displayed as:
Day MM/DD/YYYY.
NOTE: The system clock must be set to the correct date and time to
ensure that the LTC -MAP properly acquires data. If the date or time are
incorrect, refer to the SAGE documentation for procedures for setting
the date and time.
C u r r e n t T i m e :
1 2 : 3 0 : 2 2
C u r r e n t D a t e :
W e d 0 9 / 1 7 / 1 9 9 7
Figure 4-6: Current Time and Date Screen
Acknowledging Alarms
Alarms are acknowledged by pressi ng the Acknowledge Alarm button,
located in the lower left corner of the face panel. Pressing Acknowledge
Alarm deactivates the alarm relay on the LTC -MAP so subsequent alarms
can trip the annunciator outputs.
NOTE: The LTC -MAP remains in alarm mode, and the
corresponding ALARM indicators remain lit, until the alarm
condition goes away.
70055MP Revision D February 3, 2000
Section 5: Troubleshooting Procedures
Refer to Table 5-1 for common troubleshooting procedures.
Table 5-1: Common Troubleshooting Procedures
Condition Possible Cause(s) Corrective Action
Incorrect Temperature Reading on a
4-20 mA Channel.
Unrecorded tap change events. Incorrect wiring.
Incorrect Current Readings. Incorrect installation.
Incorrect Voltage Readings. Incorrect wiring.
Defective sensor.
Loose wiring connection from sensor
to circuit board
Defective circuit board.
Ribbon cable between CPU and I/O
circuit boards loose.
Ground loop exists with another
connection.
Incorrect parameter settings.
No current present.
Incorrect parameter settings.
Incorrect parameter settings.
Power glitch.
Swap suspect sensor with a known good sensor.
Check wiring connection from the sensor to the
circuit board; ensure that the wire is correctl y
inserted into the screw down connector block.
Swap suspect circuit board with a known good
board.
Temporarily move the suspect RTD sensor wire to
an unused 4-20 mA channel to determine
whether fault follows sensor or circuit board.
Inspect ribbon cable connection at CPU board and
at I/O board.
Systematically remove other connections to the
circuit board until the cause of the loop is found.
For example, problems may be caused having
the individual wire (color) order incorrect for the
cable between the control isolator and the I/O
board.
Check wiring diagram and installation.
Check event start and stop parameters.
Check for a minimum motor current parameter.
Check wiring diagram and installation.
Verify current with a handheld meter.
Check CT Ratio.
Check Calibration Parameters.
Check wiring diagram and installation.
Check Calibration Parameters.
Cycle Power.
70055MP Revision D February 3, 2000
5-2 Section 5: Troubleshooting Procedures
Table 5-1: Common Troubleshooting Procedures (Cont’d)
Condition Possible Cause(s) Corrective Action
Incorrect Tap Position
Displayed/Recorded.
Heater ON at ambient over
60 ºF (15.5 ºC).
Heater not ON at ambient under 50 ºF
(10 ºC).
Sensor Input and Sensor Common
connections reversed.
Battery supply for OEM resistor string
not stable or floating to ground
causing a ground loop.
Faulty heater.
Faulty connections. Check heater connections.
Disconnect inputs and test voltage on the wires
with a volt meter referenced to earth ground.
Disconnect inputs and test voltage on the wires
with a volt meter referenced to earth ground.
Cut or remove the strap for Sensor Common input
to chassis ground connection on the circuit
board.
Use a DC voltage from the monitor, rather than a
battery, to supply the OEM resistor string.
Disconnect heater from I/O board; contact Reuter-
Stokes, Inc..
February 3, 2000 70055MP Revision D
Appendix A: User-Specific Information
Forms
Use the Analog Channel Configuration form to document LTC -MAP 2130
channel settings.
Use the Tap Position Calibration form to document tap position calibration
settings.
Use the wiring diagram forms to document specific system connections.
Analog Channel Configuration
Jumper Position
A or B
N/A N/A 4-20 mA Sensor Input #1.
N/A N/A 4-20 mA Sensor Input #2.
N/A N/A 4-20 mA Sensor Input #3.
N/A N/A 4-20 mA Sensor Input #4.
N/A N/A 4-20 mA Sensor Input #5.
N/A N/A 4-20 mA Sensor Input #6.
N/A N/A 4-20 mA Sensor Input #7.
N/A N/A +10 VDC Input Channel #8.
JP1
(5A Input per CT or 4-20 mA Input #9)
JP2
(5A Input per CT or 4-20 mA Input #10)
JP3
(5A Input per CT or 4-20 mA Input #11)
JP4
(50 A Current per CT or 4-20 mA Input #12)
JP5
(Voltage Input 1 or 4-20 mA Input #13)
JP6
(Voltage Input 2 or 4-20 mA Input #14)
JP7
(Voltage Input 3 or 4-20 mA Input #15)
JP8
(Voltage Input 4 or 4-20 mA Input #16)
Selected Input Input Description
70055MP Revision D February 3, 2000
A-2 Appendix A: User-Specific Information Forms
Tap Position Calibration
Low Point High Point
February 3, 2000 70055MP Revision D
Appendix A: User-Specific Information Forms A-3
LTC-MAP 2130 Customer Installation Information (Part 1)
70055MP Revision D February 3, 2000
A-4 Appendix A: User-Specific Information Forms
LTC-MAP 2130 Customer Installation Information (Part 2)
February 3, 2000 70055MP Revision D
Appendix A: User-Specific Information Forms A-5
LTC-MAP 2130 Customer Installation Information (Part 3)
70055MP Revision D February 3, 2000
Appendix B: Firmware Upgrades
Use the following procedure to replace the EPROM for firmware upgrades:
NOTE: Be sure to download to the PC the LTC -MAP 2130 monitor
configuration, calibration, and parameter settings via SAGE host
software package before replacing the EPROM.
1. Open the front cover by releasing the fasteners on the right side of the
LTC-MAP 2130.
2. Loosen the thumbscrews on the face panel.
3. Swing out the panel to access the I/O and CPU circuit boards.
4. Slip the supplied static control wrist strap over your hand and connect
the other end to any convenient electrical ground.
5. Remove the F1 power fuse from the power board.
CAUTION: To avoid equipment damage, you must remove F1 on the I/O
board when installing the EPROM.
6. Unplug the ribbon cable and modem serial port connector from the CPU
circuit board.
CAUTION: To avoid damage to the ribbon cable, pull the ribbon cable by the
hard plastic connector.
7. Using a No.1 Phillips head screwdriver, remove the five screws
securing the CPU circuit board to the face panel.
8. Carefully remove the CPU circuit board and turn it component side up.
70055MP Revision D February 3, 2000
B-2 Appendix B: Firmware Upgrades
9. Using a 3/16” slotted screwdriver, carefully remove the existing EPROM.
Note the orientation of the EPROM notch and the location within the
socket. See Figure B-1 for EPROM location.
NOTE: Pin number 1 of the EPROM is placed into contact number 3
of the socket.
Figure B-1: EPROM Replacement
10. Remove the new EPROM from the protective packaging.
CAUTION: To avoid damage to the component, do not remove the EPROM
from the protective packaging until you are ready to install it.
11. Determine the proper notch orientation and location within the socket.
12. Carefully bend the pins on the EPROM until they align with the socket
contacts.
CAUTION: To avoid damage to the component , do not push the EPROM into
the socket until all pins are perfectly aligned with the contacts.
13. Once all pins are aligned with the socket contacts, push down on the
EPROM until it is fully seated.
14. Verify that all pins are inserted in the socket contacts.
NOTE: Carefully inspect each pin and contact to verify that none of the
pins are bent under the EPROM.
15. Carefully re-install the CPU circuit board into the face panel.
NOTE: The Operating Conditions and Alarm Status & Settings buttons must
be aligned and inserted into the face panel.
February 3, 2000 70055MP Revision D
Appendix B: Firmware Upgrades B-3
16. Re-install the hardware that secures the CPU board to the face panel.
17. Re-install the ribbon cable and modem serial port connector.
18. Remove the static control wrist strap.
19. Re-install F1 in the power circuit board.
20. Depress the Operating Conditions and Alarm Status & Settings buttons
while applying power to the system.
21. Verify that the LTC -MAP displays copyright information for ten seconds
before going blank.
NOTE: If the copyright information does not appear, and you have
checked the EPROM installation, contact Reuter-Stokes, Inc..
22. Place the old EPROM in the protective packaging and return it to
Reuter-Stokes, Inc.
70055MP Revision D February 3, 2000
Appendix C: Glossary of Terms
Amperes.
A
Alarm
Averaging Interval
Calibration Parameters
Clear Memory
COM
Combustible Gas
CPU
CT
Download
Gland Plate
Event
I/O
Operating condition occurring when data point value exceeds
the alarm parameter set point.
Configurable time period, up to 60 minutes, when the monitor
automatically takes incoming data levels and transfers them
into memory.
Calibration setpoints for voltage, current, temperature,
combustible gas, and tap position.
Action removes the monitored input data from the monitor non-
volatile memory.
Serial communication port on a personal computer.
Fault gas in the dielectric oil.
Central Processing Unit.
Current transducer.
Command that transfers data stored in memory from the monitor
to a personal computer.
Assembly with pre-punched holes, used for routing cables and
conduits into the monitor.
Tap change time period.
Input/Output.
Load Tap Changer installed on the transformer.
LTC
Milliamperes.
mA
Profile Data Recording
Mode
Relay Parameters
Remote Site
Settable Parameters
Tap Position
Upload
Method in which data is stored and updated in the monitor
memory.
Parameters for transformer control relay and cam signals.
Transformer location – substation.
Root mean square of a number.
Rms
Resistance temperature detector.
RTD
Alarm level parameters for sensor inputs.
LTC tap location.
Command that transfers alarm parameters and site description
information to the monitor.
Volts alternating current.
cleaning, 1-4
combustible gas sensor, 1-6
common point lead, 3-15
communications, 1-4, 2-13, 3-1, 3-20,
3-21, 3-22
configurable input, 1-3
configuration jumpers, 3-4
configuration parameters, 3-24
control isolator, 1-2, 1-3, 1-6
control isolator input, 3-17
CPU board, 2-9, 2-12
CT ratio, 5-1
current date and time screen, 4-5
current readings, 5-1
current time and date screen, 4-6
customer support, 2-1
D
data analysis, 1-2
data retrieval, 1-2
data storage, 1-4
digital channel display, 4-2
digital input channels, 1-2
digital inputs, 3-17
dimensions, 1-5
display, 1-4, 3-1, 4-1, 4-2, 4-5, 4-6
C
cable installation, 3-3
calibration parameters, 5-1
center point, 3-13
channel configuration, 4-1
channel name, 2-4
channel number, 2-4
circuit board location, 2-9
circuit boards, 2-3
clamp-on AC current (CT) sensor, 1-6
3-20, 3-21
signal conditioning circuitry, 2-10
specifications, 1-3
status screen, 4-1, 4-5
status Screen, 4-5
string resistance, 3-15
supply voltage fluctuation, 1-5
system parameters, 3-23
T
tap change summary screen, 2-4
tap position, 3-7, 3-11, 3-14, 3-15, 3-16
tap position calibration, 2-4
tap position indicator, 3-11, 3-16
thumb screws, 2-3
troubleshooting, 5-1
typical application, 1-7
V
voltage drop resistor, 3-14, 3-15
voltage inputs, 3-4, 3-5, 3-17
voltage readings, 5-1
voltage supplies, 2-11