Power Requirements - General.................................................................................................................. 12
Pickup-voltage Test ................................................................................................................................... 12
Target and Seal-in Unit.............................................................................................................................. 14
Voltage Setting .......................................................................................................................................... 14
Time Setting............................................................................................................................................... 15
PERIODIC CHECKS AND ROUTINE MAINTENANCE.............................................................................. 15
LIST OF ILLUSTRATIONS ............................................................................................................................ 17
Cover Photo(8043180)
These instructions do not purport to cover all details or variations in equipment nor provid e for every possible
contingency to be met in connection with installation, operation or maintenance. Should further information be desired
or should particular problems arise which are not covered sufficiently for t h e purchaser's purposes, the matter should be
referred to the General Electric Company.
To the extent required the products described herein meet applicable ANSI, IEEE and NEMA standards; but no
such assurance is given with respect to local codes and ordinances because they vary greatly.
OVERVOLTAGE RELAYS
TYPES IAV51D, IAV51K, IAV52C, IAV52D, IAV52K
2
GEK-45404
DESCRIPTION
These are single-phase, sensitive overvoltage relays of the induction disk construction. They are
equipped with a time dial so as to provide adj ustable time delay i n their operation. The relays are
principally applicab le for sensitive overvoltage ground detection for high-impedance grounded
generators or for ungrounded power systems. The differences among the four rel ays are as indicated
in Table A below. Each relay is mounted in a standard size S1 drawout case and the outline and
panel drillings are shown in Figs. 14 and 15; Fig. 13 shows the outline for an external capacitor when
used. The internal connections of the relays are indicated in the table. Each relay contains a target
seal-in unit that is used to protect the relay m ain contact s and control spring from damage due to
breaker-trip current.
*The two normally-open contacts have a common connection; refer to the internal connections of
the relay.
** All relays have a 360 volt 10 second rating.
PICKUP
RANGE,
VOLTS
TAPSCONTACTS
INTERNAL
CONNECTIONS
FIGURE
3
GEK-45404
APPLICATION
These are single-phase, sensitive, time-delay overvoltage relays. They are princip ally a pplicabl e for
sensitive overvoltage ground detection for high-impedance grounded generators or for ungrounded
power systems. These relays all have a capacitor in series with the operating coil. For the IAV51K
and IAV52K relays, this capacitor is external to the relay because o f its large size. The effect of the
capacitor is to tune the relay c oil circuit so that the relay pickup on third harmonic (180Hz) voltage is
approximately eight times the relay pi ckup at 60 Hz. Thi s is particularly important in overvoltage
ground detection for generators, since they produce a large third- harmonic component of voltage
during normal operation.
The external connection diagram for the IAV51K or the IAV52K relay for sensitive generator ground
detection is shown in Fig. 8. This is a typical protection scheme for a unit generator transformer
using a distribution transformer connected in the neutral with a resistor across the transformer
secondary. The IAV51K/52K relays are usually us ed for thi s application because they p rovide the
very s ens itive 5.4 volt pickup rating. This enables the relay to detect a ground fault within a few
percent of the wi nding from the neutral. Since the power transformer and the station service
transformer in a unit generator transformer scheme are both connected in delta on the generator side,
coordination with other protection is virtually unnecessary and the ground relay u sed can be very
sensitive. Some time delay in relay operation is usually us ed to coordinate with fuses protecting
against faults on the secondary side of potential transformers that are normally connected to the
generator terminals. The usual practice is to use these relays to trip the generator breaker and shut
down the machine. If the relay is used only t o sound an alarm when a ground fault is detected, the
application should be reviewed. It may be necessary to add another relay to provide ground
protection with good sensitivity simultaneously with a high continuous-voltage rating.
The resistor, shown in Fig. 8 connected across the broken delta secondary of the PT's, or alternatively
connected in series in the primary neutral connection, is usually required to prevent the occurrence of
ferro-resonance. Thi s phenomenon could occur due to the int eraction of the PT inductance with the
distributed capacitance-to-ground of the primary power system.
The external connection diagram for the IAV51D, 52D, or the IAV52C relay for ground-fault
detection on an ungrounded power system is shown in Fig. 9. The relay operates to detect the first
ground fault that occurs on the system, connections so that it can be removed before a second
ground occurs, causing a double phase-to-ground fault, which requires a service interruption. Since
the relay ma y b e applied merely to sound an alarm in this application, it is necessary that it be
continuously rated for the full broken-delta voltage expected for a single phase-to-ground fault
located right at the potential transformers, or some automatic means must be employed to disconnect
the relay from the voltage supply.
When this fault occurs it is equivalent to shorting out one phase of the pot ential transformer primary.
The other two unfaulted phases of the PT primaries now have full phase-to-phase voltage applied
and their corresponding dJelta secondaries will be supplying √ 3 times their normal rated voltage.
The broken delta equivalent voltage will be these two voltages added in series at a 60o angle and the
4
GEK-45404
broken delta voltage will therefore be three times the normal delta phase-to-phase voltage with no
fault.
RATINGS
The operating-circuit ratings available are shown in Table I. The operating coil will stand rated
voltage continuously on any tap.
RELAYVOLTAGE RATINGS
60HZ50HZ
IAV51D115115
199199
345345
IAV51K6767
IAV52C115115
199199
345345
IAV52D199
IAV52K6767
The current-closing rating o f the contacts is 30 amperes for voltage not exceeding 250 volts. The
current-carrying ratings are affected by t he selection of the tap on the seal-in coil, as indicated in
Table II.
TABLE II
FUNCTIONAMPERES
2-Amp Tap0.2-Amp Tap
Tripping Duty Carry
Continuously
The 2-ampere tap has a DC resistance of 0.13 ohms and a 60 cycle impedance of 0.53 ohms, while
the 0.2-ampere tap has a 7-ohm DC resistance and a 52-ohm 60 cycle impedance. The tap setting
used on the seal-in element is determined by the current drawn by the trip coil.
The 0.2-ampere tap is for use with trip coils that operate on currents ranging from 0.2 up to 2.0
amperes at the minimum control voltage. If this tap is used with trip coils requiring more than two
amperes, there is a possibility th a t the 7-ohm resistance will reduce the current to so low a v alue t hat
the breaker will not be tripped.
The 2-ampere tap should be us ed with trip coils that take 2 amperes or more at minimum control
voltage, provided the tripping current does not exceed 30 amperes at the maximum control voltage.
If the tripping c urrent exceeds 30 amperes an auxiliary r e l a y s hould be used, the connections being
30
3
0
0.3
5
GEK-45404
such that the tripping current does not pass through the contacts of the target and seal-in coil of the
protective relay.
BURDENS
Burdens for the various relay types are give in Tables IIIA and B.
The Type IAV51D relay is a low-pickup voltage relay normally u s e d for ground fault protection on
AC rotating machines. It has single-circuit closing contacts that close when the voltage increases to
pickup value, as set on the tap block. The time delay in closing the contacts is determined by th e
se tting of the time dial at the top of the shaft. The IAV51D has a capacitor and tapped resistor
connected in series with the operating coil. The capacitor is added to tune the circuit, giving a low
pickup voltage at rated frequency. At rated voltage the operating U magnet is highly saturated,
increasing the impedance of the circuit, thus limiting the current to a s afe value. The taps on the
resistor are connected to the tap block to provide a four-to-one range of pickup. As shown in the
typical external connection diagram, Fig. 8, this relay is connected to the machine neu tral potential
transformer through a closed contact on the auxiliary tr i pping r elay, hence is energized only w h e n a
ground occurs. To obtain still-lower pickup than the normal calibration, it is permissible to insert an
inverted potential transformer between the machine neutral transformer and the relay c oil circuit.
The IAV51D has a seal-in element. Time curves are shown in Fig. 11.
The IAV51K relay is similar to the IAV51D except that it has an external capacitor. Time curves are
shown in Fig. 11.
8
GEK-45404
The IAV52K relay is similar to the IAV51K except that it has two, instead of one, normally-open
contacts.
The IAV52C is a low-pickup, time-overvoltage relay with two normally-open contacts. It has a sealin element. It has a capacitor connected in series with the operating coil but, unlike the IAV51D
relay, it does not have a tapped resistor connected in series with the operating c oil. The time-voltage
characteristics at the #1, #5, and #10 time-dial settings are the same as for the "A" taps of the
IAV51/52D and K relays shown in Fig. 11.
CONSTRUCTION
These relays are the induction disk construction. The disk is actuated by a potential operating coil on
a laminated U-magnet. The disk shaft carries the moving c ontact, which completes the trip or al arm
circuit when it touches the stationary contact or contacts. The disk shaft is restrained by a spiral
spring to give the proper contact-closing voltage, and its motion is retarded by per ma ne nt magnets
acting on the disk to give the correct time delay.
There is a seal-in unit mounted to the left of the shaf t. This unit has its coil in series and its contacts
in parallel with the main contacts, such that when the main contacts close, the seal-in unit picks up
and seals in. When the seal-in unit picks up, it raises a target into view that latches up and remains
exposed until released by pressing a button beneath the lower-left corner of the cover.
The case is suitable for either surface or semi-flush panel mounting and an assortment of hardware is
provided for either mounting. The cover attaches to the case and also carries the reset mechanism
when one is required. Two of the cover screws have provision for a sealing wire.
The case has studs or screw connections at the bottom for the external connections. The electrical
connections between the relay units and the case studs are made through spring-backed contact
fingers mounted in stationary, molded inner and outer blocks, between which nests a removable
connecting plug that completes the circuits. The outer blocks, attached to the case, have the st uds for
the external connections, and the inner blocks have the terminals for the internal connections.
The relay mechanism is mounted in a s teel framework called the cradle and is a complete unit, with
all leads being terminated at the inner block. This cradle is held firmly i n the cas e by a latch at the
top and the bottom and by a guide pin at the back of the case. The case and cradles are so contructed
that the relay cannot be ins erted in the case upside down. The connecting p lug, besides making the
electrical connections between the respective b locks of the cradle and case, also locks the latch in
place. The cover, which is fastened to the case by thumbscrews, holds the connecting plug in place.
To draw out the cradle from a single-ended case, the cover must first be removed. Then the
connecting plug can be drawn out. In so doing, the trip circuit is the first one opened, then the
voltage circuits are opened. After the connecting plug has been removed, the lower latch can be
released and the cradle easily drawn out. To replace the cradle, the reverse ord er should be fo llowed.
The internal connections of the relays are shown in Figs. 3, 4, 5, 6, and 7.
9
GEK-45404
RECEIVING, HANDLING, AND STORAGE
RECEIVING
These relays, when not shipped as a part of a control panel, will be shipped in cartons designed to
protect them against damage. Immediately upon receipt of the relay, an examination should be made
for an y damage su stai ned during s hipment. If injury o r damage resulting from rough handling is
evident, a damage claim should be filed at once with the transportation company a nd the nearest
General Electric Sales Office should be notified promptly.
HANDLING
Reasonable care should be exercised in unpacki n g the relay in order that none of the p art s are in j u red
nor the adjustments disturbed.
STORAGE
If the relays are not to be installed immediately, they should be st ored in their original cartons in a
place that is free from moisture, dust, and metallic chips. Foreign matter collected on the outside of
the case may find its way inside when the cover is removed and cause trouble in the operation of the
relay.
ACCEPTANCE TESTS
Immediately upon receipt of the relay an inspection and acceptance test should be made to make sure
that no damage has been sustained in shipment and that the relay calibrations have not been
disturbed.
VISUAL INSPECTION
Check the nameplate stamping to make sure that the model number and rating of the relay agree with
the requisition.
Remove the relay from its case and check that there are no broken or cracked molded parts or other
signs of physical damage, and that all screws are tight.
10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.