GE HOME GENERATOR 10000 WATT User Manual

5 (1)

GE Home Generator Systems

10,000 Watt

Home Generator System

Operator’s Manual

Reproduction

Not

for

 

Thank you for purchasing this quality-built GE home generator. We’re pleased that you’ve placed your confidence in the GE brand. When operated and maintained according to the instructions in this manual, your home generator will provide many years of dependable service.

This manual contains safety information to make you aware of the hazards and risks associated with home standby generators and how to avoid them. Because we do not necessarily know all the applications this equipment could be used for, it is important that you read and understand these instructions thoroughly before attempting to start or operate this equipment. Save these instructions for future reference.

This home standby generator requires professional installation before use. Refer to the separate installation manual for full information. Your installer should follow the instructions completely.

Where to Find Us

You never have to look far to find GE support and service for your generator. For quick service when you need it, keep your original receipt with this manual. You may contact Customer Service at 888 575 8226 or use the Service Center Locator at BRIGGSandSTRATTON.COM, which provides a list of authorized service dealers.

Generator and engine model and serial numbers should be recorded in the installation manual.

Reproduction

Not

for

 

2

Table of Contents

Important Safety Instructions . . . . . . . . . . . . . . . . 4

Installation . . . . . . . . . . . . .

.

. . .

 

            7

For the Home Owner . . . . . . . . . . . .

.

. . .

.

            7

For the Installing Dealer/Contractor . . . . .

.

. . .

.

. . . . . . . 7

Owner Orientation . . . . . . . . . . . . .

.

. . .

              8

Fuel Factors . . . . . . . . . . . . . . . .

.

 

                  8

Generator Location . . . . . . . . . . . .

.

. . .

.

              9

Delivery Inspection . . . . . . . . . . . . .

.

. . .

              10

Controls . . . . . . . .

.

Reproduction

. . .

.

. . . .

              11

Setting Exercise Timer . . . .

.

. . .

. .

. . for. . . . .

          15

Operation . . . . . . .

.

. . .

.

. . . .

.             14

Automatic Operation . . . .

.

. . . .

.

. . . . .

. .             14

Generator Maintenance . . .

.

. Not. . . . . . . .

. . .

.         18

Maintenance . . . . . .

.

. . .

.

. . . .

. .

        16

Fault Detection System . . .

.

. . . .

.

. . . . .

. . .

          16

Engine Oil . . . . . . . . .

.

. . . .

.

. .  

     

              18

Battery . . . . . . . . . . .

.

. . .

. .

     

     

            19

Storage . . . . . . . . . .

.

. . . .

.

.    

     

              21

Troubleshooting . . . .

.

. . .

.

. . . .

. . .

.       22

Warranty . . . . . . . .

.

. . .

.

. . . .

            23

Product Specifications . .

.

. . .

.

. . . .

. .

. . . . 25

3

Safety Rules
Important Safety Instructions

SAVE THESE INSTRUCTIONS - This manual contains

 

The manufacturer cannot possibly anticipate every possible

important instructions that should be followed during

 

circumstance that might involve a hazard. The warnings

installation and maintenance of the generator and batteries.

 

in this manual, and the tags and decals affixed to the unit

Safety Symbols and Meanings

 

 

 

 

 

are, therefore, not all-inclusive. If you use a procedure, work

 

 

 

 

 

 

 

 

 

 

 

method or operating technique that the manufacturer does

 

 

 

 

 

 

 

 

 

 

 

not specifically recommend, you must satisfy yourself that it

 

 

 

 

 

 

 

 

 

 

 

is safe for you and others. You must also make sure that the

 

 

 

 

 

 

 

 

 

 

 

procedure, work method or operating technique that you

Explosion

Fire

 

 

Electrical Shock

 

choose does not render the generator system unsafe.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING Running engine gives off carbon monoxide, an

 

 

 

 

 

 

 

 

 

 

 

 

 

odorless, colorless, poison gas.

 

 

 

 

 

 

 

 

 

 

 

 

 

Breathing carbon mo

oxide can cause headache, fatigue,

 

 

 

 

 

 

 

 

 

 

 

 

 

dizziness, v

miti g, co

fusion, seizures, nausea, fainting

Toxic Fumes

Rotating Parts

 

 

 

Hot Surface

 

 

 

or death.

 

 

 

 

 

 

 

 

 

 

 

 

 

Operate genera

r ONLY utdoors.

 

 

 

 

 

 

 

 

 

 

 

Install a ba ery operated carbon monoxide alarm near

 

 

 

 

 

 

 

 

 

 

 

 

the bedrooms.

 

 

 

 

 

 

 

 

 

 

 

 

for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keep exha st gas from entering a confined area through

Auto Start

Explosive Pressure

 

 

Chemical Burn

 

 

win ows, doors, ventilation intakes, or other openings.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING The engine exhaust from this product contains

 

 

 

 

 

 

 

 

 

 

chemicals known to the State of California to cause cancer, birth

 

 

 

 

 

 

 

 

 

 

defects, or other reproductive harm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lift Hazard

Read Manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING Certain components in this product and related

The safety alert symbol indicates a potential rsonal

 

accessories contain chemicals known to the State of California

injury hazard. A signal word (DANGER, WA

NING, or

 

to cause cancer, birth defects, or other reproductive harm. Wash

CAUTION) is used with the alert symbol to designate a degree

hands after handling.

 

 

 

 

 

 

or level of hazard seriousness. A safety symbol may be used

 

 

 

 

 

 

 

 

 

 

 

 

Reproduction

to represent the type of hazard. The signal word NOTICE is

 

 

 

 

 

 

used to address practices not related to personal injury.

 

 

 

 

 

 

DANGER indicates a hazard which, if not avoided, will result in death or serious injury.

WARNING indicates a hazard which, if not avoided, could result in death or serious injury.

CAUTION indicates a hazard which, if not avoided, could result in minor or moderate injury.

NOTICE addresses practices not related to personal injury.

4

 

WARNING Storage batteries give off explosive hydrogen gas

 

 

 

WARNING Generator produces hazardous voltage.

 

during recharging.

 

 

 

 

Failure to properly ground generator can result in

 

Slightest spark will ignite hydrogen and

 

 

 

electrocution.

 

cause explosion.

 

 

 

 

Failure to isolate generator from power utility can result in

 

Battery electrolyte fluid contains acid and is

 

 

death or injury to electric utility workers due to backfeed of

 

extremely caustic.

 

 

 

 

electrical energy.

Contact with battery contents will cause severe chemical burns.

 

 

When using generator for backup power, notify utility company.

A battery presents a risk of electrical shock and high short

 

 

DO NOT touch bare wires or bare receptacles.

circuit current.

 

 

 

 

 

 

DO NOT use generator with electrical cords which are worn,

DO NOT dispose of battery in a fire. Recycle battery.

 

 

 

 

 

frayed, bare or otherwise damaged.

DO NOT allow any open flame, spark, heat, or lit cigarette during

 

 

 

DO NOT handle generator or electrical cords while standing in

 

and for several minutes after charging a battery.

 

 

 

 

 

 

water, while barefoot, or while hands or feet are wet.

DO NOT open or mutilate the battery.

 

 

 

 

 

 

 

If you must work arou d a u it while it is operating, stand on an

Wear protective goggles, rubber apron, rubber boots and

 

 

 

 

 

insulated dry surface to reduce the risk of a shock hazard.

 

rubber gloves.

 

 

 

DO NOT allow unqual fied persons or children to operate or

Remove watches, rings, or other metal objects.

 

 

 

 

 

service genera

r.

Use tools having insulated handles.

 

 

 

In ase of an a

dent caused by electrical shock, immediately

 

 

 

 

 

 

shut down he source of electrical power and contact the local

 

WARNING Propane and Natural Gas are extremely flammable

fora thorities. Avoid direct contact with the victim.

 

 

 

Despite the safe design of the residential generator, operating

 

and explosive.

 

 

 

 

Fire or explosion can cause severe burns or death.

 

 

this eq ipment imprudently, neglecting its maintenance or being

Install the fuel supply system according to FPA 37 and other

 

 

 

careless can cause possible injury or death.

 

 

Remain alert at all times while working on this equipment.

 

applicable fuel-gas codes.

 

 

 

 

 

 

 

 

Never work on the equipment when you are physically or

Before placing the generator into service, the fuelNotsystem lines

 

 

 

 

 

 

mentally fatigued.

 

must be properly purged and leak tested.

 

 

 

 

 

 

 

 

Before performing any maintenance on the generator, disconnect

After the generator is installed, you should insp the fu l

 

 

 

 

 

the battery cable indicated by a NEGATIVE, NEG or (-) first. When

 

system periodically.

 

 

 

 

 

 

 

 

 

finished, reconnect that cable last.

NO leakage is permitted.

 

 

 

 

 

 

 

After your system is installed, the generator may crank and start

DO NOT operate engine if smell of fuel is present or other

 

 

 

without warning any time there is a power failure. To prevent

 

explosive conditions exist.

 

 

 

 

possible injury, always set the generator’s system switch to OFF,

DO NOT smoke around the generator. Wipe up any oil spills

 

 

 

remove the service disconnect from the disconnect box AND

 

 

Reproductionremove the 15 Amp fuse BEFORE working on the equipment.

 

immediately. Ensure that no combustible materials are left in the

 

 

 

 

 

generator compartment. Keep the area near the generator clean

 

 

 

 

 

and free of debris.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

• Observe that the 15 Amp fuse has been removed from the control panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has been completed and inspected.

 

WARNING Contact with muffler area can result in

 

 

 

CAUTION Excessively high operating speeds increase risk of

 

serious burns.

 

 

 

injury and damage to generator.

 

Exhaust heat/gases can ignite combustibles or

 

 

Excessively low speeds impose a heavy load on generator.

 

structures causing a fire.

 

 

 

DO NOT tamper with governed speed. Generator supplies correct

DO NOT touch hot parts and AVOID hot exhaust gases.

 

 

 

rated frequency and voltage when running at governed speed.

Allow equipment to cool before touching.

 

 

 

DO NOT modify generator in any way.

DO NOT install the generator closer than 5 feet (1.5m) from any

 

 

 

 

 

 

 

 

 

 

 

combustibles or structures with combustible walls having a fire

 

 

NOTICE Exceeding generators wattage/amperage capacity can

 

resistance rating of less than 1 hour.

 

 

 

 

 

 

 

damage generator and/or electrical devices connected to it.

Keep at least minimum distances shown in General Location

 

 

 

 

Start generator and let engine stabilize before connecting

 

Guidelines to insure for proper generator cooling and

 

 

 

 

 

 

electrical loads.

 

maintenance clearances.

 

 

 

 

 

 

 

 

 

 

 

It is a violation of California Public Resource Code, Section 4442,

 

NOTICE Improper treatme t of generator can damage it and

 

to use or operate the engine on any forest-covered, brush-

 

 

 

 

 

sh ten its life.

 

covered, or grass-covered land unless the exhaust system is

 

 

 

 

 

Use genera

r nly f r intended uses.

 

equipped with a spark arrester, as defined in Section 4442,

 

 

 

 

 

If you have ques ns ab ut intended use, contact your

 

maintained in effective working order. Other states or federal

 

 

 

jurisdictions may have similar laws.

 

 

 

 

authorized dealer.

 

Contact the original equipment manufacturer, retailer, r dealer

 

 

Operate generator only on level surfaces.

 

 

 

for

 

 

obtain a spark arrester designed for the exhaust system installed

 

Adeq ate,

nobstructed flow of cooling and ventilating air is

 

on this engine.

 

 

 

 

 

 

 

 

critical to correct generator operation.

Replacement parts must be the same and installed in the same

 

 

 

 

 

The access panels/door must be installed whenever the unit

 

position as the original parts.

 

 

 

 

 

 

 

 

is running.

 

 

 

 

 

 

 

 

 

 

Not

 

 

DO NOT expose generator to excessive moisture, dust, dirt, or

 

WARNING Starter and other rotating parts can entangle hands,

 

 

corrosive vapors.

 

hair, clothing, or accessories.

 

 

 

Remain alert at all times while working on this equipment.

 

 

 

 

 

 

Never work on the equipment when you are physically or

 

 

 

 

 

 

mentally fatigued.

NEVER operate generator without protective housings, cov rs, or

 

DO NOT start engine with air cleaner or air cleaner cover removed.

 

guards in place.

 

 

 

DO NOT insert any objects through cooling slots.

DO NOT wear loose clothing, jewelry or anything that may be

 

 

DO NOT use the generator or any of its parts as a step. Stepping

 

caught in the starter or other rotating parts.

 

 

 

the unit can cause stress and break parts. This may result in

Tie up long hair and remove jewelry.

Reproduction

 

 

 

 

dangerous operating conditions from leaking exhaust gases, fuel

Before servicing, remove 15 Amp fuse from control panel and

 

 

 

leakage, oil leakage, etc.

 

disconnect Negative (NEG or -) battery cable.

 

 

If connected devices overheat, turn them off and disconnect them

 

 

 

 

 

 

from generator.

 

 

 

 

 

 

 

 

 

 

 

Shut off generator if:

 

CAUTION Installing the 15A fuse could cause the engine

 

 

 

 

 

-electrical output is lost;

 

to start.

 

 

 

 

 

 

 

 

 

-equipment sparks, smokes, or emits flames;

 

 

 

 

 

 

 

 

 

 

 

 

-unit vibrates excessively.

 

 

 

 

 

 

 

 

6

Installation

We sincerely appreciate your patronage. For this reason, we have made every effort to provide for a safe, streamlined and cost-effective installation. Because each installation is unique, it is impossible to know of and advise the trade of all conceivable procedures and methods by which installation might be achieved. Neither could we know of possible hazards and/or the results of each method or procedure. For these reasons,

Only current licensed electrical and plumbing professionals should attempt home generator system installations. Installations must strictly comply with all applicable codes, industry standards and regulations.

Your home generator is supplied with this “Operator’s Manual” and a separate “Installation Manual”. These are important documents and should be retained by the owner after the installation has been completed.

For the Home Owner

To help you make informed choices and communica e

 

The home genera r warranty is VOID unless the system is

effectively with your installation contractor(s),

 

installed by li ensed electrical and plumbing professionals.

Read and understand Owner Orientation in this

forEvery effort has been made to ensure that information in this

manual before contracting or starting your h me

 

man al is accurate and current. However, we reserve the

generator installation.

 

 

right to change, alter, or otherwise improve the product and

To arrange for proper installation, contact the store at which

this ocument at any time without prior notice.

 

Not

The Emission Control System for this generator is warranted

you purchased your home generator, your dealer, a licensed

 

electrician or your utility power provider.

 

 

f standards set by the U.S. Environmental Protection

 

 

 

Agency and by the California Air Resources Board (CARB).

 

Reproduction

For the Installing Dealer/Contractor

For most applications, the installation manual contains all the information required to properly install and start the home generator. This operator’s manual describes routine operation and owner maintenance procedures.

If you need more information in this matter, please call 888 575 8226 between 8:00 AM and 5:00 PM CT.

7

Owner Orientation

This section provides home generator owners with the information necessary to achieve the most satisfactory and cost effective installation possible.

The illustrations are for typical circumstances and are meant to familiarize you with the installation options available with your home generator. A thorough understanding of these options will provide fundamental control over the cost of your installation, as well as ensure your final satisfaction and security.

Federal and local codes, appearance, noise levels, fuel types, and distances are the factors that must be considered when negotiating with an installation professional. Remember that as the distance from the existing electrical service and

gaseous fuel supply increases, and the number of 90 degree bends in the fuel supply increases; compensations in piping and wiring materials must be made. This is necessary to comply with local codes and overcome electrical voltage drops and gaseous fuel pressure drops.

The factors mentioned above will have a direct affect on the overall price of your home generator installation.

In some areas you may need to acquire electrical permits for installing the home generator, building permits for installing gas lines, and permits for noise allowances. Your installer should check your local codes AND obtain the permits before installing the system.

Fuel Factors

 

 

for

 

 

 

An important consideration affecting the entire installati

n

 

 

 

 

WARNING Propane and Natural Gas are extremely flammable

is the type of fuel used by your home generator. The system

 

 

 

 

and explosive.

was factory tested and adjusted using natural gas, but can

 

 

 

 

Fire or explosion can cause severe burns or death.

be converted to use LP vapor. For proper engine function,

 

 

The residential generator is equipped with an automatic safety

factors that are inherent to each of these fuels, your

 

 

 

 

 

gas “fuel shut-off” valve.

 

Not

 

 

 

 

 

 

location and the duration of possible utility interru tions a

 

DO NOT operate the equipment if the “fuel shut-off” valve is

important considerations in the following fuel guidelines:

 

 

 

 

 

missing or inoperative.

• Use clean, dry fuel, free of moisture or any

 

 

 

 

 

 

 

 

 

Power Decrease at High Altitude or

particulate material. Using fuels outside the

 

 

 

 

High Temperature

following recommended values may cause

 

 

 

 

Air density is less at high altitudes, resulting in less available

performance problems.

 

 

 

• In engines set up to run on propane (LP), commercial

 

engine power. Specifically, engine power will decrease 3.5%

grade HD5 propane with a minimum fuel energy of

for each 1,000 feet (300 meters) above sea level and 1%

 

Reproduction

2500 BTUs/ft3 with maximum propylene content of

for each 10° F (5.6°C) above 77°F (25°C). Make sure you and

your installer consider these factors when determining total

5% and butane and heavier gas content of 2.5% and

generator load.

minimum propane content of 90%.

 

Natural gas rating will depend on specific fuel but typical derates are between 10 to 20% off the LP gas rating.

8

Generator Location

The actual physical location of your home generator has a

 

 

 

 

 

WARNING Running engine gives off carbon monoxide, an

direct affect on:

 

 

 

 

 

 

 

 

odorless, colorless, poison gas.

1. The amount of plumbing required to fuel

 

 

 

Breathing carbon monoxide can cause headache, fatigue,

your generator.

 

 

 

 

dizziness, vomiting, confusion, seizures, nausea, fainting

 

 

 

 

or death.

2. The amount of wiring required to control and connect

 

 

 

Operate generator ONLY outdoors.

your generator.

 

 

 

 

 

 

Install a battery operated carbon monoxide alarm near

 

 

 

 

Specific location guidelines are discussed in the installation

 

 

the bedrooms.

manual. Acquaint yourself with that information and confer

 

Keep exhaust gas from entering a confined area through

with your installer. Be sure to ask how your site might

 

 

 

windows, doors, ventilation intakes, or other openings.

affect installation costs and compliance with local codes

 

 

 

and standards.

 

 

 

 

 

 

 

 

 

WARNING Exhaust heat/gases can ignite combustibles or

The generator must be installed outdoors. DO NOT install

 

 

structures causing a fire.

generator where exhaust gas could accumulate and enter

 

DO NOT install the generator closer than 5 feet (1.5m) from any

inside or be drawn into a potentially occupied building.

 

 

 

 

 

combustibles or structures with combustible walls having a fire

Ensure exhaust gas is kept away from any windows, doors,

 

 

 

 

resistance rating of less than 1 hour.

ventilation intakes or other openings that can allow exhaust

 

 

 

 

 

 

 

 

gas to collect in a confined area. Prevailing winds and air

 

 

 

currents should be taken into consideration when positioning

 

generator. See the installation manual for full details

safe

for

generator location.

 

 

 

Not

 

 

 

 

 

Reproduction

9

Delivery Inspection

Carefully inspect the home generator for any damage that may have occurred during shipment.

If loss or damage is noted at time of delivery, have the person(s) making delivery note all damage on the freight bill and affix his signature under the consignor’s memo of loss or damage. If loss or damage is noted after delivery, separate the damaged materials and contact the carrier and your installer for claim procedures. Missing or damaged parts are not warranted.

The home generator system is supplied with:

• Pre-attached mounting pad

 

 

• Fully-serviced oil/lubricating system

 

• Flexible fuel hook-up hose

 

 

• Installation and start-up manual

 

 

Operator’s manual

Reproduction

 

 

Engine operator’s manual

 

for

 

 

Installation checklist

 

 

• Spare access door keys

 

 

Spare 15A fuse

Not

 

• Two pin control panel connector

 

 

 

• Ten pin control panel connector

 

 

Touch up paint

 

 

Oil drain tray

 

 

Roof hardware

 

 

• Remote LED indicator kit (LED/plate/screws)

 

Not included:

 

 

Starting battery

 

 

• Connecting wire and conduit

 

 

Fuel supply valves/plumbing

 

 

Various specialty tools/equipment

 

 

10

Controls

Home Generator

Read this operator’s manual and Important Safety Instructions before operating your generator. Compare the illustration with your generator to familiarize yourself with the locations of various controls and adjustments. Save this manual for future reference.

E F

G

 

Reproduction

H

D

 

for

J

C

Not

 

 

 

 

 

K

B

 

 

 

A

 

 

L

 

 

 

Generator is shown with roof and access covers removed

F - Engine Label — Identifies engine model and type.

for clarity.

 

G - Oil Fill Cap/Dipstick — Check and fill engine with

 

 

A - Lifting Pocket — Provided at each corner for

recommended oil here.

 

lifting generator.

 

H - Control Panel — Used for various test, operation and

B - Exhaust Port — High-performance muffler lowers engine

maintenance functions. See System Control Panel.

noise to comply with most residential codes.

J - Oil Drain Hose — Located inside access cover on side

C - Fuel Inlet — Attach appropriate fuel supply to

panel. Provided to facilitate oil changing.

generator here.

 

K - Unit Identification Label — Identifies unit by serial number.

D - Oil Filter — Filters engine oil to prolong generator life.

L - Battery (installer supplied) — 12 Volt DC, sealed battery

E - Air Cleaner — Uses a dry type filter element and foam

provides power to start the engine.

 

precleaner to protect engine by filtering dust and debris out of intake air.

11

GE HOME GENERATOR 10000 WATT User Manual

System Control Panel

Compare this control panel illustration with your generator to familiarize yourself with the location of these important controls:

D E F

A

Reproduction

 

for

C

 

 

B

 

 

 

Not

 

A - SET EXERCISE— Used to set the exercise cycle start

E - System Switch — This two-position switch is the most

time and day-of-the-week. Exercise cycle only occurs in

important control the system and is used as follows:

AUTO mode.

 

• “AUTO” position is the normal operating position. If a

B – MANUAL OVER-RIDE With system switch in AUTO

utility power outage is sensed, the system will start the

position, push the manual over-ride switch to start the

generator. When utility power is restored, AUTO lets

generator. To turn off the generator, push and hold the

the engine stabilize internal temperatures, shuts off the

manual over-ride switch again until engine stops.

generator, and waits for the next utility power outage.

C - Circuit Breaker — Protects the generator from shorts and other over-current conditions. Must be ON to supply power to the automatic transfer switch.

D - 15 Amp Fuse — Protects the home generator DC control circuits. If the fuse has ‘blown’ (melted open) or was removed, the engine cannot crank or start. Replace the fuse using only an identical ATO 15A fuse.

OFF” position turns off running generator, prevents unit from starting and resets any detected faults.

F - Digital Display — Displays the total number of hours the generator has been running and fault codes. Used to schedule maintenance tasks and for troubleshooting operational problems with the residential generator. A constant number displayed indicates the total hours of operation. Fault conditions will flash “FC” followed by a fault code number. All fault conditions are described in

Fault Detection System.

12

3. Replace panel screw(s).
4. Replace roof and screws.
To install side panel:
1. Guide bottom of side into base.
Access Ports

The home generator is equipped with several access

 

Each home generator is suppied with a set of identical keys.

openings and a removable roof to permit simple oil and

 

These keys fit the locks that secure the access door.

filter servicing.

 

 

To open access door:

 

 

 

 

To remove roof:

 

 

 

1. Insert key into lock of access door and turn key one

Remove the four screws and lift off. Replace roof in

 

 

quarter turn counterclockwise.

reverse order.

 

 

 

2. Grasp door’s handle and turn one quarter turn

 

 

 

 

 

To remove access cover:

 

 

 

counterclockwise to open. Remove key.

 

 

 

 

Remove the two screws, tilt cover out, and lift cover off

 

To close access door:

panel. Replace cover in reverse order.

 

 

 

1. Close door and turn doors handle one quarter

 

 

 

 

 

To remove side panel (if necessary):

 

 

 

turn clockwise.

 

 

 

2. Insert key into lock of access door and turn key one

 

1. Remove roof.

 

 

 

 

 

 

 

quarter turn clockwise. Remove key.

 

2. Remove screw(s) attaching side panel.

 

 

 

 

 

 

 

 

 

 

 

 

WARNING Contact with muffler and engine parts can result in

 

for

 

 

serious burns.

 

 

 

DO NOT touch hot parts and AVOID hot exhaust gases.

 

 

Allow equipment to cool before touching.

Not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reproduction

3. Pull panel outward (away) from unit while pulling panel upward and out of base.

2. Push panel until it is flush with sides.

13

Operation

Important Owner’s Considerations

Engine Oil

NOTICE Any attempt to crank or start the engine before it has been properly serviced with the recommended oil will result in equipment failure.

Refer to Maintenance in the operator’s manual and engine manual for oil fill information.

Damage to equipment resulting from failure to follow this instruction will void engine and generator warranty.

WARNING Battery posts, terminals and related accessories contain lead and lead compounds, chemicals known to the State of California to cause cancer and reproductive harm. Wash hands after handling.

With the battery installed, all wiring to transfer switch and home generator completed, utility power supplied to the automatic transfer switch, and the unit in AUTO mode, the battery receives a trickle charge while the engine is not

This engine is shipped from the factory pre-run and filled

 

running. The trickle charge cannot be used to recharge a

with synthetic oil (API SJ/CF 5W-30). This allows for system

 

battery that is completely discharged.

operation in a wide range of temperature and climate

 

15 Amp Fuse

conditions. Before starting the engine, check oil level as

 

The generator’s 15 Amp fuse is critical to correct system

described in the engine manual.

 

 

 

 

pe ation. The 15 Amp fuse was removed at the factory to

Battery

 

 

 

 

prevent the un fr m starting during shipping. Your installer

The installer must supply a valve-regulated, rechargeable

 

will ensure he fuse s properly installed upon completion of

12 volt DC starting battery. See Battery in Final Installa

 

the installa ion.

Considerations in the installation manual.

Not

for

Automatic Operation

 

 

 

 

 

 

 

 

To select automatic operation, do the following:

 

 

 

CAUTION With the system switch set to AUTO, the engine may

 

 

 

1. Confirm 15 Amp fuse is installed in control panel.

 

crank and start at any time without warning.

2. Set the main distribution panel circuit breaker that

 

• To prevent possible injury that may be caused by such sudden

sends utility voltage to the transfer switch to ON.

 

 

Reproductionstarts, always set the system switch to OFF if performing

3. Set the generator’s main circuit breaker to its

 

maintenance on the system.

ON position.

 

 

 

 

• Remove the 15 Amp fuse before working on or around the

 

 

 

4. Set the control panel system switch to AUTO.

 

generator or transfer switch.

14

Checking Automatic Operation

To check the system for proper automatic operation, proceed as follows:

1.Turn OFF the main distribution panel circuit breaker sending power to the automatic transfer switch.

When utility voltage is lost and the sensor has timed out, the engine will crank and start. Let the system go through its entire automatic operation sequence.

2.With generator output supplying its loads, turn ON the service disconnect or main distribution panel circuit breaker that supplies utility power to the automatic transfer switch.

3.The automatic transfer switch will transfer loads back to utility power after a 5 minute minimum run time and utility power is available.

4.The generator will run for one additional minute for engine cool down, then will shut down.

If utility is restored and generator does not shut down after 10 minutes, set system switch to OFF and contact your installer or local service center.

This completes the test procedures for automatic operation. The home generator will now start automatically and will supply power to the transfer switch when utility power is lost.

Setting Exercise Timer

The home generator is equipped with an exercise timer hat

 

To perform he Set Exercise procedure:

will start and exercise the system once every seven days.

for

1. Choose he day and time you want your home

During this exercise period, the unit runs for appr

xima ely

generator to exercise.

20 minutes and then shuts down. Electrical load transfer

 

 

2. On that day and time, press and hold “SET EXERCISE”

DOES NOT occur during the exercise cycle (unless an utility

 

 

 

 

for three seconds.

power outage occurs during the cycle).

 

 

 

 

 

 

 

A button on the control panel is labeled “SETNotEXERCISE”

 

“SET EXERCISE” will flash until the button is pressed for

(see System Control Panel). The specific day and the specific

 

 

three seconds, then “SET EXERCISE” will illuminate for

 

 

5 seconds, and finally turn off.

time of day this button is pressed is programmed into the

 

 

 

 

3. The unit will then start and run it’s 20 minute

control board memory. This date and time is th

us d

 

 

to automatically initiate the system exercise cycle. The

 

 

exercise cycle.

“SET EXERCISE” legend on the control panel will flash until the

For example, if you press SET EXERCISE on Sunday morning

set exercise cycle is set.

 

 

 

 

Reproductionat 10:00 AM, the unit will run an immediate exercise cycle and an exercise cycle every following Sunday at 10:00 AM

(+/- 1/2 hour).

“Set Exercise” will only work if the unit is in the AUTO mode and this exact procedure is followed. The exerciser will need to be re-set if the 15 Amp fuse is removed or changed, or if the starting battery is disconnected.

If you want to change the day and time the unit exercises, simply perform the “Set Exercise” procedure at the exact weekday and time you want it to take place.

15

Maintenance

Servicing the System

Before performing any generator maintenance, always perform the following steps:

1.Set generator’s circuit breaker to its OFF position.

2.Set control panel system switch to OFF.

3.Remove 15 Amp fuse from control panel.

4.Utility voltage is present at generator control panel.

Disconnect power before servicing control panel by removing the fuses from the transfer switch.

5.After all servicing has been completed, replace fuses in transfer switch, replace 15 Amp fuse in control panel, set system switch and circuit breaker ON and reset exercise timer. See Setting Exercise Timer

in Operation.

Fault Detection System

Reproduction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for

The generator may have to run for long periods of time

 

Reset Fault Detecti n System

with no operator present. For that reason, the system is

 

The pera or must reset the fault detection system each time

 

 

Not

 

equipped with sensors that automatically shut down he

 

it activates. To do so, place the control panel System switch

generator in the event of potentially damaging c ndi i

ns,

 

 

in the OFF position for 30 seconds or more. Remedy the

such as low oil pressure, high temperature, over speed, and

 

 

fa lt ondition, then return the home generator to service

other conditions.

 

 

 

 

 

 

 

 

 

 

 

 

by placing the system switch in the AUTO position, installing

The generator’s control panel has a digital display that

 

 

 

 

the 15 Amp fuse, and resetting the exercise timer. See Setting

shows fault codes, like “FC_1”. The table below lists the

 

 

Exercise Timer in Operation.

detected fault, the fault code as displayed

the cont ol

 

No LED - Discharged Battery

panel, and the number of LED flashes (also described as

 

 

If there is a detected fault condition but the LED is not

‘blinks’) seen on the remote LED indicator.

 

 

 

 

 

 

 

 

 

 

blinking, this is because the battery is completely discharged.

 

 

 

 

 

 

 

Fault Description

Fault Codes

 

LED Flashes

 

To remedy the problem, remove the 15 Amp fuse and

Low battery voltage

FC_1

 

 

 

1

 

disconnect the battery from the generator. Take the battery

Low oil pressure

FC_2

 

 

 

2

 

to a local battery store for analysis. Reinstall the battery

 

 

 

 

 

 

 

after it has been fully recharged, connecting the NEGATIVE

Low voltage

FC_3

 

 

 

3

 

 

 

 

 

cable last. Then reset the fault detection system, as

Engine fails to start

FC_4

 

 

 

4

 

 

 

 

 

described earlier.

 

 

 

 

 

 

 

Low frequency

FC_5

 

 

 

5

 

 

 

 

 

Low Battery Voltage (FC_1)

 

 

 

 

 

 

 

Engine overspeed

FC_6

 

 

 

6

 

 

 

 

 

This fault is indicated by fault code FC_1 and one blink on the

High temperature

FC_7

 

 

 

7

 

 

 

 

 

LED indicator. This condition occurs if the generator cannot

 

 

 

 

 

 

 

Transfer switch fault

FC_8

 

 

 

8

 

 

 

 

 

start because the starting battery output power is below that

The remote LED indicator is installed at a convenient inside

 

needed to crank the engine. Causes for this problem may be

 

a faulty battery or battery charge circuit.

location. The LED will remain lit when the generator is in

 

Remove the 15 Amp fuse and disconnect the battery from

AUTO. Should a system fault be detected, the LED will turn

the generator. Take the battery to a local battery store for

on and off in a series of blinks that identify the problem. The

analysis. Or contact your local service center for assistance.

blink pattern is repeated with a brief pause between each

Reinstall the battery (replace if necessary - see Battery in

series of blinks.

Final Installation Considerations in the installation manual).

 

 

Then reset the fault detection system, as described earlier.

16

Low Oil Pressure (FC_2)

 

Low Frequency (FC_5)

This fault is indicated by fault code FC_2 and two blinks on

 

This fault is indicated by fault code FC_5 and five blinks on

the remote LED indicator. The unit is equipped with an oil

 

the LED indicator. This feature protects devices connected

pressure switch that uses normally closed contacts held

 

to the transfer switch by shutting the generator down if the

open by engine oil pressure during operation. Should oil

 

engine runs slower than 55 Hz for three seconds.

pressure drop below the 8 psi range, switch contacts close

 

This condition is caused by a failed engine component or by

and the engine is shut down.

 

excessive loads on the generator. To remedy the problem,

To remedy the low oil pressure condition, add the

 

contact your installer or an authorized dealer.

recommended oil to the FULL mark on the dipstick.

 

Engine Overspeed (FC_6)

If the low oil pressure condition still exists, the engine will

 

This fault is indicated by fault code FC_6 and six blinks on the

start, then shut down again. The fault code will appear and

 

 

LED indicator. This feature protects devices connected to the

the LED will flash. In this case, contact an authorized dealer.

 

 

transfer switch by shutting the generator down if the engine

Low Voltage (Generator, FC_3)

 

 

happens to run faster than the preset limit.

This fault is indicated by fault code FC_3 and three blinks on

 

The overspeed fault is detected as follows:

the LED indicator. This condition is caused by a restriction in

 

• If the generator output frequency is 65-70 Hz, after

the fuel flow, a broken or disconnected signal lead, a failed

 

three seconds, the generator will shut down.

alternator winding, the control panel circuit breaker is open,

 

• If the generator output frequency is greater than

or the generator is overloaded.

 

 

70 Hz, the ge erator will shut down immediately.

To remedy the problem, contact your installer or an

 

 

This condition is caused by a failed engine component.

authorized dealer.

 

 

To emedy the pr blem, c tact your installer or an

Engine Fail To Start (FC_4)

 

 

auth rized dealer.

This fault is indicated by fault code FC_4 and four blinks

 

High Tempera ure (FC 7)

the LED indicator. This feature prevents the generator from

 

This fault is indi ated by fault code FC_7 and seven blinks on

damaging itself if it continually attempts to start in spi e

 

for

of another problem, such as no fuel supply. Each time the

 

the LED indi ator. The contacts of the temperature switch

 

are normally open. If the engine temperature exceeds

system is directed to start, the unit will crank f r 10 sec nds,

 

 

approximately 149°C (300°F), the fault is detected and the

pause for 10 seconds, and repeat. If the system does not

 

 

engine shuts down.

begin producing electricity after approximately 2 minutes,

 

 

C mmon causes for this condition include running the unit

the unit will stop cranking and the LED will blink.

 

Not

 

with access panels removed, obstructed air inlet or exhaust

Check to make sure the generator’s main circuit breaker is in

port, low oil level, or debris in the engine cylinder cooling fins.

the ON position in order for the sensing leads to v rify that

 

 

To resolve the problem, let the engine cool down and remove

the unit is running.

 

The most likely cause of this problem is no fu l supply. Check

any accumulated debris and obstructions. Ensure that all

access panels are installed whenever the unit is running.

the internal and external fuel shut off valves to ensure they

 

 

Transfer Switch Fault (FC_8)

are fully open. Other causes could be failed spark plug(s),

 

failed engine ignition, or the engine air filterReproductionis clogged. You

may need to contact your installer for assistance if you can’t

 

This fault is indicated by fault code FC_8 and eight blinks

 

on the LED indicator (if transfer switch is equipped with

remedy these problems.

 

fault detection).

The most likely cause of this fault is a blown fuse in the transfer switch. To remedy the problem, contact your installer or an authorized dealer.

17

Changing Engine Oil

Generator Maintenance

The generator warranty does not cover items that have been subjected to operator abuse or neglect. To receive full value from the warranty, the operator must maintain the system as instructed in the engine operator’s manual.

All adjustments should be made at least once each season. Follow the requirements in the engine operator’s manual.

Generator maintenance consists of keeping the unit clean. Operate the unit in an environment where it will not be exposed to excessive dust, dirt, moisture or any corrosive vapors. Cooling air louvers on the enclosure must not become clogged with snow, leaves, or any other

foreign material. To prevent generator damage caused by overheating, keep the enclosure cooling inlets and outlets clean and unobstructed at all times.

Check the cleanliness of the unit frequently and clean when dust, dirt, oil, moisture or other foreign substances are visible on its exterior/interior surface. Inspect the air inlet and outlet openings inside and outside the enclosure to ensure air flow is not blocked.

DO NOT use direct spray from a garden hose to clean generator. Water can enter the engine and generator and cause problems.

Engine Oil

The engine is filled with synthetic oil (API SJ/CF 5W-30). This allows for system operation in the widest range of temperature and climate conditions.

The use of synthetic oil does not alter the required oil change

Changing Engine Oil and Oil Filter

Remove the two screws from each access cover and rem ve both access covers from the generator enclosure.

intervals described in the engine operator’s manual.

for

 

Not

Reproduction

CAUTION Avoid prolonged or repeated skin contact with used motor oil.

• Used motor oil has been shown to cause skin cancer in certain laboratory animals.

• Thoroughly wash exposed areas with soap and water.

KEEP OUT OF REACH OF CHILDREN. DON’T POLLUTE. CONSERVE RESOURCES. RETURN USED OIL TO COLLECTION CENTERS.

1.Set control board system switch to OFF.

2.Remove 15 Amp fuse from control panel.

3.Place oil drain hose into an approved container.

4.Remove brass fitting from end of drain hose.

Change oil while the engine is still warm from running, as described in the engine operator’s manual.

5.When oil has drained, replace brass fitting on hose.

6.Add oil if not changing oil filter. See below.

18

Changing Oil Filter

1.Place oil drain tray over tubing and slide it under oil filter.

2.Follow instructions given in engine operator’s manual for changing oil filter.

3.Remove oil drain tray from under oil filter and clean up any spilled oil.

NOTICE Any attempt to crank or start the engine before it has been properly serviced with the recommended oil will result in equipment failure.

Refer to Maintenance in the operator’s manual and engine manual for oil fill information.

Damage to equipment resulting from failure to follow this instruction will void engine and generator warranty.

To fill your engine with oil:

Follow the synthetic oil grade recommendation and oil fill instructions given in the engine operator’s manual.

If all engine servicing is complete, replace 15 Amp fuse in control panel and reset exercise timer. See Setting Exercise Timer in Operation.

Battery

 

 

 

 

 

 

 

 

 

Reproduction

Servicing of batteries is to be performed or supervised

for

 

WARNING Battery posts, terminals and related accessories

by personnel knowledgeable of batteries and the

 

contain lead and lead compounds, chemicals known to the State

required precautions. Keep unauthorized pers

nnel away

 

of California to cause cancer and reproductive harm. Wash hands

from batteries.

 

Not

 

after handling.

Servicing the Battery

 

 

5. Connect black negative battery cable to negative

 

 

 

 

If it is necessary to service the battery, proc

 

d as follows:

 

 

 

battery terminal (indicated by NEGATIVE, NEG, or (-).

1. Set control board system switch to OFF.

 

 

6. Ensure hardware both positive and negative

2. Remove 15 Amp fuse from control panel.

 

 

battery terminals is secure.

3. Service or replace battery as required. See Battery

 

 

7. Reinstall 15 Amp fuse in control panel.

in Final Installation Considerations in the installation

 

 

8. Set generator’s system switch to AUTO.

manual for specific battery needed.

 

 

 

 

 

 

 

4. Connect red battery cable to battery positive terminal

 

9. Reset exercise timer. See Setting Exercise Timer.

 

 

(indicated by POSITIVE, POS, or (+)).

 

 

 

DON’T POLLUTE. CONSERVE RESOURCES, RETURN

 

 

 

 

 

USED BATTERY TO RECYCLING COLLECTION CENTER.

19

• Use a vacuum cleaner to pick up loose dirt and debris.
• Use low pressure air (not to exceed 25 psi) to blow away dirt. Inspect cooling air slots and openings on the generator. These openings must be kept clean and unobstructed.
4. Reinstall 15 Amp fuse in control panel.
5. Set generator’s system switch to AUTO.
6. Reset exercise timer. See Setting Exercise Timer.
• Remove the 15 Amp fuse before working on or around the generator or transfer switch.
5. Connect negative battery cable to negative battery terminal (indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative battery terminals is secure.
7. Reinstall 15 Amp fuse in control panel.

Charging the Battery

If it is necessary to charge the battery, proceed as follows: 1. Set control board system switch to OFF.

2. Remove 15 Amp fuse from control panel.

3. Disconnect negative battery cable from negative battery terminal (indicated by NEGATIVE, NEG, or (-)).

NOTICE Failure to disconnect negative battery cable will result in

 

CAUTION With the system switch set to AUTO, the engine may

equipment failure.

crank and start at any time without warning.

DO NOT attempt to jump start the generator.

 

Damage to equipment resulting from failure to follow this

• To prevent possible injury that may be caused by such sudden

 

instruction will void engine and generator warranty.

 

4. Charge battery with battery charger at 2 Amps until

starts, always set the system switch to OFF if performing

 

maintenance on the system.

battery holds 12 Volts. DO NOT exceed 13.7 volts when charging.

 

WARNING Storage batteries give off explosive hydrogen gas

 

 

8. Set generator’s system switch to AUTO.

 

during recharging.

 

 

 

9. Reset exercise timer. See Setting Exercise Timer.

 

Slightest spark will ignite hydrogen and

 

 

 

 

 

 

 

cause explosion.

 

 

 

 

 

Battery electrolyte fluid contains acid and is

for

 

 

extremely caustic.

 

 

 

Contact with battery contents will cause severe chemical burns.

 

 

A battery presents a risk of electrical shock and high short

 

 

circuit current.

 

 

 

DO NOT dispose of battery in a fire. Recycle battery.

 

 

DO NOT allow any open flame, spark, heat, or lit cigare during

 

 

and for several minutes after charging a battery.

 

 

 

 

 

 

DO NOT open or mutilate the battery.

 

 

 

 

Wear protective goggles, rubber apron, rubber boots and

 

 

 

 

rubber gloves.

 

 

 

 

Remove watches, rings, or other metal objects.

 

 

 

Use tools having insulated handles.

Not

 

 

 

 

 

 

 

 

 

 

 

 

Cleaning the Generator

 

 

 

 

 

 

 

 

NOTICE Improper treatment of generator can damage it and

 

 

3. Clean generator as desired.

shorten its life.

 

 

 

• Use a damp cloth to wipe exterior surfaces clean.

 

 

 

 

 

 

Reproduction

DO NOT expose generator to excessive moisture, dust, dirt, or

 

 

• Use a soft, bristle brush to loosen caked on dirt, etc.

 

corrosive vapors.

 

 

 

• DO NOT insert any objects through cooling slots. 1. Set control board system switch to OFF. 2. Remove 15 Amp fuse from control panel.

20

When Calling for Assistance

You must have the following information at hand if it is necessary to contact a local service center regarding service or repair of this unit:

1.Obtain the unit Model Number and Serial Number from the unit ID label. See Controls for location of the label or refer to the information recorded on the inside front cover of the installation manual.

2.Obtain the engine identification numbers from the engine label. See the engine operator’s manual for location of this information. Please note that several different engines are described in the engine manual, so your engine may vary from that shown.

Storage

Reproduction

 

 

 

for

The home generator system is designed for long term service

as a backup generator. There is no need to take any storage

 

precautions. However, if it becomes necessary to take the

 

system out of service for an extended period, call Technical

 

 

Not

 

Services at 888 575 8226, between 8:00 AM and 5:00 PM CT for specific recommendations. Refer to the engine perat r’s manual for additional information.

21

Troubleshooting

Problem

 

 

 

Cause

 

Correction

 

 

 

 

 

 

 

 

1.

Circuit breaker open or defective.

1.

Reset or replace circuit breaker.

Engine is running, but no AC output

 

2.

Fault in generator control panel.

2.

Contact local service facility.

is available.

 

3.

Poor wiring connections or

3.

Check and repair or contact

 

 

 

 

 

defective transfer switch.

 

local service facility.

 

 

 

 

 

 

 

 

1.

Short circuit in a connected load.

1.

Disconnect shorted

 

 

 

 

 

 

electrical load.

 

 

2.

Generator is overloaded.

2.

Turn off one or more loads.

Engine runs good at no-load but “bogs

3.

Shorted generator circuit.

3.

Contact local service facility.

 

 

 

for

 

 

Loss of power on circuits.

 

Reproduction

 

 

down” when loads are connected.

 

4.

Fuel pressure mixtu

4.

See Gaseous Fuel System in the

 

 

 

is incorrect.

 

i stallation manual.

 

 

5.

Kinked

uel line between regulat r

5.

Remove kink. Replace

 

 

 

and engine.

 

if necessary.

 

 

1.

15 Amp fuse missing or blown.

1.

Install (new) 15 Amp fuse.

 

 

 

 

 

 

See System Control Panel.

Engine will not start; or starts and

 

2.

Fuel supply turned off or depleted.

2.

Open fuel valve(s); check

runs rough.

 

 

 

 

 

propane tank.

 

 

3.

Failed batte y.

3.

Replace battery.

 

 

Not4. Clogged air filter.

4.

Clean or replace air filter.

 

 

1.

Fu l su

ly turned off or depleted.

1.

Check fuel valves, fill

Engine shuts down during operation.

 

 

 

 

 

propane tank.

 

2.

Fault indicator blinking.

2.

Count blinks and refer to

 

 

 

 

 

 

 

 

Fault Detection System.

 

 

 

 

 

 

 

 

1.

Generator circuit breaker is open.

1.

Reset circuit breaker.

 

 

2.

Transfer switch problems.

2.

See transfer switch manual.

 

 

 

 

 

 

 

22

Warranty

Limited Warranty

Briggs & Stratton Power Products Group, LLC will repair or

FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED TO ONE

replace, free of charge, any part(s) of the equipment that

YEAR FROM PURCHASE, OR TO THE EXTENT PERMITTED BY

is defective in material or workmanship or both. Travel

LAW. ANY AND ALL IMPLIED WARRANTIES ARE EXCLUDED.

expenses are reimbursed as specified under the Briggs

LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES

& Stratton Warranty Guidelines document to authorized

IS EXCLUDED TO THE EXTENT EXCLUSION IS PERMITTED

Briggs & Stratton dealers for performing applicable warranty

BY LAW. Some states or countries do not allow limitations

repair work. This warranty is effective for the time periods

on how long an implied warranty lasts, and some states

and subject to the conditions stated below. For all warranty

or countries do not allow the exclusion or limitation of

service, find the nearest Authorized Service Dealer in our

incidental or consequential damages, so the above limitation

dealer locator map at BRIGGSandSTRATTON.COM.

and exclusion may not apply to you. This warranty gives

 

 

 

 

you specific legal rights and you may also have other rights

THERE IS NO OTHER EXPRESS WARRANTY. IMPLIED

which vary from state to state or country to country.

for

WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND

 

 

 

 

Warranty Period

 

 

 

 

 

 

 

 

 

Consumer Use

 

4 yea s 1,600 h urs, whichever comes first

 

 

Not

 

 

Commercial Use

None

 

The warranty period begins on the date of purchase by the

NO WARRANTY REGISTRATION IS NECESSARY TO OBTAIN

first retail consumer or commercial end user, and continues

WARRANTY ON BRIGGS & STRATTON PRODUCTS. SAVE YOUR

for the period of time stated in the table above. “Consum r”

PROOF OF PURCHASE RECEIPT. IF YOU DO NOT PROVIDE

means personal residential household use by a retail

PROOF OF THE INITIAL PURCHASE DATE AT THE TIME

consumer. “Commercial” means all other uses, including

WARRANTY SERVICE IS REQUESTED, THE MANUFACTURING

use for commercial, income producing or rental purposes.

DATE OF THE PRODUCT WILL BE USED TO DETERMINE THE

 

Reproduction

Once equipment has experienced commercial use, it shall

WARRANTY PERIOD.

thereafter be considered as commercial use for purposes of this warranty.

Warranty Terms continue on next page

is a trademark of General Electric Company and is under license by Briggs & Stratton Power Products Group, LLC.

Copyright © 2010. All rights reserved. No part of this material may be reproduced or transmitted in any form without the express written permission of Briggs & Stratton Power Products Group, LLC.

23

About Your Warranty

We welcome warranty repair and apologize to you for

 

 

 

Other Exclusions: This warranty excludes starting

being inconvenienced. Any Authorized Service Dealer may

 

 

battery, accessory parts, wear items such as oil

perform warranty repairs. Most warranty repairs are handled

 

gauges, o-rings, filters, fuses, or spark plugs, etc., or

routinely, but sometimes requests for warranty service

 

 

 

damage or malfunctions resulting from accidents,

may not be appropriate. For example, warranty service

 

 

 

abuse, modifications, alterations, or improper

would not apply if equipment damage occurred because

 

 

 

servicing or freezing or chemical deterioration.

of misuse, lack of routine maintenance, shipping, handling,

 

 

This warranty excludes failures due to acts of

warehousing or improper installation. Similarly, the warranty

 

 

God and other force majeure events beyond

is void if the manufacturing date or the serial number on

 

 

 

the manufacturers control. And this warranty

the equipment has been removed or the equipment has

 

 

 

excludes used, reconditioned, and demonstration

been altered or modified. During the warranty period, the

 

 

 

equipment; equipment used for prime power in

Authorized Service Dealer, at its option, will repair or replace

for

place of utility power, equipment used in mobile

any part that, upon examination, is found to be defective

 

or rental applicati

s, a d equipment used in life

under normal use and service. This warranty will not cover

support appl cati

s.

the following repairs and equipment:

 

 

Enclosure s warranted against surface rust and

 

 

 

orros on for the first year of the warranty period.

Normal Wear: Outdoor Power Equipment and

 

Surfa e rust and corrosion is defined as any rust or

 

orrosion that has penetrated the paint but has not

engines, like all mechanical devices, needs peri dic

 

 

penetrated through the metal substructure.

parts and service to perform well. This warranty d

es

 

 

Enclosure is warranted against rust-through for the

not cover repair when normal use has exhausted the

 

 

 

 

first two years of the warranty period.

life of a part or the equipment.

Not

 

 

Rust-through is defined as rust or corrosion that

 

 

 

has penetrated completely through the paint and

 

 

 

metal substructure.

Installation and Maintenance: This warranty does

 

 

 

 

Enclosure is not warranted for surface rust or

not apply to equipment or parts that have b

 

 

 

 

 

 

corrosion or complete rust-through that may result

subjected to improper or unauthorized installation

 

 

 

 

due to improper installation, damage to painted

or alteration and modification, misus , glig nc

,

 

 

surfaces that compromise the paint’s corrosion

accident, overloading, overspeeding, improper

 

 

 

prevention properties, or if the unit is installed in

maintenance, repair or storage so as, in our

 

 

 

environments that expose the generator to high levels

judgment, to adversely affect its performance and

 

 

of corrosive agents.

 

Reproduction

reliability. This warranty also does not cover normal

 

 

 

 

maintenance such as adjustments, fuel system

 

 

Warranty terms effective November 1, 2009 - replaces all undated Warranties and

cleaning and obstruction (due to chemical, dirt,

 

 

Warranties dated before November 1, 2009. 209453E, Rev. C, 2 November 2009

 

 

 

 

 

carbon, lime, and so forth).