BEFORE YOU BEGIN
Read these instructions completely and carefully.
WARNING/AVERTISSEMENT
RISK OF ELECTRIC SHOCK
Turn power off before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL or IEC approved wire for input/output connections.
Minimum size 18 AWG.
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des ls approuvés par UL ou IEC pour les entrées/sorties de connexion. Taille minimum 18 AWG.
Installation Guide
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. CAN ICES-3 (A)/NMB-3(A)
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Save These Instructions
Use only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.
Prepare Electrical Wiring
Electrical Requirements
• The LED driver must be supplied with 120-277 VAC, 50/60 Hz per product label and connected to an individual properly grounded branch circuit, protected by a 15 or 20 ampere
circuit breaker.
Grounding Instructions
• The grounding and bonding of the overall system shall be done in accordance with National Electric Code (NEC) Article 600 and local codes.
Tools and Components Required
• ALC3 Series xture
• Chain or cable (80 lbs. minimum load rated) or RodMount kit
Cord Install:
• SJO or SJOW cable
• UL Listed strain relief(s)
(Hubbell SEC5O strain relief or UL listed equivalent)
Conduit Install:
• 1/2” trade size exible conduit
• 1/2” trade size conduit
imagination at work
Page 2
Electrical Connections
Carefully unpack unit and properly inspect for defects
1
before installing. Wear work gloves to prevent dirt and oil from being transferred to the luminaire.
A) Conduit B) Power cord
Option 1: power input from side. Remove knockout in
3
endcap and A) Install 1/2” conduit, or B) install AC power cord with strain relief. Plug unused hole on top with appropriate tting.
For safety, turn off main power before installation of
2
xture.
A) Conduit B) Power cord
Option 2: power input from top. A) Install 1/2” conduit,
4
or B) install AC power cord with strain relief.
Assuming Option 2 was chosen in previous step, remove
5 6
access panel to reach power supply wiring.
Restore main power.
7
Connect the green (ground), black (line) and white
(neutral) wires of the AC line to the similarly colored wires of the xture’s power supply using UL listed wire connectors. Re-attach access panel.
Page 3
Mounting Options
Please follow all UL, NEC and minimum load rating guidelines when selecting and installing a chain, cable or rod.
OPTION A
Hang two chains/cables (rated to support a minimum load of 80 lbs.) from a structural member of the ceiling. Fixture must be
1
supported independently of an outlet box.
Attach chain or cable to mounting holes on the end plates at both ends of the
2
xture. Assure that the xture is secure and cannot come free of mounting means.
OPTION B
Cable or Chain
Attach to structural member
Rod Mount Kit
Attach to structural member
NOTE: When selecting chain, a joint in a circular chain link shall be welded. A joint
in a chain link of another shape shall
not be located within 30 degrees of the
vertical unless welded.
Materials Required:
• 3/8” threaded rod (Qty. 2)
• 3/8” nuts (Qty. 4)
• Rod Mount Kit
Attach all rod mount brackets to xture end plates
1 2
using screws and lock washers supplied in the Rod
Mount Kit.
Attach to structural member
Fasten
with nuts
Secure 3/8” threaded rods into structural members in the ceiling. Place a nut on each threaded rod where xture should hang. Slide xture onto threaded rods, and place second nut on to threaded rods to secure xture in place. Assure that the xture is secure and cannot come free of
mounting means.
GE Lighting • 1-888-MY-GE-LED (1-888-69-43-533) • www.gelighting.com