There are three types of xtures: starter (ISS Series),
continuous (ISC Series) and independent (IS1 series)
BEFORE YOU BEGIN
Read these instructions completely and carefully.
Installation Guide
WARNING/AVERTISSEMENT
RISK OF ELECTRIC SHOCK
• Turn power off before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only IEC approved wire for input/output connections.
Minimum size 18 AWG (0.75 mm2) or 14 AWG (2.5 mm2) for
continuous runs.
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des ls approuvés par IEC pour les entrées/sorties de connexion.
Taille minimum 18 AWG ou 14 AWG pour les rangées continues.
Save These Instructions
Use only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.
Tools and Components Required:
• T15 torx screwdriver
Prepare Electrical Wiring
Electrical Requirements
• The LED driver must be supplied with 120-240 VAC, 50/60 Hz
and connected to an individual properly grounded branch circuit,
protected by a 20 ampere circuit breaker. Use min. 75°C supply
conductor.
Grounding Instructions
• The grounding and bonding of the overall system shall be
done in accordance with National Electric Code (NEC) Article
600 and local codes.
• Maximum length of electrical run per table below
Supply
voltage
120V50m40m
230V-240V95m75m
• Please see technical data sheet for electrical
properties to ensure safe installation.
• Under any circumstance, maximum driver current
through connected xtures shall not exceed 15A.
Lumen Code
AB
imagination at work
Mechanical Installation
IS series luminaires come in three versions: Starter units (ISS series), continuous units (ISC series) and independent units (IS1 series).
A continuous electrical run will consist of one starter unit and a number of continuous units up to a maximum current of 15A. When
installing luminaires use clean gloves in order to avoid fouling the reective surface.
Choose suspension method
Carefully unpack unit from its
13
packaging. Properly inspect for
defects before installing. Wear work
gloves to prevent dirt and oil from
being transferred to the luminaire.
Clip luminaire to the previously
45
installed mounting brackets.
Attach mounting bracket to ceiling
2
support structure either directly or
using a GE suspension kit according
to the suspension kit instructions
(kit number 69075, 69076, 69077 or
94210 supplied separately). Maximum
distance between suspension points
shall not exceed the length of the
luminaire.
Fix the mounting position and secure
the suspension by tightening the two
screws on both mounting brackets.
Prepare luminaire for installation
by loosening the PSU cover screws
and removing the cover.
Electrical Connections
AC line
Carefully remove appropriate
13
knockout for AC line input wires
(inner knockout for 22mm conduit,
outer knockout for 28mm conduit.
Install supplied cable glands in the
Connect the green (ground), black
2
(line) and white (neutral) wires of the
AC line to the similarly colored wires
of the power supply unit using the
provided terminal.
knockout holes for wire protection
and pass supply conduit through the
cable glands.
Wiring Diagrams
DALI
Fixture
Line
Neutral
Ground
DALI
DALI
Black
White
Green
Violet/White
Violet
0-10V
Fixture
Neutral
Ground
(0-10V) +
(0-10V) –
Line
Black
White
Green
Violet
Grey
Dimming line
(optional)
Optional dimmer: Install supplied
cable glands in the knockout holes
for wire protection and pass supply
conduit through the cable glands.
Connect dimming control wires
(grey and violet for 0-10V or violet
and violet/white strip for DALI) to the
similarly colored xture wire using
the provided terminal.
Replace power supply cover by
4
sliding over the captive screws and
secure by tightening them.
Mechanical Installation for Continuous Runs
Continuous runs must begin with a starter unit which is suspended at both ends. The power supply side end cap from the starter unit
must be removed and used to terminate the run.
Previously
hung unit
To add a continuous unit to a
123
continuous run, rst suspend the
new unit per the instructions above.
Position the non-power-supply end of
the luminaire near the power-supply
end of the previously hung luminaire.
New unit
Remove the PSU cover from the
previously hung luminaire if present.
Continuous runs must begin with
a starter unit. Remove the power
supply side end cap from the starter
unit and save for Step 5.
Pull out continuous wiring
Pull the continuous wiring out of the luminaire being mounted and slide the bridge of the luminaire down onto the bridge of the
4
already installed luminaire so that the tabs and slots at top and bottom nest into one another. The bridges will engage with a load
click when fully mated.
Align tabs
with slots
Push down
to engage
Connect the power and control
5
connectors of the through wiring
harness.
To terminate a mechanical run
67
take the end cap from the starter
luminaire and clip down onto the
last bridge.
Replace the PSU covers and secure
using the mounting screws.
Note: When installation is complete,
all lead wires and connectors shall be
totally enclosed.
Troubleshooting
SymptomSolution
Luminaires will not turn on• Check that the color of the supply side wires match the color of the wires they are connected to.
• Check that the LED driver connector is fully engaged to the LED light engine connector.
Luminaire on through wiring
will not turn on
Luminaire to luminaire mating
in continuous run is loose
Suspension method won’t
engage with luminaire
• Check that the through wiring connector from the previous xture in the linear row is fully
engaged to the malfunctioning luminaire.
• Ensure that both upper and lower connecting features are correctly engaged.
• Ensure that through wires are correctly routed in the wiring notch.
• Check that the suspension method is one of the approved types in the installation instruction.
GE Lighting • 1-888-MY-GE-LED (1-888-69-43-533) • www.gelighting.com