GE
Lighting
GE LED Luminaire
(IS Series)
There are three types of xtures: starter (ISS Series),
continuous (ISC Series) and independent (IS1 series)
BEFORE YOU BEGIN
Read these instructions completely and carefully.
Installation Guide
WARNING/AVERTISSEMENT
RISK OF ELECTRIC SHOCK
• Turn power off before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only IEC approved wire for input/output connections.
Minimum size 18 AWG (0.75 mm2) or 14 AWG (2.5 mm2) for
continuous runs.
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des ls approuvés par IEC pour les entrées/sorties de connexion.
Taille minimum 18 AWG ou 14 AWG pour les rangées continues.
Save These Instructions
Use only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.
Tools and Components Required:
• T15 torx screwdriver
Prepare Electrical Wiring
Electrical Requirements
• The LED driver must be supplied with 120-240 VAC, 50/60 Hz
and connected to an individual properly grounded branch circuit,
protected by a 20 ampere circuit breaker. Use min. 75°C supply
conductor.
Grounding Instructions
• The grounding and bonding of the overall system shall be
done in accordance with National Electric Code (NEC) Article
600 and local codes.
Components Supplied:
• Luminaire
• 2 Mounting Brackets
• Cable glands for 18-14 AWG (0.75-2.5 mm2) supply
input cable/cord connection
Important
• Maximum length of electrical run per table below
Supply
voltage
120V 50m 40m
230V-240V 95m 75m
• Please see technical data sheet for electrical
properties to ensure safe installation.
• Under any circumstance, maximum driver current
through connected xtures shall not exceed 15A.
Lumen Code
A B
imagination at work
Mechanical Installation
IS series luminaires come in three versions: Starter units (ISS series), continuous units (ISC series) and independent units (IS1 series).
A continuous electrical run will consist of one starter unit and a number of continuous units up to a maximum current of 15A. When
installing luminaires use clean gloves in order to avoid fouling the reective surface.
Choose suspension method
Carefully unpack unit from its
1 3
packaging. Properly inspect for
defects before installing. Wear work
gloves to prevent dirt and oil from
being transferred to the luminaire.
Clip luminaire to the previously
4 5
installed mounting brackets.
Attach mounting bracket to ceiling
2
support structure either directly or
using a GE suspension kit according
to the suspension kit instructions
(kit number 69075, 69076, 69077 or
94210 supplied separately). Maximum
distance between suspension points
shall not exceed the length of the
luminaire.
Fix the mounting position and secure
the suspension by tightening the two
screws on both mounting brackets.
Prepare luminaire for installation
by loosening the PSU cover screws
and removing the cover.