GE CEY52B Instructions Manual

INSTRUCTION
S
GEK—45495
U
MHO
DISTANCE
TYPE
RELAY
GENERALS
ELECTRIC
LsURJPTION
APF’L
(Al
I
I
ON
RATINGS OPERATING
PRINCIPLES
CHARACT[RISEILS
BURDENS
LALCULA1 UONSTRUCT RECEIVING,
ACLEPTANCE
ASTALLATION
iON
OF
ION
HANDLING TESTS
PROCEDURE
INSPECTION
PLRIODIC
CHECKS
SERVICING
RENEWAL
PARTS
SETTINGS
AND
AND
ROUTINE
STORAGE
MAINTENANCE
GE
K-A
5495
CONTENTS
PAGE
3 3 2
4
5 7
7 N 8
9 11 14
14 15 17
‘S.) to C-) CD
to
to
“S
GE
K-4
54
95
The
designed
is
relay testing. dimensions
is
relay not
been
The itself, relays
may
they protection. distance
When
that
tap
highest
Since
fault,
a voltage protection
The
CEYS2B
section
the
than
less
The
cycles
t desired the
back
A-B
as
adjust-nd
means
by
evuuj
u’ctfte’L
the
pu’tcha.ea’-
hIlt
,‘to
CEY52B specifically
constructed
The
not limited
C[Y52B
but
may
be
scheme
applying
will
possible
the
at
section
in
type
rating.
will basic
of
determine
in
of
Thnie
sA6e
po
-ui1jo’tnri..tLon
Io
the
ucJi
relay
interndl
shown
are
intended
in
relay
rather
used
be
as
used
Figure
with
acconinodate
level
memory
the
relay
relay.
the
this
for
under
typical
a
entitled
percent.
25
CEY52
The
noted
be
minimum
relay
the
the
percent
one
autotransformer
utcton
con.tA,nqenc.y
pwtpoe,
oxteiit
asu.’utnce
three-phase,
is
a
use
for
three
of
connections
Figure
in
for
use
respect.
this
BASIC
TAPS
0.5
1.0
is
a
is
designed
a
step-distance
in
of
part
illustrates
4
CEX2OB
the
relay
this
the
of
torque.
action
should
not
The
contingency
CALCULATION
application.
TAPPED
covered
relay
minimum
basic
that reach
(see
basic
steps
do
bi
de’u’,d
.‘LequL’ted
guJen
..a
MHO
TYPE
DESCRIPTION
speed,
high
the
with
single—phase
for
Typical
16. first
a
as
MINIMUM
CEY52R
OF
-
1.0
-
2.0
-
three—phase,
to
be
high-speed
a
typical
CEX2OA
the
REACH
1.5
3.0
used
scheme
or
units
relay
external
function,
zone
single
with
to
pilot-relaying
external
relay.
the
the
relied
is
protection reach
CLY52B
should
required.
SETTINGS
OF
Once
the
on
setting.
will
provide
to
be
settings
for desired
of
be
protection
AUTO—TRANSFORMERS.
instructions
these
three
setting Fig. minimum
over
tap
pu.’tpo-’t-t
no.t
be
to
o.’
rnattc’t
the
the
w-tk
by
reach
basic
for
2). setting
a
leads
met
I-touLd
p’wduc.ta
The
4/1
UL
hou.fd
‘tc.apee.t
and
minimum
each
position
range
the
on
eovciz.
-to connec,tcon
pa.’ct
dci.eailied
adjustment
unit
of
the
tap
be
to
DiSTANCE
CEY52B
single-zone CEX2OB mounted
shown
are
connections
TABLE
ICATION
APPL
mho
zone
CEX2OA
a
provide
connections
given
a
of
This
be
only supplemented
provides
have
Under
RATINGS
settings
reach
made
is
the
of mho
any
for
blocks
detaiJs
aU
wLth
pitobfms
cithvi.
e1eived
eke4n
eode4
tocitf
RELAY
reactance
one
in
in
the
thus
I
distance
CEX208
or
zones
two scheme
circuit,
will
effective
time-delay
worked
a
been conditions,
no
available
is
ranges
by
two
units.
of
the
the
at
n-taitiou,
thc
to
rnec’-t
azid
directional
type
L2—D
Figure
to transient,
SELECT
relay
in to
insure
protection
other
by
example
calculated,
the
of
are
means
sets
The
basic
right
0L
aJLe
(cvtc’uct
appcaIit’e
icknanet’
relay.
case
10,
the
CEX
CEX2OA
CEX2OR
that
reactance
protection
of addition
relay
the
select
that
several
for
devices
should
for
inho
listed
of
links
links,
of ohmic
minimum
side
ope’Litu)e
wh{cJ!
with
while
relay
overreach
SHOWN
for
the
120
units
for
reach
of
aiz.C
distance
mho
See provisions
outline
are
BELOW
is
not
type
providing
to
when
the the
cycles
for
to
determining
taps
the
volts,
are
the
a
on
(for
of
reach
the
c2u.prnnnt
n
not
etsc
ANSI,
b1
cauc
Table
shown
characteristics
meant
relay.
against
is
it
highest relay
after
fault
any
detect
are
restraint
5
given
mho terminal each
the
settings
relay.
miLtefltliIrc.
o’
cOvQYted
Conipanu.
1H
tlzoe
relay.
I.
for
panel
and
in
Figure
to
The phase step-distance
used
basic
operate
will
that
this
the
set
taps
amperes,
in
units.
board
unit),
inho
units
—--..____
no
IMA
a,id
oa-i
it
CEY52B
The
sirjle
drilling
used
be
combination
faults,
step-
a
in
minimum
inception
the
provides
condition
settings
described
as
ever
60
Table
Selection
located
each
can
listed
to
p4ovd
Lt?etif
ttz;
L’att’1.
WaS
phase
4.
The
have
by
or
at
be
50
or
II.
identified
be
Table
in
St(!Led
reach the
zero
if
of
in
set
of
at
oi
OL
of
of
the
the
II
3
BASIL
**MaxiIiluIli
CONTACTS
The
the
circuit
the
relay
REACH
-
1,0
0.5
1-2-3
*Adjustment
increase
contacts
breaker
contacts
TAPS
-
1.5
taps
torque
to
approximately
of
the
trip
have
are
angle
CEY52 circuit
no
interrupting
set
can
relay
BASIC
(ØN
using
be
120
must
MTN
OHMS)*
0.5
1.0
1.5 1 2
middle
adjusted
percent
will
be
rating.
REACH
close
opened
tap up
of
and by
GE
K-4
TABLE
r
at
the
to
75
its
carry
an
auxiliary
5495
II
RANGE
(0-N
OHMS)
0.5
-
1.0
-
1.5
-
1—4 2-8
3-
factory.
degrees.
reach
momentarily
at
2.0
4.0
6.0
The
the
switch
60
reach
degree
30
contact
ANGLE
MAX
TORQUE
600
600 60°
600 600
of
amperes
OF
**
**
**
**
**
the
setting.
direct
or
other
iriho
units
current. suitable
ONE
RATING
150
150
150 150
150
will
SECOND
However,
means
since
TARGET
The
The
‘o:roduced
operating
The
se—tc-jhuse
Dr
entaq
tcr
we.
zhse-
to-phase
The
SEAL-IN
target
inum
nihc
units
ty
quantities.
sc[.emlii:
f
Th
Cl
torque
UNIT
Carry Carry Carry
0-C
60
the
c’
the
ux
ot
seal-in
Continuously 30 10
Resistance
Cycle
of
interaction
connections
tage,
5éiPi in
the
taqe,
the
unit
TARGET
Operating
amps amps
Impedance
the
CEY52
prodoce
priase
rear
interacts
balance
in
used
the
SEAL-IN
-
CEY52
UNIT
for for
+lOt
relay
are
of
betweenapolarizing
of
-to-phasa pole,
point
the
the
with
rho
gel
vo1tiçc
which
o
jr
arzinc
1.
the
the
relay
TABLE
0.2
AMP
0.2
amp
0.4
amp
0.03_=
0.25
7.0
ohms
52
ohms
OPERATING
the
four
flux
are
shown
t
iu
ntr
•nero1z:
nolan
wit
cc
car
has
ratings
III
TAP
sec.
PRINCIPLES
pole
induction
and
n
The
flu
s
iith
by
the
t
triereforo
i
fluxes
Fia
in
the
two
produce
.ne
as
0.6
0.6
1.5
0.5
4.0
0.6
6.0
.a.
the polorizing
I
rxpr’.sed
shown
in
AMP
TAP
amp
amp sec.
sec. ohms ohms
cylinder
proportional
Tue
two
front
currents
inc
operating
Table
construction
to
side
p010,
flux
associated torque.
by
the
III.
0
2.0
3.5
4.0
30.0
0.13
0.53
the
poles, which
produce
to
following
AMP
TAP
amp amp sec. sec.
ohms ohms
in
restraining
oneraized
is
energized
restrain
with
equation:
which
the
torque
or
by
by
seme
a
where:
Torque
=
0
E
phase-to—phase
I
=
delta
0
=
angle
=
power
0
K
=
design
El
of factor
4
cos
current
maximum
constant
(0-9)
angle
-
voltage
1
torque
KE
2
(E12)
-
12)
of
the
unit
of
fault
impedance
equation
GE
K—4
54
95
to
prove
that
the
reduces
equation
to:
defines
a
mho
characteristic
divide
both
sides
by
[2
and
transpo.e.
The
angle
MHO
UNIT
1.
setting the
autotransformer unit through unit
as
The resulting Ths
is
.
irec
Thus,
of
maximum
Impedance
The
impedance
at
by
means the
expressed
angle
increase
shown
.iunal
the
Characteristic
maximum
a
of
origin
of
iy
unit
torque.
characteristic
the
and
by
where:
maximum
in
the
Action
will
torque
tap
links
the
reach
dotted
pick
Hence,
block
have
following:
2
njin
torque
up
at the
of
angle
of
providing
on
the
rear
a
diameter
=
basic
of
to
approximately
characteristic
or:
a
a 60
the
constant
name
mho
degrees.
a providing along
Ohmic
mm.
mho
cos
(
Y
cos
(
component
mho
unit.
CHARACTER
unit
is
This
range
of
a
he
60
Reach
phase-to-neutral
unit
can
120
percent
in
Fig.6.
-
-
shown
up total
degree
be
0)
B)
ISTICS
circle
to
tap
adjusted
of
K
K
of
admittance
in
Fig.
4/1
,
range
impedance
(lo0
setting
ohmic
its
can
or
of
z
reach
6 by
up
up
for
be
expanded
changing
to line
()
reach
to
at
a
fixed
angle
depending
the
one
ohm
basic
by
means
the
12/1.
equal
of
75
degrees
at
60
The
the
degrees
basic
to
unit.
(see
of
minimum circle the
ohmic
SERVICING)
for
the
minimum
the
will
same
mho
reach
always
reach
reach
with
tap
on
taps
of
the
on
of
pass the
setting.
the
:eri
tact: shown. ‘tecessary
For
performance
to
the
low
volts
between
fault,
TihO
current
between
This
see
unit
is
conditions.
0
current
the
adjustment
SERVICING.
BASIC
REACH
1.0
1.5
2
*The
unit
for
1/2/3
range.
during
refer
to
carefully
and
60
is
MIN TAP
i
is
ohm
A
variation
transient the
adjusted
For
amperes.
limits
a
function
set
at
unit)
paragraph
faults
For
in
Table
of
the
factory
for
correct
of
+10
low-voltage
below
to
in
faults IV
the
percent
on
have
correct
the
non-tripping
for
core
*VOLTS
2.0
vol
2.0
volts
2.0
volts
2.0
volts volts
2.0
on
the
directional
can
conditions,
memory
in
the
the
(inner
TABLE
ts
middle
be
action.
three
IV
expected
where
directional
direction,
tripping
basic
stator)
tap
action
the
direction, minimum position
j_
(lii
over
on
voltage
action
under
the
contacts
the
reach
and
CURRENT
steady—state,
unit
settings
should
RANGE
CORRECTOIRECTIONAL
ACTION
12
-
60
6
-
60
4.5
-
60
3
60
2
-
60
for
the
0.5/1/1.5
the
indicated
values
was
unit
listed.
normal
will
will any
amps amps
amps
amps
amps
and
current
at
remain
close
at
the
adjustment
FOR
2
120
volts
low
open its
voltage
prior
voltage
at
con
be
5
3,
linderreach
t
LJICulat(d
miiInuI1
oi
,L:ing.
of
rig.
‘pHed.
hr
laul
4.
Memory
[he
polorizing
effective
be
nost
ri
ht
at
percent
zero
percent
the
memory
percent
The
cannot is
delayed application depending
reduced
reach
liree
wirer
3
The
mis
t
dynamic
at
forcefully
time
of
action
tap
memory
be
relied
by
on
value.
settings.
dynamic
applied.
Action
flux
low
relay
its
of
setting
the
to
memory
voltaqe
This
ohmic
The
determined
curves
for
a
voltage
illustrated bus
setting.
the
relay
is
will
action
on
if
zone
operate
action.
the
pullback The
reach
itho
unit
curves
of
few
levels
and
Fig.
effective,
operate
will
the
2
setting
for
ohmic
unit
tap
will
by
tests
were
Fig.
cycles
therefore,
3
setting
close
tripping
nearby
value
or
reach
settings.
Operate
performed
obtained
illustrate
3
following
where
for
a
shows
regardless
Fig.
if
the
of
faults
reduction
it
zero
to that
3
I3
contact is the
at
which
in
percent
Note for
with
the
enables
voltage
protect
the
shows
is
greater
delayed.
type
and
all
with
the
who of that
for
RPM
there
GEK-45495
the
in
reach of
that
points no
full
effect
inception
the
fault
for
unit,
the
mho
than
only
When
relay,
will
niho
the
voltage rated
who this
tap
unit
the
unit is
setting
fault
to
of
of
unit
by
under
setting.
1.6
a
short
the
be
shown
the
supplied
voltage
memory
the
referring
fault,
with
amperes.
relay
static
sufficient
will
is
plotted
current
right
fault.
to
operate
it
static
a
period
is
action
However, three-ohm
operate
in
Fig.
against
scale
of
the
to
the
of
120
in
This
for
to
Fig.
is
imperative
conditions,
of
time
used,
as
characteristic
voltage
may
for
3
changes
volts
the
memory
low
3.
under
basic
a
be
curve. relay
supplied
who
A
and
second
to
somewhat
the
1,
the
with
before
unit
action
fault
zero
that
will
dynamic
minimum
therefore, should
give
lower
and
2
three—phase
the
The
steady-state
the
the
to
which
is currents. voltage the
relay
not
see
conditions
reach
zone
relay
be
used.
tripping
than
3
ohm
fault
basic
fault
relay
maintains
particularly
This
fault
reach fault
a
and
memory
and
without
the
basic
r,iniiuuw
curves
W.i
before
must
when
100
action
tripping
For
this
cur
the
can
be
zero at
5.
Operating The
setting relay fault.
rnho TAPPED
operating
of
voltage
Time
taps
were
AUTO-TRANSOFRMERS
The
ohmic auto-transformer The
other
winding
The
necting
desired
the
subtracted
The
ale
tap
impedance
1:
neutral
:Xj
TAP
the
prior
curves
in
two
from
setting
SETTING
Time
time
unit,
the
reach
has
is
tap
windings
the
expressed
of
fault
to
the
are
given
100
of
the
two
windings.
tapped setting
of
15-95
required
DESIRED
the current fault.
percent
(See
mho at
the
percent
in
who
unit magnitude, The
for
four
position
Fig.
7)
units
may
One
percent,
0
is
made
by
auto-transformer.
winding.
to
protect
secondary
Tap
Setting
where:
=
91
is
curves ratios
winding
the
a terms,
0 9
determined
ratio in
of
and
the
be
adjusted
1
percent, proper
zone
(100)
=———
Power Angle
Fig. fault
angle
is
tapped
location Note
Z
ohms
is
determined
(Mm.
factor
of
maximum
by
of
fault
8
impedance
by
percent
3
long,
a are of
means
in
that
Ohms
angle
number
impedance
for
the
maximum
of
10
percent
and
of
the
the
0—5
where
by
the
Setting)
of
fault
torque
of
to
torque
taps
5 leads
Z
of
factors
to
condition relay
on
steps
percent.
marked
percent
is
positive
following
Cos
impedance
the
unit
relay reach
was
the
winding
(—@)
such
as
reach,
of
rated
setting.
set
at
two
auto-transformers.
from
15
No.
1
may
phase
equation:
the
and volts
60
degrees
percent
and
sequence
basic
magnitude
In
the
be
added
minimum
prior
all
lag.
to
jumper
phase-to-
to
cases,
95
or
reach
of
the
the
Each
percent.
con
cite
:xample
m,Nate
Set
Set
the
the
2:
one
4
TAP
one
4
end
percent
SETTING
end
percent
of
of
jumper setting
DESIRED
jumper
setting
lead
of
lead
of
the
the
to
89
to
95
0—5
85 0-5
percent.
percent
percent.
percent
Set
winding
Set
winding
the
the
6
other
subtracts
other
adds
end
to
percent.
5
from
the
95
end
to
percent.
the
85
1
percent
to
percent
Set
setting.)
Set
No. setting)
No.
1
to
1
percent.
1
to5percent.
GEK-45495
BURDENS
CURRENT
CIRCUITS
The
This
or
50
cycles
POTENTIAL
The
The The
setting
maximum
data
will
CIRCUITS
maximum
CIRCUIT
Polarizing Restraint
Polarizing Restraint
potential
restraint
is
less
current
AMPS
5
is
for
be
potential
than
the
lower.
burden circuit
100
burden
CYCLES
3.0
burden
of
burden
percent.
imposed
ohm
FREQ
60 60
50 50
the
basic
imposed
niho
and
unit
hence
on
R
.043
reach
on
R
1534 1060
2200 1160
each
each
is
maximum
the
current
tap
TABLE
setting
potential
TABLE
total
transformer V
X
.026
VI
X
10
1580
35
1
1600
when
relay
for
60
transformer
restraint
the
burden
at
P.F.
0.86 cycles.
P.F.
1
.00
0.55
1.00
0.73
will
amperes
5
The
at
tap decrease
WATTS
1.08
120
WATTS
is
is
burden
volts
9.4
4.2
6.5
4.3 set
when
listed
for
for
is
100
the
in
VA
1.25 the
lower
listed
VARS_—
0.1
6.3
0.4
5.9 percent.
restraint
Tah1€
in
.
tap
Table
VA
9.4
7.6
6.5
7.2
tap
setting
VI.
formula.
watts
(wattc
The
The
and
+
Tcride
potential
terms
vars
vars)
j
(a
with
230kv
burden
+
for
jb)(c
their
at
+
jd),
taps
restraint
transmission
PT CT
tap
VA
Zpri
Ratio Ratio
sec
z
settings
=
etc.
on
100
circuit
ec
+
jb)
(a
represent percent.
and
line
50
0.14
=
50
(0.14
=
230,000/115
=
600/5
=
pri
=
than
less
rTap
L
(c
÷
Setting] 100
the The jd)
100
burdens values
=
CALCULATION
long
miles
ohms
0.80
+
j
jO.80)
+
=
2000/1
=
120/1
CT
Ratio
PT
Ratio
+
j40.Q)
2000
(watts
OF
having
=
120
percent,
2
of
of
+
SETTINGS
a
nile,
per
7
+
j40
=
0.42
be
+
mho
terms
calculated
unit
are
for
+
the
these
j
can
(c
vars)
phase—to—neutral
ohm
total
j?.a
+
ohms
potential
given
polarizing
impedance
from
in
the
circuit
Table
circuit.
following
VI.
of:
expressed
(a
in
=
+
jb)
Zsec
=
2.43
80.5°
/
ohms
7
GE
K-45495
Assume
is
it
this
For given
The
both
at
case
the connection
external
overlap
(see brush locking
leads bottom
connections
cover,
mechanism
thick
insure
to
panel
the
drawn
‘abo1s nagram
ito
a’
2.
minmJm
most
orotect
that
application
section
the
type
in
studs
plug
connections
circuit
the
when
contact
circuits.
relay
by
between
is a
is
relay
appropriate
that
either and
1
aid
tc
usea in
Fip.
ralav
after
CEYS2
are
which
connections
mechanism
a
part
case
proper
replaced
icaludes
uesired,
*i
ends
Every
internal
make
The
terminated
and
which
The
and
separate
A
out
Pies.
The
wittrrisforrners
The R23
The
he
hese
rio
ssed
reach
tap
removed
relays,
them
sub-a;seIHbly
in
car
blockS
against
CEY52
the
considering
the
under
relays rear
the
made
and
in
connecting
as
at
the
guide
the
drawn
of
is
testing
from
2
show
identify
10.
settinq oe
for
from
when
is
to
three-ohm
CHARACTERISTICS-
Percent
750
80.5°
are
external
for
inner
the
drawout
plug
Fig.
in
mounted
is
inner
the
at
respective
case
the
cover
can
plug
own
another
relay
the
=
Percent
Percent
assembled
block.
will
source
z
=
=
9
=
through
completes
the
indicated
pin
to
the
suitable hardware hardware
its
by
nircuit
similar
th’en
and
tap
includes
angle
tie
adjusted
from
changirg
to
case
its
included
not
damage.
Irnediately
used
be
effects
the
basic
3.54
stationary
circuits.
the
blocks
case
withdrawn
is
10) Fig.
in
inasteel
back
blocks
by
assembly.
either
for
available.
is
be
which
removed
components
blocks
the
the
the
make
conjunction
in
of
minimum
TAPPED
Setting
Tap
Minimum
Setting
Tap
Setting
Tap
in
a
connections.
molded
have
an
has
on
and
with
9
cradle
This of
the
of
thumbscrews,
semi—flush
included.
be
inserted
current
of
has
been
ro
are
suhassembi:
rho
mounted
i—pole
fOL
f
ma.’inlui
front
r;inioum
basic
the
settings.
RECEIVIND,
i
part
as
upon
with
infeed,
reach
CONSTRUCTION
deep
The the
auxiliary
or
those
adequate
framework
case. the
However,
in
place
and
its
the
to
setting
AUTO-TRANSFORMERS
(100)
=
Ohms
(100)
=
=
size,
large
electrical
The
and
inner
inserted.
is
cradle
holds
outer
terminals
circuits,
held
The
or
panel
blocks
brush,
pressure
called
connecting and
the
surface
of
voltage,
tested
in
drawout
arie
Cienents
‘bc
or
back
or
the
inS
relay.
torce
of
reach
a
AND
control
of
HANDLING
of
receipt
a
set
(Mm.
3.0
(3.6)
outer
Some
firmly
case, connecting
the
the
case
those
as
-‘
rrnostats
of
ne
STORAGE
panel,
relay,
a
CEX2OA
relay
the
should
ohms)
7
at
60
Cos
3.64
double-end
blocks
attached
for
the
shown
as
circuits
is
it
to
the
in
also
mounting
thickness
connecting
from
or
laboratory.
wth
which
mojntcd
the
ossoc
units
provide
to
to used.
be
is
used.
Cos
deg.,
(80.5
connections
internal
in
especially
prevent
cradle
case
the
plug,
locks
plugs
must
plug
other
all
appear
on
cradle.
i
ated
,
811
are
will examine
reach
(0—9)
3.6
75)
(L2D)
between
the
to
Fig.
are
the
and
besides
on
be
sources;
major
the
See
circuit R2,
mounted
shipped
be
it
second
3.64 ohmic
The
75
at
drawout
between
which
case
connections.
to
9, equipped important
opening
isacomplete
latch
a
with
making latch
the in
place.
panels
all
indicated
test
to
components
the
an
front
Rj
05
cunipcnents.
used
813
on
in
any
for
/80.50
dog.
have
provide
the
or
of
the
zone
reach
case the nests
the
with
that of
at
the
in
place.
The
up
on
relay
the
interncl
the
and
jr
back.
cartons
4
mage
protection
secondary
having
relay
a
studs
adequate
shorting
the
important
unit both
electrical
target
two
to
the
relay
ider.ti
cradle
2
heostt.
settinj
sustained
equation,
units
removable
auxiliary
with
top
The
reset
inches
relay
in
place
ca
fiec
connection
ann
the
The
designed
studs
for
bars
inter
be
-
relay
and ohms.
and
th’
all
and
order
on
a
basic
to
in
GE
K-4
5495
transit.
transportation
Reasonable
or
the
adjustments
If place case
the
that
may
Immediately
no
damage
exwiination ViSUAL
INSPECTION
Check
requisition.
Remove
of
physical
MECHANICAL
It
1.
2.
3.
4.
is There
Make
With
moving
5.
The
armature
at
least
6.
Check
diagram
If
injury
company
care
relays
is
free
find
its
has
been
or
test
the
nameplate
the
relay
damage,
INSPECTION
recomended
should
sure
control
the
relay
contacts
1/32
the
location
for
the
or
disturbed. are
from
way
upon
sustained
indicates
and
be
no
well
of
and
inch
relay.
damage
and
should
not
moisture,
nside
receipt
stamping
from
that
that
noticeable
springs
leveled
the
contacts
wipe of
promptly
be
to
when
of
in
that
its
all
the
units
on
the
resulting
exercised
be
installed
dust
the
the
shipment
readjustment
to
case
screws
mechanical
friction
are
not
in
should
of
the
the
seal—in
contact
notify
relay,
insure
and
its
seal-in
from
in
and
cover
and
check are
adjustments
deformed
upright
rest
brushes
rough
the
nearest
unpacking
ininediately,
metallic
is
removed
ACCEPTANCE
an
inspection
that
the
is
that
the
that
tight.
in
the
and
position
against unit
should
contacts.
on
the
handling
General
the
chips.
and
relay
necessary,
model
there
in
rotating
spring
the
cradle
is
relay
they
should
Foreign
cause
TESTS
and
calibrations
number
are
no
Table
structure
convolutions
the
contacts
backstop.
move
and
evident, Electric
in
order
be
matter
trouble
acceptance refer
to
and
broken
VIII
freely
case
rating
or
be
of
of
when
blocks
file Apparatus
that
stored
collected
in
tests
have
the
section
cracked
checked.
the
do
not
all
operated
a
damage
none
in
the
should
not
of
units.
touch
three
against
Sales
of
their
operation
been
on
the
relay
molded
each
units
by
the
claim
at
Office.
the
parts
original
on
the
outside
of
be
made
disturbed.
SERVICING.
agree
parts
other.
must
hand.
internal
once
the
to
or
be
There
with
are
injured
cartons
of
relay.
insure
If
with
the
other
open.
should
connection
the
in
the
that
signs
The
the
a
be
L[CRJCAL
1
a.•
s:er
1
r.r
rTJ-:’
wit-c
;ese
•idjtrnentc
Test
(a)
Fig.
11
sho
;etion-.
setiini
and
CHECKS
e:-
cernected
s’r
jt
.,.
r
ur
t.
r1ecs
re
connections Control Re
sure
leave
-
WHO
be
i1ane or
to ibratd
to
T
he
mho
necessarY
Spring
that the
restraint
UNiTS
adde
energed factory
check
uitc
the
follewing
for
checking
Adjustment
the
ss
relay
with
shown
meters
refer
Rotating Contact Contact
adjustment
the
were
to
is
taps
e1a
in
at
are,
fctory
carafully checks
the
correct
level
in
CHECK
in
Fig.
rateu
of
section
the
POINTS
Shaft Gap Wipe
case.
l
vcltiqe
and
:ovrse,
sOttinU
indicate
mho
in
its
100
TABLE
End
Before
an•
be
if
rechecied
Lnd
adjusted
on
unit
upright
percent
VIII
Play
f
I
____
any
allowed
and
the
esential
calibration
at
the
conclusively SERVICING
operation.
position.
position.
9
MHO
.010 .145 .003
electrical
to
restraint
when
factory for
-
-
-
warm
col
by
that
the
UNITS
.015
inch
.155
inch
.005
inch
checks
op
for
taps
a
will
means
and the
settings
recommended
Leave
the
are
approximately
set
at
tend
to
of
the
it
is
not
relay
made
on
100
percent.
underreach
test
described
advisable
have
procedures.
connected
been
the
15
disturbed.
mho
minutes
The
by
in
to
disturb
as
shown
3
units
units
or
the
with
4
the
the
per
fol
If
in
voltage
the
angle
the rent
should
value
to
across
dbout
occur
Use
shown of
following
the
relay
in
Table
maximum
amperes.
two
between
voltage torque
the
procedure
studs
for
IX
of Gradually
currents
the
the
at
unit
unit.
listed
checking
in 120
volts,
being
Now
increase
in
reduce
Table
GEK-45495
each
set
tested,
current:
the
IX.
the the
unit.
that
phase vol
until
is taqe
With
shifter so
the
current
to
the
current
so
the
contacts
low
that lags
test
set the
voltage
voltage
of
the
amperes
five
at phase—angle
by
an
and
just
unit
meter angle reduce
close.
and
reads
equal
the
the
to
cur
This
(b)
prevent
to approximately
of
terms
ii
in
45
Table from studs
amperes
value leads relay and
(c)
position,
angle
the
normally screws
open
on
table.
minimum
the ing
reach.
units basic
nameplate
Clutch
mho
Toe
damage
40-60
volt-amperes
ise
the
X tap
the
set
for
Ohmic
the
With
connections
make
shown
reduce
Now
contacts transactor
the
that
Note
relays
The
in
the
minimum
marking.
Adjustment
units
during
grads
connections
the
for
block
120
at
the
Reach
relay
the
in
the
for
are
intermediate
reach
include
heavy
applied
by
unit and
volt
unit
3c
still
table
voltage
of
the
tap
the
normally
taps,
the
of to
set
increase
shown
for
unit
blocks
test
setting, 2
high-set
a
conditions.
fault
tangentially
following
Fig.
be
checked,
the
just
or
connected
Table
in the
the
to
just
are
conditions,
shipped
3
or
11
mho the
above
unit
that
ohms,
clutch
method. and units
current
as
X
to
value
close.
set
from
set at
52
shown and
be
to
the
is
the
at
the
120
for
until
amperes
set checked.
shown
This
the
mho
the the basic
between These
the
moving
phase
volts
maximum
Fig.
in
the
in
should
position
units
factory
ohm-tap.
2
reach
the
clutches
and
ohm
the
for
11
phase
Table
cup
contact.
shifter
5
clutch
1
.5s2
and
shifter
X
occur
which
see
with
of
the
shaft
and
have
been
that
so
amperes.
minimum
basic
just
unit.
restraint
the
so
increase
and
within gives
a
phase-to-phase
basic
the
units
the
If
units
set
This
Disconnect
slips.
that
the
the
minimum
will
assembly
at
can
phase—angle
the
reach.
This
tap
the
the
limits
basic
are
be
and
the
be
best
the
With
should
leads
phase-angle
current
shown.
minimum
fault
reach
on
set
within
the
factory
checked
No.
the
in the
gradually
reach
twice
of
adjustment
either
+4
percent
moving
meter
1
occur
Note
slip
to
in
reads
restraint
voltage
between
100
meter
that
shown
the
the
of
contact
the
percent reads
until
basic
taps
of
at
field
the
across
the the in
of
remain the
tap 26
tc
the
tap
be
to
tat
should
1’crease
cnown
the
(d)
leads
checked.
the
in
mhci
Angle For
set
In
phase-angle
he
t
‘ie
the
unit
Connect
of
checking
100
at
The
ciecking
mDeres
5 current table.
Tii
Maximum
the
percent
minimum
the
meter
and
s1owly
:10w
carren:
relay
the
UNIT
LOCATION
TOP MIDDLE
bTTl
Torque angle
mho
rcset
position,
reach
reads the
until
should
as
of
units
330
voltage the
follows:
F-
maximum
taps
the
degrees.
nho
the
phase fall
3T
l-2
and
with
should
following
120
at
unit
angle
within
LEAD
14-15
13-16-17 1L-19-20
torque
the
be
Note
volts.
picks
at
the
CONNECT
TUDSA
A
the
voltage
set
to
procedure
that
Now
up.
degrees
270
same
.
LEAD
13—16-17 18-19-20
l4-15
connections
set
at
position.
2—ohm
the
should
while
the
the pickup and
as
LEAD
voltage again
for
set The
limits
LEAUTORELAY
.
B
7 9
of
the
be
phase
current
C
Fig.
value
used.
check
the
11)
LEAD
7
9
5
will
11
showninTable
First
is
angle
the
at
should
the
degree
330
JUMPER
STUDS
D
6-8-10 6-8-10
6-8-10
be
set
being
value
current
used
be
check.
the
set,
shown
within
with
XI
phase
the ir
required
the
the
for
Table
restraint
the
shifter
currert
1
imits to
unit
Yl;
pick
sc
u
in
TABLE
IX
tEK-45495
(CONTROL
SPRING
ADJUSTMENT)
LOCAION
TOP MIDDLE BOTTOM
LOCATION
TOP
MIDDLE
BOTTOM
UNIT
LO
TION
TOP MIDDLE BOTTOM
PHASE-ANGLE
METER
SETTING
3000
3000
300°
PHASE-ANGLE
METER
SETTING_—
300° 300°
3000
TABLE
PHASEANGLE
ANGLE
MAX.
OF
TORQUE
3000 3000
3000
TABLE
(ANGLE
XI
METER
TEST
2700 270°
2700
SOR
1.5
Volts
Volts
1.5 Volts
1.5
(OHMIC
X
O.5/l.O/1.5c1UNIT
.oc
1
-
READING
Volts
30
Volts
30
Volts
30
OF
MAXIMUM
ANGLES
3300
and
3300
and and
330°
-
O,5/l.O/L5c2UNIT
ADJUSTMENT)
REACH
VA-B
SET
TAP
TORQUE
1
.5sz
5/1/1
TAP
l
30 30 30
PICKUP
]iZTAP
6.0-7.0
6.0-7.0
6.0-7.0
AT
l/2/3cUNIT
2i2
TAP
Volts
60
60
Volts Volts
60
ADJUSTMENT)
VA-H
SET
UNIT
AT
l/2/32
2s
AMPS
UNIT
TAP
60 60 60
l/2/3I2UNIT
22TAP
3.0-3.5
3.0-3.5
3.0-3.5
PICKUP
AMPS
14.6-15.4
14.6-15.4
14.6-15.4
AMPS
16.5-18.5
16.5-18.5
16.5-18.5
Note
away
from
shows
0.866
that
times
ELECTRICAL
target
The
2.0
amperes
The
of
1
through
so
that
increase
Do
relay
the
point stud also and lower.
LOCATION
The
The
location
be
relay
16.
should
MOUNTING
Fig.
in
that the
the
the
TESTS
depending
seal-in
the the
not
well
the
angle
ohmic
reach
seal-in
is an
seal—in d—c
attempt
lighted
should
two
angles
of
maximum
reach
at
TARGET
on
shipped
unit
adjustable
current
to
of
the
to
be
of
the
SEAL-IN
unit
model
from can
contact
interrupt
relay
facilitate
mounted
used
torque.
the
angle
either
ordered.
the
be
resistor
will
until
should
on
in
unit
of
has
factory
checked
the
the
inspection
a
the
previous
An
examination
should
maximum
operating
an
with
by
connecting
and
an
protect
seal-in
current
d-c
INSTALLATION
be
clean
vertical
be
the
torque.
the
ammeter
the
ruho
unit
and
and
surface.
check,
same
coil
tap
back
unit operates. by
dry,
testing.
means
i.e. the at
330
mho
both
of
tapped
in
screw
from
d-c
source
to
(-).
contacts.
It
of
the
PROCEDURE
free
from
The
outline
degrees unit 330
at
the
Connect
should
dust,
degrees
0.6
lowest
Then
reho
and
and
impedance
or
2.0
tap
(+)
to
jumper
a close
pick
contacts.
excessive
panel
degrees,
270
characteristic
and
270
amperes
position.
stud
11
the
at
up
heat
drilling
degrees
or
of
from
mho
tap
and
are
and
tapped
The
the
relay
stud
12
unit
contact
value
or
vibration,
dimensions
degrees
30 in
Fig.
should
at
0.2
operating
and
stud
to
slightly
are
from
by
and
shown
6
be
or
11
hand
11
Loading...
+ 25 hidden pages