GE Genius GFK0121E User Manual

Page 1
GE Fanuc Automation
Programmable Control Products
Genius
t
Hand-held Monitor User’s Guide
Page 2
Warnings, Cautions, and Notes as Used in this Publication
Warning notices are used in this publication to emphasize that hazardous voltages, currents, temperatures, or other conditions that could cause personal injury exist in this equipment or may be associated with its use.
In situations where inattention could cause either personal injury or damage to equipment, a Warning notice is used.
Caution notices are used where equipment might be damaged if care is not taken.
GFL–002
Warning
Caution
Note
Notes merely call attention to information that is especially significant to understanding and operating the equipment.
This document is based on information available at the time of its publication. While efforts have been made to be accurate, the information contained herein does not purport to cover all details or variations in hardware or software, nor to provide for every possible contingency in connection with installation, operation, or maintenance. Features may be described herein which are not present in all hardware and software systems. GE Fanuc Automation assumes no obligation of notice to holders of this document with respect to changes subsequently made.
GE Fanuc Automation makes no representation or warranty, expressed, implied, or statutory with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warranties of merchantability or fitness for purpose shall apply.
The following are trademarks of GE Fanuc Automation North America, Inc.
Alarm Master CIMSTAR Helpmate PROMACRO Series Six CIMPLICITY GEnet Field Control Logicmaster Series One Series 90 CIMPLICITY 90–ADS Genius Modelmaster Series Three VuMaster CIMPLICITY P owerTRA C Genius PowerTRA C ProLoop Series Five W orkmaster
e
Copyright 1994 GE Fanuc Automation North America, Inc.
All Rights Reserved
Page 3
Preface
Content of this Manual
Chapter 1. Introduction: Chapter 1 describes the Hand-held Monitor. This chapter lists catalog numbers and specifications. It also explains compatibility between different versions of the Hand-held Monitor and various other products.
Chapter 2. Hardware Setup: Chapter 2 gives instructions for powering the HHM, changing its EPROM, and changing its battery pack. It also describes how to install the HHM on a panel, and how to install a separate HHM connector on a bus.
Chapter 3. Getting Started: Chapter 3 explains how turn on the Hand-held Monitor, and how to set up its features for your application. Chapter 3 also explains how to test the Hand-held Monitor’s operation.
Chapter 4. Device Configuration: Overview: Chapter 4 gives basic
instructions for using the Hand-held Monitor to configure Genius devices.
Chapter 5. Monitoring the Bus and its Devices: Chapter 5 explains how to use the
Hand-held Monitor to displ ay data and status information from other devices on the bus. It also expl ai ns how to clear faults, switch a dual bus , ex ecute Pulse Testing, and display the bus scan time.
Chapter 6. Reading CPU Memory:
Chapter 6 explains how to use the HHM to read the contents of specified memory locations in CPUs on the bus.
Chapter 7. Error Messages: Chapter 7 defines messages that may be displayed during HHM startup or operation, or device configuration.
Related Publications
For more information, refer to these publications:
Genius I/O System User’s Manual
(GEK-90486–1). Reference manual for system designers, programmers, and others involved in integrating Genius I/O products in a PLC or host computer environment. This book provides a system overview, and describes the types of systems that can be created using Genius products. Datagrams, Global Data, and data formats are defined.
Genius Discrete and Analog Blocks User’s Manual (GEK-90486–2). Reference
manual for system designers, operators, maintenance personnel, and others using Genius discrete and analog I/O blocks. This book contains a detailed description, specifications, installation instructions, and configuration instructions for all currently–available discrete and analog blocks.
Series 90-70 Remote I/O Scanner User’s Manual (GFK-0579). Reference manual
for the Remote I/O Scanner , which interfaces a drop containing Series 90-70 modules to a Genius bus. Any CPU capable of controlling the bus can be used as the host. This book describes the Remote I/O Scanner features, configuration, and operation.
Genius Bus Interface Unit and Field Processor User’s Manual (GFK-0825).
Reference manual for the Bus Interface Unit and the Field Processor, which interface a station containing Field Control modules to a Genius bus. Any CPU capable of controlling the bus can be used as the host. This book describes the features, configuration, and operation or a Bus Interface Unit or Field Processor.
Field Control I/O Modules User’s Manual
(GFK-0826). Reference manual for system
GFK-0121 E
Index-3
Page 4
Preface
designers, operators, maintenance personnel, and others using Field Control I/O modules. This book contains a detailed description, specifications, and installation instructions for all currently–available I/O modules.
Series 90-70 Bus Controller User’s Manual (GFK-0398). Reference manual
for the Bus Controller, which interfaces a Genius bus to a Series 90-70 PLC. This book describes the installation and operation of the Bus Controller. It also contains the programming information needed to interface Genius I/O devices to a Series 90-70 PLC.
Series 90-30 Bus Controller User’s Manual (GFK-1034). Reference manual
for the Bus Controller, which interfaces a Genius bus to a Series 90-30 PLC. This book describes the installation and operation of the Bus Controller. It also contains the programming information needed to interface Genius I/O devices to a Series 90-30 PLC.
Series Six Manual (GFK-0171). Reference manual
for the Bus Controller, which interfaces a Genius bus to a Series Six PLC. This book describes the installation and operation of the Bus Controller. It also contains the programming information needed to interface Genius I/O devices to a Series Six PLC.
Bus Controller User’s
describes the installation and operation of the Bus Controller. It also contains the programming information needed to interface Genius I/O devices to a Series Five PLC.
Genius I/O PCIM User’s Manual
(GFK-0074). Reference manual for the PCIM, which interfaces a Genius bus to a suitable host computer. This book describes the installation and operation of the PCIM. It also contains the programming information needed to interface Genius I/O devices to a host computer .
Genius I/O Single-slot PCIM User’s Manual (GFK-0881). Reference manual
for the Single-slot PCIM, which interfaces a Genius bus to a suitable host computer. This book describes the installation and operation of the PCIM. It also contains the programming information needed to interface Genius I/O devices to a host computer .
We Welcome Your Comments and Suggestions
At GE Fanuc automation, we strive to produce quality technical documentation. After you have used this manual, please take a few moments to complete and return the Reader’s Comment Card located on the next page.
Series FiveBus Controller User’s Manual (GFK-0248). Reference manual
for the Bus Controller, which interfaces a Genius bus to a Series Five PLC. This book
Index-4
Hand-held Monitor User’s Guide – June 1994
Jeanne L. Grimsby
Senior Technical Writer
GFK-0121E
Page 5
Contents
Chapter 1 Introduction 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hand-held Monitor Description 1-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HHM Compatibility 1-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HHM Specifications 1-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ordering Information 1-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 Hardware Setup 2-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power for the Hand-held Monitor 2-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing the PROM 2-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Permanent Installation 2-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing a Separate Hand-held Monitor Connector 2-9 . . . . . . . . . . . . . . . . . . .
Chapter 3 Getting Started 3-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 4 Device Configuration: Overview 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 5 Monitoring the Bus and its Devices 5-1 . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitor Block Display for Discrete I/O and Input Blocks 5-4 . . . . . . . . . . . .
Monitor Block Display for Discrete Relay Output Blocks 5-5 . . . . . . . . . . . .
Monitor Block Display for Analog Blocks 5-5 . . . . . . . . . . . . . . . . . . . . . . . . .
Monitor Block Display for RTD or Thermocouple Blocks 5-5 . . . . . . . . . . . .
Monitor Block Display for a High-speed Counter Block 5-6 . . . . . . . . . . . . .
Monitor Block Display for a P owerTRAC Block 5-7 . . . . . . . . . . . . . . . . . . . .
Monitor/Control Reference Display for a Discrete, Relay , or High-speed Counter
Block 5-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitor/Control Reference Display for an Analog, RTD, or Thermocouple Block 5-10
Monitor/Control Reference Displays for a P owerTRA C Block 5-11 . . . . . . . .
Chapter 6 Reading CPU Memory 6-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 7 Error Messages 7-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GFK-0121E
Table of Contents i
Page 6
Restarts for autonumbers that do not restart in each chapter . figure bi level 1, reset table_big level 1, reset chap_big level 1, reset1 app_big level 1, resetA figure_ap level 1, reset table_ap level 1, reset figure level 1, reset table level 1, reset
these restarts must be in the header frame of chapter 1. a:ebx, l 1 resetA a:obx:l 1, resetA a:bigbx level 1 resetA a:ftr level 1 resetA c:ebx, l 1 reset1 c:obx:l 1, reset1 c:bigbx level 1 reset1 c:ftr level 1 reset1
Reminders for autonumbers that need to be restarted manually (first instance will always be 4) let_in level 1: A. B. C. letter level 1:A.B.C. num level 1: 1. 2. 3. num_in level 1: 1. 2. 3. rom_in level 1: I. II. III. roman level 1: I. II. III. steps level 1: 1. 2. 3.
Chapter 1 Introduction
1
The Hand-held Monitor (HHM) is a convenient operator interface device that can be used to set up and monitor a Genius I/O and communications system.
The HHM features:
H
An LCD display with four lines of 16 characters each.
H
Selectable display language: English, German, French, or Italian.
H
A 20-key sealed-membrane keypad.
H
A keyswitch that can be used to restrict operator access to certain functions, as selected for the application.
H
Operation from its battery pack, or by 115 volt AC or 230 volt AC power .
The Hand-held Monitor screen is the operator’s window to the Genius bus and all of its devices. It can be used to display:
h
I/O data for any device on the bus.
h
Diagnostics.
h
Bus scan time.
h
Descriptions of all devices on the bus.
h
Global Data addresses.
h
Memory data from CPUs on the bus.
The Hand-held Monitor can also be used for device configuration, fault clearing, and forcing I/O circuits and dual bus selection. It can also be set up to prevent the use of any of these capabilities.
A k ey feature of the Hand-held Monitor is its ability to communicate with I/O blocks and to force discrete and analog I/O, whether or not there is a PLC or computer connected to the bus. This greatly simplifies system check-out prior to full-scale system operation.
GENIUS
Hand Held Monitor
GE Fanuc
F1 F2 F3 F4
789Home
456
123Clear
+
0
mon
cfg
Y
Menu
On
D
Off
GFK -0121E
1-1
Page 7
1
Hand-held Monitor Description
GENIUS
Hand Held Monitor
GE Fanuc
Mode Select Keyswitch
mon
cfg
HHM Cable
F1 F2 F3 F4
789Home
456
123Clear
+ –
Menu
0
D
Y
On Off
LCD Display
Function Keys
Decimal Keys
Operation Keys
Connection for Charger/Adapter
The HHM Keypad
The Hand-held Monitor keypad has three types of keys: function keys (F1 - F4), decimal keys, and operation keys.
Function K eys: The four keys in the top row (F1, F2, F3, and F4) have functions that change as the display changes.
F1 F2 F3 F4
The bottom line of the screen shows the current functions of these keys. For example:
Decimal Keys: The decimal keys are used to enter numbers and change sign. Operation Keys: The four keys on the right side of the keypad are used to control HHM
operations:
Home
Menu
1-2
Hand-held Monitor User’s Guide – June 1994
displays the Home menu.
displays the previous screen.
n x t p r v a c t v b u s
Clear
On
Off
clears HHM error messages, clears Genius faults, deletes HHM keypad entries.
turns the HHM on or off.
GFK-0121E
Page 8
The HHM Display
The Hand-held Monitor has a 4-line LCD screen. On a new Hand-held Monitor, displays are in English. The display language can easily be changed to French, German, or Italian. (Instructions for changing the display language are on page 3-5).
In addition to alphanumeric characters, the display uses the following special characters:
tri-state input.
I
T
Output with Feedback, or block with both inputs and outputs.
O
T
circuit is forced OFF .
4
circuit is forced ON.
1
relay block point is forced open.
O
relay block point is forced closed.
C
circuit controls a Bus Switching Module.
B
S
reference address or Device Number not yet assigned.
?
reference address is out of range for the presently-selected HHM host.
*
For a list of other HHM abbreviations and their meanings, select F3 (HELP) from the HHM Utilities menu.
1
K eyswitch
The Hand-held Monitor’s keyswitch can be used to restrict access to certain features of the HHM.
With the key present, the switch can be placed in either “configure” (cfg) or “monitor”
(mon) position. cfg with the switch in Configure position, all HHM functions are available. In this
mode, the Hand-held Monitor can be configured to determine which of its fea­tures will be usable once the key is removed.
mon: with the keyswitch in Monitor position, the HHM can monitor bus and block
data. Additional HHM functions, such as clearing faults or configuring I/O blocks, can be used in Monitor mode only if the HHM has been set up to permit their use.
The key must be present to move the switch from Monitor to Configure mode position; it can only be removed in MON position. Two identical keys are supplied with each Hand-held Monitor . The key should be removed if system security is a concern.
Accessories
The Hand-held Monitor comes with:
H
A sturdy removable leather case. The case has a rear tab with snap closure for carrying the HHM on a belt. The handle can be pivoted back to stand the Hand-held Monitor upright on a table.
H
A rechargeable battery pack.
H
A battery charger/adapter with 8-ft cord.
H
Two keys for the mode-selection keyswitch.
H
A removable 5 ft (1.5 meter) coiled communications cable.
GFK-0121E
Chapter 1 Introduction
1-3
Page 9
1
HHM Compatibility
The following table shows which Hand-held Monitor versions are compatible with specific Genius I/O, Field Control, and related products.
Note that the functionality of an older Hand-held Monitor can be upgraded by replacing its firmware PROM. (PROM installation instructions are in chapter 2).
Product
Type
24/48VDC Analog 4 Input/2 Output block 24/48VDC RTD 6 Input block 24/48VDC Thermocouple 6 Input block 24/48VDC Current-Source Analog 4 Input/2 Output block 24/48VDC Current-Source Analog 6 Output block 115V A C Analog 4 Input/2 Output block 115V A C/125VDC RTD 6 Input block 115VA C/125VDC Thermocouple 6 Input block 115V A C/125VDC Current-Source Analog 4 Input/2 Output block 115V A C/125VDC Current-Source Analog 6 Output block 24/48VDC Source 16 I/O block 24/48VDC Sink 16 I/O block 24VDC Source 16 I/O block 24VDC Sink 16 I/O block 12/24VDC Source 32 I/O block 5/12/24VDC Sink 32 I/O block 115V A C 8 I/O block 115V A C 8 I/O Low Leakage block 115VA C 16 Input block 115V AC/10-30VDC High-Speed Counter block, v1.x 115V AC/10-30VDC High-Speed Counter block, v2.0 115/230VAC Relay Normally-closed 16 Output block 115/230VAC Relay Normally-open 16 Output block 115V AC/125VDC 8 I/O Isolated Block with Failed Switch Diagnostic 115V AC/125VDC 8 I/O Isolated without Failed Switch Diagnostic 115-230V A C/125VDC PowerTRAC block, v .2.2 or earlier 115-230VA C/125VDC PowerTRAC block, v.2.3
Product Catalog
Number
IC660BBA020 IC660BBA021 IC660BBA023 IC660BBA024 IC660BBA025 IC660BBA100 IC660BBA101 IC660BBA103 IC660BBA104 IC660BBA105 IC660BBD020 IC660BBD021 IC660BBD022 IC660BBD023 IC660BBD024 IC660BBD025 IC660BBD100 IC660BBD101 IC660BBD110 IC660BBD120 IC660BBD120D IC660BBR100 IC660BBR101 IC660BBS100 IC660BBS101 IC660BPM100 IC660BPM100C
Requires this Hand-
held Monitor Ver-
sion (or later)
any
IC660HHM501B (v2.0)
IC660HHM501D (v3.5)
IC660HHM501E (v3.7)
IC660HHM501G (v4.0)
any
IC660HHM501B (v2.0)
IC660HHM501D (v3.5)
IC660HHM501E (v3.7)
IC660HHM501G (v4.0)
any any any
any IC660HHM501B (v2.0) IC660HHM501B (v2.0)
any
any IC660HHM501B (v2.0)
IC660HHM501D (v3.5) IC660HHM501G (v4.0)
IC660HHM501B (v2.0) IC660HHM501B (v2.0)
any
any
IC660HHM501D (v3.5) IC660HHM501G (v4.0)
Series Five Genius Bus Controller Series 90-70 Genius Bus Controller Series Six Genius Bus Controller with Diagnostics Series Six Genius Bus Controller without Diagnostics Series 90-30 GENIUS Communications Module GENIUS Network Interface (GENI) module IBM PC Interface Module (PCIM) GENIUS Network Interface (GENI) module with inverted connector
Series 90-70 Remote I/O Scanner IC697BEM733 IC660HHM501G (v4.0) 24/48VDC Bus Switching Module (BSM)
115V AC/125VDC Bus Switching Module (BSM) Field Control products (all) IC670xxxxxx IC660HHM501J (v4.6)
1-4
Hand-held Monitor User’s Guide – June 1994
IC655BEM510 IC697BEM731 IC660CBB902 IC660CBB903 IC693CMM301 IC660ELB905 IC660ELB906 IC660ELB910
IC660BSM021 IC660BSM115
IC660HHM501C (v3.0)
IC660HHM501F (v3.8)
any
any
IC660HHM501C (v3.0)
any
any
any
any
GFK-0121E
Page 10
HHM Specifications
Operating temperature 0–60 C(32–140 F) Storage temperature –40 to +70 C(–40 to 158 F) Humidity 5-95% (non-condensing) Weight: without case 1.3 lbs (0.6 Kg)
with case 1.8 lbs (0.8 Kg)
Size (HxWxD): without case 8.00” x” 3.75 x” 1.25 (cmx)
with case 10.85” x 4.30” x 2.25”
Requir ed AC power (for battery charger) 115/230VAC 15%, 47-63 Hz
Fully charged operation 6 hours Display characters 4 lines each of 16 LCD (0.2” - 5 mm high) K eyboard 20 sealed keys with tactile feedback Featur es Performs Genius I/O block configuration, monitors
Display language English, German, French, or Italian Drop T est Survives drop from 4 feet (1.2 meters) to concrete
Data Rates 153.6 Kbaud standard, 153.5 Kbaud extended, 76.8
1
(16-hour charging period for IC660BPM500B. 8-hour charging period for IC660BPM500A, now discontinued.)
I/O data on Genius bus, displays diagnostic in­formation.
floor landing on any surface or corner without af­fecting its operation.
Kbaud, 38.4 Kbaud
Ordering Information
GFK-0121E
Description Catalog Number
Hand-Held Monitor (includes all items listed below) IC660HHM501 Cable from HHM to I/O Block IC660HHC005 Battery P ack IC660BPM500 Battery Charger IC660BCM501
Optional Accessories
External HHM Connector: A panel-mountable or DIN rail-mountable HHM connector (catalog number 44A736310-001-R001) is available. It can be used to provide a permanent HHM connection point on a Genius bus. See chapter 2 for a description.
230VAC Power A dapter: An optional 230V AC P ower A dapter (IC660MCA512) can be used to connect the Hand-held Monitor Charger to variety of 230 VAC power outlets by means of a standard computer cable (not supplied). See chapter 2 for a description.
Extra HHM Keys: For applications requiring extra keys for the Hand-held Monitor, a group of five sets can be ordered separately. The catalog number is IC660MKS511.
Chapter 1 Introduction
1-5
Page 11
Chapter 2 Har dwar e Setup
2
Power for the Hand-held Monitor
The Hand-held Monitor can be operated using its built-in battery, or connected to either 115 volt or 230 volt AC power. A battery pack must always be installed to operate the HHM,
even when using AC power.
A n optional 230VAC Power A dapter can be used to connect the Hand-held Monitor Charger to variety of 230 VA C power outlets. See page 2-2 for more information.
Charging the Battery Pack for AC Operation
To operate the HHM using AC power , if the battery pack is new or has become fully discharged by operating the HHM on battery power, it must be charged for at least 20 minutes. If it is necessary to restore temporary operation before charging is complete:
H
Plug the adapter cable into the HHM.
H
Wait 15 seconds and power up the HHM. It may be necessary to remove the battery pack for 15 seconds, then reinstall it.
GFK-0121E
Note that continuall y usi ng the Hand-held Monitor in AC mode for an extended period of time causes the battery pack to deteriorate. A fter up to two years of AC operation of the HHM, the battery pack may not be able to accept enough charge to operate the HHM independently. However, it can still be used for AC operation.
Selecting 120 VAC or 230 VAC
Before plugging the adapter into AC power to operate or charge the Hand-held Monitor, be sure the switch at the base of the adapter is correctly set to match the incoming power (120 volts AC or 230 volts A C).
120V position
230V position
The Hand-held Monitor will operate while the adapter is connected.
120V
230V
2-1
Page 12
2
Using the 230VAC Power Adapter
The optional 230VAC Power Adapter (IC660MCA512) can be used to connect the Hand­held Monitor Charger to variety of 230 VAC power outlets by means of a standard com­puter cable (not supplied).
The Adapter has a receptacle on the top for the Hand-held Monitor Charger and an IEC 320 receptacle on the side for the computer cable.
HHM Charger receptacle in
top of Adapter
IEC 320 receptacle in
side of Adapter
Instructions
1. Se t the powe r selection switch on the Han d-held Monitor Charger to the 230V position.
120V
230V position
2. Plug the Hand-held Monitor Charger into the top receptacle on the Power A dapter unit.
3. Plug the computer cable into the IEC receptacle on side of the Power Adapter unit.
4. Connect the computer cable to a suitable 230VAC power source.
During normal operation, it is best to connect and disconnect the cable at the outlet, not at the Adapter.
230V
2-2
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 13
Battery Operation
The HHM’s battery pack provides up to 6 hours of operation. To maximize battery life, allow the battery to discharge fully between charges. The battery should be allowed to fully discharge once a month.
Low Battery Power
Low battery power may cause this message:
**LOW BATTERY** **HHM HALTED** Please Recharge
Or the display may blank, or two black lines may appear briefly. Low battery power suspends the current operation.
Charging the Battery Pack
When you receive a new Hand-held Monitor, its battery pack is not charged. Before using a new battery pack to power the HHM for the first time, charge it by plugging the adapter into a power source for 24 hours. After this initial charging, subsequent rechanges will require only 16 hours.
Maintaining spare battery packs will allow the HHM to operate using one battery pack while another is being charged.
If the battery pack won’t take a charge, it usually indicates a faulty battery pack, not a faulty Hand-held Monitor. Try another batter y pack. Replacement (uncharged) batter y packs are available.
If a battery pack is left uncharged for a long time, it may be necessary to remove the battery pack from the HHM and charge it while removed for up to 15 minutes.
2
GFK-0121E
Replacing the Battery Pack
To replace the battery pack, use a Phillips screwdriver (size 0 or 1) to release the retaining screw at the bottom of the HHM. Slide the battery pack out, insert another, and tighten the screw.
Automatic Shutoff
To conserve power, the Hand-held Monitor automatically shuts off 10 minutes after the last key is pressed. For applications where continual operation is preferred, the automatic shutoff feature can be disabled. See page 3-5 for more information.
Chapter 2 Hardware Setup
2-3
Page 14
2
Changing the PROM
New features can be added to upgrade a Hand-held Monitor by replacing its PROM as described below .
To prevent possible damage to the Hand-held Monitor, this operation should be performed in an area equipped with suitable electrostatic discharge protection.
1. If the HHM is connected to AC power, disconnect it.
2. Remove the HHM battery pack as described on the previous page.
3. On the front of the Hand-held Monitor, remove the two Phillips-head screws located near the 7 and HOME keys.
4. Gently raise the keyboard up from the bottom to release the lip between the keyboard and the display.
Caution
5. Once this lip is free, open the keyboard to the right, as illustrated below. It is not necessary to remove the ribbon connector .
GENIUS
Hand Held Monitor
GE Fanuc
mon
cfg
Install PROM with notch to right as shown
6. Remove the old PROM. If you don’t have a PROM extraction tool, a small screwdriv-
er can be used instead, carefully working from side to side.
2-4
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 15
7. If necessary, bend the pins on the PROM so they line up properly with the holes in the socket. Bend the pins by pressing each side against a clean desk or table top as shown below. If possible, a conductive mat should be used.
46024
Conductive mat
8. Insert the EPROM or Battery-Backed RAM into the socket. IMPORTANT: Inserting the PROM backward can damage the Micro PLC and
destroy the PROM.
2
Newer PROMs may be physically longer, but all PROMs must be inserted flush with the left edge of the socket, with the notch toward the ribbon connector.
9. Reposition the keyboard in its lip and tighten the two screws.
10. Reinstall the battery pack.
GFK-0121E
Chapter 2 Hardware Setup
2-5
Page 16
2
Permanent Installation
If the Hand-held Monitor is to be installed using the metal bracket provided, follow the instructions below. Do not install the HHM yet if it will be used to configure I/O blocks.
The mounting bracket provid ed can be used to install the Hand-held Monitor behind a panel. You will need to make a cutout in the panel for the HHM (see next page).
You will also need to install a connector for the Hand-held Monitor within reach of the HHM’s cable. The extra D-shell connector provided with the Hand-held Monitor requires a panel cutout, with the bus cable and Hand-held Monitor located on the opposite sides of the panel (see page 2-8).
An optional panel-mountable or DIN rail-mountable connector is also available. It does not require a cutout. See page 2-9 for details.
Behind PanelBack of HHM
Bracket
To Power Source
Optional HHM
Connector
Bus In
Bus Out
Configuring a Permanently-installed HHM
Ordinarily, a Hand-held Monitor installed on a panel serves as an operator station. Its configuration may be different from that of a portable HHM.
H
Its Device Number must be changed from 0 to some other number .
H
Automatic shutoff may be disabled.
H
I/O block configuration and other features may also be disabled.
After the HHM is configured, its keyswitch should be placed in MON position, and the key removed.
2-6
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 17
HHM Installation Instructions
1. Select a suitable location for the HHM. Environmental specifications are listed on
page 1-5. The location must have 115 VAC or 230 VAC power.
2. Cut an opening 3.75I (9.53cm) wide x 8I (20.32cm) high in the panel. Drill four
mounting holes as shown below.
4.38in
(11.13cm)
3.75in
(9.53cm)
1.00in (2.54cm)
Cutout
6.00in
(15.24cm)
2
1.00in (2.54cm)
3. Attach the bracket to the HHM with the screws, washers, and lockwashers provided.
(4) holes for
mounting on
panel
(2) holes for mounting to
back of Hand-held Monitor
4. Using appropriate hardware (not provided), mount the HHM and bracket in the cutout.
5. Connect the power cord to the HHM, and connect the signal cable to the connector.
GFK-0121E
Chapter 2 Hardware Setup
2-7
Page 18
2
Installing the D -Shell HHM Connector
Follow the instructions below if you are installing the supplied D-shell connector on the bus.
1. Using the mounting plate as a template, cut an opening in the panel for the mating connector. Also drill two holes for the mounting hardware.
2. Attach the mounting plate and mating connector to the panel using the mounting hardware supplied.
3. Secure the two ends* of the serial bus cable to the back of the panel using strain relief brackets.
4. Strip the ends of the wires. Twist the two Serial 1 wires together and attach them to pin 5 of the connector. Twist the Serial 2 wires together and attach them to pin 9. Similarly, attach the Shield wire(s)* to pin 4.
The following illustration shows connections for incoming and outgoing serial bus cable. As with other devices, the HHM connector may be at either end of its bus. If it is, there will only be one bus cable attached.
Bus
Cable
SER 2 (Pin 9)
Strain
Reliefs
SER 1 (Pin 5)
Crimp
(Qty. 3)
Bus
Cable
Shield
(Pin 4)
Mounting
Hardware
Mating
Connector
Mounting Surface
(rear view)
Mounting
Plate
a42240c
Hand-held
Monitor
Connector
When making bus connections, the maximum exposed length of bare wires should be two inches. For added protection, each shield drain wire should be insulated with spaghetti tubing to prevent the Shield In and Shield Out wires from touching each other.
* If the HHM connector is at either end of its bus, it is necessary to install an
appropriate terminating resistor across the Serial 1 and Serial 2 wires. The Genius I/O System and Communications User’s Manual lists appropriate terminating resistors for each recommended bus cable type.
2-8
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 19
Installing a Separate Hand-held Monitor Connector
You can add a connector to the bus for a permanently-mounted Hand-held Monitor, or to provide an additional attachment point for a portable HHM.
The unit shown below (catalog number 44A736310-001-R001) provides a Hand-held Monitor connector and serial bus terminals.
2
.5 in
1.27 cm
7.198 cm
2.834 in
1.673 in
4.249cm
X1
X2 SA SB
X1 X2
SA SB
shown at 100% of actual size
46357
Hand-held Monitor
Connector
Panel Mounting Ear
Serial Bus Terminals
X1 Serial 1 X2 Serial 2 SA Shield In SB Shield Out
GFK-0121E
Mounting the HHM Connector
This unit can be easily mounted on a rail such as a standard 35mm (shown below) or 15mm DIN rail. The panel-mounting ears are not used if the unit is installed on a DIN rail.
46358
35mm DIN rail
(Removable) DIN rail
Mounting Feet
side view: shown at 50% of actual size
Alternatively, it can be installed directly on a panel using screws through its mounting ears. The DIN rail feet on the back of the unit are removed when the unit is panel-mounted.
Chapter 2 Hardware Setup
2-9
Page 20
2
Making the Bus Connections
The HHM connector has two sets of terminals; one for incoming cable and the other for outgoing cable.
Connect the Serial 1, Serial 2, and Shield In terminal of either connector to the previous device. Connect the Serial 1, Serial 2, and Shield Out terminal of the other connector to the next device.
When making bus connections, the maximum exposed length of bare wires should be two inches. For added protection, each shield drain wire should be insulated with spaghetti tubing to prevent the Shield In and Shield Out wires from touching each other.
The following illustration shows connections for incoming and outgoing serial bus cable. As with other devices, the HHM connector may be at either end of its bus. If it is, there will only be one bus cable attached.
46366
Bus In
Bus Out
X1
X2 SA SB
X1 Serial 1 X2 Serial 2
X1 X2
SA SB
SA Shield In SB Shield Out
As with other devices, if the HHM Connector is at either end of its bus, install an appropriate terminating resistor across the Serial 1 and Serial 2 terminals. The Genius I/O System and Communications User’s Manual lists appropriate terminating resistors for each recommended bus cable type.
2-10
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 21
Chapter 3Getting Started
3
This chapter explains how to:
H
Turn on the Hand-Held Monitor
h
Set the HHM Baud Rate
h
Display the Home Menu
H
Change the Hand-held Monitor ’s configuration:
h
the HHM Device Number
h
the HHM Display Language
h
the Host CPU
h
automatic shutoff
h
ability to Change Block ID Parameters
h
ability to Change the Baud Rate of Devices on the Bus
h
ability to Configure Devices on the Bus
h
ability to Force I/O Circuits
h
ability to Clear Faults
H
H
GFK-0121E
Test the operation of the Hand-held Monitor.
h
the Keypad
h
the Display Screen
h
the Internal Electronics
Display an alphabetical list of definitions for the definitions used on the HHM screen.
3-1
Page 22
3
Turning on the Hand-Held Monitor
With the battery pack charged, or with the HHM connected to a suitable AC power source, press the ON/Off key to turn the Hand-held Monitor on.
Caution
Do not connect or disconnect the HHM to/from another device or con­nector while it is ON.
Connecting or disconnecting the HHM while it is ON may disrupt communications on the bus.
Each time you turn on the Hand-held Monitor, it executes a brief self-test.
GENIUS HHM (version) COPR. (date) GE Fanuc N.A. SELFTEST WORKING
1. If the baud rates match, press F4 (Ok).
If the baud rates do not match, press F2 (Change) instead. The HHM screen changes to allow you to select a different baud rate:
HHM BAUD RATE ACTIVE=(baud rate) PROG =(baud rate)
tgl entr ok
A. With the key in CFG position, press F2
(Toggle). The selection changes to 76.8K,
38.4K, 153.6K extended, and back to 153.6K standard.
B. When the correct baud rate appears on line
3, press F3 (Enter). Press F4 (Ok) to return to the first baud rate screen.
2. Press F4 (Ok) to display the Home menu.
Powerup Error Messages
Setting the HHM Baud Rate
Before the HHM completes the self-test, this screen appears:
HHM BAUD RATE ACTIVE=153.6K ST MUST MATCH BUS
chng ok
It shows the baud rate that is currently set up for the Hand-held Monitor. The baud rate
     
.
  
Chapter 7 lists error messages that may appear at powerup.
Sometimes, an error message appears although the HHM has powered up normally. POWERUP ERROR #4 or #5 may be caused by excessive noise on the bus, or by an attempt to use different baud rates on the same bus.
3-2
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 23
Displaying the Home Menu
3
This is the Hand-held Monitor’s Home menu:
F 1 : H H M U T I L I T I E S F 2 : A N A L Y Z E F 3 : C O N F I G U R A T I O N F 4 : D E V I C E M E M O R Y
Display the Home menu by either: A. Pressing F4 (Ok) from the first baud rate
screen, or
The Main HHM Screens
F1: HHM CONFIG F2: SELF–TEST F3: HELP
F1
HHM CONFIG BLOCK NO. 0
chng nxt
See page 3-4 for instructions.
F2
F1: KEYPAD TEST F2: DISPLAY TEST F3: TEST INTRNALS F4:
See page 3-7 for instructions.
F3
(help screens)
F1: MONITOR BLOCK F2: MNTR/CTRL REF F3: BLOCK/BUS STS F4: PULSE TEST
F1
REFS O 3 4 5 6 7 8 9 0 O O O O O O O A 1 0 0 0 1 1 1
See page 5-4 for instructions.
F2
MNTR/CNTL O STATE: 0 NO FAULTS > on off reles
See page 5-9 for instructions.
F3
REFS O DC16K 15 v2.0ACT FORCED, NO FAULTS nxt prv actv bus
See page 5-2 for instructions.
F4
PULSE TEST REFS 0 NO FAULTS exec
See page 5-17 for instructions.
B. Pressing the Home key or DMenu key from a
Use the Home menu to get to any other HHM function, as shown below.
Notice that different screens appear, depending on the type of device that is currently communicating with the HHM.
F1: HHM UTILITIES F2: ANAL YZE F3: CONFIGURATION F4: DEVICE MEMORY
F3F2F1
F1: PROG BLOCK ID F2: CONFIG BLOCK F3: COPY CONFIG
F1
PROG BLOCK ID I/O BLOCK NO. ref blk nxt
See page 4-4 for instructions.
F2
(individual feature
configuration
screens)
See Genius I/O Blocks Manual or
individual block manual for instructions.
F3
COPY CONFIG FROM : TO :
chng entr
See page 4-6 for instructions.
For Most
Genius Devices
lower-level screen.
F2
F1: MONITOR F2: CONFIGURATION
F1
F1 Monitor I/O F2:Faults
F3 Previous Menu
See page 5-15 for instructions.
F2
F1: GENIUS CONFIG F2: Module Config
F3: Previous Menu
See page 4-7 for instructions.
F4
DEVICE MEMORY # (reference)
tgl chng entr SBA
See chapter 6 for instructions.
For Field
Control
GFK-0121E
Chapter 3 Getting Started
3-3
Page 24
3
Configuring the Hand-held Monitor
You can change the following operating characteristics of the Hand-held Monitor:
H
PLC reference format.
H
153.6 Kbaud “standard” baud rate.
H
Device Number set to 0.
H
English language displays.
H
Shutdown after 10 minutes of inactivity.
H
I/O block configuration enabled.
H
I/O circuit forcing enabled.
H
Fault clearing enabled.
Select F1 (HHM Utilities) from the Home menu to access the HHM Utilities menu:
F1:HHM CONFIG F2:HHM SELF TEST F3:HELP F4
To change the configuration of the Hand-held Monitor, select F1 (HHM Config) from the HHM Utilities menu.
Changing the HHM Device Number
The Device Number (serial bus address) assigned to the Hand-held Monitor appears on line 2 of the first HHM configuration screen.
HHM CONFIG BLOCK NO. O
chng nxt
Each device on a Genius bus must have a unique serial bus address number. A new HHM has number 0. If multiple HHMs will be used on the same bus, each of them must be assigned a different Device Number.
If you want to change the HHM Device Number, follow these steps:
H
Press the ON key. Go to the Home menu. Se­lect F1 (HHM Utilities), then F1 (HHM Config).
H
From the HHM Configure menu, press F2 (Change) to clear the existing Device Number. Enter the new number and press F3 (Enter).
Note
The HHM key must be in the key­switch, turned to CFG position.
After setting up the configuration, you can prevent changes by turning the keyswitch to the MON position and removing the key.
Pressing F4 from the buad rate screen will advance you through additional HHM configuration screens. Press Home if you want to return to the
Home menu, or use the DMenu key to go back to the previous screen.
3-4
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 25
3
Changing the HHM Display Language
The next display shows the current language selection.
HHM CONFIG LANGUAGE
ENGLISH
tgl entr nxt
Press F2 (TGL) to change the display language (French, German, Italian, English). Press F3 (Enter) to save the change.
Selecting the Host CPU
The next display shows the Hand-held Monitor’s host CPU selection. The choices are: Series Six, Series Five, PCIM/QBIM/GENI, or Series 90.
SELECT HOST CPU SERIES SIX
Enabling/Disabling Automatic Shutoff
The next screen shows whether automatic shutoff is selected.
AUTO OFF = 1Omin ENABLED
This feature conserves battery power by shutting off the Hand-held Monitor 10 minutes after the last key press. To change the current selection, press F2 (Toggle), then F3 (Enter).
Enabling/Disabling the Ability to Change Block ID Parameters
The next display shows whether the Hand-held Monitor is able to configure the Block Number (serial bus address) of bus devices, as well as the I/O circuit mix of some types of I/O blocks.
To change the host CPU type, press the F2 (TGL) key, then press F3 (Enter).
CHNG BLK ID ENABLED
This selection also determines whether the HHM is able to assign the Reference Address of I/O blocks, or change the I/O mapping of a Remote I/O Scanner (for the modules in its remote drop).
To enable or disable this capability , press F2 (TLG), then F3 (Enter).
GFK-0121E
Chapter 3 Getting Started
3-5
Page 26
3
Enabling/Disabling the Ability to Change the Baud Rate of Devices on the Bus
The next configuration screen shows whether the HHM is able to change the baud rate of bus devices.
CHNG BLK BAUD ENABLED
To change the current selection, press F2 (Toggle), then press F3 (Enter).
Enabling/Disabling the Ability to Configure Devices on the Bus
The next display shows whether the HHM is able to change the other configurable features of bus devices.
Enabling/Disabling the Ability to Force I/O Circuits
The next display shows whether the HHM can be used to force I/O circuits.
CIRCUIT FORCING ENABLED
To change the current selection, press F2 (Toggle), then press F3 (enter).
Enabling/Disabling the Ability to Clear Faults
The next display shows whether the HHM can clear faults on bus devices.
CLEAR BLK FAULTS ENABLED
CHNG BLK CONFIG ENABLED
To change the current selection, press F2 (Toggle) then press F3 (Enter).
3-6
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 27
Testing Operation of the Hand-held Monitor
3
If you want to test the Hand-held Monitor display, keypad, or internal electronics, select F2 (HHM SELF- TEST) from the HHM Utilities menu. This menu of tests appears:
F1:KEYPAD TEST F2:DISPLAY TEST F3:TEST INTRNALS F4:
Testing the Keypad
Press F1 (KEYPAD TEST). The HHM prompts:
KEYPAD TEST STRIKE ANY KEY KEY= MON/CFG KEY=CFG
H
Press any key you want to test. Each key press is shown on the display. The HOME, D MENU, and ON/OFF keys are tested by their
operation.
H
To test keyswitch operation, turn the key and observe the bottom line of the display.
H
Press D MENU to perform another test, or press HOME to return to the Home menu.
Testing the Display Screen
Press F2 (DISPLA Y TEST) from the HHM Utilities menu. The screen first displays uppercase letters and special characters:
Testing the Internal Electronics
Press F3 (TEST INTRNALS) from the Self -Test menu. After a moment, the HHM displays:
TEST INTRNALS
SELFTEST WORKING exec
If an error occurs, one of the following messages will appear instead.
E : P R O C E S S O R F A I L E : R A M F A I L U R E E : E P R O M F A I L U R E E : E E P R O M F A I L U R E E : C O M M E R R O R
Press the Clear key and try the test again. If the message returns, replace the HHM. Otherwise, continue.
An EEPROM failur e will not pr event use of the Hand-held Monitor. However, the HHM will not be able to retain changes to its default configuration through a power cycle.
The COMM ERROR message may indicate that the Hand-held Monitor is not attached to a correctly-terminated bus.
DISPLAY TEST ABCDEFGHIJKLMNOP QRSTUVWZYZO12345 6789:>?–./1O
Next, a screen of lowercase letters appears, followed by a continuous test pattern, which checks pixel operation. When the test pattern is
finished, press DMENU to perform another HHM test, or press HOME to return to the Home menu.
GFK-0121E
Chapter 3 Getting Started
OII
T
3-7
Page 28
Chapter 4Device Configuration Overview
4
The Hand-held Monitor can be used to configure (establish the operating characteristics for) a wide variety of other devices. Some configurable devices are:
H
Genius I/O Blocks, High-speed Counter Blocks, and P owerTRAC Blocks
H
the Series 90-70 Remote I/O Scanner and its remote drop
H
Field Control stations.
The Hand-held Monitor displays a unique set of configuration screens for each type of configurable device.
Because of the wide assortment of configuration features provided by the HHM, it has not been possible to include them all here. You should refer to the more detailed configuration instructions in the User’s
Manual for the type of device you are configuring.
GFK-0121E
4-1
Page 29
4
Online or Offline Configuration
Devices can be configured before or after installation on a properly-terminated serial bus. If a new device is to be added to an existing bus running at a baud rate other than 153.6 Kbaud standard, the device must first be configured offline. Be careful adding new devices to existing systems. Be sure the baud rate configured for the new device matches that of the system - never mix baud rates on a bus.
Online Configuration
When configuring a device on an operating bus, the Hand-held Monitor must be the ONLY HHM plugged into a device on the bus. If devices are configured online, the HHM automatically check for PLC reference address conflicts.
Offline Configuration
It may be most convenient to configure devices off-line at a central location. Each device will need to be connected to an appropriate source of power and to earth ground. To prepare a device for off-line configuration:
1. Connect a 75 ohm resistor across the Serial 1 and Serial 2 terminals, or use the 75 ohm terminator plug (IC660BLM508).
Warnings
If the device is not properly grounded, hazardous voltages may exist. Death or injury may result.
DO NOT TOUCH the connectors or wiring after powering up the device. Hazardous voltages exist, and death or injury may result.
Starting Configuration
Note: To assign a serial bus address, the Hand-held Monitor must be directly attached to the device being configured. Additional features can be configured with the Hand-held Monitor connected at any point on the bus. In that case, the device being configured must be selected as the active device (on the Block/Bus Status screen).
1. Begin with the Hand-held Monitor turned off. Attach the HHM to the device (see below) or to another bus connection point.
a42307
2. Attach a grounding strap to the device’s ground screw. Be sure that the strap is connected to earth ground.
a42468
Attach
Ground
Strap
Terminator
Plug
1 2 3 4
H
N
3. Wire the device to the power source and apply power.
4-2
Hand-held Monitor User’s Guide – June 1994
2. Turn the Hand-held Monitor on. After the HHM completes its powerup sequence, the Home menu appears. The Hand-held Monitor’s Change Block Configuration option must be enabled to complete the instructions in this section. For a new device, the HHM’s Change Block ID and Change Block Baud options must also be enabled.
GFK-0121E
Page 30
Displaying the Configuration Menus
4
The illustration below shows how to reach the HHM’s device configuration menus from the Main Menu.
H
For all devices, you will need to select F3 (Con­figuration) then F1 (Program Block ID) to con­figure a block’s required features.
h
Device Number (serial bus address).
h
I/O type for input/output blocks.
h
CPU references.
h
Baud rate.
For new blocks, this must be done first.
H
To configure Genius blocks, select F3 (Configu­ration) from the Main Menu, then F2 (Config­ure Block) to view and modify other features. Detailed configuration instructions for each type of device are provided in its User’s Manual.
You can use F3 (Copy Configuration) to copy a configuration from one block on the same bus to another.
H
To configure a remote drop, continue from the Program Block ID screens to enter the remote map (I/O References) and Drop ID. Then go to
the Configure Block screens to configure re­dundancy and Configuration Protection.
H
For a F ield Control device, select either F2 (Analyze) or F3 (Configuration) from the Main Menu. The HHM will then display a special set of screens for Field Control. (The currently-ac­tive device must be the Field Control device for these screens to appear. See page 4-7 if you need instructions to select the active device).
If the message E: CONFIG PROTECT appears, you can remove Configuration Protection by:
1. Going through the configuration screens to
reach the Configuration Protection screen.
2. Pressing F2 (Toggle) to select either DISABLED
or ENABLED.
3. Pressing F3 (Enter) to save the selection.
4. Pressing F4 (Next) to go to the first configura-
tion display , D MENU to return to the Configu­ration menu, or HOME to return to the Home menu.
Displaying the HHM
Configuration Menus
F 1 : P R O G B L O C K I D F 2 : C O N F I G B L O C K F 3 : C O P Y C O N F I G F 4 :
F1
All Devices
P R O G B L O C K I D I / O (device references) B L O C K N O . (device) r e f b l k n x t
Configure a Remote
Map
Remote I/O Scanner
F 1 : H H M U T I L I T I E S F 2 : A N A L Y Z E F 3 : C O N F I G U R A T I O N
F3
Configure an
Genius Blocks
and Remote I/O Scanner
F 4 : D E V I C E M E M O R Y
F2
C O P Y C O N F I G F R O M : n T O :
c h n g e n t r
I/O Block
F2 or F3
F 1 : M o n i t o r F 2 : C o n f i g u r a t i o n
F3
Field Control
Devices
F 1 : G E N I U S C O N F I G F 2 : M o d u l e C o n f i g
F 3 : P r e v i o u s M e n u
GFK-0121E
Chapter 4 Device Configuration: Overview
4-3
Page 31
4
Completing the Program Block ID Screens
Select F1 (Program Block ID) from the Configuration menu to complete the mandatory part of a device’s configuration. (The HHM’s CHNG BLK ID capability must be enabled).
When the HHM is set up for a PLC host, the Program Block ID screen looks like this:
PROG BLOCK ID I / O (device references) BLOCK NO. (device #) ref blk nxt
If there are ? symbols on the screen, the reference address and/or Device Number have not yet been configured. If there are * symbols on the screen, a reference address was previously assigned, but is out of range for the host CPU currently set up for the HHM. If this happens, check the host CPU setup in the HHM Utilities.
When the HHM is set up for a PCIM/QBIM/GENI host, references are not used. Instead, the second line describes the device:
To Complete the Program Block ID Screen: The Program Block ID screen is used to configure additional features for some devices. These vary from device to device; you should refer to the device’s User’s Manual if you need more information.
To Change the Device’s Baud Rate: press F4 (Next) from the Program Block ID screen. (The HHM’s CHNG BLK BAUD capability must be enabled).
SELECT BAUD RATE ACTIVE=153.6K ST PROG =153.6K ST
tgl entr nxt
The bus will not operate unless all devices are set for the same baud rate. Check the baud rate before
introducing blocks onto an operating bus.
H
To change the device’s baud rate, press F2 (Toggle), then press F3 (Enter).
H
Cycle power to all devices on the bus at the same time to use the new baud rate.
PROG BLOCK ID I S O L 8 (device #) BLOCK NO. (device #) ref blk nxt
To Enter or Change the Device Number: the Hand-held Monitor must be connected directly to the device.
1. Press F2 (blk). Then, enter the intended num­ber (1-30). If you make a mistake, press F2 twice again, then enter the correct number.
2. Press the F3 (Enter) key. If the device is on-line and the number has already been used, an er­ror message appears.
To Set the I/O Map for a Remote I/O Scanner:
The next screen is used to assign data types and lengths for a Series 90-70 Remote I/O Scanner. See the next page.
4-4
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 32
Configuring a Remote I/O Scanner
4
After selecting the baud rate, the next Program Block ID screen is used to assign data types and lengths for a Series 90-70 Remote I/O Scanner.
PROG REMOTE MAP %I LENGTH(PTS) tgl ref send nxt
Configuration Notes
The Remote I/O Scanner User’s Manual explains remote drop configuration in detail. You should use it as a reference during remote drop configuration.
Also, look over the information below. Especially, note that it is not always possible or desirable to use a HHM for remote drop configuration.
H
If the remote drop includes any Analog Expan­der Modules, Logicmaster 90 must be used for configuration; do not use a HHM.
H
When a remote drop is configured with a HHM, all I/O modules will operate in default mode; module options can only be configured with
the Logicmaster 90-70 software.
H
Unless the Remote I/O Scanner is configuration protected, pressing F3 (send) from the Remote Map configuration screen causes the HHM to automatically configure the remote drop. This configuration will REPLACE any existing I/O configuration (including one entered using Lo­gicmaster 90-70), and return I/O module op­tions to their original defaults.
H
Remote drops configured with Logicmaster 90-70 are automatically protected. Please check carefully before removing configuration protec­tion with a Hand-held Monitor.
H
The Hand-held Monitor automatically creates a configuration for a nine-slot rack, regardless of the actual rack size. If the remote drop has a five-slot rack, the HHM will later assume that there are unfilled slots. If this is a problem, Lo­gicmaster 90-70 can be used for configuration, or to edit an automatic configuration done with a Hand-held Monitor. Then, the configuration can be stored to the Remote I/O Scanner.
Configuring the Remote Drop
To configure the remote drop with the HHM:
1. Enter a starting address and length for: %I (dis­crete inputs), %Q (discrete outputs), %AI (ana­log inputs), %AQ (analog outputs) on the screen shown at left. The data lengths must not add up to more than 128 bytes of inputs and 128 bytes or outputs. If they do, an error message will appear when you attempt to send the data to the Remote I/O Scanner.
2. Next, press F2 (drop) and enter a Remote Drop ID (between 16 and 254).
PROG REMOTE MAP DROP ID _____________
tgl drp send nxt
3. Press the F3 (send) key to download these selections to the Remote I/O Scanner.
Note: Do not perform this step if you want to preserve a configuration entered using the Lo­gicmaster software.
The HHM configures the I/O references of Se­ries 90-70 I/O modules (only) in the remote drop. It assigns references in ascending order, starting with the slot next to the Remote I/O Scanner. The leftmost module of each type (%I, %Q, %AI, or %AQ) in the rack receives the first available reference of the appropriate type.
4. Press F4 (nxt) to go to the Program Block ID screen.
5. After completing these screens, press F2 (Con­figure Block) to complete the Genius configura­tion screens, or to display information about the I/O modules in the remote drop.
The module description screens that appear during the configuration sequence are read­only; boards cannot be configured here.
Go through these block description screens to configure:
H
BSM Present
H
BSM Controller
H
CPU Redundancy
H
Configuration Protection
GFK-0121E
Chapter 4 Device Configuration: Overview
4-5
Page 33
4
Configuring Genius Blocks
To configure individual features of a Genius block, the block must be the “active” device.
Selecting the Active Device
1. F rom the Analyze menu, select F3 (Block/Bus Status).
2. Press F1 (Next) or F2 (Previous), to reach the device’s description screen.
3. When the desired device appears, press F3 (Ac ­tive) to make it the active device. (On a dual bus, the HHM must be on the same bus as the active block. If it is not, either move the HHM or force the bus selection as described on page 5-3).
4. Press D MENU twice to return to the Main Menu.
Configuring Block Features
Select F3 (Configuration), then F2 (Config Block). For Genius blocks, the HHM shows the first configuration display. For example:
PULSE TEST REFS (block references) ENABLED
tgl entr nxt
The HHM shows the feature to be configured (in the example above, it is the Pulse Test option). It also shows the current status of that feature.
When the Hand-held Monitor is set up for a PLC host, line 2 shows the references assigned to the device being configured. If there are ? symbols on the screen, the device’s reference address has not yet been configured. If there are * symbols on the screen, a reference address was previously assigned, but it is out of range for the host CPU currently set up for the Hand-held Monitor. If this happens, check the host CPU setup in the HHM Utilities.
When the HHM is set up for a PCIM/QBIM/GENI host, line 2 shows the device type and Device Number (serial bus address) instead.
Because there are so many different device configuration screens, it is not possible to show
O
I
them all here. You should refer to the User ’s Manual for the device you are configuring for
descriptions of its configuration screens and detailed instructions for completing them.
Configuration Instructions
1. To advance through the HHM configuration displays making changes as needed, use the F4 (Nxt)key. You can pass through feature dis­plays without making entries.
2. To change a feature, use the TGL and CHNG keys to select choices or enter other values. On screens used to enter individual I/O circuit op­tions, use the F1 ( > ) key to choose a circuit, then select the option using the TGL or CHNG key. On some displays, you can enter new val­ues from the keypad.
3. Press the F3 (Enter) key to save each change.
Copying a Configuration
If there are similar devices on an operating bus, you can use the Copy Configuration feature to copy the configuration from one to the another. Both of the devices must have a Device Number already configured, and they must be operating at the same baud rate. The device to be copied TO must not be Configuration Protected.
The device to be copied FROM must be the active device (move the HHM to that block or select it from the Block/Bus Status screen).
1. To begin, press F3 (Copy Configuration) from the Configuration menu. The HHM shows:
COPY CONFIG FROM: n TO:
chng entr
2. The Device Number of the active device ap­pears next to the word FROM. Enter the De­vice Number of the device being copied TO. Press F3 (Enter).
3. Press the F4 (Execute) key. The configuration is copied.
4-6
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 34
Configuring Field Control Station
4
1. From the HHM Main Menu, display the special set of menus for Field Control.
A. If the Bus Interface Unit or Field Processor is
the current-selected device, press F2 (ana­lyze) twice or F3 then F2.
B. If it is NOT the currently-selected device:
H
Select F2 (analyze) then F3 (Block/Bus Status).
H
Press the F1 (nxt) or F2 (prev) key repeat­edly to reach the serial bus address of the BIU or Fiel d Processor. Press F3 to make it the active de vice. The n, pressMenu, fol­lowed by F2 (Monitor/Control Ref).
F1:Monitor F2:Configuration
From this menu, press F2 (Configuration). This menu appears:
F1:GENIUS CONFIG F2:Module Config
F3:Previous Menu
H
Press F1 to configure the BIU/Field Processor.
H
Press F2 to configure individual modules.
Change the Bus Address
When you press F1 (Genius Configuration) from the Configuration menu, the HHM shows the serial bus address previously configured for the BIU or Field Processor:
1. If you want to change the address, enter the new address using the keypad.
2. Press F4 (entr). An error message appears if the number has been used for another device.
Select a PLC Reference Address
If the host is not a Series Six PLC or Series Five PLC, no entry is necessary here.
If the host is a Series Six PLC or Series Five PLC, assign an I/O or register reference address.
S t a t T b l Addr
OOOOO
< > I O 6 e n t r
shows reference type
1. Use the F3 key to toggle the selection of Series Six I/O memory, Series Five I/O memory, or register memory. (See the BIU/F ield Processor User’s Manual for information about memory usage in the Series Five and Series Six PLC).
If I/O memory is used, the amount required is equal to the number of bits of discrete data PLUS analog data. Each analog reference used consumes 16 points.
If register memory is used, an amount is re­quired that is equal to the total number of bytes of input data PL US all of the output data
2. Key in the number of the block’s beginning I/O or register reference. This may be:
Series Six I/O 1 to 993 Series Five I/O 1 to 2041 Registers 1 to 16383
3. Press the F4 (Entr) key.
D e v i c e S B A 1 4
P r v > e n t r
If the bus address is correct, press F2 to go on. Note: If a BIU or Field Processor has a Serial Bus
Address conflict on an operating bus, it will not scan the modules in the station until the fault is cleared.
GFK-0121E
Chapter 4 Device Configuration: Overview
Configure Additional Features
On the screens that follow, select these features:
H
Fault Reporting
H
Genius bus redundancy
H
BSM Controller
H
Output default time (for redundancy)
H
CPU redundancy
H
Duplex redundancy: default mode for outputs
H
Configuration protection
4-7
Page 35
4
Configuring Individual Field Control Modules
Go to the Field Control configuration menu:
F 1 : G E N I U S C O N F I G F 2 : M o d u l e C o n f i g
F 2 : P r e v i o u s M e n u
From this menu, press F2 to configure the individual modules in the station.
Disable the I/O Scan
While you configure the modules in the station, you may want to disable I/O scanning. (The Bus Interface Unit or Field Processor begins scanning I/O as soon as it is powered up).
I O S c a n D I S A B L E D *
P r v > t g l e n t r
Configure Data Addresses and Lengths
The next screens are used to assign the starting addresses and lengths for I, then Q, then AI, then AQ data.
If the host is a Series 90 PLC, these should correspond to the memory assignments made for the BIU or Field Process o r during PL C c onfi g uration.
If the host is a Series Six or Series Five PLC, only the length selected here is used; the entry made on the starting address screen is not used by the PLC. For those PLC types, the starting address was assigned on an earlier screen.
1. For each data type, enter a starting address for disc rete input data (I). For example:
Blk Map Start 1 IOOOO1
< > e n t r
2. Press F4 to accept the value. Then, enter a length in bits for I data. For example:
When the I/O scan is disabled, previously unconfigured module inputs and outputs default to 0. For previously-configured modules, inputs and outputs either default or hold their last state or value, as configured.
1. If you want to change the present selection, press F3 (tgl).
2. Press F4 (entr). If you want to go to the next screen without changing the selection, press F2 ( > ).
B l k M a p L n g t h 6 4
< > e n t r
3. Press F4 (entr) to accept the value.
4. Continue as above, entering starting addresses and lengths for the other data types.
The lengths entered must not add up to more than 128 bytes of inputs (discrete + analog) and 128 bytes of outputs (discrete + analog).
5. Press F1 ( > ) after entering the length for AQ data (the fourth data type).
If you changed any starting address or length entries, the HHM displays this screen:
M a p h a s c h a n g e d A c c e p t ?
n o y e s
6. To accept the changes and continue to the next menu, press F4 (yes).
4-8
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 36
4
Add Modules and Assign References
The first module configuration screen looks like this:
Rack number
R O :S1 EMPTY
< > t g l r e a d
Use F1 and F2 to display another slot (module)
The Rack Number is always 0. The Slot Number refers to the location of the
module relative to the BIU or Field Processor.
Read a Module Identification
If there is a module in the currently-selected slot, pressing F4 (read) from the “empty slot” screen brings up the module identification screen:
Slot number
Assign I/O References for the Module
After you “accept” a module into the slot, a screen like this appears:
R O :S1 I16 I_
e n t r
Specify the I/O references to be used by the module. For most applications, you can simply have the BIU/Field Processor assign the next available references in that memory type.
A. To assign the next available references, just
press F4 (entr).
B. If you want to assign specific references, enter
the starting address. Press F4 (entr).
Module references are automatically assigned by the BIU or Field P rocessor based on its configured data addresses and the number of points appropriate for the module type.
R O :S1 Mod type? D i s c r e t e O u t 1 6
t g l e n t r
H
If you want to change the module type dis­played, press F3 (tgl) to list other module types.
H
To accept the module type, press F4 (entr).
Module type
Select a Module Type
If a module is not present in the selected slot, press F3 (tgl) to select Generic I/O or Special I/O. Then press F4 (entr).
R O :S1 I/O type? G e n e r i c I / O
t g l e n t r
H
Use the F3 (tgl) key again to go through the module names.
H
When the correct module name appears, press F4 (entr).
Editing a Module Configuration
To edit the module’s configurati on, press F4 (zoom). Refer to the module configuration instructions in the BIU/Field Processor User’s Manual.
Delete an Existing Module Configuration
To delete the configuration of the module in the present slot, press F3 (delete) then F4 (enter). Note
that this removes the entire module configuration.
Configuring Module Features
Configure additional module features as described in the BIU/Field Processor User’s Manual. For example:
H
Change the module’s reference address.
H
Module F ault Reporting (discrete)
H
Default inputs (or outputs) or Hold Last State (discrete and analog)
H
Channel Fault Reporting (analog)
H
Channel Active (analog)
H
Input Current/Voltage Ranges (analog)
H
Input or output scaling (analog)
H
Alarm thresholds (analog)
H
Output default values (analog)
GFK-0121E
Chapter 4 Device Configuration: Overview
4-9
Page 37
Chapter 5Monitoring the Bus and its Devices
5
This chapter explains how to perform monitoring and control operations with the Hand-held Monitor.
Di s p la y in g Inform at i on A b o u t Bu s De v ic es (p age 5-2).
h
Selecting the Active Device (page 5-2) .
h
Cl ea r ing Fau l t s ( pa ge 5- 3) .
Display for a Bus Controller (page 5-3). Monitoring the Bus Status (page 5-3). Switching a Dual Bus (page 5-3). Monitoring a Genius Block (page 5-4).
h
Discrete I/O and Inpu t Bl o c k s (p a g e 5- 4) .
h
Discr ete Relay Output Blocks (page 5-5).
h
A nal og Blocks (pa ge 5-5).
h
RT D or Thermocoupl e Blocks (pag e 5-5).
h
Hi g h - s pe e d Co u nt e r Bl o ck ( p a g e 5- 6) .
h
Power TRAC Bloc k ( page 5-7).
Monitoring and Operation
HHM Menus
F 1 : M O N I T O R B L O C K F 2 : M N T R / C N T L R E F F 3 : B L O C K / B U S S T S F 4 : P U L S E T E S T
Monitoring and Controlling Individual Circuits on a Genius Block (page 5-8).
h
Discr ete, Relay, High-speed Counter Block (p. 5-9). – F o r cing an Input or Output (page 5-9).
– Clea r i n g Ci r c u i t F a u l t s (p a g e 5- 9) .
h
A nalo g, RTD, or Thermocou ple Block (page 5-10). – F o r cing an Anal o g Value (page 5-10).
Clearing Circuit Faults (page 5-10).
h
Power TRAC Bloc k ( page 5-11). – F orc ing P o werT RAC Data (page 5-12).
Diagnostics (page 5-12).
Monitoring /Controlling Remote Drop Data (page 5-13).
Forcing a Circuit (page 5-1 4). – Dis pl ay ing and Clear ing Fa ul ts (pag e 5-14).
Monitoring /Controlling Field Control Data (page 5-15).
–Forcing/Unfor c i ng the Refer enc e (p 5-15). – Dis pl ay ing and Clear ing Fa ul ts (pag e 5-16).
P ul s e Testi n g Ou t p u t s on D is cre t e B lo ck s (pag e 5-17) .
F 1 : H H M U T I L I T I E S F 2 : A N A L Y Z E F 3 : C O N F I G U R A T I O N F 4 : D E V I C E M E M O R Y
F 1 : M o n i t o r F 2 : C o n f i g u r a t i o n
F2 or F3 (Field Control)
F1 (Genius)
R E F S (block references) 3 4 5 6 7 8 9 0
OIOIB
I I
S
A1011001
F2 (Genius)
M N T R 4 4 1 – 4 6 4 A I 2 : – 1 9 3 7 0 N O F A U L T S > f o r c e r e l e s
GFK-0121E
OIOIO
O
I
I
F4 (Genius)
Pulse Test
discrete outputs
F3 (All Devices)
R E F S (device references) D C 1 6 K 1 5 v 2 . 0 A C T
F O R C E D , N O F A U L T S n x t p r v a c t v b u s
S E R I A L B U S S T A T S A C T V D E V I C E S = 7 S C A N T I M E = 1 0 m s
F 1 : M o n i t o r I / O F 2 : F a u l t s
F 3 : P r e v i o u s M e n u
O
I
Select the
Active Device
here
5-1
Page 38
5
Displaying Information About Bus Devices
Select F3 (Block/Bus Status) from the Analyze menu to:
H
Display the references assigned to any device.
H
Display the revision level of any device.
H
Display the description and Global Data ad­dress of a bus controller.
H
Display the fault status of a Genius block or Remote I/O Scanner (remote drop).
H
Select the active device.
H
Clear all faults on the active device.
H
Access the Bus Status display.
This screen provides a quick way to check for faults and forced circui ts before starting up a system.
Block/Bus Status Displays for Bus Devices
Example displ ays are shown below. (Display format for bus controllers is shown on the next page).
Genius Block (discrete)
REFS (devicereferences) DC16K 15 v2.OACT FORCED,NO FAULTS nxt prv actv bus
Remote I/O Scanner
REFS *_ * G RIO 15 v3.5ACT NO FORCE,FAULTS nxt prv actv bus
BIU/Field Processor
REFS *_ * fldpr 2O v1.OACT NO FORCE nxt prv actv bus
Line 1 shows the I/O references used by the device. If * symbols appear instead of references, the device’s references are incorrect for the type of host CPU curren t ly set up f o r t he HHM. F o r e xamp le, if a device is assigned to Series Six registers, and the HHM is set up for a Series 90 host, the HHM will display * sy m b o ls instead of references .
O
I
O
I
Line 1 also provides information about the device currently being displayed:
= Input block
I
= Output block
O
O
= Block with both inputs and outputs
I
= Analog, RTD or Thermocouple block
A
= PowerTRAC block or Remote I/O Scanner
G
Line 2 identifies the device and shows its serial bus address (also called its Device Number or block number), and its revision level.
Line 3 shows whether the device presently has any forces or faults. If the device is a Field Control BIU or Field Processor, however, the presence of faults is not indicated on this screen.
Selecting Another Device
Press F1 (Next) or F2 (Previous) as needed to display information about other device.
Note: Poor bus conditions may cause the HHM to skip (not display) a device that is present on the bus. Try moving the HHM to a different connector on the bus. Occasionally, this problem is caused by certain older Genius blocks that do not communicate with the HHM properly. If the problem persists, such blocks can be upgraded.
Selecting the Active Device
Initially, the active device is the one to which the HHM is connected.
You can display information about other devices without making them “active”.
However, for many functions the HHM must be attached to another device or the other device must be made “active” by following the steps below.
1. F rom the Analyze menu, select F3 (Block/Bus Status).
2. Press F1 (Next) or F2 (Previous), to reach the device’s description screen.
3. When the device’s screen appears, press F3 (Active) to make it the active device. (On a dual bus, the HHM must be on the same bus as the active block. If it is not, either move the HHM or force the bus selection)
4. Press D MENU to return to the Analyze menu.
5-2
Hand-held Monitor User ’s Guide – June 1994
GFK-0121E
Page 39
5
Clearing Faults from the Block/Bus Status Screen
Pressing the CLEAR key from this screen clears faults on the active device. For Genius blocks, if you want to clear a specific circuit fault, select F2 (Monitor/Control Reference) from the Analyze menu instead.
all
Block/Bus Status Display for a Bus Controller
If the active device is a bus controller, the Block/Bus Status display shows information appropriate to that bus c o n t roller ty p e. For exam ple:
S E R I E S 6 B U S A D R : (device #)(vers) R E G (registers) n x t p r v r / g b u s
The first line identifies the bus controller type. If it is a Series Five bus controller, PCIM, or QBIM, the first line indicates:
G E N I
The second line of the display shows the bus controller’s Device Number followed by its firmware revision level.
Reading a Global Data Address
The third line of a bus controller’s Block/Bus Status screen shows its assigned Global Data address.
If no Global Data address appears, it means that either:
H
The bus controller has no Global Data address.
H
A Seri es 90-70 bus controller has a Global Data address in % I, %Q , %AI, %AQ, or %R me mo r y, and no optional Series Six register address was configured for the bus controller.
If a Global Data address has been set up, you can use the F3 (R/G) key to toggle between (R)egister and (G)lobal memory format. If no Global Data reference has been set up, the F3 key is not assigned.
Monitoring the Bus Status
To display the number of devices currently operating on the bus, and the curren t bus scan time, select F4 (Bus) from the Block/Bus Status displ ay.
SERIAL BUS STATS ACTV DEVICES= 7
SCAN TIME 1Oms
The bus scan time shown is rounded down to the nearest millisecond (10mS represents 10.01 to
10.99mS).
Switching a Dual Bus
To force a bus switch in a redundant bus system, the HHM must be connected to the same bus as the presently-active device.
1. If necessary, make the BSM Controller the ac­tive device.
A. F rom the Analyze menu, select F3 (Block/
Bus Status).
B. Press F1 (Next) or F2 (Previous), to reach the
status screen for the BSM Controller.
C. When it appears, press F3 (Active) to make
the BSM Controller the active device.
2. Press D MENU to return to the Analyze menu.
3. F rom the Analyze menu, select F2 (Monitor/ Control Reference). The HHM shows the ac­tive bus and whether it is forced. For example:
M N T R / C T R L (input ref) S T A T E : B U S B F R C
> b u s A b i s B r e l s
4. Press F2 or F3 to select the other bus. The LED on the BSM is off when bus A is selected and on when bus B is selected. The I/O Enabled LED on each block on the active bus blinks.
GFK-0121E
Chapter 5 Monitoring the Bus and its Devices
5-3
Page 40
5
Monitoring a Genius Block
Select F2 (Monitor Block) from the Analyze menu to:
H
Display the I/O type of all circuits on the active block.
H
Display (not change) forces on the active block.
H
Display the bus presently selected by the BSM Controller.
Making the Block Active
If the block is not presently selected as the “active” block, follow the steps below.
1. F rom the Analyze menu, select F3 (Block/Bus Status).
2. Press F1 (Next) or F2 (Previous), to reach the device’s description screen.
3. When the block’s screen appears, press F3 (Ac ­tive) to make it the active device. (On a dual bus, the HHM must be on the same bus as the active block. If it is not, either move the HHM or force the bus selection)
4. Press D MENU to return to the Analyze menu.
After selecting the active device, use F1 (Monitor Block) to monitor its data. This is a example display for a discrete I/O block:
R E F S (block references) 3456789O
BSOIO
I
I
OIOIO
O
I
I
I
A1O11OO1
Monitor Block screens for other types of Genius blocks are described below .
Block References
On all the Monitor Block screens for a Genius blocks, line 1 shows the block references. If * symbols appear instead, the references are out of range for the CPU host currently setup for the Hand-held Monitor. For example, if a block is assigned to Series Six registers, and the HHM is set up for a Series 90 host, the HHM displays *symbols instead of references.
If the HHM is set up for PCIM mode, references are not used; a device description appears instead.
Monitor Block Display for Discrete I/O and I nput Blocks
For a discrete block, the Monitor Block display shows the I/O type and current state of each circuit. This is an example display for an 8-circuit grouped I/O block:
R E F S (block references) 3456789O
BSOIO
I
I
OIOIO
A1O11OO1
Line 1 indicates the block’s I/O type:
= Input
I
= Output
O
O
= Combination (I/O)
I
Line 2 shows the last digit of each circuit’s reference address. The abbreviation on line 3 describes the I/O type of each circuit:
= Input
I
I
= Tri–State input
T
= Output
O
O
= Output with feedback
I
= Circuit that controls a BSM
Bs
Line 4 shows the current state of each circuit. This information is updated continuously as the I/O states change.
An underline means a circuit is forced (and does not reflect actual circuit status):
= OFF
O
= forced OFF
O
=ON
1
= forced ON
1
If the circuit is configured as a BSM controller, the selected bus is displayed on line 4. If forced, the active bus letter is underscored.
= bus A
A
= forced to bus A
A
= bus B
B
= forced to bus B
B
Displayin g A dd i ti onal Circuits for a 32-circuit DC block: Press a key from F1 to F4 to toggle the
display between circuits 1 to 16 and circuits 17 to 32.
O
I
I
I
5-4
Hand-held Monitor User ’s Guide – June 1994
GFK-0121E
Page 41
5
Monitor Block Display for Discrete R elay Output Blocks
For a Relay block, the Monitor Block screen shows the current open (O) or closed (C) states of all relay outputs:
REFS (blockreferences)O 123456789O123456 OOOOOOOOOOOOOOOO OOOOCCOOOOOCOOCC
Line 2 shows the last digit of each circuit’s reference address. The ‘O‘s on line 3 show that each circuit is an output. Line 4 shows each relay output’s present state. An underline means the relay is forced.
= open
O
= forced open
O
= closed
C
= forced closed
C
Monitor Block Display for RTD or Thermocouple Blocks
For an RTD or Thermocouple Input block, the Monitor Block screen shows the current values of two inputs at a time. Values reported by the block may be tenths of degrees (Celsius or Fahrenheit), tenths of ohms, or unconverted counts. This is an example display showing tenths of degrees Celsius:
REFS(circuit references) A I1: 15O.O C I2: 25.5 C
Line 1 indicates that the block is an (A)nalog block. Lines 2 and 3 display the input values. The abbreviation FRC means a value is forced.
Press F1 ( > ) to display the next pair of inputs.
Monitor Block Display for Analog Blocks
For an analog block, each Monitor Block screen shows the current value of two circuits at a time. This is an example display:
REFS(circuit references) A I1: 18357 I2: 29O61 FRC
>
Line 1 indicates that the block is an (A)nalog block. Lines 2 and 3 display the current values of two circuits. On an analog block, each circuit may report either unconverted analog data, or data that has been scaled to be suitable for the application.
The abbreviation FRC means a value is forced. Press F1 ( > ) to display the next pair of circuits.
GFK-0121E
Chapter 5 Monitoring the Bus and its Devices
5-5
Page 42
5
Monitor Block Display for a High-speed Counter Block
For a High-speed Counter block, the Monitor Block function displays a sequence of screens with the following information:
1. The states of the block’s four Preset Outputs.
2. The states of the block’s Control Inputs.
3. The current values of the block’s internal data storage registers: Accumulator, Counts per Timebase, and Strobe.
The exact appearance and sequence of screens depends upon whether the block has been set up for four-counter (Type A), two-counter (T ype B), or one-counter (Type C) operation. The letter a, b, or c on the top line of the screen shows how the block is set up.
Preset Outputs
First, the Preset Outputs are displayed:
R E F (ctrnumber) (ctrtype) PRESET OUTPUT 1234
OOOO
Outputs that are forced are shown with an underscore (forced outputs do NOT respond to the actual value of the counter).
Control Inputs
Press F1 ( > ) to display the block’s Control Inputs:
CONTROL INPUTS c 1112123 DHPPSSS 111111O
On this screen, the numbers on line 2 identify the first, second, third, of fourth control input of the same input type on the block. The third line identifies the input type: Disable Input (D), Home Input (H), Preload Input(P), or Strobe Input (S). The screen’s bottom line shows the current state of each Control Input.
Register Values
Press F1 ( > ) to display the current value in each counter’s accumulator, Counts-per- Timebase register, and Strobe register(s):
R E F (number)(countertype) ACC 1:_+(acc.value) CTB 1:_+(countvalue) > nxt
5-6
Use the F1 ( > ) key to display the strobe value(s), and additional values appropriate to the counter type. For more detailed instructions for using a Hand-held Monitor with a High-speed Counter, refer to the High-speed Counter User’s Manual.
Hand-held Monitor User ’s Guide – June 1994
GFK-0121E
Page 43
Monitor Block Display for a PowerTRAC Block
5
If the active device is a P owerTRAC block, the HHM’s Monitor Block function displays the following screens:
H
One screen showing the states of all of the block’s Status Inputs.
H
Individual screens showing the block’s current calculated data values. In the Monitor Block function, these values are NOT labelled. It is easier to display this information using the Monitor/Control Reference function (F2), be­cause those displays are labelled.
H
One screen showing the states of all of the block’s Control Outputs.
On each of these screens, you can press F1 ( > ) to display next screen, or press F2 (ref) and enter a reference location to display a specific screen. For a sequential list of the P owerTRAC block data, see page 5-11.
Status Inputs
The Monitor Block function first displays the P owerTRAC block’s Status Inputs:
R E F (inputreferences) I 123456789O123456 OOO11OOOOOO1OOOO > ref
Line 2 indicates each of the 16 possible bit locations for status data. Lin e3 shows the current states of all inputs.
Bits 1 – 3 indicate the status of table data transfer,
for datagram communications.
Bit 4 = 1 indicates the block has captured an over-
current event.
Bit 5 should always be 1, indicating that the block’s
phase-lock loop is synchronized with the incoming AC voltage.
Bit 12 = 1 means the overcurrent event indicated
by bit 4 occurred on phase A.
Bit 13 = 1 means the overcurrent event indicated
by bit 4 occurred on phase B.
Bit 14 = 1 means the overcurrent event indicated
by bit 4 occurred on phase C.
Bit 15 = 1 means the overcurrent event indicated
by bit 4 occurred on the auxiliary current line.
Bit 16 = 1 indicates an internal calculation has re-
sulted in an out-of-range value. The block should be reconfigured to prevent this.
Calculated Data
After the Status Inputs, the HHM displays the block’s calculated data. If the P owerTRAC Block is version 2.3 or later, this includes the additional “low-priority I/O” data listed on page 5-11.
R E F (input reference) I
1 1 7 > r e f
Control Outputs
After the calculated data screens, the HHM’s Monitor Block function displays the P owerTRAC block’s Control Outputs. You can also display this data by using the F2 (ref) key to select output 1. You may need to toggle (F2) the memor y type.
R E F (outputreferences) O 123456789O123456
OOOOOOOOOOOOOOOO
> ref
Line 2 indicates each of the 16 possible bit locations for Control Outputs. Line 3 shows the current state of each Control Outputs. These outputs are communications handshaking bits, sent from the CPU to the block for certain datagram communications. Information about these outputs is in the PowerTR A C Block User’s Manual.
GFK-0121E
Chapter 5 Monitoring the Bus and its Devices
5-7
Page 44
5
Monitoring and Controlling Individual Circuits on a Genius Block
Select F3 (Monitor/Control Reference) from the Analyze menu to:
H
Display the present state or value of any circuit on the active block.
H
Display the diagnostics status of any circuit.
H
Force and unforce individual circuits.
H
Force a bus switch on a dual bus.
H
Clear individual circuit faults.
Making the Block Active
The block whose circuits wil l be monitored or controlled must first be made “active” by following the steps below.
1. F rom the Analyze menu, select F3 (Block/Bus Status).
2. Press F1 (Next) or F2 (Previous), to reach the device’s description screen.
3. When the block’s screen appears, press F3 (Ac ­tive) to make it the active device. (On a dual bus, the HHM must be on the same bus as the active block. If it is not, either move the HHM or force the bus selection)
Basic Monitor/Control Display Format
Each Monitor/Control Reference screen provides information about one circuit, channel, or data value. For example:
M N T R 4 4 1 – 4 6 4 A I 2 : – 1 9 3 7 N O F A U L T S > f o r c e r e l e s
Line 1 shows the references used by that circuit. If these are out of range for the host CPU set up for the Hand-held Monitor, line 1 instead shows:
M N T R (circuit number) + * A
For example, the first circuit on the block appears as: 1 + *
If the HHM is set up for PCIM mode, references are not used; a block description appears instead.
O
4. Press D MENU to return to the Analyze menu.
From the Analyze menu, press F2.
5-8
Hand-held Monitor User ’s Guide – June 1994
GFK-0121E
Page 45
Monitor/Control Reference Display for a Discrete, Relay, or High-speed Counter Block
5
For a discrete, Relay, or High-speed Counter block, the Monitor/Control Reference screen looks like this:
M N T R / C N T L (reference) I S T A T E : N O F A U L T S > o n o f f r e l e s
Line 1 identifies the circuit currently being monitored. Pressing F1 ( > ) displays other circuits.
Line 2 shows the state of the circuit. In the example above, the circuit is OFF and not forced (no underline). Status is obtained directly from the block for both inputs and outputs. If the circuit is an output and no–load sensing is enabled it reflects the current flow out of the I/O block to the load, as well as voltage at the field terminals; otherwise, it indicates only the voltage at the field terminals (output from the switch).
O
Diagnostics
Line 3 of the Monitor/Control Reference screen shows whether the circuit has any faults. If it does, one of the following diagnostic messages appears:
Failed switch: The commanded state of the circuit
does not match the actual state of the switch or load.
Loss of I/O power: One pair of circuits on an dis-
crete isolated block is not receiving power.
No load: The load is drawing less than the block’s
minimum current level.
Open wire: An open wire condition has been de-
tected on a tristate input.
Overload: The output exceeds the block’s steady
state current limit.
Overtemperature: The block’s internal tempera-
ture exceeds 100_C.
Short circuit: Transient current above the block’s
short circuit limit.
Forcing an Input or Output
(The Hand-held Monitor’s circuit forcing capability must be enabled to force or unforce a circuit). To force a circuit on, press F2 (ON). To force it off,press F3 (OFF). The force remains until changed by the HHM (even through loss of block power). To clear a force, press F4 (reles).
Clearing Circuit Faults
After correcting a fault condition, press the CLEAR key to remove the message and restore the reference to normal operation (the Clear Block Faults function must be enabled to use this feature). If the fault condition still exists, the fault message will reappear.
GFK-0121E
Chapter 5 Monitoring the Bus and its Devices
5-9
Page 46
5
Monitor/Control Reference Display for an Analog, RTD, or Thermocouple Block
For an analog, RTD, or Thermocouple block, the Monitor/Control Reference screen shows the current value for each circuit. For example:
M N T R (ckt. reference) A I 2 : – 1 9 3 7 N O F A U L T S > f o r c e r e l e s
For an analog block, the values may represent either engineering units or unscaled analog data.
For an RTD or Thermocouple block, the values represent tenths of degrees (Celsius or Fahrenheit), tenths of ohms, or unconverted counts.
Press F1 ( > ) to display other circuits.
O
Forcing an Analog, RTD, or Thermocouple Value
The HHM’s circuit forcing capability must be enabled to perform this function.
1. Press F2 (Force) to force the displayed circuit.
2. If you make a mistake entering a value, use the
3. Press F3 (Enter) to save this value as the value
Clear key to delete one digit at a time, starting with the last. To exit without forcing a circuit, press F2 (Change).
for the circuit. The forced value will remain until you press F4 (reles), or enter a new value.
Diagnostics
Line 3 shows whether the circuit has any faults. If it does, one of these messages appears on line 3:
Feedback error: There is a wiring error or other
hardware fault on a Current-source Ana­log block. The output’s actual current dif­fers from the commanded current by
more than 250mA.
High alarm/low alarm: An analog input value ex-
ceeds its high or low alarm limit.
Input shorted: An RTD input circuit measurement
is less than expected for the RTD type.
Internal fault: Internal calibration readings for a
pair of RTD circuits are out of tolerance.
Open wire: On an RTD block, the RTD is missing
or faulty, or there is an open wire. On an analog block, an input configured for 4 to 20mA has less than 2mA present.
Overrange/underrange: An analog or RTD circuit
exceeds its maximum value.
Overtemperature: The block’s internal tempera-
ture exceeds 100_C.
Wiring error: There is a faulty connection be-
tween an RTD and the block.
Clearing Circuit Faults
After correcting a fault condition, press the CLEAR key to remove the message and restore the reference to normal operation (the Clear Block Faults function must be enabled to use this feature). If the fault condition still exists, the fault message will reappear.
5-10
Hand-held Monitor User ’s Guide – June 1994
GFK-0121E
Page 47
Monitor/Control Reference Displays for a PowerTRAC Block
2 3 4 5 6 7 8 9 0
V oltage phase A to B
10
1 2 3 4 5 6 7 8 9
ated
Current phase C A uxiliary CT current
5
For a PowerTRA C block, the Monitor/Control Reference function displays:
H
16 screens, each showing the state of one Status Input. This information is more easily dis­played with the Monitor Block function,which shows all 16 Status Inputs on one screen. See page 5-7.
H
Individ ual labell ed dis pl ays of the block’s current calcula ted d a ta v a lues. F o r PowerT R AC block version 2.3 or later, this includes the “low-priority I/O”screen s described on the next page.
H
16 screens, each showing the state of one of the block’s Control Outputs. Control outputs are also more easily di spl ayed using Monitor Block.
PowerTRAC Data Sequence
The following table shows the sequence of P owerTRAC block data that can be displayed on the Monitor/Control Reference screens:
Input W ord
1
Status inputs (16 screens in Monitor/Control Reference)
V oltage phase B to C V oltage phase C to A Voltage A to N (Line–to–neutral PTs only) Voltage B to N (Line–to–neutral PTs only) Voltage C to N (Line–to–neutral PTs only) Current phase A Current phase B
d Data
Current phase C
1 1
A ctive power phase A
1
A ctive power phase B
1
Calcul
A ctive power phase C
1
Reactive power A
1
Reactive power B
1
Reactive power C
1
Total power factor
1
A ccumulated power
1 20
Fundamental VARs phase A
21
Fundamental V ARs phase B
22
Fundamental V ARs phase C
23
Fundamental P ower Factor, total
24
Harmonic VARS as % of V–A, phase A
25
Harmonic VARS as % of V–A, phase B
26
Harmonic VARS as % of V–A, phase C
27
Harmonic VARS as % of V–A, total
28
Line Frequency
29
T emperature Alarm Status
Low–P riority I/O Data
30
Extended Watt-hour accumulator (upper 5 digits)
31
32–64
GFK-0121E
Output
W ord 1
Extended Watt-hour accumulator (lower 3 digits) not used
Control outputs (16 screens in Monitor/Control Reference)
Chapter 5 Monitoring the Bus and its Devices
For explanations of the data provided by a PowerTRAC block, see the PowerTR A C Block User’s Manual.
Selecting a Memory Type or Address
To select a specific data item, you can enter its memory type and/or address. Press F2 (ref). This screen appears:
M N T R __
t g l c h n g e n t r
1. Enter the reference number and press F3 (entr). If the HHM is set up for a PLC host, I/O refer­ences increment by 16 and word(register) refer­ences increment by 1. For a PLC host, both I/O and word references start at the first reference assigned to the block. If the HHM is set up for a PCIM/QBIM/GENI host, references begin at 1 and increment by 1.
2. The memory type blinks on the screen. To change the memory type, use the F2 (tgl) key.
3. Press F3 (entr) to display the information.
5-11
Page 48
5
PowerTRAC Status Inputs Screens
First, the Hand-held Monitor displays 16 screens showing the states of Status Inputs:
M N T R / C N T L (references) O S T A T U S I N P U T S S T S
> r e f f o r c e d i a g
To display additional data, press the F1 ( > ) key.
O
PowerTRAC Calculated Data Screens
After the Status Inputs, the HHM displays the block’s calculated data values. Lines 2 and 3 identify the data being displayed and show its present value. In the example below, voltage A to N is 117 volts.
M N T R (input references) 1 V a n S T S 1 1 7 > r e f f o r c e d i a g
PowerTRAC Control Outputs Screens
Finally, the HHM displays 16 screens showing the states of individual Control Outputs (datagram handshaking bits). If you use the F1 ( > ) key to reach the Control Outputs, notice that there are several unused references following the Extra Calculated Data data. You can use F2 (ref) to go directly to output 1. You may need to toggle the memory type to %Q (or O, depending on the host CPU setup of the HHM).
M N T R / C N T L (reference) O C O N T R O L O U T P U T S S T S
> r e f f o r c e d i a g
O
Forcing PowerTRAC Data
(The HHM’s circuit forcing capability must be enabled to perform this function). Display the data you want to force. Press F3 (force).
For bit data, the HHM displays:
m o n o n o f f r e l e s
PowerTRAC Extra Calculated Data (LPIO) Screens
If the P owerTRAC block is version 2.3 or later , the Hand-held Monitor next shows a series of screens with extra calculated (“Low-Priority I/O”) data. The block may or may not automatically provide this data to the host, depending on the block’s revision level and configuration. A CPU can use datagrams to read the data.
L P I O # 1 W 2 O I F U N D . V A R a S T S – 2 7 O > r e f d i a g
On these screens, the top line shows the serial bus address of the block and the relative data word being displayed. For example, the screen above shows the 20th input word (Fundamental VARs for phase A). This area of line 1 blinks as a reminder that the numbers shown are not reference addresses.
Press F2 (on) or F3 (off). To release the force, press F3 (reles).
For word data, the HHM displays:
S T S 4 f o r c e r e l e a s e
Press F2 (force). The screen next displays:
F O R C E T O : c h n g e n t r
Press F2 (chng). Enter the force value, then press F3 (entr). To release the force, press F4 (release).
Diagnostics
The PowerTRAC block does not report circuit faults. If you use the F4 (diag) key from the Monitor/Control Reference screen, the message NO FAULTS will appear.
5-12
Hand-held Monitor User ’s Guide – June 1994
GFK-0121E
Page 49
Monitoring/Controlling Remote Drop Data
5
The HHM can display diagnostics and current I/O states, and force and unforce individual I/O points on I/O modules in a remote drop.
When the active device is a Remote I/O Scanner, the HHM’s Monitor Block and Monitor/Control Reference functions display the same set of screens. This is unlike HHM operation for Genius blocks, where the screens for Monitor Block and Monitor/Control Reference are different.
For the Remote I/O Scanner, the monitoring screens provide the following information:
1. The states of the discrete inputs in the remote drop, in ascending order.
2. The values of the analog inputs in the remote drop, in ascending order.
3. The states of the discrete outputs for the re­mote drop, in ascending order.
4. The values of the analog outputs for the re­mote drop, in ascending order.
On each screen, line 3 shows the state or value of one circuit at a time. It also indicates whether the circuit is forced, or has a fault as illustrated below . The first screen that appears is the Monitor screen for the module with the first %I reference.
It shows the Remote Drop ID (143 in this example), the rack number (0),the slot number (2), and the memory type (%I). The number on the righthand side of the second line represents a data word.
1 4 3 # 4 . 2 % I 1
Starting reference (groups of 16)
Reference Type Slot Number
Rack Number Remote ID Number
The Series 90-70 I/O reference for the circuit is one less than the sum of the two numbers on the righthand side of the HHM screen. For example:
M N T R 3 1 4 3 # 4 . 3 % I 3 3
3 + 33 – 1=35
In this example, the circuit being monitored is %I0035.
GFK-0121E
MNTR 1 143#O.2 %I 1 STS O FAULT > ref force diag
Line 1 shows the relative number in the word of the circuit being monitored:
M N T R 1
Here, it is the first circuit on the block. The second line identifies the I/O module being monitored:
1 4 3 # 4 . 2 % I 1
Chapter 5 Monitoring the Bus and its Devices
Displaying Other Circuits
To display additional circuits, press the F1 ( > ) key. The HHM will step through each available circuit. To jump directly to a particular device, memory type, or address, press F2 (ref). This screen appears, to enter the desired information.
M N T R 3
t g l c h n g e n t r
1. Enter the reference number. Press F3 (entr). The memory type blinks on the screen.
2. If you want to select a different reference type (for example, to display%AQ instead of %I), press F2 (chng) to toggle the memory type.
3. With the desired information displayed, press F3 (entr) to monitor the circuit.
5-13
Page 50
5
Forcing a Circuit
(The HHM’s circuit forcing capability must be enabled to perform this function). Display the circuit you want to force. Press F3 (force).
For a discrete circuit, the HHM displays:
m o n o n o f f r e l e s
Press F2 (on) or F3 (off) to force the circuit. The forced state appears on line 3. To release the force, press F3 (reles).
For an analog circuit, the HHM displays:
S T S 4
f o r c e r e l e a s e
Press F2 (force) to force the circuit. The screen next displays:
F O R C E T O :
Press F2 (chng). Enter the force value, then press F3 (entr). The forced value will appear on line 3.
Displaying and Clearing Remote Drop Faults
To display diagnostics for a circuit, press F4 (diag) from the Monitor screen. If there is a fault, it appears on line 3. For example:
DIAG 3 143#O.3 %I 33 OVERCURRENT mon nxt
If there is no fault on the circuit you are monitoring, the Hand-held Monitor searches the Remote I/O Scanner’s internal fault table to see whether there are any faults on the remote drop. If there are any uncleared faults on the remote drop, the HHM displays the fault that occurred first (the oldest fault). For example:
DIAG 3 143#O.2 %AI 1 UNDERRANGE mon nxt
F R C 1 > r e f f o r c e d i a g
To release the force, press F4 (release) from the force/release screen.
The HHM identifies the location where the fault occurred (on line 2). From this screen, you can display additional faults on the remote drop by pressing F4 (nxt). Faults will appear in the same sequence in which they occurred. For example,if the fourth oldest is being shown, pressing F4 (nxt) displays the fifth oldest, and so on.
To return to the Monitor screen you started from, press F1 (mon).
Clearing Faults
After correcting fault–causing conditions, you can return to the Block/Bus Status menu to clear all fault messages for the remote drop. (The Clear Block Faults function must be enabled to use this feature).
5-14
Hand-held Monitor User ’s Guide – June 1994
GFK-0121E
Page 51
Monitoring/Controlling Field Control Data
5
The HHM can display diagnostics and current I/O states, and force and unforce individual I/O points on Field Control modules.
1. From the HHM Main Menu, display the Field Control main menu.
F 1 : M o n i t o r F 2 : C o n f i g u r a t i o n
A. If the BIU or Field Processor is the active de-
vice, press either F3 (Configuration) or F2 (analyze) twice.
B. If it is NOT the active device select F2 (ana-
lyze) then F3 (Block/Bus Status).
H
Press the F1 (nxt) or F2 (prev) key re­peatedly to reach the serial bus address of the BIU/Field Processor . Press F3 to make it the active device.
H
Then, pressMenu, followed by F2 (Monitor/Control Ref).
2. Press F1 (Monitor). This menu appears:
F 1 : M o n i t o r I / O F 2 : F a u l t s
F 3 : P r e v i o u s M e n u
3. Select F1 (monitor I/O) to display the Monitor screen for the first %I reference.
Reference
being
monitored
Indicates force is in effect
Current
state or value
Displaying Another Reference
Use the F2 ( > ) key to advance through the point reference screens for the selected reference type.
Changing the Display Mode
The letter in the upper right corner of the display shows the present data type:
B binary
Hhex D decimal
Use the F4 (mode) key if you want to change the display data type.
Returning to the Previous Menu
Press the HHM Clear key when you want to return to the main Field Control menu.
Forcing/Unforcing the Displayed Reference
I/O points can be forced and unforced from the Hand-held Monitor (the HHM’s circuit forcing capability must be enabled to use this function). Forcing an I/O point changes its state in the F ield Processor’s EEPROM memory . If the circuit is an output, the physical state of the output also changes. If the circuit is an input, the forced input data is sent to the CPU. A circuit retains its forced state or value if power is removed. The forced circuit ignores data from an attached input device, or output data from the CPU. The force can ONLY be removed from the Hand-held Monitor.
1. If the display is set to hex (H) or binary (B), change it to decimal (D) by pressing F4.
2. Press the F3 (force) key to force the reference now being displayed.
I OOOO1*O B
< > f r c h e x
Changing the Reference Type Being Displayed
Use the F1 ( < ) key to select a reference type: I (discrete inputs), Q (discrete outputs), AQ (analog outputs), or AI (analog inputs).
GFK-0121E
Chapter 5 Monitoring the Bus and its Devices
I OOOO1*1 D
f r c u n f r c
3. Press F3 (force) again. Then, enter the forced state or value. The HHM displays an asterisk to indicate the state of value now shown is forced. See the illustration at left.
4. Use the F4 (unforce) key from the same screen when you want to unforce the point.
5-15
Page 52
5
Displaying Field Control Faults
A Hand-held Monitor can display faults from a Bus Interface Unit or Field Processor while attached anywhere on the Genius bus.
1. From the HHM Main Menu, display the Field Control main menu (instructions are on the previous page).
F 1 : M o n i t o r F 2 : C o n f i g u r a t i o n
2. From this menu, select F1 (Monitor). The fol­lowing menu appears:
F 1 : M o n i t o r I / O F 2 : F a u l t s
F 3 : P r e v i o u s M e n u
3. Select F2 (faults) to display fault information for the Field Processor and its modules.
The Faults menu appears:
F 1 F i r s t 1 6 F l t s F 2 L a s t 1 6 F l t s
F 3 P r e v i o u s M e n u
4. Press F1 to display the first set of 16 faults (one fault at a time). For example:
S l o t # 1 F a u l t # 1 E X T R A I / O M O D U L E
< > e x i t
A. Use F1 and F2 to display another fault B. If there are no faults, the HHM displays the
message: No Faults on the top line.
5. To display the last 16 faults (if any): A. Press F4 (exit) to return to the screen shown
at the top if this page.
B. Press F2 (last 16 faults).
Clearing Field Control Faults
If faults are present, pressing the HHM Clear key here has no effect. To clear faults from the Hand-held Monitor you need to do the following:
1. Return to the HHM Main Menu.
2. Press F2 (Analyze).
3. Press F3 (Block./Bus Status).
4. Make the BIU or Field Processor the active de­vice if it is not.
5. Press the Clear key.
Clearing faults from the Hand-held Monitor does not clear faults at the host PLC. To keep the entire system in step and up-to-date, fault clearing should be performed from the host PLC.
5-16
Hand-held Monitor User ’s Guide – June 1994
GFK-0121E
Page 53
Pulse T esting Outputs on Discrete Genius Blocks
5
Pulse Testing verifies the ability of outputs on a discrete block to change state. Pulse Testing also indicates whether output circuits (wires, power sources, loads) will start or stop current flow . Pulse testing is recommended for blocks controlling outputs that seldom change state. It provides assurance that when needed, an output will operate correctly. Blocks that control outputs which frequently change state do not need to use the Pulse Test feature. Pulse Testing does not provide enough energy to activate mechanical devices such as motor starters, relays, or solenoid valves, but it may change the state of a very small load.
Executing a Pulse Test
(To execute a Pulse Test, the Hand-held Monitor’s PULSE TEST capability must be enabled). The block being Pulse Tested must be the active block.
1. From the Analyze menu, press F4 (Pulse Test). The Pulse Test display appears:
P U L S E T E S T R E F S (ckt references) N O F A U L T S e x e c
O
I
Clearing Pulse Test Faults
If you press the CLEAR key from the Pulse Test screen, all faults on the block will be cleared.
If you press the Clear key from the Monitor/Control screen (after displaying a specific circuit fault), only that fault will be cleared.
Pulse Test Error Messages
If the Pulse Test cannot be performed or if the block fails to respond, an error message appears. Press the Clear key to remove the message.
E : P U L T S T D I S A B L E
A Pulse Test cannot be performed unless the block’s configuration is changed.
E : I N V L D B L K T Y P E
The block does not support Pulse Tests.
E : I N V L D B L K C O N F I G
The active block is an inputs–only block.
E : P U L S E T E S T F A I L
The HHM has not received an acknowledgement from the block within the predetermined amount of time. Retry the test. If it continues to fail, check the serial bus cable and active block.
For a PLC host, line 2 shows the block’s as­signed references and its I/O configuration. Line 3 shows whether the block has any faults.
2. Press F1 (Execute) to pulse all outputs on the block once. If the word FAULTS appears, it means that one or more diagnostic errors have occurred. Go to the Monitor/Control menu to display the specific type of fault that has oc­curred.
GFK-0121E
Chapter 5 Monitoring the Bus and its Devices
5-17
Page 54
Chapter 6Reading CPU Memory
6
This chapter explains how to use a Hand-held Monitor to read data in a specified memory location in a Series 90–70, Series Six, or Series Five PLC. New data from the specified memory location is displayed every three seconds.
General Instructions _________________________________________
1. Be sure the Hand-held Monitor is set up for the type of PLC host you want to read data from. (See page 3-5 for instructions).
2. If the Hand-held Monitor is NOT attached directly to the PLC’s bus controller, or if another device is designated as “active” when you enter the Device Memory function, use the F4 (SBA) key and enter the bus controller’s Device Number (serial bus address).
3. To read data from the selected bus controller, press F4 from the Main Menu and specify the memory location to be read as instructed below.
GFK-0121E
6-1
Page 55
6
Series 90 PLC
For a Series 90-70 PLC, the Hand-held Monitor can read data from %R, %AI, %AQ,%I, %Q, %T, %M, %S, %SA, %SB, %SC, and %G memory.
For a Series 90-70 PLC, the memory location/content screen looks like this example:
D E V I C E M E M O R Y 1 5 % R 1
t g l c h n g e n t r S B A
The top line shows the currently-selected Device Number (15 in the example above). Line 2 shows the memory type currently accessed, and a reference location within that memory type. In this example, the selected location is %R0001.
From this screen, use the HHM function keys to: A. Select a different bus device (press F4 (SBA)). B. Select another memory type (press F1 (tgl)). C. Select another reference location (press
F2(chng), then enter the desired numerical offset).
D. Display the current memory contents of the
specified location (press F3 (entr)).
When F3 (entr) is pressed, the HHM displays the content in either bit or word format, as appropriate for the selected memory type. For example, here word data is displayed, because the selected memory type (%R) is word-based:
D E V I C E M E M O R Y 1 5 % R 1 W O R D 1 3 9 > < l o c
From this screen, you can display the current contents of other locations in the selected memory type:
A. Use the F1 ( > ) key to increment the memory
offset (location).
B. Use the F2 ( < ) key to decrement the memory
offset.
C. Use the F3 (loc) key if you want to enter an off-
set from the HHM keypad.
6-2
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 56
Series Six PLC
6
For a Series Six PLC, the Hand-held Monitor can read data from register memory. That includes I/O data mapped into register memory, (it is easier to display I/O data with the HHM’s Monitor Block or Monitor Control Reference function).
For a Series Six PLC, the Device Memory screen looks like this example:
D E V I C E M E M O R Y 7 M E M : (location)
t g l c h n g e n t r S B A
The top line shows the currently-selected Device Number (7 in the example above). If there is a currently-selected memory location, it appears on the second line of the display as two numbers separated by a colon.
The number on the left will be:
32768 for a Series Six PLC
The number on the right is the actual memory location that will be read.
From this screen, use the Hand-held Monitor function keys to:
A. Select a different device on the bus (press F4
(SBA)).
B. Select another memory type (press F2 (chng)).
See right for instructions.
C. Select another reference location in the dis-
played memory type (press F2(chng)). See right for instructions.
D. Display the current memory contents of the
specified location (press F3 (entr)).
Enter or Change the PLC Type
To enter or change the PLC type:
1. Press F3 (chng). A cursor appears at the left of the colon. For a Series Six PLC, enter the num­ber 32768.
2. Press the F3 (entr) key.
Enter or Change the Memory Location
To enter or change the memory location:
1. On the same screen, press F1 ( > ) to move the cursor to the right of the colon.
2. Press F2 (chng).
3. Enter a number equal to the actual register number plus 16383. For example, for regis­ter#100, you would enter (16383 + 100), which is 16483:
M E M : 3 2 7 6 8 : 1 6 4 8 3
Expanded I/O Data
Expanded I/O data is mapped into registers and can be accessed as described above. I/O data from channel 0, or the main I/O chain in an expanded I/O system can be displayed using the integer result of the following formula:
((point number – 1) / 8) + table offset
The table offset is either 8192 for the output table or 8320 for the input table. Example: to display input 672, you would enter: ((672 – 1) / 8) +8320, which is 8403.
GFK-0121E
Chapter 6 Reading CPU Memory
6-3
Page 57
6
Series Five PLC
For a Series Five PLC, the Hand-held Monitor can read data from register memory. That includes I/O data mapped into register memory, (it is easier to display I/O data with the HHM’s Monitor Block or Monitor Control Reference function).
For a Series F ive PLC, the Device Memory screen looks like this example:
D E V I C E M E M O R Y 7 M E M : (location)
t g l c h n g e n t r S B A
The top line shows the currently-selected Device Number (7 in the example above). If there is a currently-selected memory location, it appears on the second line of the display as two numbers separated by a colon.
The number on the left will be: 133 for a Series Five PLC The number on the right is the actual memory
location that will be read. From this screen, use the Hand-held Monitor
function keys to: A. Select a different device on the bus (press F4
(SBA)).
B. Select another memory type (press F2 (chng)).
See right for instructions.
C. Select another reference location in the dis-
played memory type (press F2(chng)). See right for instructions.
D. Display the current memory contents of the
specified location (press F3 (entr)).
Enter or Change the PLC Type
To enter or change the PLC type:
1. Press F3 (chng). A cursor appears at the left of the colon. For a Series Six PLC, enter the num­ber 32768.
2. Press the F3 (entr) key.
Enter or Change the Memory Location
To enter or change the memory location:
1. On the same screen, press F1 ( > ) to move the cursor to the right of the colon.
2. Press F2 (chng).
3. Enter the byte offset of the data. This is equal to (2 x register #) – 2. For example, for regis­ter#100, you would enter (2 x 100) – 2, which is 198.
I/O Data
Series Five I/O data can be displayed using the integer result of this formula:
(point number) / 8 + table offset
The table offsets for Series Five I/O are:
channel 1 inputs 32768 channel 2 inputs 32896 channel 1 outputs 33024 channel 2 outputs 33152
Example: to display channel 2 output 12, you would enter:12/8 + 33152, which is 33153:
M E M : 1 3 3 : 3 3 1 5 3
Press F3 (ENTR) to save the memory location. To display the memory content of this location, press F3 (ENTR) again.
6-4
Hand-held Monitor User’s Guide – June 1994
GFK-0121E
Page 58
Changing the Data Format
6
When the memory display first appears, it looks like this example:
D E V I C E M E M O R Y 7 M E M : 1 : 6 5 5 2 4 W O R D 1 2 3 4 5 v a l a d d r
You can display either one byte or one word of data. You can also select either decimal display:
W O R D 1 2 3 4 5 B Y T E 3
or binary display:
4 4 1 4 4 1 1 1 4 4 4 4 4 4 1 1
4 4 4 4 4 4 1 1
To change the data format:
1. Press F2 (VAL).
2. Use the function keys to select the format you want.
Changing the Selected Address
To change the address being monitored, press F3 (ADDR). The HHM shows:
D E V I C E M E M O R Y 7 M E M : (location) W O R D (value) > < l o c
To Display Information from Another Device: press F3 (Location). The function key assignments change. Now press F4 (SBA). Select the new Device Number then press F3 (ENTR).
To Increment or Decrement the Memory Address: use the F1 ( > ) and F2 ( < ) keys.
To Enter a New Address: press F3 (LOC). Line 4displays new function key assignments. Key in the memory location as explained previously.
3. Press the D MENU key to return to the pre- vious screen, where the value will be displayed.
GFK-0121E
Chapter 6 Reading CPU Memory
6-5
Page 59
Chapter 7Error Messages
7
This chapter explains error messages that may be displayed on the Hand-held Monitor.
Powerup Error Messages
If an error occurs during the Hand-held Monitor’s self-test, this multi-language error display may appear:
P W R U P E R R O R # 1 E R R E U R # 1 E I G T E S T : F E H L # 1 E R R O R E I N I Z # 1
Cycle power to the Hand-held Monitor and try again. If the message returns, look for its error number in the list at right.
#2 The HHM has a faulty EPROM. Obtain a
replacement or an HHM upgrade kit.
#4 The HHM may have been assigned a De-
vice Number already used on the bus. Press the ON/OFF key, then disconnect the HHM from the device it is attached to. Press the ON/OFF key again. Following the instruc­tions on page 3-4, assign the HHM a differ­ent Device Number.
At 38.4 Kbaud, unterminated HHM cable may cause this message. Remove the HHM cable or check that HHM is connected to a properly-terminated bus.
This error may occur if the Hand-held Mon­itor is connected to a bus and an incorrect baud rate is selected.
#5 This number indicates an internal fault, or
excessive noise on the bus, or that the bus is operating at a different baud rate from the HHM. Press the ON/OFF key then discon­nect the HHM cable from the bus the HHM. Press the ON/OFF key again. If the message reappears, replace the HHM.
This error may occur if the Hand-held Mon­itor is connected to a bus and an incorrect baud rate is selected.
and
from
GFK-0121E
#1, 2, 3, or 6 indicates that the Hand-held Monitor must be replaced.
7-1
Page 60
7
Operating Error Messages
The HHM may display one of the messages shown below when the ON/OFF key is pressed or during operation. If a message appears, press the Clear key, then follow any action suggested.
E : N O A C T I V E A D D R
No active device has been selected, so many functions do not operate. See page 5-2 to select an active device.
E : K E Y = M O N T R O N L Y
Place the keyswitch in Configure mode (the key must be present). Press Clear, then retry the operation. Press Enter.
E : F N C T N D I S A B L E D
The function just selected is disabled by the HHM’s current configuration. Press the Clear key to remove the message.
E : C O M M E R R O R
HHM cannot communicate with the device. If the HHM is connected directly to a device which is not on an ope rating bus, be sure a terminating resistor is connected across Serial 1 and Serial 2. If the message returns, check the bus controller and HHM cab le connectio n s. Try other dev ices.
E : E E P R O M F A I L U R E
Configuration Error Messages
The following messages may appear while configuring a bus device. They usually indicate an incorrect selection.
E : C O N F I G P R O T E C T
The device’s configuration is protected, its features cannot be changed. To configure the block, disable Configuration Protection.
E : N O T O N B L O C K
To configure the Device Number, connect the HHM directly to that device.
E : D U P B L O C K N O
The Device Number has already been assigned. This message only appears if the device is connected to a operating bus. Another number must be assigned to one of the devices in conflict.
E : D U P L I / O R E F S
The PLC Reference Number conflicts with or overlaps one already assigned to another device on the bus. Assign a different reference to one of the devices in conflict.
E : O U T O F R A N G E
The Reference Number is too high.
E : N O T B Y T E B N D R Y
If you are using the HHM to configure or force a block, clear the message and go to Block/Bus Status menu. Press the Clear key. If the block’s Unit OK LED continues to blink, power down the block and replace the Terminal Assembly, configuring the replacement to match the original.
D I F F E R E N T B A U D
The HHM and block have been set for different baud rates: one is set for 153.6Kbaud standard and the other is set for 153.6 Kbaud extended (the HHM will not communicate with the bus if any baud rate conflict exists). All devices on the bus must be set to the same baud rate.
Additional Messages: The following additional messages may appear during normal system use:
E : F N C T N D I S A B L E D E : N O S U C H D E V I C E E : M O N I T O R O N L Y
7-2
Hand-held Monitor User’s Guide – June 1994
The Reference Number does not begin on a byte boundary (1, 9, 17 . . .).
E : I N V A L D B L K C F G
The configuration entry is not valid.
E : N O S U C H D E V I C E
The destination device does not exist. Check the Device Number.
E : D I F F B L K T Y P E S
Copy Configuration cannot be used between dissimilar device types.
E : C O P Y E R R O R
An error has occurred during Copy Configuration. Press Clear and try again.
E : F N C T N D I S A B L E D
The function is not currently enabled for the HHM.
GFK-0121E
Page 61
Index
A
AC operation, 2-1 AC power required, 1-5 , 2-1 Accessories, 1-3 Active device, selecting on HHM, 4-6 , 5-2
, 5-4 , 5-8
Adapter
230VAC connector, 2-2
AC power, 2-1 Alar m diagnostic, 5-10 Analog blocks
Monitor block screen, 5-5
Monitor/Control Reference screens, 5-10
B
Battery pack, 1-3
charging, 2-1 , 2-3
operation, 2-3
replacing, 2-3 Baud rate, 1-5
configuring for bus devices, 4-4
configuring HHM to change for blocks,
3-6 error , 7-2 selecting after powering up HHM, 3-2
Block ID, configuring HHM to change for
blocks, 3-5
Block/Bus Status display
for Bus Controller, 5-3 for Genius block, Remote I/O Scanner ,
or Field P rocessor, 5-2
Bracket, mounting, 2-7 Bus
displaying number of devices on, 5-3 dual
switching, 5-3
viewing presently active bus, 5-4 scan time, display , 5-3 status, 5-3
Bus controllers
Block/Bus Status display, 5-3 compatibility with HHM versions, 1-4
Bus Switching Module, compatibility with
HHM versions, 1-4
C
Case, 1-3 Catalog numbers
Genius blocks and HHM versions, 1-4 HHM, options, accessories, 1-5
Charger, 1-3
catalog number, 1-5
using, 2-1 COMM Error message, 3-7 Communications error , 7-2 Compatibility with other devices, 1-4 Configuration
for bus devices
copying, 4-6 Field Control modules, 4-8 Field Processor, 4-7 Genius blocks, 4-6 grounding required for offline config-
uration, 4-2 menus, 4-3 online or offline, 4-2 Program Block ID, 4-4 Remote I/O Scanner , 4-5
for permanently installed HHM, 2-6 sequence for HHM, 3-4 setting up HHM to configure bus de-
vices, 3-6 Configuration Protected error, 4-3 , 7-2 Connector, external
catalog number, 1-5
installation instructions, 2-9 Copy error, 7-2 CPU, host, configuring HHM for, 3-5 Current, display for P owerTRAC block,
5-11
D
D connector, 2-8 Data type, changing when monitoring re-
mote drop, 5-15 Description, 1-2 Device number
HHM, 3-4 of bus device, changing, 4-4
Diagnostics
displaying, 5-9
GFK-0121E
Index-1
Page 62
Index
for analog, RTD, or Thermocouple
block, 5-10 Different Baud error, 7-2 Different Block Types error, 7-2 Dimensions, 1-5 Display, 1-5
special characters, 1-3
testing, 3-7 Duplicate Block Number error, 7-2 Duplicate I/O References error , 7-2
E
EEPROM failure, 3-7 EEPROM Failure error, 7-2 Error messages, during HHM test, 3-7
F
Failed switch diagnostic, 5-9 Fault clearing
configuring HHM to enable fault clear-
ing, 3-6 from Block/Bus Status screen, 5-3 on analog, RTD, or Thermocouple
block, 5-10 on discrete, relay or High-speed Count-
er block, 5-9 on remote drop, 5-14 , 5-16
Features, 1-1 Feedback Error diagnostic, 5-10
viewing present status of circuit on RTD
or Thermocouple block, 5-5
Function Disabled error, 7-2
G
Genius blocks
compatibility with HHM versions, 1-4 I/O type, 5-4 monitoring with HHM, 5-4
H
Hardware setup, 2-1 High-speed Counter blocks, Monitor
block screen, 5-6
High-speed Counter Block
Inputs, display , 5-6 presets, display , 5-6
Humidity, 1-5
I
I/O forced status, 5-4 I/O scanning, for Field Processor , disable,
4-8 I/O type, 5-4 Input Shorted diagnostic, 5-10 Installation, instructions, 2-6 , 2-7 Installed HHM, configuration sugges-
tions, 2-6 Internal Fault diagnostic, 5-10 Invalid Block Configuration error , 7-2
Field Control products, compatibility with
HHM versions, 1-4
Field P rocessor, configuration overview,
4-7
Forcing I/O
configuring HHM to perform, 3-6 on analog, RTD, or Thermocouple
block, 5-10
on Monitor/Control Reference screen,
5-9 on remote drop, 5-14 , 5-15 viewing present status, 5-4 viewing present status of analog circuit,
5-5
Index-2
K
Key=Monitor error, 7-2 Keypad, 1-1 , 1-2
testing operation, 3-7 Keys, 1-3 , 1-5 Keyswitch, 1-1
positions, 1-3
L
Languages, 1-1 , 1-5 , 3-5
GFK-0121E
Page 63
Index
LCD display , 1-1 Loss of I/O P ower diagnostic, 5-9 Low power, 2-3
M
Memory, reading, 6-1 Menus, main, 3-3 Monitor Block screens, 5-4 Monitor Only error, 7-2 Monitor/Control Reference screens
for Field Processor, 5-15 for Genius blocks, 5-8
for Remote I/O Scanner , 5-13 Monitoring, menus, 5-1 Mounting bracket, 2-7
N
No Active A ddress error, 7-2 No Faults diagnostic, 5-12 No Load diagnostic, 5-9 No Such Device error, 7-2 Not Byte Boundary error, 7-2 Not on Block error, 7-2
P owerTRAC block
data sequence, 5-11 display data, 5-7 Monitor/Control Reference screens, 5-11
P owerup, 3-2 P owerup Error messages, 7-1 Program Block ID screens, 4-4 PROM, changing, 2-4 Pulse Testing outputs, 5-17
R
Redundant bus, 5-4
switching, 5-3
References
asterisks appear on screen, 5-2 not on byte bundary, 7-2
of Genius block, displaying, 5-4 Relay blocks, monitor block screen, 5-5 Remote drop, configuration, 4-5 Remote I/O Scanner
compatibility with HHM versions, 1-4
configuring I/O map, 4-4 , 4-5 RTD blocks
Monitor block screen, 5-5
Monitor/Control Reference screens, 5-10
O
Open Wire diagnostic, 5-9 , 5-10 Operating time, 1-5 Out of Range error, 7-2 Overload diagnostic, 5-9 Overrange diagnostic, 5-10 Overtemperature diagnostic, 5-9 , 5-10
P
PCIM/QBIM, selecting as host, 3-5 P ower , display for PowerTRA C block, 5-11 P ower sources, 2-1
GFK-0121E
S
Serial bus address
configuring for HHM, 3-4
error caused by duplicating, 7-2
of bus device, changing, 4-4 Series 90 PLC
reading memory, 6-2
references displayed, 5-2
selecting as host type, 3-5 Series Five PLC
reading memory, 6-4
references displayed, 5-2
selecting as host type, 3-5 Series Six PLC
reading memory, 6-3
references displayed, 5-2
selecting as host type, 3-5
Index-3
Page 64
Index
Short Circuit diagnostic, 5-9 Shutoff
automatic, 2-3 configuring for HHM, 3-5
Specifications, 1-5
T
Temperature specifications, 1-5 Testing, 3-7 Thermocouple blocks
Monitor block screen, 5-5 Monitor/Control Reference screens, 5-10
U
Underrange diagnostic, 5-10 Upgrading the HHM, 2-4
V
V ARs, display for P owerTRA C block, 5-11 Voltage, display for PowerTRAC block,
5-11
W
W att-hours, display for PowerTRA C block,
5-11
Wiring Error diagnostic, 5-10
Index-4
GFK-0121E
Loading...