GE DCCD330EGWC User Manual

Installation
Electric Dryer
Instructions
BEFORE YOU BEGIN
Read these instructions completely and
carefully.
IMPORTANT-
instructions for local inspector’s use.
IMPORTANT-
all governingcodes and ordinances.
Note to Installer - Be sure to leave these
instructions with the customer.
Note to Customer -
ions with your Use and Care Book for future reference.
Before the old dryer is removed from service or discarded, remove the dryer door.
Service information and the wiring dia­gram are located in the control console.
Do not allow children on or in the appli­ance. Close supervision of children is necessary when the appliance is used near children.
Install the dryer where the temperature is above 50°F for satisfactory operation of the dryer control system.
Keep these instruct-
Save these
Observe
01
WARNING
To reduce the risk of severe injury or death, follow all installation instruc-
• tions.
Clothes dryer installation must be performed by a qualified installer.
• Install the clothes dryer according to these instructions and in accordance
• with local codes.
This dryer must be exhausted to the outdoors.
• Use only 4” rigid metal ducting for exhausting the clothes dryer to the
• outdoors.
DO NOT install a clothes dryer with flexible plastic ducting materials. If
• flexible metal (semi-rigid or foil-type) duct is installed, it must be UL listed and installed in accordance with the instructions found in "Connecting The Dryer To House Vent" on page 5 of this manual. Flexible venting materials are known to collapse, be easily crushed, and trap lint. These conditions will obstruct dryer airflow and increase the risk of fire.
Do not install or store this appliance in any location where it could be
• exposed to water and or weather.
Save these instructions. (Installers: Be sure to leave these instructions with
• the customer).
NOTE: Installation and service of this dryer requires basic mechanical and electrical skills. It is your responsibility to contact a qualified installer to make the electrical connections.
RISK OF FIRE
TOOLS YOU
MATERIALS YOU WILL NEED
WILL NEED
4" DIA. METAL DUCT
FLAT BLADE SCREWDRIVER
PHILLIPS SCREWDRIVER
LEVEL
Step 1 Prepare the Area and Exhaust for Installation of
New Dryer (see section 1).
Step 2 Check and Ensure the Existing External Exhaust is
Clean (see section 1) and Meets Attached Installation
Specifications (see section 3). Step 3 Remove the Foam Shipping Pads (see section 1). Step 4 Move the Dryer to the Desired Location. Step 5 Connect the Power Supply (see section 2). Step 6 Connect the External Exhaust (see section 4). Step 7 Level Your Dryer (see section 5).
4" DIA. FLEXIBLE METAL (SEMI-RIGID)
KIT WX08X10077 (INCLUDES 2 ELBOWS)
(RECOMMENDED)
UL LISTED TRANSITION DUCT
(IF NEEDED)
4" DIA. FLEXIBLE METAL (FOIL TYPE)
UL LISTED TRANSITION DUCT
(IF NEEDED.)
4" DUCT
CLAMPS (2)
OR
4" SPRING
CLAMPS (2)
4" DIA. METAL
ELBOW
DUCT TAPE
Step 8 Check the Operation of the Power Supply
Step 9 Place the Owners Manual and the Installation
For Alcove or Closet Installation, see section 6. For Bathroom or Bedroom Installation, see section 7. For Mobile or Manufactured Home see, section 8. For side or bottom exhaust, see section 9.
EXHAUST
HOOD
GLOVES
and Venting.
Instructions in a Location Where They Will Be Noticed By the Owner.
SAFETY
GLASSES
UL RATED 120/240V,30A WITH 3 OR 4 PRONGS.
3/4" STRAIN
RELIEF
UL RECOGNIZED
IDENTIFY THE PLUG TYPE AS PER THE HOUSE RECEPTACLE BEFORE PURCHASING LINE CORD.
DRYER POWER
CORD KIT
(NOT PROVIDED
WITH DRYER)
Installation Instructions
Minimum Clearance Other Than Alcove or Closet Installation
Minimum clearance to combustible surfaces and for air opening are: 0 in. clearance both sides and 1 in. rear. Consideration must be given to provide adequate clearance for installation and service.
1 PREPARING FOR INSTALLATION OF NEW DRYER
TIP: Install your dryer before installing your washer. This will allow better access when installing dryer exhaust.
REMOVING LINT FROM WALL
EXHAUST OPENING
Remove and discard existing plastic or metal foil
transition duct and replace with UL listed transition duct.
WALL
INTERNAL DUCT OPENING
CHECK THAT EXHAUST HOOD DAMPER OPENS AND CLOSES FREELY.
TILT THE DRYER SIDEWAYS AND REMOVE THE FOAM SHIPPING PADS BY PULLING AT THE SIDES AND BREAKING THEM AWAY FROM THE DRYER LEGS. BE SURE TO REMOVE ALL OF THE FOAM PIECES AROUND THE LEGS.
2 ELECTRICAL CONNECTION INFORMATION
WARNING - TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK AND PERSONAL INJURY:
DO NOT USE AN EXTENSION CORD OR AN ADAPTER PLUG WITH TH IS APPLIANCE.
Dryer must be electrically grounded in accordance with local codes and ordinances, or in the absence of local codes, in accordance with the NATIONAL ELECTRI­CAL CODE, ANSI/NFPA NO. 70.
ELECTRICAL REQUIREMENTS
This dryer must be connected to an individual branch circuit, protected by the required time-delay fuses or circuit breakers. A four or three-wire, single phase, 120/240V or 120/208V, 60Hz, 30 amp circuit is required.
If the electric supply does not meet the above specifications, then call a licensed electrician.
GROUNDING INSTRUCTIONS
This dryer must be connected to a grounded metal, permanent wiring system, or an equipment-grounding conductor must be run with the circuit conductors and connected to the equipment­grounding terminal on the appliance.
CONNECTING DRYER USING 4-WIRE CONNECTION (MUST BE USED FOR MOBILE HOME INSTALLATION)
NOTES: SInce January 1,1996, the National Electric code requires that the new constructions utilize a 4-wire connection to
an electric dryer
WARNING:Only a 4-conductor cord shall be used when the
appliance is installed in a location where grounding through the neutral conductor is prohibited. Grounding through the neutral is prohibited for the new branch-circuit installations, mobile homes, recreational vehicles, and areas where local codes prohibit grounding through the neutral conduction.
REMOVE GROUND STRAP AND DISCARD. KEEP GREEN GROUND SCREW
SCREWS (3)
HOT WIRE
L1
N
L2
RELOCATE GREEN GROUND SCREW HERE
GREEN OR YELLOW WIRE
STRAIN RELIEF BRACKET
NEUTRAL (White)
3/4", UL RECOGNIZED
HOT
STRAIN RELIEF
WIRE
4 #10 AWG MINIMUM COPPER
COVER
2
CONDUCTORS OR 120/240V 30A POWER SUPPLY CORD KIT MARKED FOR USE WITH DRYERS & PROVIDED WITH CLOSED LOOP OR SPADE TERMINALS WITH UPTURNED ENDS (NOT SUPPLIED).
Installation Instructions
1. Turn off the circuit breaker (s) (30 amp) or remove the dryer’s circuit fuse at the electrical box.
2. Be sure the dryer cord is unplugged from the wall receptacle.
3. Remove the power cord cover located at the lower back.
4. Remove and discard ground strap. Keep the green ground screw for step 7.
5. Install 3/4 in. UL recognized strain relief to power cord entry hole. Bring power cord through strain relief.
6. Connect power cord as follows:
7. Attach ground wire of power cord with the green ground screw (hole above strain relief bracket). Tighten all terminal block screws (3) completely.
8. Properly secure power cord to strain relief.
9. Reinstall the cover.
A. Connect the 2 hot lines to the outer screws of the terminal block (marked L1 and L2). B. Connect the neutral (white) line to the center of the terminal block (marked N).
WARNING: NEVER LEAVE THE
COVER OFF OF THE TERMINAL BLOCK.
CONNECTING DRYER USING 3-WIRE CONNECTION
IF REQUIRED, BY LOCAL CODE, INSTALL EXTERNAL GROUND (NOT PROVIDED) TO GROUNDED METAL, COLD WATER PIPE, OR OTHER ESTABLISHED GROUND DETERMINED BY A QUALIFIED ELECTRICIAN.
GREEN GROUND SCREW
SCREWS (3)
GROUND STRAP
HOT WIRE
L1
L2
STRAIN RELIEF BRACKET
3/4", UL RECOGNIZED STRAIN RELIEF
3 EXHAUST INFORMATION
WARNING - IN CANADA AND IN THE UNITED
STATES, THE REQUIRED EXHAUST DUCT DIAMETER
IS 4 IN (102mm). DO NOT USE DUCT LONGER THAN SPECIFIED IN THE EXHAUST LENGTH TABLE.
Using exhaust longer than specified length will:
The correct exhaust installation is YOUR RESPONSIBILITY. Problems due to incorrect installation are not covered by the warranty.
Remove and discard existing plastic or metal foil transition duct and replace with UL listed transition duct.
The MAXIMUM ALLOWABLE duct length and number of bends of the exhaust system depends upon the type of duct, number of turns, the type of exhaust hood (wall cap), and all conditions noted below. The maximum duct length for rigid metal duct is shown in the table below.
• Increase the drying times and the energy cost.
• Reduce the dryer life.
• Accumulate lint, creating a potential fire hazard.
EXHAUST LENGTH
RECOMMENDED MAXIMUM LENGTH
Exhaust Hood Types
Use only for short
No. of 90º
Elbows
0 1 2 3 4
Recommended
4" DIA.
4"
Rigid
Metal
90 Feet 60 Feet 45 Feet 35 Feet 25 Feet
4" DIA.
run installations
4" DIA.
2-1/2"
Rigid
Metal
60 Feet 45 Feet 35 Feet 25 Feet 15 Feet
NEUTRAL (White)
COVER
1. Turn off the circuit breaker(s) (30 amp) or remove the dryer’s circuit fuse at the electrical box.
2. Be sure the dryer cord is unplugged from the wall.
3. Remove the power cord cover located at the lower back.
4. Install 3/4 in. UL recognized strain relief to power cord entry hole. Bring power cord through strain relief.
5. Connect power cord as follows: A. Connect the 2 hot lines to the outer screws of the
terminal block (marked L1 and L2).
B. Connect the neutral (white) line to the center of
the terminal block (marked N).
6. Be sure ground strap is connected to neutral (center)
terminal of block and to green ground screw on cabinet rear. Tighten all terminal block screws (3) completely.
7. Properly secure power cord to strain relief.
8. Reinstall the cover.
3 #10 AWG MINIMUM COPPER CONDUCTORS OR 120/240V 30A POWER SUPPLY CORD KIT MARKED FOR USE WITH DRYERS & PROVIDED WITH CLOSED LOOP OR SPADE TERMINALS WITH UPTURNED ENDS (NOT SUPPLIED).
HOT WIRE
WARNING: NEVER LEAVE THE
COVER OFF OF THE TERMINAL BLOCK.
HOOD OR WALL CAP
EXHAUST SYSTEM CHECK LIST
• Terminate in a manner to prevent back drafts or entry of birds or other wildlife.
• Termination should present minimal resistance to the exhaust air flow and should require little or no maintenance to prevent clogging.
Never install a screen in or over the exhaust duct.
• Wall caps must be installed at least 12 in. above ground level or any other obstruction with the opening pointed down.
SEPARATION OF TURNS
For best performance, separate all turns by at least 4 ft. of straight duct, including distance between last turn and exhaust hood.
TURNS OTHER THAN 90º
• One turn of 45º or less may be ignored.
• Two 45º turns should be treated as one 90º turn.
• Each turn over 45º should be treated as one 90º turn.
SEALING OF JOI NTS
• All joints should be tight to avoid leaks. The male end of each section of duct must point away from the dryer.
• Do not assemble the ductwork with fasteners that extend into the duct. They will serve as a collection point for lint.
• Duct joints can be made air and moisture-tight by wrapping the overlapped joints with duct tape.
• Horizontal runs should slope down toward the outdoors ½ inch per foot
INSULATION
Duct work that runs through an unheated area or is near air conditioning should be insulated to reduce condensation and lint build-up.
3
This could cause lint build up.
Installation Instructions
4 EXHAUST CONNECTION
WARNING - TO REDUCE THE RISK
OF FIRE OR PERSONAL INJURY:
This clothes dryer must be exhausted to the outdoors.
Use only 4” rigid metal ducting for the home exhaust
duct.
Use only 4” rigid metal or UL-listed flexible metal
(semi-rigid or foil-type) duct to connect the dryer to the home exhaust duct. It must be installed in accordance with the instructions found in “Connecting The Dryer To House Vent” on page 5 of this manual.
Do not terminate exhaust in a chimney, a wall, a
ceiling, gas vent, crawl space, attic, under an enclosed floor, or in any other concealed space of a building. The accumulated lint could create a fire hazard.
Never terminate the exhaust into a common duct with
a kitchen exhaust system. A combination of grease and lint creates a potential fire hazard.
Do not use duct longer than specified in the exhaust
length table. Longer ducts can accumulate lint, creating a potential fire hazard.
Never install a screen in or over the exhaust duct. This
will cause lint to accumulate, creating a potential fire hazard.
Do not assemble ductwork with any fasteners that
extend into the duct. These fasteners can accumulate lint, creating a potential fire hazard.
Do not obstruct incoming or exhausted air.
Provide an access for inspection and cleaning of the
exhaust system, especially at turns and joints. Exhaust system shall be inspected and cleaned at least once a year.
THIS DRYER COMES READY FOR REAR EXHAUSTING. IF SPACE IS LIMITED, USE THE INSTRUCTIONS IN SECTION 9 TO EXHAUST DIRECTLY FROM THE SIDES OR BOTTOM OF THE CABINET.
STANDARD REAR EXHAUST
(Vented at floor level)
STANDARD REAR EXHAUST
(Vented above floor level)
ELBOW HIGHLY RECOMMENDED
RECOMMENDED CONFIGURATION TO MINIMIZE EXHAUST BLOCKAGE.
ELBOW HIGHLY RECOMMENDED
NOTE: ELBOWS WILL PREVENT DUCT KINKING AND COLLAPSING.
5 LEVELING AND STABILIZING YOUR DRYER
STAND THE DRYER UPRIGHT NEAR THE FINAL LOCATION AND ADJUST THE 4 LEVELING LEGS, AT THE CORNERS, TO ENSURE THAT THE DRYER IS LEVEL FROM SIDE TO SIDE AND FRONT TO REAR.
LEVEL FRONT-TO-BACK.
LEVEL SIDE-TO-SIDE.
FOR STRAIGHT LINE INSTALLATION, CONNECT THE DRYER EXHAUST TO THE EXTERNAL EXHAUST HOOD USING DUCT TAPE OR CLAMP.
EXTERNAL DUCT OPENING
DUCT TAPE OR DUCT CLAMP
4" METAL DUCT (CUT TO PROPER LENGTH)
NOTE: WE STRONGLY RECOMMEND SOLID METAL EXHAUST DUCTING. HOWEVER, IF FLEXIBLE DUCTING IS USED IT NOT PLASTIC.
DUCT TAPE OR DUCT CLAMP
MUST BE UL-LISTED METAL
4 LEVELING LEGS
4
Installation Instructions, Indoor Exhausting
DO NOT USE EXCESSIVE EXHAUST LENGTH
DON’T
CONNECTING THE DRYER
TO HOUSE VENT
RIGID METAL TRANSITION DUCT
For best drying performance, a rigid metal transition
duct is recommended.
Rigid metal transitions ducts reduce the risk of crush-
ing and kinking.
UL-LISTED FLEXIBLE METAL (SEMI-RIGID) TRANSITION DUCT
If rigid metal duct cannot be used, then UL-listed
flexible metal (semi-rigid) ducting can be used (Kit WX08X10077).
Never install flexible metal duct in walls, ceilings, floors
or other enclosed spaces.
Total length of flexible metal duct should not exceed 8
feet (2.4m).
For many applications, installing elbows at both the
dryer and the wall is highly recommended (see illustra­tions below). Elbows allow the dryer to sit close to the wall without kinking and or crushing the transition duct, maximizing drying performance.
Avoid resting the duct on sharp objects.
UL-LISTED FLEXIBLE METAL (FOIL-TYPE) TRANSITION DUCT
In special installations, it may be necessary to connect
the dryer to the house vent using a flexible metal (foil­type) duct. A UL-listed flexible metal (foil-type)duct may be used ONLY in installations where rigid metal or flexible metal (semi-rigid) ducting cannot be used AND where a 4" diameter can be maintained throughout the entire length of the transition duct.
In Canada and the United States, only the flexible
metal(foil-type) ducts that comply with the “Outline for Clothes Dryer Transition Duct Subject 2158A” shall be used.
Never install flexible metal duct in walls, ceilings, floors
or other enclosed spaces.
Total length of flexible metal duct should not exceed 8
feet (2.4m).
Avoid resting the duct on sharp objects.
For best drying performance:
1. Slide one end of the duct over the clothes dryer
outlet pipe.
2. Secure the duct with a clamp.
3. With the dryer in its permanent position, extend the duct to its full length. Allow 2” of duct to overlap the exhaust pipe. Cut off and remove excess duct. Keep the duct as straight as possible for maximum airflow.
4. Secure the duct to the exhaust pipe with the other clamp.
DO
ELBOW HIGH RECOMMENDED
ELBOWS HIGH RECOMMENDED
DO NOT SIT DRYER ON FLEXIBLE EXHAUST.
6
ALCOVE OR CLOSET INSTALLATION
6
ALCOVE OR CLOSET INSTALLATION
• If your dryer is approved for installation in an alcove or closet, it will be stated on a label on the dryer back.
• The dryer MUST be vented to the outdoors. See the EXHAUST INFORMATION sections 3 & 4.
• Minimum clearance between dryer cabinet and adjacent walls or other surfaces is:
0 in. either side 3 in. front and rear
• Minimum vertical space from floor to overhead cabinets, ceiling, etc. is 52 in.
• Closet doors must be louvered or otherwise ventilated and must contain a minimum of 60 sq. in. of open area equally
distributed. If the closet contains both a washer and a
dryer, doors must contain a minimum of 120 sq. in. of open
area equally distributed.
7
BATHROOM OR BEDROOM
DO NOT CRUSH FLEXIBLE EXHAUST AGAINST WALL.
INSTALLATION
• The dryer MU ST be vented to the outdoors. See EXHAUST INFORMATION section 3 & 4.
• The installation must conform with local codes or, in the absence of local codes, with the NATIONAL ELECTRI-
CA L CODE, ANSI/NFPA NO. 70.
8
MOBILE OR MANUFACTURED
HOME INSTALLATION
• Installation must conform to the MANUFACTURED HOME CONSTRUCTION & SAFETY STANDARD,
TITLE 24, PART 32-80 or, when such standard is not applicable, with AMERICAN NATIONAL STANDARD
FOR MOBILE HOME, ANSI/NFPA NO. 501B.
• The dryer MUST be vented to the outdoors with the
termination securely fastened to the mobile home structure. (See EXHAUST INFORMATION section 3 & 4.)
• The vent MUST NOT be terminated beneath a mobile or
manufactured home.
• The vent duct material MUST BE METAL.
• Do not use sheet metal screws or other fastening devices
which extend into the interior of the exhaust vent.
• See section 2 for electrical connection information.
5
Installation Instructions
9 DRYER EXHAUST TO RIGHT, LEFT OR BOTTOM CABINET
WARNING - BEFORE PERFORMING THIS EXHAUST INSTALLATION, BE SURE TO DISCONNECT THE DRYER FROM ITS ELECTRICAL SUPPLY. PROTECT YOUR HANDS AND ARMS FROM SHARP EDGES WHEN WORKING INSIDE THE CABINET. BE SURE TO WEAR GLOVES
REMOVE SCREW AND SAVE.
REMOVE DESIRED KNOCKOUT (ONE ONLY).
Detach and remove the bottom, right or left side knockout as desired. Remove the screw inside the dryer exhaust duct and save. Pull the duct out of the dryer.
FIXING HOLE
ADDING NEW DUCT
FIXING HOLE
PORTION "A"
RIGHT OR LEFT SIDE EXHAUST
Reconnect the cut portion (A) of the duct to the blower housing. Make sure that the shortened duct is aligned with the tab in the base. Use the screw saved previously to secure the duct in place through the tab on the appliance base.
ADDING ELBOW AND DUCT FOR EXHAUST TO LEFT OR RIGHT SIDE OF CABINET
• Preassemble 4" elbow with 4" duct. Wrap duct tape around joint.
• Insert duct assembly, elbow first, through the side opening and connect the elbow to the dryer internal duct.
CAUTION: Be sure not to pull or damage the electrical wires inside the dryer
when inserting the duct.
AB
9"
Cut the duct as shown and keep portion A.
TAB LOCATION
BEND TAB
o
UP 45
Through the rear opening, locate the tab in the middle of the appliance base. Lift the tab to about 45º using a flat blade screwdriver.
EXHAUST CAN BE ADDED TO LEFT OR RIGHT SIDE
• Apply duct tape as shown on the joint between the dryer internal duct and the elbow.
DUCT TAPE
CAUTION: Internal duct joints must be secured with tape, otherwise they may separate and cause
6
a safety hazard.
DUCT TAPE
Installation Instructions
ADDING ELBOW FOR EXHAUST THROUGH BOTTOM OF CABINET
• Insert the elbow through the rear opening and connect it to the dryer internal duct.
• Apply duct tape on the joint between the dryer internal duct and elbow, as shown on page 6.
CAUTION: Internal duct joints must be secured with tape, otherwise they may separate and cause a safety hazard.
ADDING COVER PLATE TO REAR OF CABINET (SIDES AND BOTTOM EXHAUST)
10 CHANGING DIRECTION OF DOOR OPENING
1. Open the door and remove the filler plugs opposite the hinges. With the door completely open, remove the bottom screws from each hinge on the dryer face. Insert
these screws about half way into the TOP holes, for each hinge on the opposite side (where you removed the filler plugs). Apply firm pressure to get the screw started.
2. Loosen the top screws from each hinge on the dryer face half way. With one hand holding the top of the door and the other hand holding the bottom, remove the door from the dryer by lifting it UP and OUT.
3. Rotate the door 180º. Insert the door on the opposite side of the opening by moving the door IN and DOWN until the top hinge and the bottom hinge are resting on the top screws inserted in step 1.
4. Remove the remaining screws from the side of the opening from which the door was removed. With these screws secure each hinge at the bottom. Tighten the two top screws on each hinge. Reinsert the plastic plugs on the side from which the door was removed.
REMOVE THE
BOTTOM SCREW
FROM EACH HINGE
ON THE DRYER
FACE.
LOOSEN THE TOP SCREWS FROM EACH HINGE ON THE DRYER FACE HALF WAY.
PLATE (KIT WE1M454)
Connect standard metal elbows and ducts to complete the exhaust system. Cover back opening with a plate (Kit WE1M454) available from your local service provider. Place dryer in final location.
WARNING - NEVER LEAVE THE BACK
OPENING WITHOUT THE PLATE.
500A436P001_Rev0
(Kit WE1M454)
Pub # 31-16220
MOVE THE DOOR IN AND DOWN UNTIL THE TOP HINGE
AND THE BOTTOM HINGE ARE RESTING ON THE TOP SCREWS INSERTED IN STEP 1.
SECURE EACH HINGE AT THE BOTTOM AND TIGHTEN THE TWO TOP SCREWS OF EACH HINGE.
11 SERVICING
WARNING - LABEL ALL WIRES PRIOR TO DISCONNECTING WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION AFTER SERVICING/INST ALLATION.
For servicing phone numbers for replacement parts, and other information, refer to Owner’s Manual or visit our Web site.
7
Notes
Loading...