GE Digital Energy LP 11 Operating Manual

GE Consumer & Industrial
Power Protection
OPERATING MANUAL
Digital Energy™ LP 11
Uninterruptible Power Supply
OPERATING MANUAL Digital Energy LP 3/5/6/8/10-11 UPS LX-DO C File: OPM_LPE_11X_3K0_10K_1GB_V041
Manual versio n 4 . 1 S o f t ware ve rsion R2 .11
OPERATING MANUAL
Digital Energy™ LP 11
Uninterruptible Power Supply
3-5-6-8-10 kVA
Preface
We thank you for selecting a General Electric Digital Energy™ LP Series Uninterruptible Power Supply (UPS) and recommend that you read these instructions carefully before installation and start-up of the UPS.
Please keep this manual in a safe place for future reference and carefully read the important safety instructions in chapter 1 before installation of this device.
© 2006 by GE Industrial Systems
All rights reserved. The information contained in this publication is intended solely for the purposes indicated. The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE. The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail. The content of this publication may be subject to modification without prior notice.
OPM_LPE_11X_3K0_10K_1GB_V041 1 GE DE LP 11 UPS: User manual 4.1 (GB)
OPM_LPE_11X_3K0_10K_1GB_V041 2 GE DE LP 11 UPS: User manual 4.1 (GB)
CONTENTS
1 IMPORTANT SAFETY INSTRUCTIONS...................................................................3
1.1 Save these instructions
1.2 General
1.3 Installation
1.4 Storage
1.5 Batteries
2 INTRODUCTION .......................................................................................................5
2.1 Description
2.2 Warranty
3 FUNCTIONAL EXPLANATION..................................................................................6
3.1 Principles of operation
3.2 Normal conditions
3.3 Utility failure
3.4 Automatic bypass switch
3.5 Manual bypass switch
4 INSTALLATION..........................................................................................................8
4.1 Transport
4.2 Unpacking
4.3 Package contents
4.4 Location
4.5 Installation
4.5.1 LP 3/5/6-11: standard installation procedure
4.5.2 LP 3/5/6-11: installation of Digital Energy™ LP battery extension pack(s)
4.5.3 LP 8/10-11: standard installation procedure
4.5.4 LP 8/10-11: installation of Digital Energy™ LP battery extension pack(s)
4.5.5 LP-11 series: 2 / 3 / 4 parallel operating units – additional info
5 OPERATION.............................................................................................................16
5.1 Description of front and rear panel
5.2 Start-up
5.3 Use
5.3.1 Information menu
5.3.2 Status and alarm menu
5.3.3 Service menu
5.3.4 Set-up menu
5.4 Test screens
5.4.1 Battery test, general
5.4.2 Quick battery test
5.4.3 Deep battery calibration test
5.5 Other features
5.5.1 Shutdown
5.5.2 Start without batteries
5.5.3 Sleep and wake-up
5.5.4 Overload protection in bypass mode
5.5.5 ECO-Mode 5 5.6 Auto restart
5.5.7 Superior battery management
6 INTERFACING FEATURES.....................................................................................29
6.1 RS232/Contact interface
6.2 Emergency shutdown
6.3 Relay card (optional)
6.4 SNMP interface (optional)
7 OPTIONAL FEATURES...........................................................................................30
7.1 Extended runtime versions
7.2 Plug-in cards
7.3 RPA-facility (Redundant Parallel Architecture)
8 MAINTENANCE .......................................................................................................31
8.1 General
8.2 Cooling fan
8.3 Batteries
8.4 Safety
8.5 Storage
8.6 Recycling the UPS at the end of service life
9 TROUBLESHOOTING.............................................................................................32
10 SPECIFICATIONS....................................................................................................33
APPENDIX: INSTALLATION DRAWINGS
1 - Important Safety Instructions
1.1 Save these instructions
This manual contains important instructions that should be followed during installation and maintenance
of the UPS. It also gives all necessary information about the correct use of the UPS.
Full understanding and compliance of the safety instructions and warnings contained in this manual are
the ONLY CONDITION to avoid any dangerous situation during installation, operation and maintenance work, and to preserve the maximum reliability of the UPS system.
GE refuses any responsibility in case of non-observance, unauthorized alterations or improper use of
the delivered UPS.
Before attempting to install and start up the UPS, carefully read this manual. Keep this manual next to the UPS for future references. All servicing must be done by qualified personnel. Do not attempt to service the UPS unless you have had proper training.
CAUTION: By opening or removing covers you run the risk of exposure to dangerous voltages!
While every care has been taken to ensure the completeness and accuracy of this manual, GE accepts no responsibility or liability for any loss or damage resulting from the use of the information contained in this document. This document shall not be copied nor reproduced without the permission of GE. Due to technical improvements, some of the information contained in this manual may be changed without notice.
1.2 General
CAUTION: RISK OF ELECTRIC SHOCK Do not remove the cover, there are no user serviceable parts inside. All maintenance and service work should be performed by qualified service personnel.
The UPS contains batteries. The output terminals may be electrically live, even when the UPS is disconnected from the utility supply. Dangerous voltages may be present during battery operation. The batteries must be disconnected during maintenance or service work.
The UPS contains potentially hazardous voltages.
WARNING: This is a Class A-UPS product. In a domestic environment this product may cause radio
interference, in which case the user may be required to take additional measures.
1.3 Installation
Move the UPS in an upright position and in its original package to the final destination room.
To lift the UPS, use a forklift or lifting belts with spreader bars.
Check for sufficient floor and elevator loading capacity.
Check carefully the integrity of the UPS equipment. In case you note some visible damage, do not
connect any voltage to the UPS but contact the nearest Service Centre.
This UPS is intended to be used in a controlled indoor environment and free of conductive contaminants and protected against animal intrusion.
The UPS should only be powered from a single phase, three wire AC source equipped with an earth connection.
Do not install the UPS in an excessively humid environment or near water.
Avoid spilling liquids or dropping any foreign object into the UPS.
The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 40°C. Optimal battery lifetime is obtained if the ambient temperature does not exceed 30°C.
It is important that the unit has adequate ventilation. Maintain air movement around and through the
unit. Do not block the air vents.
Avoid placing the unit in direct sunlight or near heat sources.
Do not plug household appliances such as electric heaters, toasters or vacuum cleaners into the UPS.
The UPS output is intended to be used only for electronic loads such as computers and telecommunications equipment.
OPM_LPE_11X_3K0_10K_1GB_V041 3 GE DE LP 11 UPS: User manual 4.1 (GB)
1.4 Storage
Store the UPS with its batteries fully charged in a dry location, storage temperature must be within -20 and +45°C.
If the unit is stored for an extended period of time, the batteries must be recharged periodically. Connect the unit to the mains and switch it on:
- if the storage temperature is within -20 and +30°C, recharge the batteries every 3 months, for 24
hours,
- if the storage temperature is within -20 and +45°C, recharge the batteries every month, for 24 hours.
1.5 Batteries
NOTE: All maintenance and service work, including battery replacement, should be performed by qualified service personnel.
When replacing the batteries, use only the same type and size battery.
Never short circuit batteries. When working with batteries, remove watches, rings or other metal
objects, and use only insulated tools.
Avoid charging in a sealed container.
Never dispose of batteries in a fire: they may explode.
Do not open or mutilate batteries: their contents may be extremely toxic. If exposed to electrolyte, wash
immediately with plenty of water.
Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal requirements.
OPM_LPE_11X_3K0_10K_1GB_V041 4 GE DE LP 11 UPS: User manual 4.1 (GB)
2 - Introduction
2.1 Description
More than ever before, today's advanced electronic equipment, with complex integrated circuits and other sensitive electronics, needs a stable and continuous AC power supply to operate correctly. While the power coming from the wall outlet is often unreliable, a GE Digital Energy™ LP UPS provides the security of completely uninterrupted power.
A compact, truly on-line system, the LP UPS protects your equipment from all forms of power interference, including complete power failure. A simple and elegant circuit design, together with extensive protection against abnormal operating conditions (e.g. overload, short circuit, overheating), makes the LP UPS exceptionally reliable.
Figure 1. The GE Digital Energy™ LP 11 UPS: 3/5/6-11 (front) and 8/10-11 (rear)
2.2 Warranty
GE Digital Energy, operating through its authorized agents, warrants that the standard products will be free of defects in materials and workmanship for a period of 24 months (12 months for the battery) after the date of invoice, or such other period as may be specified.
NOTE: This warranty does not cover failures of the product which result from incorrect installation, misuse, alterations by persons other than authorized agents, or abnormal operating conditions.
OPM_LPE_11X_3K0_10K_1GB_V041 5 GE DE LP 11 UPS: User manual 4.1 (GB)
3 - Functional Explanation
3.1 The Principles of Operation
The UPS stores electric energy in batteries. This allows the UPS to supply output power even when the incoming utility power is cut off completely. Energy is stored as Direct Current (DC), while input and output energy must be Alternating Current (AC). Therefore the UPS contains an input converter (AC to DC) and an output converter (DC to AC). (fig.2)
3.2 Normal Conditions
Under normal conditions, energy from the utility is channelled through the input converter, which supplies the output converter and the battery charger. The batteries are kept in a fully charged state, and the output converter synthesizes a completely new AC output sine wave to supply the load (electrical equipment).
TO LOAD
AUTOMATIC
BYPASS SWITCH
FRONT
PANEL
STANDARD INSTALLED:
RS232/
CONTACT
INTERFACE
OPTION
SLOTS FOR:
RPA CARD
SNMP CARD
RELAY CARD
RFI
FILTER
OUTPUT: PERFECT UPS POWER
1-PHASE
MAINS INPUT
MANUAL BYPASS SWITCH
OUTPUT
CONVERTER
SYSTEM ON/OFF
MICROPROCESSOR CONTROL
BATTERY
BATTERY
EXTENSION
OPTIONAL
RFI
FILTER
INPUT
CONVERTER/
BATTERY
CHARGER
BYPASS
FILTER
INPUT: MAINS POWER WITH DISTURBANCES
Figure 2. Block diagram of the LP 11 UPS, mains present
3.3 Utility Failure
In the event of a utility power failure (i.e. absent or outside tolerance) the system uses the energy reserve stored in the battery to continue to produce AC power, ensuring unbroken output (fig. 3). No interruption or alteration will ever be noticed in the output power. In the event of an extended utility failure, the output converter will stop when the battery has been discharged. At this point, the UPS is no longer able to power the connected equipment. When the utility is re-established within tolerance, the output converter will restart automatically (if stopped, see above) and will be supplied again by the input converter. The batteries will be recharged, making them ready to support future power failures.
TO LOAD
STANDARD INSTALLED:
RS232/
CONTACT
INTERFACE
OPTION
SLOTS FOR:
RPA CARD
SNMP CARD
RELAY CARD
RFI
FILTER
AUTOMATIC
BYPASS
SWITCH
MANUAL BYPASS SWITCH
OUTPUT
CONVERTER
FRONT PANEL
SYSTEM ON/OFF
MICROPROCESSOR CONTROL
BATTERY
BATTERY
EXTENSION
OPTIONAL
RFI
FILTER
INPUT
CONVERTER/
BATTERY CHARGER
BYPASS
FILTER
NO INPUT: MAINS FAILURE (BLACK OUT)
OUTPUT: PERFECT UPS POWER
Figure 3. Block diagram of the LP 11 UPS, utility failure
OPM_LPE_11X_3K0_10K_1GB_V041 6 GE DE LP 11 UPS: User manual 4.1 (GB)
3.4 Automatic Bypass Switch
If the output converter is unable to deliver the demanded output power because of overload or overtemperature, the automatic bypass switch will automatically transfer the load to the utility. When the situation is corrected the UPS will switch back to normal operation, i.e. the load is transferred back to the output converter. Though the automatic bypass switch is shown as a simple mechanical switch in figures 2-5, the transfers are done by means of thyristors, i.e. electronically, without any interruption of the power supplied to the load.
In case of a severe overload or short-circuit the magnetic bypass circuit breaker (rear panel) may trip in order to protect the UPS. If the current is insufficiently high to trip the breaker, the UPS will be switched off by the software in order to protect the UPS and connected equipment.
TO LOAD
AUTOMATIC
BYPASS SWITCH
FRONT PANEL
1-PHASE
MAINS INPUT
STANDARD INSTALLED:
RS232/
CONTACT
INTERFACE
OPTION
SLOTS FOR:
RPA CARD
SNMP CARD
RELAY CARD
RFI
FILTER
MANUAL BYPASS SWITCH
OUTPUT
CONVERTER
SYSTEM ON/OFF
MICROPROCESSOR CONTROL
BATTERY
BATTERY
EXTENSION
OPTIONAL
RFI
FILTER
INPUT
CONVERTER/
BATTERY
CHARGER
BYPASS
FILTER
Figure 4. Bypass operation: automatic bypass
If a power failure occurs during bypass operation, load power is lost. If the UPS functions under overload conditions it may not be able to protect the load.
3.5 Manual Bypass Switch (Service switch)
The system can be bypassed manually using the manual bypass switch located at the rear panel. It is a two­position switch: the normal position is '1': as in figures 2-4. Position '2' is the service position: the load is directly connected to the utility input. This way maintenance of the UPS (e.g. battery replacement, as in fig. 5) is possible without interruption of the power supplied to the load.
CAUTION: REFER SERVICE TO QUALIFIED PERSONNEL ONLY.
TO LOAD
STANDARD INSTALLED:
RS232/
CONTACT
INTERFACE
OPTION
SLOTS FOR:
RPA CARD
SNMP CARD
RELAY CARD
RFI
FILTER
AUTOMATIC
BYPASS SWITCH
FRONT
PANEL
1-PHASE
MAINS INPUT
MANUAL BYPASS SWITCH
OUTPUT
CONVERTER
SYSTEM ON/OFF
MICROPROCESSOR CONTROL
BATTERY
EXTENSION
OPTIONAL
RFI
FILTER
INPUT
CONVERTER/
BATTERY
CHARGER
BYPASS
FILTER
Figure 5. Bypass operation: manual bypass
OPM_LPE_11X_3K0_10K_1GB_V041 7 GE DE LP 11 UPS: User manual 4.1 (GB)
4 - Installation
4.1 Transport
NOTE: Transport the UPS only in upright position. Check for sufficient floor and elevation loading
capacity. Move the UPS in its original package to the final destination room. Do not stack other package on top.
4.2 Unpacking
Cut the two wrapping bands, and remove the shipping box. Loosen the four bolts with which the UPS is fixed to the pallet. Remove the UPS from the pallet.
BE CAREFUL! Pay attention to the HEAVY WEIGHT of the UPS when downloading the UPS from the pallet! Never try to lift the unit by y ourself!
The UPS is equipped with castors, which allow easy displacement of the unit. Please take appropriate measures to avoid damage on vulnerable floors.
4.3 Package Contents
The shipping box contains a LP 11 UPS, a CD-ROM, an RS232 cable, cable clamps, a safety guide and this manual. If the UPS is equipped with an RPA plug-in card (Redundant Parallel Architecture, right option slot at the rear of the unit) the shipping box also contains a yellow network cable and one bus terminator. Inspect the UPS for damage after unpacking. If any damage is present please notify the carrier and place of purchase immediately.
4.4 Location
Please refer to sections 1.2 and 1.3 of ‘IMPORTANT SAFETY INSTRUCTIONS’.
4.5 Installation
IMPORTANT:
Before making any connection and switching on the LP UPS, please check the following conditions:
- the voltage and frequency of your utility supply is 220/230/240 Vac and 50/(60) Hz; off-factory the output of the UPS is set to 230 Vac / 50 Hz,
- the branch circuit supply is protected as follows:
UPS model branch protection LP 3kVA 16A slow LP 5/6kVA 25A slow LP 8kVA 50A slow LP 10kVA 50A slow
Table 1. external input fuse value
CAUTION: To reduce risk of fire, connect the UPS only to a circuit provided with the fuse
values according to Table 1 above.
- Ensure that the total power requirement of the equipment to be protected does not exceed the rated output power of the UPS (output power for your unit is indicated on the rating label on the rear panel).
- The UPS must be grounded when in use: Connect the UPS to a single phase, three wire AC source equipped with an earth connection.
The following sections describe the installation of the LP 11 UPS.
LP 3/5/6-11 UPS: 4.5.1 and 4.5.2 LP 8/10-11 UPS: 4.5.3 and 4.5.4 LP 11 UPS, general: 4.5.5
OPM_LPE_11X_3K0_10K_1GB_V041 8 GE DE LP 11 UPS: User manual 4.1 (GB)
4.5.1 LP 3/5/6-11: standard installation procedure
If a battery extension pack is to be installed, please proceed with section 4.5.2. If 2, 3 or 4 parallel operating units will be installed, please proceed with section 4.5.5. The numbers between (brackets) refer to figure 12 in section 5.1.
BATTERY DISCONNECTED
EMERGENCY SHUTDOWN
stand-alone and RPA card available
see 4.5.5 / 7.3
see 6.3-4
10
9
8 7
6
5 4
3
2
1
1. Make sure that all circuit breakers (7-8-9) are in ‘off’ position (down).
2. Loosen the 3 screws and remove the metal cover (11) of the I/O terminals.
3. Lead the input/output cables through the swivels of the metal cover (11).
4. Input (11a). Connect the mains supply wires to the terminals 2 (Line) and 3 (Neutral) and the ground wire to terminal 1. Ground connection is essential!
5. Output (11b). Connect the load wires to the terminals 4 (Line) and 5 (Neutral) and the ground wire to terminal 6. Ground connection is essential!
6. Re-install the metal cover (11). Fasten the cables in the
swivels. Insert the battery fuse in the fuse holder (17)
and close the fuse holder.
7. An emergency shutdown switch can be connected to connector J3 on the RS232/Contact Interface Card, between pins 3 and 4. See section 6.2 for more information.
8. For advanced communication possibilities, the RS232/contact interface port (12a) can be connected to a computer system. See section 6.1 for more information. *
9. The middle ‘option slot’ (13) allows easy installation of plug-in cards: SNMP Card or Relay Card. See sections 6.3 and 6.4 for more information. *
10. The right ‘option slot’ (14) allows easy installation of the RPA-card (Redundant Parallel Architecture). If the card is already mounted, and if the unit is intended to be used stand-alone, a bus terminator (delivered with the unit) has to be placed in one of the two bus connectors on the card. If the unit will be part of a parallel system, see sections 4.5.5 and 7.3 for more information. *
* The data cables can be attached to the cabinet with
tie-wraps, position the tie-wraps in the small holes (18) underneath the option slots.
11. Connect the utility power to the UPS.
Figure 6. LP 3/5/6-11:
Standard installation procedure
12. For a quick start proceed with section 5.2 ‘Start-up’.
OPM_LPE_11X_3K0_10K_1GB_V041 9 GE DE LP 11 UPS: User manual 4.1 (GB)
4.5.2 LP 3/5/6-11: installation of GE Digital Energy™ LP battery extension pack(s)
The numbers between (brackets) refer to figures 12-13 in section 5.1.
Battery extension pack(s) are shipped with all materials necessary to connect them to the UPS. The pack(s) can be connected to the DC connector (15) at the rear panel of the UPS. We recommend to switch off the UPS before proceeding: be sure that the UPS can be switched off without causing damage to the load, and turn all circuit breakers (7-8-9) into ‘off’ position (down).
5
4
3
2
1
1. Open the fuse holders at the rear panel of the UPS (17) and battery pack (18) and make sure that the fuses have been removed.
2. UPS rear panel: loosen the 4 screws that hold the cover of the DC connector (15), and open the cover. The actual DC socket is fixed to the inner side of the cover.
CAUTION! The battery voltage is 240Vdc
and is NOT isolated from the mains.
3. Break out a part of the cover: a large part (grey in fig.
7) if your battery extension pack is equipped with a swivel (19, fig. 13a), otherwise a small part. If applicable, mount the swivel in the cover.
4. Connect the DC connector of the battery pack (15a) to the DC socket of the UPS (15). You will hear a click when the cable is properly installed.
5. If applicable lead the DC cable through the hole on the left side of the cover. Re-install the cover. Fasten it with 4 screws.
6. In case of 14Ah battery packs: using the DC connector of the battery pack (15) you can install a second, third, etc. pack. 7Ah battery packs cannot be connected in series.
7. Insert the battery fuse of the UPS (17). Insert the 2 (7Ah) or 4 (14Ah) fuses of the (each) battery pack (18). Close the fuse holders (17, 18).
8. In order to calculate the available back-up time related to the actual load, information on the capacity of the battery set is stored in the UPS. As the total battery capacity changes when battery extension packs are installed, the battery capacity must be re­programmed. See 5.3.4.
In case of a custom-built battery extension set you may want to install a ‘battery disconnected’ alarm device.
9. Be sure that the UPS is switched off, and disassemble the RS232/Contact Interface Card (12) from the unit. If the card is disassembled during normal operation the UPS will shut down!
Remove the wire from connector J3 (pin 1 and 2).
Install the wiring of a normally closed contact (e.g. an auxiliary contact of an MCB) to pin 1 and 2. Re-install the interface card. If the contact is opened, the UPS will generate an ‘EXTERNAL BATTERY FUSE FAILURE’. See 5.3.2 for more information.
Figure 7. LP 3/5/6-11:
Installation of battery pack
Proceed with 4.5.1 or 5.2.
OPM_LPE_11X_3K0_10K_1GB_V041 10 GE DE LP 11 UPS: User manual 4.1 (GB)
4.5.3 LP 8/10-11: standard installation procedure
If a battery extension pack is to be installed, please proceed with section 4.5.4. If 2, 3 or 4 parallel operating units will be installed, please proceed with section 4.5.5. The numbers between (brackets) refer to figure 12 in section 5.1.
BATTERY DISCONNECTED
EMERGENCY SHUTDOWN
stand-alone and RPA card available
see 4.5.5 / 7.3
see 6.3-4
10
9
8 7
6
5
4 3
2
1
1. Make sure that all circuit breakers (7-8-9) are in ‘off’ position (down).
2. Loosen the 5 screws and remove the metal plate (11) that covers the I/O terminals.
3. Input (11a). Connect the mains supply wires to the terminals 2 (Line) and 3 (Neutral) and the ground wire to terminal 1. Ground connection is essential!
4. Output (11b). Connect the load wires to the terminals 5 (Line) and 6 (Neutral) and the ground wire to terminal 4. Ground connection is essential!
5. Use the clamps that came with the unit to attach the wires to the rear of the cabinet. Position the clamps in the slots (16).
6. Re-install the metal cover plate (11). Insert the 2 battery fuses in the fuse holder (17) and close the fuse holder.
7. An emergency shutdown switch can be connected to connector J3 on the RS232/Contact Interface Card, between pins 3 and 4. See section 6.2 for more information.
8. For advanced communication possibilities, the RS232/contact interface port (12a) can be connected to a computer system. See section 6.1 for more information.*
9. The middle ‘option slot’ (13) allows easy installation of plug-in cards: SNMP Card or Relay Card. See sections 6.3 and 6.4 for more information.*
10. The right ‘option slot’ (14) allows easy installation of the RPA-card (Redundant Parallel Architecture). If the card is already mounted, and if the unit is intended to be used stand-alone, a bus terminator (delivered with the unit) has to be placed in one of the two bus connectors on the card. If the unit will be part of a parallel system, see sections 4.5.5 and 7.3 for more information.*
* The data cables can be attached to the cabinet with
tie-wraps, position the tie-wraps in the small holes (18) underneath the option slots.
11. Connect the utility power to the UPS.
12. For a quick start proceed with section 5.2 ‘Start-up’.
Figure 8. LP 8/10-11:
Standard installation procedure
OPM_LPE_11X_3K0_10K_1GB_V041 11 GE DE LP 11 UPS: User manual 4.1 (GB)
Loading...
+ 26 hidden pages