
LsURJPTION
APF’L
(Al
I
I
ON
RATINGS
OPERATING
PRINCIPLES
CHARACT[RISEILS
BURDENS
LALCULA1
UONSTRUCT
RECEIVING,
ACLEPTANCE
ASTALLATION
iON
OF
ION
HANDLING
TESTS
PROCEDURE
INSPECTION
PLRIODIC
CHECKS
SERVICING
RENEWAL
PARTS
SETTINGS
AND
AND
ROUTINE
STORAGE
MAINTENANCE
GE
K-A
5495
CONTENTS
PAGE
3
3
2
4
5
7
7
N
8
9
11
14
14
15
17
‘S.)
to
C-)
CD
to
to
“S

GE
K-4
54
95
The
designed
is
relay
testing.
dimensions
is
relay
not
been
The
itself,
relays
may
they
protection.
distance
When
that
tap
highest
Since
fault,
a
voltage
protection
The
CEYS2B
section
the
than
less
The
cycles
t
desired
the
back
A-B
as
adjust-nd
means
by
evuuj
u’ctfte’L
the
pu’tcha.ea’-
hIlt
,‘to
CEY52B
specifically
constructed
The
not
limited
C[Y52B
but
may
be
scheme
applying
will
possible
the
at
section
in
type
rating.
will
basic
of
determine
in
of
Thnie
sA6e
po
-ui1jo’tnri..tLon
Io
the
ucJi
relay
interndl
shown
are
intended
in
relay
rather
used
be
as
used
Figure
with
acconinodate
level
memory
the
relay
relay.
the
this
for
under
typical
a
entitled
percent.
25
CEY52
The
noted
be
minimum
relay
the
the
percent
one
autotransformer
utcton
con.tA,nqenc.y
pwtpoe,
oxteiit
asu.’utnce
three-phase,
is
a
use
for
three
of
connections
Figure
in
for
use
respect.
this
BASIC
TAPS
0.5
1.0
is
a
is
designed
a
step-distance
in
of
part
illustrates
4
CEX2OB
the
relay
this
the
of
torque.
action
should
not
The
contingency
CALCULATION
application.
TAPPED
covered
relay
minimum
basic
that
reach
(see
basic
steps
do
bi
de’u’,d
.‘LequL’ted
guJen
..a
MHO
TYPE
DESCRIPTION
speed,
high
the
with
single—phase
for
Typical
16.
first
a
as
MINIMUM
CEY52R
OF
-
1.0
—
-
2.0
-
three—phase,
to
be
high-speed
a
typical
CEX2OA
the
REACH
1.5
3.0
used
scheme
or
units
relay
external
function,
zone
single
with
to
pilot-relaying
external
relay.
the
the
relied
is
protection
reach
CLY52B
should
required.
SETTINGS
OF
Once
the
on
setting.
will
provide
to
be
settings
for
desired
of
be
protection
AUTO—TRANSFORMERS.
instructions
these
three
setting
Fig.
minimum
over
tap
pu.’tpo-’t-t
no.t
be
to
o.’
rnattc’t
the
the
w-tk
by
reach
basic
for
2).
setting
a
leads
met
I-touLd
p’wduc.ta
The
4/1
UL
hou.fd
‘tc.apee.t
and
minimum
each
position
range
the
on
eovciz.
-to
connec,tcon
pa.’ct
dci.eailied
adjustment
unit
of
the
tap
be
to
DiSTANCE
CEY52B
single-zone
CEX2OB
mounted
shown
are
connections
TABLE
ICATION
APPL
mho
zone
CEX2OA
a
provide
connections
given
a
of
This
be
only
supplemented
provides
have
Under
RATINGS
settings
reach
made
is
the
of
mho
any
for
blocks
detaiJs
aU
wLth
pitobfms
cithvi.
e1eived
eke4n
eode4
tocitf
RELAY
reactance
one
in
in
the
thus
I
distance
CEX208
or
zones
two
scheme
circuit,
will
effective
time-delay
worked
a
been
conditions,
no
available
is
ranges
by
two
units.
of
the
the
at
n-taitiou,
thc
to
rnec’-t
azid
directional
type
L2—D
Figure
to
transient,
SELECT
relay
in
to
insure
protection
other
by
example
calculated,
the
of
are
means
sets
The
basic
right
0L
aJLe
(cvtc’uct
appcaIit’e
icknanet’
relay.
case
10,
the
CEX
CEX2OA
CEX2OR
that
reactance
protection
of
addition
relay
the
select
that
several
for
devices
should
for
inho
listed
of
links
links,
of
ohmic
minimum
side
ope’Litu)e
wh{cJ!
with
while
relay
overreach
SHOWN
for
the
120
units
for
reach
of
aiz.C
distance
mho
See
provisions
outline
are
BELOW
is
not
type
providing
to
when
the
the
cycles
for
to
determining
taps
the
volts,
are
the
a
on
(for
of
reach
the
c2u.prnnnt
n
not
etsc
ANSI,
b1
cauc
Table
shown
characteristics
meant
relay.
against
is
it
highest
relay
after
fault
any
detect
are
restraint
5
given
mho
terminal
each
the
settings
relay.
miLtefltliIrc.
o’
cOvQYted
Conipanu.
1H
tlzoe
relay.
I.
for
panel
and
in
Figure
to
The
phase
step-distance
used
basic
operate
will
that
this
the
set
taps
amperes,
in
units.
board
unit),
inho
units
—--..____
no
IMA
a,id
oa-i
it
CEY52B
The
sirjle
drilling
used
be
combination
faults,
step-
a
in
minimum
inception
the
provides
condition
settings
described
as
ever
60
Table
Selection
located
each
can
listed
to
p4ovd
Lt?etif
ttz;
L’att’1.
WaS
phase
4.
The
have
by
or
at
be
50
or
II.
identified
be
Table
in
St(!Led
reach
the
zero
if
of
in
set
of
at
oi
OL
of
of
the
the
II
3

equation
GE
K—4
54
95
to
prove
that
the
reduces
equation
to:
defines
a
mho
characteristic
divide
both
sides
by
[2
and
transpo.e.
The
angle
MHO
UNIT
1.
setting
the
autotransformer
unit
through
unit
as
The
resulting
Ths
is
.
irec
Thus,
of
maximum
Impedance
The
impedance
at
by
means
the
expressed
angle
increase
shown
.iunal
the
Characteristic
maximum
a
of
origin
of
iy
unit
torque.
characteristic
the
and
by
where:
maximum
in
the
Action
will
torque
tap
links
the
reach
dotted
pick
Hence,
block
have
following:
2
njin
torque
up
at
the
of
angle
of
providing
on
the
rear
a
diameter
=
basic
of
to
approximately
characteristic
or:
a
a
60
the
constant
name
mho
degrees.
a
providing
along
Ohmic
mm.
mho
cos
(
Y
cos
(
component
mho
unit.
CHARACTER
unit
is
This
range
of
a
he
60
Reach
phase-to-neutral
unit
can
120
percent
in
Fig.6.
-
-
shown
up
total
degree
be
0)
B)
ISTICS
circle
to
tap
adjusted
of
K
K
of
admittance
in
Fig.
4/1
,
range
impedance
(lo0
setting
ohmic
its
can
or
of
z
reach
6
by
up
up
for
be
expanded
changing
to
line
()
reach
to
at
a
fixed
angle
depending
the
one
ohm
basic
by
means
the
12/1.
equal
of
75
degrees
at
60
The
the
degrees
basic
to
unit.
(see
of
minimum
circle
the
ohmic
SERVICING)
for
the
minimum
the
will
same
mho
reach
always
reach
reach
with
tap
on
taps
of
the
on
of
pass
the
setting.
the
:eri
tact:
shown.
‘tecessary
For
performance
to
the
low
volts
between
fault,
TihO
current
between
This
see
unit
is
conditions.
0
current
the
adjustment
SERVICING.
BASIC
REACH
1.0
1.5
2
*The
unit
for
1/2/3
range.
during
refer
to
carefully
and
60
is
MIN
TAP
i
is
ohm
A
variation
transient
the
adjusted
For
amperes.
limits
a
function
set
at
unit)
paragraph
faults
For
in
Table
of
the
factory
for
correct
of
+10
low-voltage
below
to
in
faults
IV
the
percent
on
have
correct
the
non-tripping
for
core
*VOLTS
2.0
vol
2.0
volts
2.0
volts
2.0
volts
volts
2.0
on
the
directional
can
conditions,
memory
in
the
the
(inner
TABLE
ts
middle
be
action.
three
IV
expected
where
directional
direction,
tripping
basic
stator)
tap
action
the
direction,
minimum
position
j_
(lii
over
on
voltage
action
under
the
contacts
the
reach
and
CURRENT
steady—state,
unit
settings
should
RANGE
CORRECTOIRECTIONAL
ACTION
12
-
60
6
-
60
4.5
-
60
3
—
60
2
-
60
for
the
0.5/1/1.5
the
indicated
values
was
unit
listed.
normal
will
will
any
amps
amps
amps
amps
amps
and
current
at
remain
close
at
the
adjustment
FOR
2
120
volts
low
open
its
voltage
prior
voltage
at
con
be
5

3,
linderreach
t
LJICulat(d
miiInuI1
oi
,L:ing.
of
rig.
‘pHed.
hr
laul
4.
Memory
[he
polorizing
effective
be
nost
ri
ht
at
percent
zero
percent
the
memory
percent
The
cannot
is
delayed
application
depending
reduced
reach
liree
wirer
3
The
mis
t
dynamic
at
forcefully
time
of
action
tap
memory
be
relied
by
on
value.
settings.
dynamic
applied.
Action
flux
low
relay
its
of
setting
the
to
memory
voltaqe
This
ohmic
The
determined
curves
for
a
voltage
illustrated
bus
setting.
the
relay
is
will
action
on
if
zone
operate
action.
the
pullback
The
reach
itho
unit
curves
of
few
levels
and
Fig.
effective,
operate
will
the
2
setting
for
ohmic
unit
tap
will
by
tests
were
Fig.
cycles
therefore,
3
setting
close
tripping
nearby
value
or
reach
settings.
Operate
performed
obtained
illustrate
3
following
where
for
a
shows
regardless
Fig.
if
the
of
faults
reduction
it
zero
to
that
3
I3
contact
is
the
at
which
in
percent
Note
for
with
the
enables
voltage
protect
the
shows
is
greater
delayed.
type
and
all
with
the
who
of
that
for
RPM
there
GEK-45495
the
in
reach
of
that
points
no
full
effect
inception
the
fault
for
unit,
the
mho
than
only
When
relay,
will
niho
the
voltage
rated
who
this
tap
unit
the
unit
is
setting
fault
to
of
of
unit
by
under
setting.
1.6
a
short
the
be
shown
the
supplied
voltage
memory
the
referring
fault,
with
amperes.
relay
static
sufficient
will
is
plotted
current
right
fault.
to
operate
it
static
a
period
is
action
However,
three-ohm
operate
in
Fig.
against
scale
of
the
to
the
of
120
in
This
for
to
Fig.
is
imperative
conditions,
of
time
used,
as
characteristic
voltage
may
for
3
changes
volts
the
memory
low
3.
under
basic
a
be
curve.
relay
supplied
who
A
and
second
to
somewhat
the
1,
the
with
before
unit
action
fault
zero
that
will
dynamic
minimum
therefore,
should
give
lower
and
2
three—phase
the
The
steady-state
the
the
to
which
is
currents.
voltage
the
relay
not
see
conditions
reach
zone
relay
be
used.
tripping
than
3
ohm
fault
basic
fault
relay
maintains
particularly
This
fault
reach
fault
a
and
memory
and
without
the
basic
r,iniiuuw
curves
W.i
before
must
when
100
action
tripping
For
this
cur
the
can
be
zero
at
5.
Operating
The
setting
relay
fault.
rnho
TAPPED
operating
of
voltage
Time
taps
were
AUTO-TRANSOFRMERS
The
ohmic
auto-transformer
The
other
winding
The
necting
desired
the
subtracted
The
ale
tap
impedance
1:
neutral
:Xj
TAP
the
prior
curves
in
two
from
setting
SETTING
Time
time
unit,
the
reach
has
is
tap
windings
the
expressed
of
fault
to
the
are
given
100
of
the
two
windings.
tapped
setting
of
15-95
required
DESIRED
the
current
fault.
percent
(See
mho
at
the
percent
in
who
unit
magnitude,
The
for
four
position
Fig.
7)
units
may
One
percent,
0
is
made
by
auto-transformer.
winding.
to
protect
secondary
Tap
Setting
where:
=
91
is
curves
ratios
winding
the
a
terms,
0
9
determined
ratio
in
of
and
the
be
adjusted
1
percent,
proper
zone
(100)
=———
Power
Angle
Fig.
fault
angle
is
tapped
location
Note
Z
ohms
is
determined
(Mm.
factor
of
maximum
by
of
fault
8
impedance
by
percent
3
long,
a
are
of
means
in
that
Ohms
angle
number
impedance
for
the
maximum
of
10
percent
and
of
the
the
0—5
where
by
the
Setting)
of
fault
torque
of
to
torque
taps
5
leads
Z
of
factors
to
condition
relay
on
steps
percent.
marked
percent
is
positive
following
Cos
impedance
the
unit
relay
reach
was
the
winding
(—@)
such
as
reach,
of
rated
setting.
set
at
two
auto-transformers.
from
15
No.
1
may
phase
equation:
the
and
volts
60
degrees
percent
and
sequence
basic
magnitude
In
the
be
added
minimum
prior
all
lag.
to
jumper
phase-to-
to
cases,
95
or
reach
of
the
the
Each
percent.
con
cite
:xample
m,Nate
Set
Set
the
the
2:
one
4
TAP
one
4
end
percent
SETTING
end
percent
of
of
jumper
setting
DESIRED
jumper
setting
lead
of
lead
of
the
the
to
89
to
95
0—5
85
0-5
percent.
percent
percent.
percent
Set
winding
Set
winding
the
the
6
other
subtracts
other
adds
end
to
percent.
5
from
the
95
end
to
percent.
the
85
1
percent
to
percent
Set
setting.)
Set
No.
setting)
No.
1
to
1
percent.
1
to5percent.

GE
K-45495
Assume
is
it
this
For
given
The
both
at
case
the
connection
external
overlap
(see
brush
locking
leads
bottom
connections
cover,
mechanism
thick
insure
to
panel
the
drawn
‘abo1s
nagram
ito
a’
2.
minmJm
most
orotect
that
application
section
the
type
in
studs
plug
connections
circuit
the
when
contact
circuits.
relay
by
between
is
a
is
relay
appropriate
that
either
and
1
aid
tc
usea
in
Fip.
ralav
after
CEYS2
are
which
connections
mechanism
a
part
case
proper
replaced
icaludes
uesired,
*i
ends
Every
internal
make
The
terminated
and
which
The
and
separate
A
out
Pies.
The
wittrrisforrners
The
R23
The
he
hese
rio
ssed
reach
tap
removed
relays,
them
sub-a;seIHbly
in
car
blockS
against
CEY52
the
considering
the
under
relays
rear
the
made
and
in
connecting
as
at
the
guide
the
drawn
of
is
testing
from
2
show
identify
10.
settinq
oe
for
from
when
is
to
three-ohm
CHARACTERISTICS-
Percent
750
80.5°
are
external
for
inner
the
drawout
plug
Fig.
in
mounted
is
inner
the
at
respective
case
the
cover
can
plug
own
another
relay
the
=
Percent
Percent
assembled
block.
will
source
z
=
=
9
=
through
completes
the
indicated
pin
to
the
suitable
hardware
hardware
its
by
nircuit
similar
th’en
and
tap
includes
angle
tie
adjusted
from
changirg
to
case
its
included
not
damage.
Irnediately
used
be
effects
the
basic
3.54
stationary
circuits.
the
blocks
case
withdrawn
is
10)
Fig.
in
inasteel
back
blocks
by
assembly.
either
for
available.
is
be
which
removed
components
blocks
the
the
the
make
conjunction
in
of
minimum
TAPPED
Setting
Tap
Minimum
Setting
Tap
Setting
Tap
in
a
connections.
molded
have
an
has
on
and
with
9
cradle
This
of
the
of
thumbscrews,
semi—flush
included.
be
inserted
current
of
has
been
ro
are
suhassembi:
rho
mounted
i—pole
fOL
f
ma.’inlui
front
r;inioum
basic
the
settings.
RECEIVIND,
i
part
as
upon
with
infeed,
reach
CONSTRUCTION
deep
The
the
auxiliary
or
those
adequate
framework
case.
the
However,
in
place
and
its
the
to
setting
AUTO-TRANSFORMERS
(100)
=
Ohms
(100)
=
=
size,
large
electrical
The
and
inner
inserted.
is
cradle
holds
outer
terminals
circuits,
held
The
or
panel
blocks
brush,
pressure
called
connecting
and
the
surface
of
voltage,
tested
in
drawout
arie
Cienents
‘bc
or
back
or
the
inS
relay.
torce
of
reach
a
AND
control
of
HANDLING
of
receipt
a
set
(Mm.
3.0
(3.6)
outer
Some
firmly
case,
connecting
the
the
case
those
as
-‘
rrnostats
of
ne
STORAGE
panel,
relay,
a
CEX2OA
relay
the
should
ohms)
7
at
60
Cos
3.64
double-end
blocks
attached
for
the
shown
as
circuits
is
it
to
the
in
also
mounting
thickness
connecting
from
or
laboratory.
wth
which
mojntcd
the
ossoc
units
provide
to
to
used.
be
is
used.
Cos
deg.,
(80.5
connections
internal
in
especially
prevent
cradle
case
the
plug,
locks
plugs
must
plug
other
all
appear
on
cradle.
i
ated
,
811
are
will
examine
reach
(0—9)
3.6
75)
—
(L2D)
between
the
to
Fig.
are
the
and
besides
on
be
sources;
major
the
See
circuit
R2,
mounted
shipped
be
it
second
3.64
ohmic
The
75
at
drawout
between
which
case
connections.
to
9,
equipped
important
opening
isacomplete
latch
a
with
making
latch
the
in
place.
panels
all
indicated
test
to
components
the
an
front
Rj
05
cunipcnents.
used
813
on
in
any
for
/80.50
dog.
have
provide
the
or
of
the
zone
reach
case
the
nests
the
with
that
of
at
the
in
place.
The
up
on
relay
the
interncl
the
and
jr
back.
cartons
4
mage
protection
secondary
having
relay
a
studs
adequate
shorting
the
important
unit
both
electrical
target
two
to
the
relay
ider.ti
cradle
2
heostt.
settinj
sustained
equation,
units
removable
auxiliary
with
top
The
reset
inches
relay
in
place
ca
fiec
connection
ann
the
The
designed
studs
for
bars
inter
be
-
relay
and
ohms.
and
th’
all
and
order
on
a
basic
to
in

TABLE
IX
tEK-45495
(CONTROL
SPRING
ADJUSTMENT)
LOCAION
TOP
MIDDLE
BOTTOM
LOCATION
TOP
MIDDLE
BOTTOM
UNIT
LO
TION
TOP
MIDDLE
BOTTOM
PHASE-ANGLE
METER
SETTING
3000
3000
300°
PHASE-ANGLE
METER
SETTING_—
300°
300°
3000
TABLE
PHASEANGLE
ANGLE
MAX.
OF
TORQUE
3000
3000
3000
TABLE
(ANGLE
XI
METER
TEST
2700
270°
2700
SOR
1.5
Volts
Volts
1.5
Volts
1.5
(OHMIC
X
O.5/l.O/1.5c1UNIT
.oc
1
—
-
READING
Volts
30
Volts
30
Volts
30
OF
MAXIMUM
ANGLES
3300
and
3300
and
and
330°
-
O,5/l.O/L5c2UNIT
ADJUSTMENT)
REACH
VA-B
SET
TAP
TORQUE
1
.5sz
5/1/1
TAP
l
30
30
30
PICKUP
]iZTAP
6.0-7.0
6.0-7.0
6.0-7.0
AT
l/2/3cUNIT
2i2
TAP
Volts
60
60
Volts
Volts
60
ADJUSTMENT)
VA-H
SET
UNIT
AT
l/2/32
2s
AMPS
—
UNIT
TAP
60
60
60
l/2/3I2UNIT
22TAP
3.0-3.5
3.0-3.5
3.0-3.5
PICKUP
AMPS
14.6-15.4
14.6-15.4
14.6-15.4
AMPS
16.5-18.5
16.5-18.5
16.5-18.5
Note
away
from
shows
0.866
that
times
ELECTRICAL
target
The
2.0
amperes
The
of
1
through
so
that
increase
Do
relay
the
point
stud
also
and
lower.
LOCATION
The
The
location
be
relay
16.
should
MOUNTING
Fig.
in
that
the
the
the
TESTS
depending
seal-in
the
the
not
well
the
angle
ohmic
reach
—
seal-in
is
an
seal—in
d—c
attempt
lighted
should
two
angles
of
maximum
reach
at
TARGET
on
shipped
unit
adjustable
current
to
of
the
to
be
of
the
SEAL-IN
unit
model
from
can
contact
interrupt
relay
facilitate
mounted
used
torque.
the
angle
either
ordered.
the
be
resistor
will
until
should
on
in
unit
of
has
factory
checked
the
the
inspection
a
the
previous
An
examination
should
maximum
operating
an
with
by
connecting
and
an
protect
seal-in
current
d-c
INSTALLATION
be
clean
vertical
be
the
torque.
the
ammeter
the
ruho
unit
and
and
surface.
check,
same
coil
tap
back
unit
operates.
by
dry,
testing.
means
i.e.
the
at
330
mho
both
of
tapped
in
screw
from
d-c
source
to
(-).
contacts.
It
of
the
PROCEDURE
free
from
The
outline
degrees
unit
330
at
the
Connect
should
dust,
degrees
0.6
lowest
Then
reho
and
and
impedance
or
2.0
tap
(+)
to
jumper
a
close
pick
contacts.
excessive
panel
degrees,
270
characteristic
and
270
amperes
position.
stud
11
the
at
up
heat
drilling
degrees
or
of
from
mho
tap
and
are
and
tapped
The
the
relay
stud
12
unit
contact
value
or
vibration,
dimensions
degrees
30
in
Fig.
should
at
0.2
operating
and
stud
to
slightly
are
from
by
and
shown
6
be
or
11
hand
11

CONNECTIONS
internal
The
external
connections
connections
shown
is
45495
GEK
typical
Fig.
10.
CEY52B
the
of
Fig.
in
relay
4.
in
shown
are
elementary
An
diagram
of
VISJL
INSPECTION
Remove
screws
all
MECHANiCAL
Recheck
To
from
TEST
eliminate
In
PORTABLE
units
mended.
impedance
fault
the
+
may
jX[
RL
is
enough
Fo
as
user
necessary
convenience
ri
relays.
the
is
This
with
arranged
distaece
well
the
ELECTRLAL
manner
The
OF
SETTINGS
To
of
have
check
purpose
which
portable
according
plugs
connections
matic
Use
is
necessary
normally
.isually
be
especially
suitable
Since
i
desirable
difference
selected
taken
being
Fig.
From
relay
the
tight.
are
INSPECTION
six
the
EQUIPMENT
the
single-phase
a
figure
this
line
the
of
switch
be
and
made
since
so
taps
a
portable
The
and
line
referred
ON
TESTS
in
section.
electrical
the
made
been
the
reactor,
test
to
the
source
of
only
considered
necessary
a
when
be
value
reactance
the
check
to
between
12
be
of
tie
it
is
should
from
adjustments
errors
RS
section
line
appear
to
it
that
field
in
test
box
source
GEI—38977.
to
MHO
THE
which
Examples
for
calibration
Cat.
14.
Fig.
in
shown
iinpedanceR
5
if
the
necessary
in
with
unit
for
used
mho
line
the
test
the
difference
seen
case
its
which
test
a-c
jX
5
+
for
impedance,
to
is
not
combination
the
testing,
box,
provided
is
impedances
UNITS
settings
reach
of
tests
particular
a
of
No.
These
Fig.
relay
at
source
the
short
this
the
of
unit
reactance,
reactor
in
twice
that
and
mentioned
may
source,
the
is
which
is
the
feasible
Cat.
calculations
this
in
mho
the
6054975;
connections
except
13
÷
be
to
is
the
connection
reach
purpose
test
pickup
tap
angle
the
check
result
source
the
tapped
relay
may
the
No.
with
may
are
line
jX5,
tested
time
setting
since
reactor
with
XL,
nearest
of
relay
that
under
from
the
relay
very
provide
to
be
fault
lO2L2Ol,
terminals
be
made
section
section.
units,
test
and
that
simulating
installation
of
may
the
and
the
reach
there
Mechanical
instrument
circuit
test
impedance,
being
is
10
percent
in
nearly
made
switch
which
readily
for
typical
for
check
to
is
it
resistor,
the
of
type
the
overreach
for
limit
to
is
to
will
this
be
fault
unit
mho
above
reactor
test
of
are
as
the
match
to
and
is
which
to
connecd.
mho
tae
suggested
test
XLA
the
current
be
tend
very
reactor
angle
twice
the
broken
no
Inspection
inaccuracies
shown
iS
SF
tested.
dnd
actual
the
portable
any
tapped
particularly
the
units
settings
ohmic
the
Cat.
and
box
test
conditions
or
during
or
checked,
to
accurately
alone,
of
the
tap
angle
or
in
in
schematic
fault
the
The
percent
1
line
test
line.
autotransformer
relay
For
a
is
are
pickup
the
that
6158546
No.
other
connections
plug
which
contact
periodic
and
limit
the
fault
it
harmonics
in
determined
due
maximum
unit
mho
impedance
of
the
cracked
section
the
to
and
form
switch,
autotransformer
so
steps
which
on
reactor
adapted
current
XL
for
and
complete
of
discussed
in
the
briefly
given
portable
arranged
be
equipment
would
coordination,
testing.
circuit
suggested
is
in
from
account
being
reach.
phase-to-neutral
the
and
reactor
test
component
on
permit
Fig.
in
and
RL
TA,
that
the
the
and
Fig.
of
testing
potential
description
section.
that
units
mho
box,
test
similar
are
now
are
encountered
be
tests
Some
a
to
that
the
its
taken
line
The
angle
unit
impedance
and
parts
ACCEPTANCE
13
jXL
which
test
13
line
is
have
the
recom
is
the
is
is
impedance
to
resistor
testing
+
the
relay
directional
circuits
the
of
CALCULATION
the
in
It
the
at
No.
Cat.
Type
with
to
included.
in
which
impedance
reasonable
reactor
a
current.
fault
calibration
the
of
reactance,
with
reach
maximum
of
is:
that
TESTS.
mho
across
be
been
test
the
is
settings
102L201;
XLA
the
practice,
are
value,
of
curve,
angular
XL,
account
used.
and
as
box
test
sche
not
will
it
reach.
unit
To
illustrete
that
has
been
by
where:
an
factory
Relay
22
example
adjusted
Z
Mm.
let
200
0=
9=
us
to
Tap
the
mho
basic
=
consider
pickup
Setting
angle
unit
minimum
at
of
angle
the
%
percent
three
12
Cos
the
of
reach
ohms
(0—0)
test
maximum
of
tap
minimum
reactor
mho
required
reach
units
impedance
on
at
and
test
the
maximum
a
autotransformer
box
torque
angle
for
of

When
becomes
the
at
apparent
checking
relatively
zero-degree
error
in
the
large
position
reach.
mho
unit
with
at
phase-angle
that
a
angles
two
GEK-4
5495
of
more
error.
or
three
This
degree
than
30
is
error
degrees
apparent
in
off
phase
from
the
Fig.
angle
maximum
12
where
will
reach
cause
position,
it
is
considerably
a
seen,
the
for
error
example,
INSPECTION
uni
ts.
cover
MHO
contact
lower
screw.
the
in
the
the
by
sary
value
reach
can
plug.
are
is
into
Before
The
armature
There
The
target
the
on
UNITS
There
should
There
jewel
If
there
bottom
jewel
All
nuts
The
felt
Determine
relay,
reduce
to
found
of
the
A
shorter
be
accomplished
All
Replace
away
from
the
placing
should
relay.
should
should
screw
of
screw.
checks
mho
units
the
station
should
just
is
the
and
gasket
the
the
the
test
should
lower
the
a
and
be
a
be
no
return
be
approximately
bearing
reason
unit
screws
on
impedance
tap
tap
with
unit
which
by
station
bus,
relay
into
contacts
screw
in
reset
promptly
noti
ceable
to
should
believe
to
and
examined.
should
the
cover
and
value
at
setting
the
calculated
low
at
currents.
will
disconnecting
have
strong
plug
and
bus
and
the
resultant
of
only
the
be
which
of
check
open
service,
the
fri
backstop
.010-015
be
screwed
that
tight,
should
phase
the
for
the
torque
the
into
target
one
when
ction
When
angle
the
relay
value.
the
phase
the
of
when
the
with
be
relay
This
most
current
to
restraint
protected
following
and
the
taps
the
reset
in
the
the
inch
firmly
jewel
replacing
particular
securely
seen
will
until
The
effect
of
the
angle
seal-in
on
button
rotating
relay
end
into
is
cracked
a
cemented
by
the
just
the
calculated
is
possible
the
circuits.
right
taps.
line
may
mechanical
units
the
is
play
place,
jewel,
attention
relays.
operate
mho
units
shown
when
All
section.
be
such
should
right-hand
at
the
structure
de-energized,
in
the
and
or
dirty
have
in
place
can
operate
value
in
Fig.
open
can
This
full
voltage
units
that
adjustments
operate
contact
bottom
of
shafts
the
top
the
the
top
paid
in
Knowing
calculated.
be
and
should
8.
circuits
be
done
should
If
the
the
units
of
the
and
of
the
pivot
screw
pivot
to
the
order
the
see
take
in
is
operate
direction
should
hand.
by
of
the
cover
mho
unit.
in
rotating
locked
assembly
in
tap
to
impedance
how
into
the
by
removing
applied.
will
the
the
keep
a-c
if
not
be
target
is
vertical
the
plugs.
It
close
account
portion
power
of
operate.
checked,
operated,
The
inho
structures.
in
place
can
shaft
Out
dust.
and
phase
is
then
the
the
and
reactive
and
position.
be
while
actual
the
of
lower
seal-in
with
unit
by
its
removed
screwing
angle
only
shorter
the
connection
reactive
power
the
moving
The
set
from
seen
neces
tap
relay
flow
flow
In
periodic
depending
as
accumulated
is
suggested
yea
rs.
CONTACT
For
ble
strip
acton
Its
flexibility
oaper
or
view
of
test
upon
that
CLEANING
cleaning
of
metal
is
so
delicate
cloth
the
vital
program
environment,
enough
the
fine
with
insures
of
any
role
be
followed.
type
experience
points
listed
silver
an
etched—roughened
that
no
the
cleaning
kind
to
PERIODIC
of
protective
of
to
contacts,
scratches
clean
It
relay
select
under
of
relay
CHECKS
relays
recognized
is
and
the
the
test
INSTALLATION
a
flexible
surface
are
left,
the
actual
contacts.
AND
ROUTINE
in
that
users
interval
burnishing
resembling
yet
it
points
14
MAINTENANCE
the
operation
the
interval
experience
best
PROCEDURE
tool
in
will
clean
of
contact.
be
effect
with
suited
checked
should
off
ofapower
between
periodic
his
to
at
be
used.
a
superfine
any
corrosion
Do
not
system
periodic
an
use
it
testing.
individual
interval
This
file.
thoroughly
knives,
is
checks
until
requirements
of
consists
The
files,
important
will
the
from
of
polishing
and
abrasive
vary
one
a
rapidly.
that
user
to
flexi
a
it
two

GEK-45495
.
.1
I
II
I
V
‘Fl
LINE
J
f3c1
FIS1
(1ANI
-
03
---—5----
T
vOj
I(
TI’
PI’IN’-V
L
15-
I
yr
—
-
0
I
A
.--
0’-
I
__
-.
1
I——I’-—•
‘“t
-
L1
1’5-
IP_9_ø2.
---;-
‘--—‘
:
--
-,
-5,-S
U
r:r
‘IT
U
S
REST
03
—cli-
--i
02-3
03-I
02-3
r
FIG.
NOTE
W1.N
7
RP
“0
4
(0108B8961-O
IJ$INc-AIJVILIARY
TWO
AlIAS.
SAP
‘ONNECT’A
0.C”.
IJE
TRIP
SH.
RELAY
4LrE4AIE
1
TO
ç94
CONNECTION
&
2)
TYPICAL
EXTERNAL
CONNECTIONS
21
TU
DEVICE
CEYS2B
21
rLcEV28’rNI,
1Z’.
DEVICE
CEYS2I3
CEX
54441713
L
2013
FOR
F
THE
541.4176
0269A3027
024
020A
102L2I8
PC
7’.
INTERNAL
6A6R30
24
Gil
AUERNACE
I3
2i
P
CEY52B
DESCRIPTION
IMHO
.ELOND
31
DIS1’*34CE.R[Iil
ZCINE
TIMER
OUTLINE
017647336
0x6A3824
4
6209274
OIO4ABS23
RELAY
J