
iNTRODUCTION
APPLICATION
RATINGS
Contacts
OPERATINO
PRINCIPLES
CHARACTERISTICS
Pickup
Operating
Time
Burden
CALCULATION
OF
CONSTRUCTION
RECEIVING,
ACCEPTANCE
Visual
HANDLING
TESTS
Inspection
Mechanical
Electrical
iNSTALLATION
Relay
PROCEDURE
Settings
Mechanical
Electrical
EQUIPMENT
PORTABLE
TEST
SERVICING
Restraint
Circuit
Directional
Maximum
Torque
Pickup
Clutch
RENEWAL
Adjustment
PARTS
SETTINGS
AND
Inspection
Tests
Checks
Checks
Characteristic
Angle
STORAGE
Angle
Adjustment
GEK-26423
NTS
E
CONT
PAGE
3
3
4
4
5
5
6
6
6
7
9
9
10
10
10
10
11
11
11
11
11
14
15
15
15
15
15
16
MINIMUM
Zero
No
With
MAXIMUM
No
Zero
MAXIMUM
With
PERMISSIBLE
Sequence
Sequence
Zero
PERMISSIBLE
Sequence
PERMISSIBLE
Sequence
Zero
REACH
Current
Current
REACH
Current
REACH
Current
SETTING
Compensation
Compensation
SETTING
Compensation
SETTING
Compensation
FOR
FOR
FUR
THE
THE
THE
APPENDIX
CEYG51A
APPENDIX
CEYGS1A
APPENDIX
CEYGS1A
I
17
17
18
II
18
18
III
20
20
2

GEK-26423
The
consists
target
reach
a
and
characteristic
first-zone
comparison
The
missive
tion.
The
faults.
be
will
ground
also
will
faults
any
The
tion.
sequence
zero
phase
to
unit
niho
minimum
In
terminal.
against
trip
and
sequence
the
on
coordinate
must
should
carrier
In
minal.
protected
The
length
required
reach
the
proper
ditions
mho
unit
minimizes
pedance
CEYGS1IX
three
of
seal-in
relay.
and
CEYG51A
overreaching
ground
this
To
high
quite
faults.
respond
not
ground
A
tapped
current
ground
reach
permissible
directional
These
single
all
internal
for
current
carrier
set
be
as
signal
permissive
acts
It
line
choice
system
and
coverage.
on
or
reach
its
present
three
a
is
single-phase
unit
of
The
transferred
ground
transferred
units
rnho
they
end
and
this
For
to
involving
units
mho
auxiliary
faults
considerably
is
reach
comparison
relays
phase
compensation
starting
will
sensitively
block
will
overreaching
a
as
section.
whether
of
conditions.
be
may
swings.
power
setting
response
from
phase,
provides
the
CEYG51A
relay
tripping
relay
mho
the
of
are
relay
the
reason,
phase
three
ground
provided
are
current
compensation
on
as
settings
operate
ground
to
faults
while
units.
operating
be
as
tripping.
combined
or
2
about
then
This
approximately
to
load
to
parallel
a
high
units
indication
relay
specifically
waS
schemes.
applied
is
tripping
CEYG5IA
supplied
will
these
faults.
simply
transformer
is
phase
three
foreshortened
under
schemes,
conjunction
in
faults
the
used
is
This
on
possible.
transferred
transferred
to
not
When
3
to
tends
use
The
or
power
line.
speed,
in
with
have
by
with
used,
on
will
the
use
zero
times
to
of
GROUND
one
has
schemes,
relay
units
If
adding
faults.
both
two
in
other
the
facilitate
same
trip
sequence
sequence
the
make
zero
1.25
swings.
DISTANCE
CEYG51A
INTRODUCTION
single
L2—D
case
of
operation
been
not
designed
Figure
APPL
the
primary
as
employing
specifically
are
quadrature
operating
high
a
not
are
is
this
non—directional
a
separate
used
is
the
ground
If
single
on
conditions.
CEYG51A
relays
with
protected
the
initiates
carrier
torque
will
This
tripping
initiating
current
current
positive
ground
the
sequence
the
times
This
RELAY
RELAY
mho
zone,
with
facilities
for
limited
for
3
shows
CAT
ION
I
ground
voltage
provided
objectionable,
current
obtain
to
unit
iiho
sequence
zero
phase
connected
a
carrier
line
carrier
stopping
the
unit
level,
to
tend
schemes,
and
compensation
compensation
sequence
mho
current
positive
true
is
type,
three
all
to
the
use
as
the
internal
relay
separate
designed
polarization.
torque
with
circuits
the
has
ground
to
channel
section.
blocking
tripping
and
settings
any
in
increase
CEYG51A
one
permissive
a
impedance
more
unit
compensation
sequence
provided
directional
for
testing
distance
point
an
overreaching
connections.
directional
in
primary
detect
to
level
even
memory
zero
the
for
proper
action.
relay
sequence
zero
ratio
essentially
compensation
faults.
back—to-back
provide
to
One
external
on
units,
insure
and
event,
the
security
relay
relay
depends
NOT
is
of
sensitive
impedance
there
units.
where
and
Thus,
on
can
sequence
relay
carrier
since
is
upon
used,
the
reduces
is
distance
one
is
it
device
separate
single
the
very
These
made
be
fault
compensation.
of
same
the
NOT
is
Appendix
See
required
are
high
acts
faults.
should
it
that
the
required
ground
for
the
the
line
operation
to
the
of
little
ground
unit
atatime.
The
suitable
in
comparison
backup
phase
polarizing
close
ground
unresponsive
detector.
current
reach
used,
speed
to
both
starting
presence
at
protected
ground
order
in
necessary
the
line
no
or
relay.
transient
for
directional
to
line
in
niho
compensa
on
ground
the
for
I
each
at
protection
carrier
Stop
zero
if
be
also
units
unit
each
faults
mho
to
on
and,
mutual
use
and
protec
ground
voltage
to
units
When
single
the
used
that
a
of
ter
in
line
unit
provide
load
ground
thus,
im
It
One
over
as
per
to
the
con
eeerc
furtn-r
tn
These
poss:ble
information
purchaser’s
To
he
:ot
sucn
nstroctions
contanJencj
purposes,
extent
-scranc.
be
,eau:red
do
desired
s
not
to
the
;iven
the
purport
be
or
matter
met
should
products
with
to
in
should
respect
cover
connection
particular
be
descrrhed
to
all
referred
local
details
with
problems
herein
installation,
to
codes
the
meet
or
arise
and
variations
which
General
applicable
ordinances
in
operation
are
Electric
?.ESI,
equipment
not
because
or
maintenance.
covorci
Ccmpant.
IEEE
he;
and
nor
sufficientlq
.S1IMA
varo
to
provide
standards;
rcatly.
For
Should
for

0.3
normally
The
amperes
closed
in
non—inductive
contacts
circuits
between
up
terminals
250V
to
GEK-26423
and
19
DC.
20
will
close,
carry
continuously,
or
interrupt
inhu
The
Fig.
with
6)
phase-to-phase
polarizing
tdye
vol
in
izing
the
The
of
rear
flux
torque
following
where:
type
schematic
flux.
the
pole,
produce
to
equation:
Ebc’
units
voltage
flux
The
protected
which
operating
balance
the
at
Torque
design
K
Phase—A-to-neutral
=
Phase
=
Phase
=
‘a
Angle
=
B
Restraint
=
T
Angle
=
CEYGS1A
the
in
connections
in
quadrature
in
phase,
energized
is
0
=
constant
to
B
current,
A
by
by
relay
shown
as
with
front
the
interacts
by
torque.
point
for
KIaEbc
=
PhaseCvoltage
at
Ea
setting
‘a
leads
which
tap
which
OPERATING
are
in
Fig.
the
phase-to—neutral
which
pole,
the
the
the
with
line
phaseAstarting
((
COS
voltage
relay
the
Ebc’
leads
Ebc
PRINCIPLES
of
the
3.
is
polarizing
current
-30)
the
at
(Eb
location
(900
four-pole
The
energized
—
TEEb’
relay
E)
-
for
of
balanced
induction-cylinder
two
side
voltage
by
flux
the
protected
can,
unit
sin
location
at
the
poles,
percentage
a
to
produce
B
relay
3-phase
which
the
of
phase,
therefore,
are
protected
of
restraint
interacts
be
(1)
condition)
construction
energized
phase,
the
phase-to-neutral
torque.
with
expressed
(see
the
by
produce
The
the
the
by
the
flux
polar
The
impedance
rather
The
diameter
current
line
there
maximum
this
voltage
The
which
compensated
not
special
positive
the
selecting
The
applied
tap
the
operating
specific
inho
passing
essentially
is
by
diameter
would
case
ohmic
to
block.
diagram
as
fault
characteristics
has
unit
through
for
(Ia
torque
600,
which
of
be
is
it
single-phase—to-ground
of
basic
the
sequence
reach
a
setting.
reach
restraint
the
Ohmic
shown
conditions
circular
a
example)
phase
no
angle
is
the
not
impedance
the
of
Fig.
in
origin
the
leads
shift
(i.e.
condition
the
impedance
minimum
accurate
an
mho
circuit,
ReQch
of
the
7.
described
characteristic
defines
the
in
maximum
circle
reach
distance
the
to
can
unit
that
2
=
Tap
E
CHARACTER
mho
units
should
It
below:
the
quadrature
the
line—to—neutral
reach
represented
would
with
the
faults
fault.
extended
be
by
is
setting
(Zi)
Setting
in
be
which
angle
polarizing
angle)
in
nomally
tap
E
measuring
where
Instructions
100
()
1ST
the
noted
passes
of
occurs
Fig.
be
leads
zero-sequence
the
reducing
by
the
1
CS
CEYG51A
that
through
maximum
voltage
voltage
when
8.
considered
on
until
are
tap
E
2
(5)
represented
be
may
relay
these
steady-state
torque
the
origin
of
(Ebc
the
for
of
unit,
example)
forasingle-phase-to-ground
current
line
the
ohmic
the
100
except
given
the
leads
as
percent.
on
impedance
in
percentage
on
However,
3-phase
Appendices
of
lower
a
to
characteristics
R-X
the
which
by
the
lags
reach
if
faults,
fault
the
and
II
fault
the
percentaoe
R—X
the
on
are
diagram.
occurs
30°.
when
Since
fault,
phase—to-neutral
unit,
the
of
niho
for
unit
the
equal
is
for
the
or
III
voltage
position
for
The
is
to
on
5

The
(600).
equation
from
PICKUP
The
ufficient
for
mum
percent
On
result
percent
current
ohmic
reduced
The
operating
magnitude
fault
voltage
by
(5)
currents
with
reach
cos
torque
to
which
currents
obtained
reach
MINIMUM
REACH
(0-N
0.5
1.5
single-phase-to-ground
will
relay
the
that
restraint
for
the
voltage
3-ohm
minimum
from
line
at
(60-0)
will
overcome
lag
OHMIC
SETTING
OHMS)
1
2
3
operate
and
close
as
faults
120
reach
equation
angles
where
the
restraint
the
unity
the
tabulated
at
volts
setting.
(5)
other
is
the
0
contacts
power
below:
quadrature
the
considerably
polarizing
GE
K—2
assumes
than
line
when
torque.
factor
CURRENT
64
23
that
600
can
angle.
the
The
position
polarizing
current
less
unit
the
line
be
fault
operating
RANGE
will
angle
obtained
current
by
FOR
36
18-60
12
9
6
potential
than
operate
maximum
and
multiplying
by
is
torque
degrees
60
RELIABLE
60
-
60
—
60
-
60
-
will
tabulated.
with
certiri
in
a
3-phase
on
and
OPERATION
remain
less
torque
is
For
than
angle
reach
the
direction
faults
reliable
quite
example,
ampere
1
high
are
obtained
is
down
with
with
equal
of
and
maxi
a
one
to
the
one
a
operating
OPERATING
typical
For
BURDEN
burden
The
percent
100
at
Basic
Ohms
1
0.5
1
the
I-f
equation:
where
TIME
30
-
15
-
30
-
restraint
Watts
VARS
T
operating
imposed
as
is
Rated
Freq
Restraint
Restraint
=
Tap
given
60
60
50
tap
VA
on
in
time
the
below:
reduced,
is
Watts
=
circuit
circuit
percent.
characteristics
potential
Polarizing
V
120
120
120
Watts
10.1
10.1
8.41
the
*(2
watts
Vars
see
transformers
Circuit
Vars
burden
+
.
table
from
table
from
Figure
by
8.88
8.88
7.38
of
the
VARS(i”)
above.
above.
13A
type
the
VA
13.5
13.5
11.2
restraint
and
CEYG51A
circuit
138.
Volts
70
70
70
relay
Restraint
Watts
2.7
0.9
1.7
given
is
with
the
Circuit
by
Vars
4.0
1.6
3.0
the
restraint
following
VA
4.8
1.8
3.4
tap
set
6

The
burdens
imposed
on
the
current
transformers
GEK-26423
the
by
current
circuits
are
given
below:
quently
be
followed
Basic
Ohms
1-3D
0.5
1
NOTE:
applying
In
do
Determimimme
1.
the
line
Determine
2.
relay
a.
b.
c.
following
The
Consider
-
15
-
30
Above
for
materialize.
not
determine
to
necessary
power
terminal.
When
further
When
further
no
neither
If
determine
lay,
the
Rated
Freq.
data
the
the
relay
if
zero
loadings
if
there
zero
evaluation
zero
Type
calculations
protected
60
60
50
is
lower
to
what
sequence
unit
rnho
and
is
sequence
sequence
evaluation
nor
a
if
it
CFPH16A.
line
3-4,
I
5
5
5
for
the
reach
particular
a
Therefore,
final
tap
power
limitation
a
current
need
current
above
b
is
necessary
are
to
5-6,
0.070
0.007
0.058
mho
settings
tap
calculations
current
settings
swings.
compensation
made.
be
compensation
be
need
is
made
between
be
7-8
or
Circuit
X
0.040
0.005 0.008
0.033
units set
on
will
CALCULATION
line
and
system,
recommended
it
is
maybenecessary
compensation
and
the
Appendix
See
application
the
in
Appendix
See
made. See
applicable,
use
an
the zero
example
to
as
breakers
their
be
less
SETTINGS
OF
is
relation
is
t.{Qi
is
used:
Appendix
evaluate
of
A
2
0.080
0.067
maximum
than
the
limitations
the
that
required.
the
of
equations
I,
for
used:
equations
II,
if
III,
the
sequence
determining
and
B
on
1
5
5
5
ohmic
the
initial
and
This
resulting
incorrect
if
Co
(3K
equations
equations
directional
the
0.210
0.021
0.175
tabulated
how
‘b
is
ha,
+
1)
actual
the
portion
Circuit
9-10
R
reach
taps.
burdens.
outlined
calculations
the
relay
will
depend
mho
and
I.
operation
equal
hib
equal to
Co
is
lIla,
of
either
overcurrent
tap
of
X
0.120
0.013
0.100
The
under
of
may
be
upon
characteristic
on
or
less
to
tIc.
and
and
hlIb
Appendix
settings
system
a
Z
0.240
0.024
0.200
burden
APPLICATION
and
2
1
applied.
evaluation
on
with
than
less
behind
C,
than
faults
or
Ihic.
II
or
supervising
be
to
in
shown
fre
below
no
III
used.
Fig.
of
the
the
C,
to
re
5.
Assume
Checking
breaker
the
Z
1
CT
Ratio
PT
Ratio
Secondary
=
21
Z0’
=
Zom
Appendix
detect
A
to
following
=
24.0
=
72.0
14.4
600/5
1200/1
Ohms
2.4
/79°
/75°
7.2
/75°
1.4
a
characteristics:
/790
/750
/75°
=
CT
PT
=
0.47
=
1.9
=
0.36+jI.35
first
I
single
primary
primary
primary
Ratio
Ratio
to
phase
ohms
ohms
Primary
x
+
j2.36
+
j6.95
establish
to
ohms
secondary
secondary
secondary
ground
Ohms
the
fault
ohms
ohms
ohms
maximum
(F2)
7
tap
at
setting
the
remote
that
bus,
would
Equation
still
permit
should
lb
the
CEYG5IA
used.
be
at

GEK-26423
Since
tap
the
Since
setting
remote
These
the
If
tings
be
at
carrier
the
terminal
set
be
setting.
reach
Thus,
setting
should
terminal.
application
of
least
as
In
any
setting
If
zero
we
all
the
61
the
same
carrier
the
1.25
starting
and
they
sensitively
case,
Thus,
as
sequence
obtain.
values
for
this
percent
used.
be
Thus,
calculations
for
is
starting
times
relay
will,
as
ALWAYS
carrier
the
tripping
the
current
of
T
application.
setting
is
It
50
for
T
=
Set
should
directional
the
setting
at
therefore,
possible.
the
set
start
K
the
in
above
will
desirable
percent
61
41
40
on
tap
be
CEYG51A
of
rear
the
coordinate
relays
CEYG51A
CEYG51A
compensation
-
6.95
=
3(2.36)
table
Thus,
insure
the
that
to
set
additional
percent
percent
repeated
comparison
relays
the
at
tripping
terminal
must
that
relay
at
relay
used,
is
2.36
= =
are
relays
the
the
reach
the
for
carrier,
both
relay
will
properly.
coordinate
terminal
at
terminal
equation
4.59
7.08
negative,
maybeset
relay
relay
the
relays
terminals.
outreach
A.
0.65
to
it
at
In
these
will
reach
restraint
at
will
the
remote
the
any
event
with
should
B
should
Ic
per
in
reach
at
the
also
The
carrier
each
unit
equations
range
the
only
least
setting
tap
remote
necessary
be
carrier
terminal.
tripping
carrier
the
other
set
be
be
used
impose
of
the
to
25to50
should
of
end
start
This
starting
the
on
the
with
instead
no
restrictions
10to61
remote
percent
be:
line
the
determine
to
settings
relay
will
at
relay
basic
same
same
equation
of
percent.
bus,
at
insure
the
units
basic
a
lower
beyond
terminal
the
remote
should
minimum
minimum
on
the
B.
set
should
that
tap
lb.
For
maximum
the
The
associated
restraint
details
tion
The
cradle
the
plug
is
case
can
attaches
the
vent
Outline
These
protect
transit.
transportation
the
Reasonable
immediately,
metallic
and
is
cover
ground
the
safe
CEYG51A
Type
tapped
circuits
of
components
locked
block
and
inserted
be
the
to
from
cover
and
relays,
against
them
injury
If
care
they
chips.
removed
fault
setting
reach
relay
autotransformer
adjustment
for
relay.
the
mounted
are
case
the
in
cradle
place
in
from
case
being
drilling
panel
not
when
damage.
damage
or
company
should
should
Foreign
cause
and
=
T
immediately
F2
consists
Internal
by
block
the
replaced
included
and
be
stored
be
matter
trouble
0.33K
using
when
of
for
of
angle
connections
a
cradle
on
means
completed
are
connection
the
of
front
and
until
dimensions
RECEIVING,
as
Immediately
resulting
promptly
exercised
in
collected
in
0.33
=
behind
zero
three
controlling
and
assembly
latches
of
includes
the
are
part
a
upon
from
notify
unpacking
in
original
their
operation
the
300=99
x
the
sequence
percent
relay,
current
CONSTRUCTION
reach
of
4—pole
and
minimum
relay
the
inho—type,
basic
which
the
at
through
plig
the
connection
shown
a
to
target
in
top
removable
permit
plug
Figure
HANDLING
control
a
of
receipt
rough
the
of
handling
nearest
the
cartons
outside
the
on
the
of
use
adjustable
can
and
reset
AND
panel,
a
General
relay.
relay.
equation
the
compensation.
induction
ohmic
shown
are
easily
be
bottom.
connection
testing
mechanism
been
has
15.
STORAGE
will
relay,
evident,
is
If
a
place
in
of
the
resistors
reach.
the
inserted.
be
examine
Electric
the
case
of
cylinder
Figures
Figure
in
removed
electrical
The
plug.
relay
and
shipped
it
a
file
Apparatus
relays
that
find
may
Appendix
units.
in
3.
from
in
an
in
any
for
damage
are
is
free
its
III
Each
polarizing
the
and2show
1
relay
the
connections
separate
A
case.
its
interlock
cartons
damage
claim
Sales
not
to
from
way
calculate
to
unit
case.
testing
The
armtopre
designed
ststained
once
at
Office.
installed
be
moisture,
inside
has
and
construc
between
cover
with
dust,
when
an
The
to
in
the
9

GE
K-
TABLE
26423
III
Set
should
unit
3.
connections
amperes,
for
5
With
unit
the
of
contact
bisector
the
at
the
unit
The
operating
4.
percent
+14
set
and
at
with
100
voltage
Table
in
phase
the
phase
the
remain
Maximum
shown
the
phase
will
just
to
left
maximum
current
Pickup
of
percent
relay
the
30
by
IV.
angle
shifter
Torque
in
with
be
open.
of
contact
torque
leads
Check
the
degrees,
Resistor
of
OHMIC
SETTING
TAP
0.5
1.0
1.5
2.0
3.0
from
open
Angle
Figure
polarizing
shifter
closed.
These
the
angle
just
angle
the
-
The
minimum
and
the
connected
check
R11-R12-R
13
restraint
the
REACH
that
so
zero
-
10,
set
Next
are
between
opens
(110
of
polarizing
following
reach
voltage
as
that
the
to
The
but
voltage
that
so
find
the
at
310)
+
the
as
shown
the
circuit
current
amperes.
60
maximum
with
at
operating
the
zero
the
1100
210°,
=
units
voltage
check
given
adjusted
in
current
should
torque
the
120
angles
torque
two
and
should
is
on
for
Figure
not
the
leads
tap
E
volts.
zero
3100.
ie
for
to
the
the
10.
required
be
same
MINIMUM
AMPERES
32
16
12
8
6
the
angle
disconnected.
current
either
on
angles
torque
The
3Q0
lead
300
be
at
particular
a
determine
nameplate.
value
Set
to
used
to
the
as
voltage
the
of
leads
the
of
lines.
angle
lead,
that
shown
the
close
adjust
phase
by
mho—type
polarizing
side
unit.
of
unit.
the
These
in
phase
the
pickup.
angle
degrees.
210
operating
The
the
of
The
example,
For
maximum
This
+3°.
ohmic
checks
Table
shifter
contacts
of
units
voltage
300
position
maximum
torque
reach
should
IV
so
The
the
MAXIMUM
AMPERES
60
60
60
60
60
The
can
be
current
by
torque
assume
will
the
is
angle
each
of
be
for
the
current
that
within
falls
resistors
polarizing
contacts
checked
30°,
which
that
be:
unit
made
specific
are
circuit.
using
should
the
cause
position
for
which
by
is
with
ohmic
leads
the
used
each
of
be
left
the
particular
a
witin
the
range
to
the
set
contact
will
the
E
range
shown
make
left
be
taps
UNIT
-N
0.5
2.0
3.0
Compensating
5.
compensating
connect
but
With
the
close
1.0
1.5
windings
the
voltage,
left
current
UNiT
E
2
contact
REACH
LINK
SETTING
Winding
between
Ml
M2
M3
tap,
0.5
1.0
1.5
2.0
3.0
circuits
of
and
edch
Check
terminals
as
phase
unit.
RESTRAINT
APPLIED
VOLTAGE
20V
25
35
35
70
-
The
9-10,
tabulated
I
•
SUD
angle
The
following
is
in
TO
3
5
7
as
set
current
TABLE
check
correct.
the
the
in
should
11
IV
POLAR.
APPLIED
VOLTAGE
120V
120
120
120
120
is
Use
following:
pickup
be
to
2
STUD
10
10
10
one
confirm
basic
the
TO
check
half
PICKUP
CURRENT
34.4
21.6
20.0
15.0-20.0
20.0
that
test
measure
(4),
the
values
45.6
—
-
28.5
-
26.6
26.6
-
relative
the
connections
listed
JUMPER
STUDS
4-9
6
8-9
the
polarity
-
9
current
in
PHASE
ANGLE
°LEAD
30°
30°
300
30°
30°
Figure
of
Table
of
required
IV.
the
10,
to

taps.
held
Refer
steps
6.
closed,
to
to
Target
Use
the
change
a
Seal-in
source
DC
can
section
the
be
Unit
with
gradually
Target
on
setting.
tap
With
—
the
increased
Seal-in
the
circuit
target
arranged
the
to
Unit
in
pickup
Settings
GEK-26423
down’
the
that
so
point.
under
unexposed
or
current
test
Pickup
INSTALLATION
position,
through
current
PROCEDURE
studs
should
check
1-11,
be
for
pickup
with
rating
tap
recommended
the
Ml
on
both
contact
less.
or
after
If
recommended
The
before
relay
vibration.
repeated
excessive
connections
SETTINGS
RELAY
Mho
1.
to
Refer
determining
reach
The
the
taps
blocks.
proper
of
MECHANICAL
Check
1.
left
the
When
reclose
and
Examine
2.
cleaned
be
surface.
use
not
Do
Operate
3.
and
make,
when
the
reset
ACCEPTANCE
the
the
that
installation.
should
shown
are
Units
section
the
mho
the
the
of
the
on
The
CHECKS
the
contact
normally
the
the
a
with
Burnishing
knives,
the
the
that
button
visual
mounted
be
The
in
unit
mho
blocks.
tap
green
movable
is
contact
burnishing
tools
files,
target
contacts
is
the
TESTS
mechanical
and
on
outline
Fig.
on
tap
units
and
and
3
CALCULATIONS
block
can
The
should
leads
contact
closed
closed
structures
by
contact
surfaces
tool,
designed
abrasive
or
seal-in
at
have
operated.
INSTALLATION
relay
vertical
a
panel
typical
AND
settings
adjusted
be
leads
red
be
and
hand
with
for
which
specially
paper
by
unit
least
is
held
inspection
surface
drilling
external
SETTINGS
for
should
connected
of
then
the
signs
consists
for
or
hand
1/32”
a
in
each
released
relay
of
cloth
and
wipe.
specific
five
tarnishing
of
cleaning
PROCEDURE
in
storage
described
location
in
a
dimensions
connections
a
for
application.
percent
connected
be
of
one
to
by
unit
the
completely
flexible
a
any
of
that
check
With
before
under
are
are
discussion
steps
the
hand.
movable
corrosion.
or
strip
contacts
relay
to
kind
the
cover
the
shipment
section
the
is
which
shown
in
shown
of
suggested
connecting
by
of
one
to
two
tap
5t
There
structure
deenergized.
metal
of
clean
target
replaced
clean
Fig.
Fig.
in
the
positions.
should
Fine
can
relay
latches
the
to
on
10
be
should
silver
with
obtained
be
contacts.
check
and
15.
4.
the
percent
before
site,
job
ACCEPTANCE
and
dry
internal
The
procedures
leads
tap
tap
noticeable
no
reset
to
contacts
etched,
an
from
contacts
the
the
that
it
is
TESTS
from
free
for
to
positions
friction.
the
should
roughened
factory.
the
target
be
the
right
resets
ELECTRICAL
Using
CHECKS
the
ACCEPTANCE
manner
The
titled
section.
up
form
SAMPLE
settings
eliminate
To
in
It
Fig.
impedance,
tested.
being
is
percent
10
nearly
very
sible
tion
to
may
provide
be
connections
test
PICKUP
-
TEST
which
in
CALCULATIONS
the
purpose
have
is
which
errors
the
for
16
is
the
5
F
and
The
percent
1
actual
the
as
the
to
made
CHECK.
reach
FOR
of
made
been
which
units
mho
switch,
fault
autotransformer
steps
line
portable
any
match
in
shown
settings
SETTINGS.
electrical
the
for
result
may
are
and
that
so
which
on
reactor
test
line.
Figure
PORTABLE
made
are
Examples
particular
a
from
recommended.
jX
+
RL
which
TA
line
the
relay
the
XL
check
10
TEST
the
on
of
in
tests
line
instrument
the
is
across
is
impedance
is
the
and
12
the
EQUIPMENT
starting
calculation
the
this
section.
inaccuracies
figure
the
In
impedance
the
RL
used.
be
to
test
relay
section
fault
jXL
+
resistor
reach
units
of
to
R
5
the
switch
may
This
with
is
of
the
+jX
5
setting
briefly
typical
check
line
be
is
enough
as
the
circuit
test
(when
section
line
and
to
made
necessary
described
discussed
settings
starting
used)
for
impedance
appear
since
taps
is
so
are
unit
shown
the
which
to
it
that
in
under
the
given
in
source
is
the
is
the
section
ohmic
schematic
relay
the
tapped
relay
not
combina
in
fea
that
pick
in