Installation, Operation, and Maintenance Manualfor the ULVersions of the EntelliGuard TU Trip Unit
Used in the following GE Circuit Breakers:
EntelliGuard G
EntelliGuard® TU Trip Unit
WavePro
AKR
Power Break I
Power Break II
Retain for Future Use.
Page 2
Page 3
HAZARD CATEGORIES
The following important highlightedinformation appears throughout this document to warn of potential hazards orto call attention toinformation that clarifies a procedure.
Carefully readall instructions and become familiar withthe devices before trying toinstall, operate, service ormaintain this equipment.
DANGER
Indicates a hazardous situation that, if not avoided,willresult in death or seriousinjury.
WARNING
Indicates a hazardous situation which, if not avoided,couldresult in death or serious injury.
CAUTION
Failure to comply with these instructions may result inproduct damage.
NOTICE
Indicates important information that mustbe remembered and aids in jobperformance
TRADEMARKS
The following aretrademarks of GE Company:
EntelliGuard®
Power Break®
MicoVersaTrip®
ProTrip®
WARRANTY
This document is based oninformation available at the time of its publication. While efforts have been made toensure accuracy, the information contained herein does not coverall details or variations in hardwareandsoftware, nor does it provide for every possible contingency in connectionwith installation, operation,and maintenance. Features may be described herein thatare not present in all hardware and software systems. GEElectrical Distribution & Control assumes no obligation ofnotice toholders of this documentwithrespect tochanges subsequentlymade. GE Electrical Distribution &Control makes norepresentation or warranty, expressed,implied, orstatutory, with respect to, and assumes noresponsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. Nowarrantees ofmerchantability or fitness for purpose shall apply.
Contact your local sales office if further information is required concerning any aspect of EntelliGuard G, AKR,Power Break, Power Break IIandoperation ormaintenance.
WaveProcircuit breaker
Page 4
EntelliGuard® TU Trip Unit Table of Contents09/25/08
TABLE OF CONTENTS
SECTION 1 – GENERAL INFORMATION..........................................................................................................................................................7
Long Time.......................................................................................................................................................9
Short Time......................................................................................................................................................9
Current Alarm.............................................................................................................................................14
ZONE SELECTINTERLOCK.......................................................................................................................................14
High Set InstantaneousProtection (HSIOC)................................................................................14
Making Current Release (MCR)...........................................................................................................14
POWER REQUIREMENTS..........................................................................................................................................15
LED STATUSINDICATOR..........................................................................................................................................20
Long Time Pickup.....................................................................................................................................21
Long TimeDelay.......................................................................................................................................21
Short Time Pickup....................................................................................................................................21
Short TimeDelay......................................................................................................................................21
Table 2: Short Time Breaker Type and Frame...................................................................................................................................................................9
Table 3: Short TimeDelay Slope Settings.........................................................................................................................................................................10
Table 4: Maximum Instantaneous for Power Break I, Power Break I, WavePro and AKR TripUnits.................................................10
Table 5: Maximum Instantaneous Thresholds for Power Break I, Power Break I,WavePro andAKR TripUnits........................11
Table 8: Ground Fault Time Delay Bands,50Hz and 60Hz.....................................................................................................................................11
Table 9: Voltage UnbalancedSettings...............................................................................................................................................................................12
Table 10: Current Unbalance Settings...............................................................................................................................................................................12
Table 11: Under Voltage Settings.........................................................................................................................................................................................12
Table 12: Over Voltage Settings............................................................................................................................................................................................12
Table 13: Power Reversal Settings.......................................................................................................................................................................................12
Table 18 LED Operation.............................................................................................................................................................................................................20
Table 22: Communications Parameters –Modbus Function 2............................................................................................................................26
Table 23: Communications Parameters –Modbus Function 3............................................................................................................................26
Table 24: Communications Parameters –Modbus Function 4............................................................................................................................32
Table 25: Communications Parameters –Modbus Function 5............................................................................................................................36
FIGURES
Figure 1: Front Panel View –Power BreakIIand WavePro Trip Units..................................................................................................................7
Figure 2: Front Panel View –Power BreakIand AKR TripUnits..............................................................................................................................7
Figure 3: Front Panel View –EntelliGuard G Trip Units.................................................................................................................................................7
Figure 4:Trip Unit Keypad...........................................................................................................................................................................................................8
Figure 6: Short Time Pickup Time CurrentCurve.............................................................................................................................................................9
Figure 8: AKRCircuitBreaker with Trip Unit....................................................................................................................................................................17
Figure 9:Installing the New Trip Unit.................................................................................................................................................................................17
Figure 10: Trip Unit Removal Sequence, Step A............................................................................................................................................................18
Figure 11: Trip Unit Removal Sequence, Step B............................................................................................................................................................18
Figure 12: Trip Unit Removal Sequence, Step C............................................................................................................................................................18
Figure 13: Trip Unit Removal Sequence, Step D...........................................................................................................................................................18
Figure 15: Five Function Keys.................................................................................................................................................................................................20
Figure 18: METER Mode(Wye and Delta Systems)......................................................................................................................................................41
Figure 19: STATUS Mode...........................................................................................................................................................................................................42
EntelliGuard®TU Trip Unit 09/25/08Section 1 – GeneralInformation
SECTION 1 – GENERAL INFORMATION
INTRODUCTION
TheEntelliGuardTU Trip Unit is an electronicdevice that interfaces with a circuit breaker. It monitors the breaker phase currents, neutral current and/or voltage and trips the breakerinthe event of an over-current orvoltagerelated condition. It alsoprovides protective relay functions, advanced metering, diagnostic features, and communications.The Trip Unit can be removed orreplaced in the field byde-energizing and removing the cover of the circuit breaker.
The Trip Unit alsoconnects withthe circuit breaker fluxshifter toprovide the electromechanical tripping function. A user interface is provided on the front panel toallow adjustment of theTrip Unit’s parameters.
ABBREVIATIONS AND ACRONYMS
The abbreviations and acronyms inTable 1 usedthroughout this manual. Slightly different abbreviationsand acronymsare used for IEC trip units.
Table 1:Abbreviations and Acronyms
Item Definition
I
RMS
xlCT
ln
PRODUCT DESCRIPTION
True RMS current measurement through aphase Multiples of currentsensorrating (non-dimensional)Rating plug ampere setting where lthe breaker nominal rated current (A)
nlCT
. This is
Figure 2: Front Panel View– Power Break I and AKRTrip Units
Figure 3: Front Panel View– EntelliGuard G Trip Units
AppearanceThe TripUnitincludesa graphical LCD. The frontpanel is
similar tothose shown in Figure 1 through Figure 3.
Figure 1: Front Panel View– Power Break IIand WavePro Trip Units
LCD ACCESS The trip unit has five function keys as shown in Figure 4.Any key,when pressed,powers up the LCD.
All SETUP, STATUS, METER and EVENTS information isaccessed through these fivekeys.
EntelliGuard®TU Trip Unit Section 1 – GeneralInformation09/25/08
Figure 4: Trip Unit Keypad
•UP: Scroll up or increment value
•DOWN: Scroll down or decrement value
•RIGHT: Next function or nextpage
•LEFT: Previous function or previous page
•ENTER: Saveorset in to memory
Electrical RequirementsNone: Plug in installation. Done on un-energized units.
Equipment InterfacesPower BreakI,PowerBreak II, WavePro, AKR andEntelliGuard G Circuit Breakers.
Trip units, for the most part, donot require directconnections tothe equipment. All wiring is intended toconnect tothe circuit breaker or cassette. Connections that are required for other equipment are the optional zone-selective interlock, input, and relay output madebythe secondary disconnect, and the neutral sensor, which uses a special dedicated disconnect.
Zone-selective interlocking coordinates breakers sothatthe downstreambreaker is allowed the first opportunityto clear a fault or overload event. The types of available zone-selective interlocking are Z, which reacts to groundfaults and short time pickups,and T, which reactstoground faults,short-time and instantaneouspickups.
Input 1 can be programmed for reduced instantaneous or trip the breaker. Other inputs can be programmed totrip the breaker only.
Power Break I, Power Break II,WavePro and AKR TripUnits have one relay. EntelliGuard G TripUnits have two output relays. The relay output can be assigned tothe following functions:
•GF Alarm
•Over-current trip (GF, INST, LT, ST)
•Reduced Instantaneous (RELT) Active
•Protective Relays
•Current Alarm 1
•Current Alarm 2
•Health status
The trip units must have thespecific option (as anexample protective relaymust be enabled in order for protective function toactuate the relay) enabled in order to actuate the relay.In additionto the inputs indicated above, Power Break I,PowerBreak II,WavePro, AKR , and EntelliGuard G TripUnits alsoreceive inputs from external voltage conditioners, a +24 VDC control power supply, andcommunication connections. (Note: external +24 VDCcontrol power is required for communication.)
All trip unit types have a connectionto an auxiliary switchwithin thebreaker that senses thebreaker’s position.
COMMUNICATIONS
External +24 VDC control power is required for communications.
Power Break I,PowerBreak II, WavePro, AKR,and EntelliGuard G Trip Units support Modbus communicationprotocol. In addition, EntelliGuard G TripUnits supportProfibus communication.
Modbus and Profibus connections aremade directly towiring terminations onbreaker frames. All Modbus/Profibus connections are made through the trip unit’s back (PowerBreak I, Power BreakII, WaveProand AKR TripUnits)and top (EntelliGuard G TripUnits)connectors, which mate with a receptacle on the breakerframe.These additional connections are made to the equipment through the secondary disconnects ofthebreaker.
ModbusThe TripUnits are fully compliant withModbus Protocol. Full details of theModbus protocol can be found in theModbus ProtocolSpecification.
The link Hostmay operate at a 300,600, 1200, 2400,4800, 9600 or 19200-baud rate.
Page 9
EntelliGuard®TU Trip Unit 09/25/08Section 1 – GeneralInformation
ProfiBusThisprotocol is integral to EntelliGuard G TripUnits.ProfiBus DP overRS485 issupported.
OVER CURRENT PROTECTIONFUNCTIONS
The TripUnitprovides the following over currentprotections:
•Long Time
•Short Time
•Instantaneous
•Reduce Let Through Energy Instantaneous (RELT)
•Ground Fault InternalSummation
•Ground Fault CT ExternalSummation
•Override (HSIOC)
•Making Current Release(MCR)
Long TimeLong Time Pickup
This setpoint establishes the breaker's nominal ampere rating,xLT, as a fraction of the rating plug value, xIn (xLT= LTmultiplier x xIn).
The adjustment range for long timepickup settings is
0.50 to1.00 times xIn in steps of0.05. The pickupvalue tolerance band has a 10% tolerance. The band is drawn at 1/(1+10%) and 1/1-10%). The actual long time pickupisincreased by 12% over the nominal so that 100%nominal current may be carried indefinitely. Soa 1000 Asetting is placed at 1120 A with the minimum pickup drawn (left side of band) is 1120 A/1.1,and the maximum pickup (right side of band) isdrawn at 1120 A/0.9. Figure5 shows the Long Time pickup setting.
Break II, WavePro and AKR circuit breakers use the 19lower thermal CB-type bands and the 22 fuse-type bands.
Short Time Short Time Pickup
The Short Time Pickup function establishes the current atwhich short time tripisactivated.Short Time Pickup iscoupled with Long Time Pickup and the choices of pickupsettings are from 1.5 to 12.0 times the Long Time setting,xLT, in steps of 0.5 xLT.
The maximum pickup depends onbreaker type andframe asshown in Table 2 below:
Table 2.Short Time Breaker Typeand Frame
Breaker AvailableSettings PowerBreak I, PowerBreak II,
1.5 to 9, steps of 0.5 WavePro,AKR conversion kitsEntelliGuard G Frame 1 and2 1.5 to 12, steps of 0.5 EntelliGuard G Frame 3 1.5 to 10, steps of 0.5
The Short Time Pickup value tolerance band is -9% to+11% of the set point basedon a 10% current sensing accuracy with the pickup calculated with 1/(1+
Tolerance).The time current curve of short timepickupisshown inFigure 6.
Figure 6: Short Time Pickup TimeCurrent Curve
Figure 5: Long TimePickup Setting
Long TimeDelayThe trip unit makes up to 44different long time bands available. Not all circuitbreakershaveall bands available.There are 22 bands using a logarithmic type curve thatresembles the thermal portion of a thermal magnetic circuit breaker. There are 22bands that are a straight linethat simulate a fuse curve. The Entelliguard circuitbreaker is able touse all 44bands. PowerBreak I, Power
Short TimeDelay The Short Time Delay settingconsists of both a slope setting and a fixed delay band setting.The slope and delay are independently selectable. The slope setting consists of three I
2
Tslopes (minimum (1),intermediate (2) and maximum (3)) and fixed delay. The fixed delay bands consist of 11 constant time bands.The width of the bandsvaries by circuitbreaker and with frequency. SeeTable 3.
Adjustable Selective Instantaneous ProtectionAdjustable Selective Instantaneous over current
protection causes an undelayed breaker trip when the chosencurrentlevel and properwaveform is reached.
The pickup value may besetin steps of 0.5 xIn from 2.0 xIn to 15 xIn and steps of 1 xIn from 15 xIn to a maximumof 30 xIn.Greater than 15xInis available onlyin tripsprovidedwith the “Extended Range Instantaneous” option onANSI EntelliGuardG circuit breakers.
The maximum possible setting depends on the trip unit instantaneous optionprovided,the circuit breaker’swithstand capability and whether or not ST has been enabled.
Table 4: Maximum Instantaneous ForPower Break I,Power Break II, WavePro and AKR Trip Units
The Instantaneous pickup accuracy is 10%. On trip units with the user-selectable switchable instantaneous overcurrent and ground-fault option,an additional value of OFF appears at the end ofthe listing of numerical values.Choose this setting to disable instantaneous protection, and or GF protections.
Short Timeand Instantaneous cannot be turned offsimultaneously. OnlyANSI circuit breakers may have the Instantaneous off option.TripswithGF off as an optionarenot UL listed.
When Instantaneous pickup is setabovethe maximum allowed for the CB without ST on, STpickupis automaticallyswitched on at a default delay isautomatically switched on at a minimum delay setting.
Reduced Energy Let-Through Instantaneous Protection (RELT)
EntelliGuardG TripUnits provide a Reduced Let-Through EnergyInstantaneous function (RELT) whichmay beenabled atthe trip’s key pad, viaa 24 VDC/ACsignaltoINPUT 1 orvia serial communications. The RELT functionprovides a faster instantaneous trip function that may beused in case faster and more sensitive protection isrequired temporarily.
The pickup value may be setin steps of 0.5 xIn from
1.5 xIn to 15xIn or the maximum allowed instantaneouspickup for the particular circuit breaker type, rating andsize. The maximum setting depends on the trip unit catalognumber, breakertype and frame,and whether ornot ST is enabled.See Table 6.
EntelliGuard®TU Trip Unit 09/25/08Section 1 – GeneralInformation
Table5: Maximum Instantaneous ThresholdsFor Power Break I, Power Break II, WavePro and AKR TripUnits
Breaker
Frame Size
(A)
800
MaximumInstantaneous Threshold with Short Time (× IOff, 1.5 to 15Off, 1.5 to 10
MaximumInstantaneous Threshold without
)
Short Time (× IN)
N
1600 Off, 1.5 to 15 Off, 1.5 to 10 2000 Off, 1.5 to 15 Off, 1.5 to 10 3200 Off, 1.5 to 13 Off, 1.5 to 10 4000 Off, 1.5 to 9Off, 1.5 to 9 5000 Off, 1.5 to 7 Off, 1.5 to 7
Ground Fault ProtectionThe TripUnitprovides two types of ground faultprotection inaddition to the GF alarm.These protectionsare independent.The GF alarm has the same pickuplevel,band choices and tolerances as GF.
The GF pickup value tolerance bandis 15%the set point.The ground fault pickup settings are listed inTable 6 as multiples of xCT the current sensor rating, in steps of
0.01 xCT. The maximum value is limited to1200.
Table 6: Ground Fault PickupSettings
ProtectionTypeGF SUM GF SUM ALARM GF CTGT CT ALARM
Sensor, I
150–2000 0.20–0.60 (max of 1200
Ground Fault Pickup
CT
Threshold (× I
)
CT
A) (increment of 0.01)withOFF as a selection when GF or GFAlarm
Switchable isoptioned. GF/ALARM Pickup
2500-3200 0.20–0.37 (increment of
0.01) with OFF as a
selection when GFor GF
Alarm Switchable is
optioned.GF/ALARM Pickup
4000 0.20–0.30 (increment of
0.01 with OFF asa
selection when GFor GF
Alarm Switchable is
optioned.GF/ALARM Pickup
5000 0.20–0.24 (increment of
0.01) with OFF as a
selection when GFor GF
Alarm Switchable is
optioned.GF/ALARM Pickup
6000 0.2 (1200 A) with OFF as
a selection when GF or
GF AlarmSwitchable is
optioned.
Table 7 gives the sensorsettings and ratings.
Table: 7: Sensor Settings andRatings
Sensor Max. X Min. A Max. A
400 0.60 80 A
240 A600 0.60 120 A 360 A800 0.60 160 A 480 A
1200 0.60 240 A 720 A1600 0.60 320 A 960 A2000 0.60 400 A1,200 A2500 0.48 500 A1,200 A3000 0.40 600 A1,200 A3200 0.37 640 A1,184 A4000 0.30 800 A1,200 A5000 0.24 1,000 A 1,200 A6000 0.20 1,200 A 1,200 A
Notes:
•Continuously adjusted in 0.01 increments.
•Minimum Xis 0.2 for all sensors.
Ground-Fault DelayThis functionsetsthe delay before the breaker trips when the ground-fault pickup current has been detected.
The Ground Fault Delay setting consists of a selectionbetween twoI
2
Tslopes:,an optional steeper fuseslope, and fixed delay only. One of fourteen fixed timebandsisalsoselected. The fixed delay bands are listed in Table 8.
EntelliGuard®TU Trip Unit Section 1 – GeneralInformation09/25/08
PROTECTIVE RELAY
The protection relay can be set to either cause a trip or an alarm. If the PR Enable on the LCD is set to ON, a trip willbe generated, ifset toNO an alarm will be generated.
Voltage UnbalanceRelayThis function compares the highest orlowest phase
voltage with the average of all three phases and initiatesa trip ifthe difference exceeds the set point.
Table 9: VoltageUnbalanceSettings
Item Option Voltage unbalance pickupVoltage unbalance delay setting
Current Unbalance RelayThis function comparesthe current in thehighest or
lowestphase withthe average of all threephases andinitiates a trip if the difference exceeds the set point.
Table 10: CurrentUnbalance Settings
Item Option Current unbalancepickupCurrent unbalancedelay setting
Under VoltageRelay This function measures the voltage in all phases and
initiates a tripif any phase voltage drops below the setpoint.
Under VoltageRelay Zero-Volt Trip EnableThis function determines ifthe relay trips when all three-
phase voltagesdropto zero volts. See Table11.
Table 11:Under VoltageSettings
Item Option Under voltage pickupUnder voltage delay setting:
Adjustablefrom 50% to90% inincrements of 1%. Adjustable from1 sec to 15 sec inincrements of 1 sec. Setting this value to zero (0) disablesthis function.
Adjustablefrom 10% to50% in increments of 1%. Adjustable from1 secto15 sec in increments of 1 sec.Setting this valueto zero(0)disables this function.
Adjustablefrom 10% to50% in increments of 1%. Adjustable from1 secto15 sec in increments of 1 sec.Setting this valueto zero(0)disables this function.
Over Voltage RelayThis function measures the voltage in all phases andinitiates a trip ifany phasevoltage exceedsthe set point.See Table 12.
Table 12: Over Voltage Settings
Item Option Over voltage pickupOver voltage delay
Power-Reversal RelayThis functionmeasures thedirection of power flow
through the breaker and initiates a trip ifa sufficient magnitude of reverse poweris detected.
Table 13: Power Reversal Settings
Item Option Power reversalpickupPower reversal delay
Power Direction Setup This functionselectsthe normal power flow direction for
the breaker, either fromline to load or from load toline.This direction setup also affects the sign of the normalpower metering displays.
Potential Transformer Primary VoltageEnter the primary voltage rating of the potential
transformer. The range ofvalues is 120 V to 600 V, withan increment of 1 V.
Adjustable from110% to 150% inincrements of 1%. Adjustable from1 sec to 15 sec inincrements of 1 sec. Setting this value to zero (0) disables this function.
Adjustable from10 kW to990 kWin increments of 10 kW.
Adjustable from1 sec to 15 sec inincrements of 1 sec. Setting this value to zero (0) will disable this function.
NOTICE
Incorrectset point will result in incorrect metering values.
Potential Transformer ConnectionSelect the appropriate potential transformer connection,
either line-to-line (Ph-Ph) or line-to-neutral (Ph-N).
EntelliGuard®TU Trip Unit 09/25/08Section 1 – GeneralInformation
Power DemandIntervalsThisfunction sets thepower demand interval,whichcan
be in the range of 5 min to 60 min, in steps of 5 min.This setpoint specifies the time interval for power demand averaging.
Communication Address The address options are from 1 to 254, in steps of 1 for
Modbus and Profibus communicationprotocols.
Bell Alarm-Alarm Only/Bell Alarm with Lock-outAccessory ConfigurationSetup (applies to PowerBreak II andWaveProTrip Units only)
This defines the types ofsignals (protection trip, Shunt trip, Shunt Trip with Lockout,or Under Voltage Releasetrip) that activate the BellAlarm-Alarm Only and Bell Alarm with Lockout accessories onthe Power Break IIbreaker only.The customermay enable or disableadifferent path toactivate these accessories fromthe different types of trip signals.
The following settings can be set onthe LCD or throughcommunication:
•Disabled
•Shunt Trip
•UVR Trip
•Over Current Trip
•Protective Relay Trip
•Shunt, UVR
•Shunt, Over Current
•Shunt, Protective Relay
•UVR, Over Current
•UVR, Protective Relay
•Over Current, Protective Relay
•Shunt Trip, UVR,Over Current
•Shunt, UVR, Protective Relay
•Shunt, Over Current, Protective Relay
•UVR, Over Current, Protective Relay
•Shunt, UVR, Over Current, Protective Relay
Settings DescriptionThe following are descriptions of the effects of each
accessory switch when it is enabled:
If Bell Alarm or Bell Alarm with Lockout is set toShunt Trip, a fault generated bya Shunt Trip will cause the BellAlarm contacts to change state.
If Bell Alarm with Lock-out is set to over current trip, afault generated by LT, ST, GF, and/or Instantaneous willcause the BellAlarm contacts to change state.
InputInputs can be assignedto two main functionalities:
•Reduced Energy Let-Through (RELT)
•Trip thebreaker
Table 14 shows the assignment for the inputs.
Table 14: InputAssignments
Input Input1
Summary Description
Assignment
1
OFF No actiontaken.TRIP Causes a breaker to trip. RELTCauses unit touse the RELT
setpoint as long as input is active.
Note: RELTmust be set to
REMOTE. OFF No actiontaken.2 TRIP Causes a breaker to trip.
OutputThe number of outputs available varies by breaker. These
outputs are relay contact outputs tosecondary disconnect. Each output can be configured per Table 15.
Table 15: OutputConfiguration
Group FunctionFunctionSummary
Description
1GF alarmTurns on when GFalarm
is activated.
2 Over-current trip
(GF, INST, LT, ST)
Over-voltage trip turnsON the relay.
3 Protective relays When protective relay
trips the relay contactcloses.
4 Current alarm 1 Exceeding current alarm
pick-up turns closestherelay contact.
5 Current alarm 2 Exceeding current alarm
pick-up turns closestherelay contact.
6 *Health statusRelay contact will be
closed or openeddepending on the health contact setting.
7 Reduced Energy
Let-Through
Output relay contact closes when the RELTpickup isenabled.
Note:The health relay can be set to either normally open (NO)or normally close (NC) via communication.The contactsare rated for 30 VDC/25 VAC MAX, 1 A.
EntelliGuard®TU Trip Unit Section 1 – GeneralInformation09/25/08
Current Alarm The trip unit provides two types of current alarms:
Current Alarm 1 and Current Alarm 2.
The Current Alarm’s ON/OFFpickup settings are 0.5 to 1.0 xIn in stepsof0.05.
The trip unit does not allow the current alarm OFFsetpoint to be set above theON threshold.
If the highest measured phase current goes aboveCurrent Alarm 1or Current Alarm 2 ON setpoint,and thenremains above the setpoint for more than 60 sec, the output will close ifassigned to either of these alarms. If the current falls below the Current Alarm 1 orCurrent Alarm 2 for more than 60 sec, the output, ifassigned toCurrent Alarm, will open.
ZONE SELECT INTERLOCK
The ZoneSelect Interlock (ZSI) function operates with a group of series-connected breakers. The ZSI is achieved with theuse of theTIMmodule or an equivalentGEqualified and recommended device.
ZSI OptionPer the trip unit catalog number there are twotypes of
zone-selective interlockingoptions:
•Z: reactsto ground faults and short time pickups.
•T: reacts to ground faults, short time and
instantaneous pickups. (Requires 24 VDC externalpower be providedto the trip unit.)
The upstream breaker uses the ST ZSI and/orGF ZSI delaybands and slope, and/ortransitionto a delay Instantaneousif it receives a downstreamZSI signal.
The desired ZSI (STand-or GF and-or Inst) must be selected in order for the downstreambreaker toissue aZSI signal, and the upstreambreaker to act upon thissignal.
The ST ZSI Delay Bands are independent and have the same bands available. Slope settingsmayalsobe interlocked.
The GF ZSIDelay Bands areindependent and have thesame bands available.Slope settings may also be interlocked.
HighSet Instantaneous Protection(HSIOC) HSIOC is also Known as Override Pickup. Some ofthe tripunits on EntelliGuard G circuit breakers may be provided with an override instantaneous trip.
Whethersuch a trip isprovided ornot depends onthe circuit breaker withinwhich the trip is installed.If thecircuit breaker’s withstand (Icw) is equal to the short circuit rating then the trip will not have an overridepickup.If thewithstand rating islower than theshort circuit rating then the trip will enable override protectionofthe circuit breaker.
In UL 489 circuit breakers the HSIOC setting is nominallyat 107%of the Icw for the circuit breaker. Taking tolerance intoaccount,the override’s minimum trip isat 100% of the circuit breaker’sIcw.
In UL 1066 (ANSI) circuit breakers the HSIOC setting isalsoat 107% Icw ifthe adjustable selectiveinstantaneous is ON. If the adjustable selective instantaneous is OFF then the HSIOC nominal pick up isat 98% of the circuit breaker’s Icw and, considering tolerance, the minimum pickup is at 91% of the circuit breaker’s Icw.
Power BreakI, WaveProand AKR circuit breakersdo not employ an override function.PowerBreak II circuitbreakers use a mechanical override function.
Making Current Release (MCR)Every EntelliGuard TU or EntelliGuard TUcircuit breaker
uses a making current release. The making current release varies per circuit breaker Envelope and is related to the circuit breaker’s close and latch rating.
The MCR pickup is activated at the time the circuit breaker closes and for six cycles thereafter. When the six cycles are over, the threshold changes to the HSIOCpickup setting.
EntelliGuard®TU Trip Unit 09/25/08Section 1 – GeneralInformation
POWER REQUIREMENTS
WARNING
IMPROPER INSTALLATION,OPERATION AND MAINTENANCEEnsure only qualified personnel install, operate, serviceand maintain all electrical equipment.Failure to comply with these instructions couldresult in death or serious injury.
A small amount of power is necessary to energize theliquid crystal display (LCD) during setup, for viewing breaker status and for metering displays.
Power BreakI,PowerBreak II, WavePro, AKR andEntelliGuard G Trip Units require external+24 VDCcontrolpower for communication
The power sources are:
•Current flow: Breaker current sensors provide
sufficient power toenergize the LCD when at least 20% of the sensor's ampererating is flowing.
•+24 VDC control power
•Internal battery power: Powers the unit temporarily
when any keypad key is pressed. Battery power automatically turns off 20 sec after the last keypadpress.The battery power supply is disabled when anycurrent issensed through the current sensors.
METERING FUNCTIONS
Table 16shows themetering data provided by thetripunit:
Table16: Metering Data
Parameter PhaseUnit Current Phase A,B,C,
neutral
VoltagePhase L1, L2, L3
(Note 1)
Real PowerPhase L1, L2, L3
and total
Reactive PowerPhase L1, L2, L3
and total Apparent Power Peak Power Demand
Energy Phase A, B, C
FrequencyPower Factor
Notes:
•Potential transformers must be connectedsimilar to
source (Wye or Delta). For Wye construction V=L-Nand for Delta construction V=L-L.
EntelliGuard® TU Trip Unit Section2 – Lifting, MountingandInstallation 09/25/08
SECTION 2 LIFTING, MOUNTING AND INSTALLATION
DANGER
ELECTROCUTION
•Ensure the circuit breaker has been tripped,
indicatingOFF and that applicable lock-out/tag-out requirements are met and followed.
•Ensure themainsprings are fully discharged.
•Do not touch the circuit breaker’s isolating
contacts duringlifting.Failure to comply with these instructions will result in death or serious injury.
WARNING
IMPROPERINSTALLATION, OPERATION, SERVICE ANDMAINTENANCE
•Ensure only qualified personnel install, operate,
service and maintain all electrical equipment.
•Donot perform any maintenance, including
breakercharging, closing, tripping, or any otherfunction that could cause significant movement ofcircuit breaker while itis on the draw-outextension rails.
•Ensure circuit breaker is always leftin the
CONNECTED, TEST or DISCONNECTEDposition to
avoid mispositioning of the breaker and flashback.Failure to comply with these instructions couldresult in death or serious injury.
WARNING
FALLING OBJECT
•Ensure lifting equipment has capabilityfor device
being lifted.
•Wear hardhat,gloves and safetyshoes.
Failure to comply with these instructions couldresult in death or serious injury.
CAUTION
PRODUCT DAMAGE
•Ensure circuit breaker and its accessoriesare
always used within their designated ratings.
•Ensure the correct trip unit is paired with the
correct circuit breaker.
•Donot useexcessiveforce when installing a trip
unit.
•Do not allow circuit breaker to hit a hard surface
while handling.
•Do not drag orslide circuit breaker across a hard
or rough surface.
Failure to comply with these instructions mayresult in product damage.
TRIP UNITREMOVAL AND REPLACEMENT
Power Break I, Power Break II,WavePro and AKR TripUnits have rejection pins, installed on the rear of these trip units, toprevent installation of an incorrect trip unit into a breaker.
Replacement of a trip unit always requires repeating the setup procedures
PowerBreak I and PowerBreakII Insulated CaseCircuit Breakers
The trip unit procedures for Power Break I and Power Break II circuit breakers are very similar and are outlinedbelow.The EntelliGuard TUtrip unit for a Power BreakI is different than that for a Power Break II (see Section 1). Ensure the correct trip unit is used.
Trip UnitRemoval
1.Loosen the four#8-32 screws on the circuit breaker
trim-plate assembly and remove the trim plate.
2.Loosen the four#10-32 screws at the corner of the
breaker cover. Remove the cover fromthe breaker face.
3.Pullthe trip unit locking levertothe right, thenhold
the trip unit near the battery cover and lift it straight out of the circuit breaker.
Trip UnitReinstallation
1.Pullthe trip unit locking levertothe right. While
holding the lever, carefully align the connector ontherearofthe trip unit with theconnectorin thebreaker.Press down onthe trip unit while holding it near the battery cover. Whenthe trip unit is fully seated, slide the locking lever back tothe left.
2.Reinstall thebreaker top cover and tightenthe four
#10-32 screwsto 32 in-lb.
3.Replace the trim plateand tightenthe four#8-32
screws to 20 in-lb.
WavePro Circuit Breakers Removal
1.Open the circuit breaker andremove it from the
2.For 800 A, 1600 A and 2000 A frame circuit breakers,
3.Depress the OPEN button toclose the racking door.
4.Remove thewireforms and remove the trimplate
cubicle orsubstructure. Place it on a suitable worksurface.
insert the racking handle (catalog number 568B731G1) andmove theracking mechanism tothe TEST position, as shown on the draw-outposition indicator.
EntelliGuard®TU Trip Unit 09/25/08Section 2 – Lifting, Mountingand Installation
5.Remove the six ¼ hex head screws, securing the
escutcheonto the breaker (three attop and three atbottom). Pull the manual-charging handle out partway, and then slide offthe escutcheon.
6.Pull out thelocking side on theright of the trip unit
mounting plate, and then pullthe trip unit out carefully disengaging the pins onthe rear connector.
7.Pull out thelocking side on theright of the trip unit
mounting plate, and then pullthe trip unit out carefully disengaging the pins onthe rear connector.
Reinstallation
1.Pull out thelocking side on theright of the trip unit
mountingplate. Push the trip unit into place, carefully, engaging the 50 pin connector and liningup the rejection posts on therear of the trip unit with theholes in the mounting plate.Push thelocking slide tothe left.
2.Ensure thebreaker racking mechanism isstill in the
TEST position. Pull the manual charging handle out partway, and then slide the handle through the slotinthe escutcheon and move escutcheoninto place. Insertthe sixmountingscrews and tighten to14-20in-lb.
3.Replace the trim platearound the escutcheon by
re-hooking the wire forms into the sides.
4.Insert the racking handle and returnthe racking
mechanism tothe DISCposition, asshown by the draw-out positionindicator.
5.Reinstall the circuit breaker into its cubical or
substructure.
AKR (225 A to 5000 A Frames)Circuit Breakers
1.Open the circuit breaker by pressing the red TRIP
button onthe front of thebreaker escutcheon.
2.Disconnectany secondary wire harnesses between
the breaker and the switchgear.
3.Ondraw-out breakers, rack the breakerall the way
out tothe DISCONNECT position.
4.Follow the instructions onthe label attachedto the
PROGRAMMER RELEASE LEVER toremove the trip unit. There are three types of mounting plates:
•Type 1: Push in the lever to release the trip unit.
•Type 2: Pull out the lever torelease the trip unit
as shown in Figure 7.
•Type 3: Push down on the lever.
Figure 7: Removing the OldTrip Unit
5.If the breaker is equipped with a MicroVersaTrip® 9
trip unit, the 36-pin trip unit connectormustberemoved and remounted onthe adapter bracketprovided. Slide the connector out of the mountingplate and install it on the adapter bracket, as shown in Figure 8.
Figure 8: AKRCircuit Breaker without Trip Unit
6.Align the connectors and rejection pin and connect
the EntelliGuard TU to the circuit breaker, as shown inFigure 9.
EntelliGuard® TU Trip Unit Section2 – Lifting, MountingandInstallation 09/25/08
EntelliGuard G Circuit Breaker InstallationTrip Unit Removal (See Figures 10through 13)
1.Loosen the six screws on the breaker
fasciaassembly and remove the fascia.
2.Depress
the trip unit locking lever on the left side ofthe trip unit, then hold the trip unit near the bottom and lift it straight out ofthemounting base.
Figure 10. Trip Unit Removal Sequence, Step A
Figure 11. Trip Unit Removal Sequence, Step B
Figure 12. Trip Unit Removal Sequence, Step C
Figure 13. Trip Unit Removal Sequence, Step D
Trip UnitReinstallation
1.Depress the trip unit locking lever on the left side of
.
the trip unit
While depressing the lever, carefullyalign the connector on the rear of the trip unit with the connector in the mounting base onthe breaker.Press down onthe trip unit while holding it near the bottom.
2.When the trip unit is fully seated, stop depressing the
trip-unit-locking lever and allow the lever to come up and lockthe trip unit tothe mounting base.
3.Reinstall thebreaker fascia and ensure that the Trip
unit is centered in the fascia window before tightening the fascia fixing screws.
EntelliGuard®TU Trip Unit 09/25/08Section 3 – Operation
SECTION 3 – OPERATION
WARNING
IMPROPER INSTALLATION,OPERATION AND MAINTENANCEEnsure only qualified personnel install, operate,service and maintain all electrical equipment.Failure to comply with these instructions couldresult in death or serious injury.
WARNING
PERSONAL INJURY
•Avoid risk of injury frommovingparts while
handling the circuit breaker.
•If advisable, use a cable/busbar lockable
grounding device (optional accessory)to provide
additional safety during system maintenance. Failure to comply with these instructions couldresult in death or serious injury.
CAUTION
PRODUCT DAMAGE
•Ensure circuit breaker and its accessoriesare
always used within their designated ratings.
•Use the specially designed circuit breaker
handling truck (optional accessory) when
removing the circuit breaker from its cassette. Failure to comply with these instructions mayresult in product damage.
When waveform capture is executed, the followingchannels will becapturedsimultaneously: Phase A current, Phase B Current, Phase C Current, Phase L1voltage, Phase L2 voltage, Phase L3 voltage. See Table 17.
Table 17: Trigger Waveform Capture Events
Event WaveformCapture
SetpointManual trigger over communications Over current (GF, ST, LT, Inst)ON,OFF Protective relays ON, OFFCurrent alarm1 ON, OFF Current alarm2 ON, OFF
EVENT LOGGING
The trip unit keeps a log of the last 10 events:
•Over current trips
•Protective relay trips
•Shunttrip (PBIIand Global EntelliGuard G TripUnits
Only)
•Under voltage Release trip (PBII andGlobal
EntelliGuard G Trip Units Only)
•BIMTrip Unit Mismatch -Breaker Interface Module
The following information is stored with eachevent:
•RMS currentsPhase
•
•Type oftrip
•Trip counter
•Time and date stamps
Trips are logged under selfpower without timestamp.Events with timestampsare only logged when24V control power is available.
All setup, status and metering information is accessed through five keys whose functions are:
EntelliGuard® TU Trip Unit Section 3 – Operation09/25/08
LED STATUS INDICATOR
Table 18 shows the operation of the green LED located onthe front of the trip unit.
Table 18: LED Operation
PowerBreak I and
LED Status
AKR Trip Units
Status
NormalON-OFF-ON-OFF (OFF for 2 sec)
Error ON-OFF-ON-OFF-ON-OFF
(OFF for 2 sec)
TripON-OFF (OFF for 2 sec)
Pickup ON-OFF-ON-OFF-ON-OFF-ON-OFF
(continuous)
Figure 14.Operating Modes and FunctionsOverview
OPERATING MODES
Power Break I,PowerBreak II, WavePro, AKR andEntelliGuardG TripUnits have four operating modes:Setup, Meter, Status and Events as shown in Figure 14.(See Appendix 2 for Operating Modes and Functions Specifics.)
EntelliGuard®TU Trip Unit 09/25/08Section 3 – Operation
SETUP MODE SETUP Mode programming must be performed withthe
rating plug installed.
These procedures apply to all trip units.
SETUP procedures should only be repeated if the trip unit or the protection characteristics arechanged,requiring different set points and time-delays.
All trip units provide longtime over current protection, long time delay, and some form ofinstantaneous overcurrent protection when installed in circuit breakers. Allother functions are optional.
If a specific set oftrip unit functions, such as relaying or short time over-current protection,has not been ordered, that function will not appearon the trip unit display.Ignore setup mode instructions for such functions. The trip unitmustbe provided with control power during SETUP. Power can come frominternal battery power,from an external +24 VDC power supply, orby energizing the breaker to at least 20% of its sensor load.
•Press UP or DOWN until the SETUP mode is selected.
•Press RIGHT or LEFTto access the functions in the
SETUP mode.
•Press ENTER tosave desired values.
•Press RIGHT to advance to the next function.
EnteringSetpoints into Memory
1.Press UP or DOWN toselectSETUP.
2.Press LEFT toselect the desired protection to change.
3.Press UP or DOWN to change values. The values will
start flashing.
4.Press ENTER tostore the value intothe memory. The
displayed value stops flashing and the save iconappears on the top of the LCD. This indicates that the value has been stored inmemory and isactive.
5.Confirmsettings onthe trip unit aftermaking
changes by exiting and re-entering SETUP mode and rechecking each changed setting.
Long Time Pickup The first SETUP mode display is always the Long Time
Pickup setpoint. This setpointestablishes the breaker's nominal ampere rating, xLT,as a fraction of the rating plugvalue, xIn (xLT = LTmultiplier x xIn).
The Long Time Pickup settings are 0.50 to 1.00 times xIn in steps of 0.05. The pickup value tolerance band is -10%to +10% ofthe set point. An additionalaccuracydegradation of±5% is allowed for waveforms withsignificant harmonic distortion.
Long Time Delay The EntelliGuard trip unit offers up to 44 long time delay
bands. Twenty-two have steep fuse-like shape and 22have a logarithmic curve toa straight I
2
T slope shape.This second shape is similar to that of the thermal element of athermal magneticcircuitbreaker.
EntelliGuard G circuitbreakers useall 44 bands.WavePro,AKR and both PowerBreak devices use the lower 19 of the curved thermal-type bands.To see the bands and the range of settings, see the TCCs in the Application Guideavailable at wwwgeelectrical.com/industrial.
Short Time PickupThe Short Time Pickup function establishes the current at
which short time tripisactivated.Short Time Pickup iscoupled with Long Time Pickup and the choices of pickupsettings are from 1.5to 12.0times thelong time setting,xLT, in steps of 0.5 xLT.
The ST pickup value tolerance band is -10% to +10% ofthe set point. An additional accuracy degradation of±5% shallbeallowedfor waveforms with significant harmonicdistortion
Short Time Delay The Short Time Delay function consists ofboth a slope
setting and a fixed delay band setting.The slope and delay are independently selectable. The slope setting consists of three I
2
Tslopes (1, 2,3) and fixed delay. The
fixed delay bands consist of15 constant time bands
The EntelliGuard TUTripUnit provides a second usersettable and user-selectableinstantaneous protection algorithm. This protection isreferred toas the RELTpickup.
This protection enables an instantaneousprotectionmode that may be set separatelyfromthe “AdjustableSelective Instantaneous”and is a bit faster. The RELTinstantaneous pickup may be set by the user to a valuefrom 1.5X triprating plug upto 15Xtriprating pluginsome circuit breakers.
The user may also enable the function “ON” or“OFF”atthe HMI,as well as set it to remote. In the “remote”mode the trip unit is able toreceive a command via serialcommunication (Modbus or Profibus) ora hardwired 24 VAC or DC signal toenablethe RELTprotection on.If theRELTprotectionis ONvia any of the three waysitmustbeturned off that same way.
When the trip unit receives a RELT on signal the RELTinstantaneous setting is enabled. Ifthe RELT pick up setting islower than theadjustableselective instantaneous setting the RELT setting willtake precedence.
EntelliGuard® TU Trip Unit Section 3 - Operation09/25/08
Ground Fault ProtectionTheEntelliGuardTU Trip Unit can provideground fault
protection intwo differentways:
•via aninternalsummation scheme that adds upthe
three phase current phasors, and ifprovided also theneutral current phasor.
•Via an externalzero sequence current signal froma
CT or a residual sum using iron core CTs.
Internal ResidualSummation The EntelliGuard trip unit uses internal air core sensorsfor
current sensing and the signals are residually summedusing advanced digital electronics. A neutral sensor may be located remotelyand connected tothe trip unit.The connection is limited to 10 m (33 ft).
Due to the air coresensor’s ability to handlea wide range of primary currents withoutdistortion,ground faultsensingisaccurate for a wide range of phaseandcurrent inputs.
External SensedZero SequenceInput The EntelliGuard trip unit can accept input fromanexternally
calculated ground fault current.Thegroundfaultcurrentmay be derived using a single zerosequenceCTor multiplephase CTs.
External CE markedzero sequence orground returnCTsareavailable for IEC applications, but are not ULListed.Phase CTs used for a summation connection are ULListed. Applications for this capability include sensing at the groundreturn connection for a transformer orgenerator as well as application inmultiplesourcegrounded systems.
Ground Fault PickupSettingsAllUL 489 and UL 1066 circuit breakers are limited toa
maximum nominal pick up setting of 1200 A per theNational Electrical Code or60% of the sensor size, whichever is lower.The minimum setting is 20% of sensor size.
Ground Fault Time Delay BandsGround fault time delay bands usedin the EntelliGuardG
circuit breakers range from 42 msec to 942 msec. In Power Break I, Power BreakII, WavePro and AKR circuit breakers, the minimum GFtime delayband is58 msec andthe maximum is 417 msec.SeeTable 19.
The available minimum settings per circuit breaker type areshown in Table 21. The maximum time delay band setting for allcircuit breakers is 0.940 secwitha1secclear.SeeTable 20.
Table 20:Minimum Pickup and ClearTime
CharacteristicPower Break I
EntelliGuard G
Power Break II,
WavePro, AKR
Minimum Pickup 0.058 sec 0.042 sec
Minimum Clear
-
0.097 sec
Maximum Pickup0.417 sec 0.940 sec
Maximum Clear
-
1.000 sec
The ground fault functionmay be shaped as a definite time function (pickup and delay),an Ior a distinctdoubleslope function designed to optimizecoordination. TheI
4
Tslope provides easier selectivity with
2
T slope an I4T slope
downstream fuses. The double knee GF curve facilitatesselectivity with downstreamdevices.
EntelliGuard®TU Trip Unit 09/25/08Section 4 – Battery
SECTION 4 – BATTERY
GENERAL BATTERYINFORMATION
The trip unit has a front pane-mounted battery. When the battery is present,the user scan view data onthe LCD and read orprogram the trip unit via the keypads.The battery allows the user to display data, change set pointsand providethermal memory.
The battery does not allow normaltrip unit operation; i.e.over current protection,alarms, relays, etc.,are not functionalwhenthe trip unit is powered from the battery.
The trip unit will automatically shut off after 20 sec whenbattery poweredto maximize battery life.
BATTERY FUNCTION
Pressing any key on theface ofthe trip unit powers the unit fromitsinternal battery. Battery power is maintainedfor 20 sec after the last key is pressed.
This self-powered modeallows setting up thetripunitorviewing trip targetswhen the breaker isde-energized and external control power is unavailable.
All normal setup, meter, and statusfunctions can beperformed with battery power.
NOTICE
For temperatures above 40°C, any key may have tobe held down for up to 5 sec for the trip unit tobe powered.
BATTERY REPLACEMENT
WARNING
IMPROPER REPLACEMENT
• Replace the battery with 3.6 V ½AA lithium batteryonly.
Wearhard hat, glovesandsafety shoes when
•
replacing the battery.
Failure to comply with these instructions couldresult in death or serious injury.
WARNING
IMPROPER DISPOSAL
• Ensure battery is properly disposed ofaccording toall applicable regulations.
Failure to comply with these instructions could
result in death or serious injury.
Replace the battery ifit doesnot power up the trip unit when any key is pressed.
Lift the battery cover on the front ofthe trip unit toexpose the 3.6 V ½ AAlithium cell. A suitable replacement isTADIRAN part number TLL-5902/S orSANYO partnumber CR14250SEwhich are commonlyavailable frommost electrical stores or industrial distributors.
EntelliGuard®TU Trip Unit Section 5 – Maintenance and Troubleshooting09/25/08
SECTION 5– MAINTENANCE AND TROUBLESHOOTING
DANGER
ELECTROCUTIONEnsure the circuit breaker has been tripped,indicating OFF, and the main springs are fully discharged whenperforming circuit breakermaintenance. Failure to comply with these instructions could result in death or serious injury.
WARNING
IMPROPER INSTALLATION,OPERATION AND MAINTENANCEEnsure only qualified personnel install, operate, serviceand maintain all electrical equipment.Failure to comply with these instructions could result in death or serious injury.
WARNING
PERSONAL INJURY
•Avoid risk ofinjury frommoving parts while handling
safety during systemmaintenance. Failure to comply with these instructions could result in death or serious injury.
Figure 16: Rating Plug Removal
TROUBLESHOOTING
Table 21providesprocedures for troubleshooting andisolating commonproblems. It does not cover every possible condition.
Contact Post Sales Service at 1-888-GE-Resolve or 1-888-437-3765if these proceduresdoe not resolve the problem.
MAINTENANCE
Rating Plug Removal and Replacement
NOTICE
Removal ofthe rating plugwhile thebreaker is carryingcurrent reduces the breaker's current-carrying capacity to approximately 40% of the current sensor rating.
Interchangeable rating plugs are removed withaRatingPlug Extractor, Catalog No. TRTOOL. (Suitable equivalents are commercially available as "integrated circuit (DIP)extractors.")Grasp theratingplug tabs with theextractorand pullthe plug out as shown in Figure 16.
Be sure tograbthe tabs and not the front cover ofthe rating plug, or theplugmaybe damaged.
EntelliGuard®TU Trip Unit 09/25/08Section 5–Maintenance andTroubleshooting
Table 21: Troubleshooting Guide
The trip unit display is blank.External +24 VDC is absent.
The load current fluctuates near 20% ofthe breaker sensor rating.
At least 20% of the current sensor rating, (xCT) must be flowing through the breakerto activate the display.If not, power the trip unit with the internalbattery.
The battery power supply is disabled whenany current is sensedthrough the current sensors.
Check that thecontrol powersupply ispresent and operational.
The trip unit display E02.
BIM error.
No communication with the BIM Checkthe BIM harness.
Mismatch trip unit / BIM optionThe trip unit display E03.Memory failure.The trip unit display E06.Internal failure. The trip unit display E08.Invalid rating plug.
Return the unit to GE.
Return the unit to GE.
Checkthe rating plug. The rating plug
value shall not exceed andbe below 40%
of the breaker sensor.
Ensure the rating plug is properly sited.Unit does not communicate withthe Master.
The communication wires are shortedor improperly connected.
Incorrect baud rate.
Incorrect address.
Locate and repair the short or the
incorrect connection.
Check that thebaud rate assigned tothe
trip unit, agrees with the baud rate at the
host.
Check that theaddress assigned tothe
trip unit, agrees with the address atthe
host. Current readings are incorrect. Incorrect rating plug value.
Checkthe rating plug label.
Voltage readings are incorrect. The potential transformer (PT) primary
voltage was definedincorrectly.
The PT connection was defined incorrectly.
Read the PTprimary rating from the PT
name plate and set trip unit PT to this
value.
Setthe trip unit phase tophase PH-PHor
phase to neutral PH-N according tothe
system. The display isblank orthe LowBatterysymbol appearswhen theBATTERY key is pressed.Line current is below 20% ofthe
The batteryis discharged.The battery was stored too long with nopower applied tothe trip unit.
EntelliGuard®TU Trip Unit Appendix 1 –Communications Parameters09/25/08
APPENDIX 1: COMMUNICATIONS PARAMETERS
Table 22: Communications Parameters–Modbus Function 2
Register VariableValue Read/Write
5 Relay 1 Status 0 – OFF, 1 – ON Read 6 Relay 2 Status 0 – OFF, 1 – ON Read 7 Relay 3 Status 0 – OFF, 1 – ON Read 8 Relay 4 Status 0 – OFF, 1 – ON Read 9 Input 1 Status 0 – OFF, 1 – ON Read
10 Input 2 Status 0 – OFF, 1 – ON Read 11 Input 3 Status 0 – OFF, 1 – ON Read 12 Input 4 Status 0 – OFF, 1 – ON Read 27 Breaker position 0 – OFF, 1 – ON Read 34 Cassette Indication 0 – OFF, 1 – ON Read 35 Draw Out 0 – OFF, 1 – ON Read 44 Remote Close 0 – OFF, 1 – ON Read 61 GF Sum Alarm Status 0 – Normal,1 –Alarm Read 62 GF CTAlarm Status0 – Normal,1 –Alarm Read
Table 23: Communications Parameters–Modbus Function 3
Register VariableValue Read/Write
2 GF Protection Sun Enable 0–Disable, 1–EnableRead 5 No. of Poles 0–3 Pole, 1–4 PoleRead 6 Protective Relays Enable0–Disable, 1–EnableRead 7 Full Metering Enable0–Disable, 1–EnableRead
8 Neutral Position 0–Disable, 1–EnableRead 10 Long Time Protection Enable0–Disable, 1–EnableRead 18 Agency Standard 0–UL, 1–IEC, 2–ANSI Read 20GTU Model Type 0– GTU C, 1–GTU D, 4–GTU ACB Read22 Current Sensor Rating1–150 A
EntelliGuard®TU Trip Unit 09/25/08Appendix 1 –Communications Parameters
Register VariableValue Read/Write
2–GF&ST3–ST
6–ST and Inst
7–GF,ST and Inst 208 PTPrimary Voltage 120–600 Read/Write209 PTConnection 0–Ph-N,1–Ph-Ph Read/Write210 Password Protection 0 to 20, 16–Lock, 19–UnlockRead/Write211 Modbus Slave Address 8 bit value Read/Write212 Profibus Slave Address 8 bit value Read/Write213 CommunicationSetting 0–300-8N1
286 Language0–English, 1–French,2–Spanish, 3–German, 4–Chinese Read/Write287 Time Sync Year 8 bit Read/Write288 Time Sync Month 8 bit Read/Write289 Time Sync Date 8 bit Read/Write
EntelliGuard®TU Trip Unit 09/25/08Appendix 1 –Communications Parameters
Register VariableValue Read/Write
290 Time Sync Day 8 bit Read/Write291 Time Sync Hour 8 bit Read/Write292 Time Sync Minute 8 bit Read/Write293 Time Sync Second 8 bit Read/Write294 Health status output type 0–NO, 1–NCRead/Write296 Current Alarm 1 Pickup On1–0.5
Read/Write2–0.55 3–0.60 … 10–0.95 11–1.00
297 CurrentAlarm 1 Pickup Off 1–0.5
Read/Write2–0.55 3–0.60 … 10–0.95 11–1.00
298 Current Alarm 2 Pickup On1–0.5
Read/Write2–0.55 3–0.60 … 10–0.95 11–1.00
299 CurrentAlarm 2 Pickup Off 1–0.5
Read/Write2–0.55 3–0.60 … 10–0.95 11–1.00
300 Bell Alarm (Bell Alarm 1)0–Disabled
Read/Write1–Shunt Trip 2–UVR Trip3–Over Current Trip4–Protective Relay Trip5–Shunt, UVR 6–Shunt, Over Current 7–Shunt, Protective Relay 8–UVR, Over Current 9–UVR, Protective Relay 10–OverCurrent, Protective Relay 11–Shunt Trip, UVR,Over Current 12–Shunt, UVR, Protective Relay 13–Shunt, Over Current, Protective Relay 14–UVR, Over Current, Protective Relay 15–Shunt, UVR, Over Current, Protective Relay
301 Bell Alarm with lockout (Bell Alarm 2)0–Disabled
Read/Write1–Shunt Trip 2–UVR Trip3–Over Current Trip4–Protective Relay Trip5–Shunt, UVR 6–Shunt, Over Current 7–Shunt, Protective Relay
Table 24: Communication Parameters – Modbus Function 4
Register VariableValue Read/Write16 GTURev 8 bit Read 17 Software Rev 8 bit Read 18 Voltage Phase A16 bit Read 19 Voltage Phase B 16 bit Read 20 Voltage Phase C 16 bit Read 21 Current Phase A(LO 16 bits ) 32 bit Read 22 Current Phase A(HI 16 bits ) –Read 23 Current Phase B(LO 16 bits ) 32 bit Read 24 Current Phase B(HI 16 bits ) –Read 25 Current Phase C(LO 16 bits ) 32 bit Read
EntelliGuard®TU Trip Unit 09/25/08Appendix 1 –Communications Parameters
Register VariableValue Read/Write26 Current Phase C(HI 16 bits ) –Read 27 Current Phase N(LO 16 bits ) 32 bit Read 28 Current Phase N(HI 16 bits ) –Read 29 RatingPlug Value –Read 31 Energy Total( 0-15 bits ) 16 bit Read 32 Energy Total(16-31 bits) 16 bit Read 33 Energy Total( 32-47 bits) 16 bit Read 34 Energy Total( 48-63 bits) 16 bit Read 35 Energy Rollover Count 16 bit Read 36 Power Factor Phase A16 bit Read 37 Power Factor Phase B 16 bit Read 38 Power Factor Phase C 16 bit Read 39 Power Factor Total16 bit Read 40 Real Power Phase A–Lo 16 bits 32 bit Read 41 RealPower Phase A–Hi 16 bits–Read 42 Real Power Phase B–Lo 16 bits 32 bit Read 43Real Power PhaseB–Hi 16 bits– Read44 Real Power Phase C–Lo 16 bits 32 bit Read 45Real Power PhaseC–Hi 16 bits– Read46 Real Power Phase Total–Lo 16 bits 32 bit Read 47Real Power PhaseTotal–Hi16 bits– Read48 Reactive Power Phase A–Lo 16 bits 32 bit Read 49 Reactive PowerPhase A–Hi 16 bits –Read 50 Reactive PowerPhase B–Lo 16 bits 32 bit Read 51 Reactive PowerPhase B–Hi16 bits –Read 52 Reactive PowerPhase C–Lo 16 bits 32 bit Read 53 Reactive PowerPhase C–Hi16 bits –Read 54 Reactive PowerPhase Total–Lo 16 bits 32 bit Read 55 Reactive PowerPhase Total–Hi 16 bits –Read 56 Power Apparent Phase A–Lo 16 bits 32 bit Read 57 Power ApparentPhase A–Hi 16 bits –Read 58 Power Apparent Phase B–Lo 16 bits 32 bit Read 59 Power ApparentPhase B–Hi 16 bits –Read 60 Power Apparent Phase C - Lo 16 bits32 bit Read 61 Power Apparent Phase C - Hi 16 bits
-
Read 62 Power Apparent Phase Total- Lo 16 bits32 bit Read 63 Power Apparent Phase Total- Hi 16 bits
-
Read 64 Power Demand Total - Hi 16bits32 bit Read 65 Power Demand Total - Hi 16bits
-
Read 66 Frequency Measured 16 bit Read 67 Event 1 8 bit Read 68 Year 8 bit Read 69 Month 8 bit Read 70 Date8 bit Read 71 Hour 8 bit Read 72 Minute 8 bit Read 73 Second 8 bit Read 74 Phase 8 bit Read 75 Event Specific 1 16 bit Read 76 Event Specific 2 16 bit Read 77 Event 2 8 bit Read 78 Year 8 bit Read
EntelliGuard®TU Trip Unit Appendix 1 –Communications Parameters09/25/08
Register VariableValue Read/Write79 Month 8 bit Read 80 Date8 bit Read 81 Hour 8 bit Read 82 Minute 8 bit Read 83 Second 8 bit Read 84 Phase 8 bit Read 85 Event Specific 1 16 bit Read 86 Event Specific 2 16 bit Read 87 Event 3 8 bit Read 88 Year 8 bit Read 89 Month 8 bit Read 90 Date8 bit Read 91 Hour 8 bit Read 92 Minute 8 bit Read 93 Second 8 bit Read 94 Phase 8 bit Read 95 Event Specific 1 16 bit Read 96 Event Specific 2 16 bit Read 97 Event 4 8 bit Read 98 Year 8 bit Read 99 Month 8 bit Read 100 Date8 bit Read 101 Hour 8 bit Read 102 Minute 8 bit Read 103 Second 8 bit Read 104 Phase 8 bit Read 105 Event Specific 1 16 bit Read 106 Event Specific 2 16 bit Read 107 Event 5 8 bit Read 108 Year 8 bit Read 109 Month 8 bit Read 110 Date8 bit Read 111 Hour 8 bit Read 112 Minute 8 bit Read 113 Second 8 bit Read 114 Phase 8 bit Read 115 Event Specific 1 16 bit Read 116 Event Specific 2 16 bit Read 117 Event 6 8 bit Read 118 Year 8 bit Read 119 Month 8 bit Read 120 Date8 bit Read 121 Hour 8 bit Read 122 Minute 8 bit Read 123 Second 8 bit Read 124 Phase 8 bit Read 125 Event Specific 1 16 bit Read 126 Event Specific 2 16 bit Read 127 Event 7 8 bit Read 128 Year 8 bit Read 129 Month 8 bit Read 130 Date8 bit Read
EntelliGuard®TU Trip Unit 09/25/08Appendix 1 –Communications Parameters
Register VariableValue Read/Write131 Hour 8 bit Read 132 Minute 8 bit Read 133 Second 8 bit Read 134 Phase 8 bit Read 135 Event Specific 1 16 bit Read 136 Event Specific 2 16 bit Read 137 Event 8 8 bit Read 138 Year 8 bit Read 139 Month 8 bit Read 140 Date8 bit Read 141 Hour 8 bit Read 142 Minute 8 bit Read 143 Second 8 bit Read 144 Phase 8 bit Read 145 Event Specific 1 16 bit Read 146 Event Specific 2 16 bit Read 147 Event 9 8 bit Read 148 Year 8 bit Read 150 Date8 bit Read 151 Hour 8 bit Read 152 Minute 8 bit Read 153 Second 8 bit Read 154 Phase 8 bit Read 155 Event Specific 1 16 bit Read 156 Event Specific 2 16 bit Read 157 Event 10 8 bit Read 158 Year 8 bit Read 159 Month 8 bit Read 160 Date8 bit Read 161 Hour 8 bit Read 162 Minute 8 bit Read 163 Second 8 bit Read 164 Phase 8 bit Read 165 Event Specific 1 16 bit Read 166 Event Specific 2 16 bit Read 167 Long Time Trip Count 8 bit Read 168 ShortTime Trip Count 8 bit Read 169 Instantaneous Trip Count 8 bit Read 170 Ground Fault Sum Trip Count8 bit Read 179 Shunt 1 Trip Count 8 bit Read 180 Shunt 2 Trip Count 8 bit Read 196 Software Rev 8 bit Read 227 Breaker Position1–CLOSE, 0–OPEN Read 228 Error Code Log 229 Error Code Log 230 Error Code Log 231 Error Code Log 232 Error Code Log 233 Error Code Log 234 Error Code Log 235 Error Code Log 236 Error Code Log