Page 1

INSTRUCTIONS
TYPE AKD-5
GEK-72r01
8-77
tOW
VOLTAGE
\
l'\
SWITCHGEAR
ilH
;q
M
,
il}
il
GENERA
L@
ELECTRTC
Page 2

2 | 0 l, Low V oh
GEK-7
ge
Swifchgeor
o
CONTENTS
INTRODUCTION
RECEIVING,
Receiving
Handling
Removing
HANDLING, STORAGE 2
Shipping Skid ..
Indoor
Equipment Only ..
........ 4
Storage
DESCRIPTION
Front Enclosure ...
BreakerCompartments....
Bus
Compartm€nt .
Feeder Cable and Busway
...
Compartment
......6,7
........ 8
GroundBus.. 9
Outdoor Equipment
EQUIPMENT INSTALLATION
Prior to Installation
Location
FoundationRequirements.....
Anchoring
Assembly of
Equipment
INTRODUCTION
This book contains
and maintaining AKD-6 Low
read carefully before
be
instructions for installing, operating
Voltage
Switchgear. It should
installation and
For application and specification information, refer to
Bulletin
lays or other devices
GEA-10279.
Separate
In
addition
publications
will be supplied for breakers, re-
not
described in this
to instruction books, the following
will be supplied:
l. Front
2. Summary of switchgear
3.
View and Floor Plan drawings. These show
general
the
space, etc.
parts
list,
vices,
etc.
Electrical
arrangement,
giving
catalog numbers of all breakers, de-
diagrams
height, recommended aisle
equipment. This is
(when
required).
........ L2
initial operation.
manual.
drawings
a
10
partial
2
Breaker
Breaker Operation
TESTING AND INSPECTION
RACKOUT MECHANISM OPERATION
4
5
6
6
8
KEY INTERLOCKS
For Breakers
For Fuse Rollouts
DOOR
RACKOUT
9
10
10
10
11
PADLOCK DEVICES
MAINTENANCE .
Breaker and Instrument
Bus Compartment .
Feeder Cable and
Overall
Paint Refinishing
RECEIVING,
RECEIVING
Every
case number, requisition number and customer's order
number. If
numbers
unit
package
All equipment leaving
packed
and
packing
and
apparatus,
sustained
Air
circuit breakers are
cartons
breakers should
possible
Be
sure to inspect devices mounted
side the hinged
Insertion
and Removal ..... L6,L7
INTERLOCKS . . . . .
MECHANISM
Compartrnents ......
Busway
Switchgear
Compartment
..
HANDLING
package
leaving
the equipment has been split
the factory is
AND STORAGE
plainly
for shipment, the
of the equipment enclosed in each shipping
are identified.
personnel
by
of
electrical equipment.
make
the factory is carefully inspected
experienced in the
Upon
inspection immediately for
an
proper
while en route.
with the
shipped
breaker in the open
separately
position.
be unpacked and inspected as soon as
after they have been received.
in compartments in-
doors.
......
. ....
marked
receipt of any
in individual
with
handling
damage
Circuit
22
22
24
26
26
27
2E
30
30
30
31
31
31
3l
All of these documents are needed for installation, op-
eration and maintenance of
in
packet
a
tingcncy
should
relcrred
inside
breaker compartments.
insfruclions do nol
fficse
to b. ,r6t in connec'lion with
parlicvlar
lo lhc
the auxiliary unit, or in one of the
problems
Gcncrsl
found
instrument or
equipment. They will be
the
pwport
orisc wfiich
Elcclric
Compony,
oll delails or
lo cover
instsllation, operclion or moinfsnonce.
crc nof covered sufricicnlly
is
portation
Sales Office
number, case
compeny the
vorialions
If
damage is evident, or indication of rough
visible,
file a claim
company. Notify
promptly.
in
eguipmenf nor lo
Should
for
pvrchoser's purposel,
lhe
number,
claim.
for
Information
requisition
provide
luilher
damage at once with the trans-
the General
lor
evcry
inlormalion bc
thc maltcr should
Electric Company
on damaged
number, etc.,
possible
desired or
handling
parts, part
should ac-
con.
bc
Page 3

The
Master
case
operate
paint,
items
crate,
contents
Packing
in
which
the
breaker
packed
are
the list
of
each shipping
List.
miscellaneous
equipment
closing devices,
in
a switchgear
will
indicate
package
This list indicates
parts
(such
as
needed
contact lubricant,
etc.) are located If
unit instead
the
appropriate unit number
are listed
the number
to install
touch-up
a
of
separate
on the
of the
and
such
Low
V ohage Swifchgeo
r, GEK-7 21
0l
which they are stored.
Large
used
with indoor equipment)
separate
To avoid the loss of small
contents
in
JACK
the
HEAE
packing
E
U
6
=
v
(such
items
crates
as hoist
or cartons.
of each case should
list
before discarding
NOI FUFNISHED
a
wrrH EoUTPMEN?
/l
rrE
/ |
t/
tt
'ABLE
1
dollies
will
parts
be carefully
6
U
o
hoist
and
always
carriages
be shipped
when unpacking,
checked against
packing
the
material;
in
the
FUR}{ISHEO
NOT
WIYH
EOUIPUE}IT
RECOMMENDED
FRONT
VIEIV
METHOD
RECOMMENDED
AFTER
SHIPPII{G
ROLLEFS
EOUIPMENT
OF
LIFTING
SKIDS ARE REMOVEO
MAY
6E USEO
PARALLEL TO FRONT
TO
ROLL
stoE vtEw
METHOD
ONLY
OF JACKING
HOIST RAIL
WHETI FUFI{ISHED
FROTIT
(FiONT
CHANNEL
ONLY}
FlG. I
(0673D0500-265)
Methods of
Hondling Indoor
Equipment
Page 4

GEK-7
21
01,
Low
V oh
age
Swilchgeor
HANDLING
The switchgear units are best handled
are
provided
crane
top of
on
for lifting, a cable spreader must be
pull
the shipping skid should
on the lifting lugs, Recom-
lugs
able
When using a
used to obtain a vertical
mended lifting method is shown in Figure 1.
practical,
If
by crane.
the indoor
be left on the
equipment until it is at or near its final location.
If
crane facilities are not available, the equipment
be moved into
placed
under the
is insufficient, the
equipment
under the equipment.
The skid is
position
by means of construction rollers
shipping skid. Where overhead clearance
shipping skid may be removed
moved by rollers
bolted
placed
to
the equipment
the
under
through the anchor
three
Remov-
switchgear.
may
and the
channels
bolt holes used for final installation.
of the
equipment
To
reach the bolts in the
may be reached
front,
bottom breaker compartment must
disconnected
and
the drawout
CAUTION:
MOVED, BE
ARE SPACED
NEI,S
DIRECT
BETWEEN
position.
Fig.
procedure
IF THE
SURE THE ROLLERS USED
SO
RES? O1V
APPLICATION
TOP
THE CHANNELS
3
is
SKID fI.4S BEEN RE-
THAT
DISTORT THE ESUIPMENT,
may also be used to handle the
Jacks
crane is not
FUFNISHED
NOT
WITH
SWGR.
available. See Figures 1 and
The bolts in
by opening the rear
the
rear
doors,
the'inner housing in the
shows
be brought out to the
the front
explained on Pages 16 and 17.
bolt
locations,
THE THREE CHAN-
OF THE ROLLERS. A
THE ROLLERS
OF
TEAR
MAY
equipment when a
2.
OR
FRONT
TIMBER
JACKING
FURNISHED
NOT
VJITH SWGF.
ll
'1
-lffill
[v_L_\
"^"..)
PARTIAL
FRONT OR REAR
FON
JACKING
FlG.
2
VIEW
RECOMMENDED
I
VIEW
METHOD OF LIFTING
PARTIAL
FOR
RECOMMENDED METHOD OF JACKING
(0673D0500-266)
Methods of
Hondling
Outdoor Equipment
srDE vlEw
SIDE
JACI(ING
VIEW
JACK
HERE
Page 5

Low V oltoge Swilchgeo
r,
GEK-7
21 0l
Methods of handling outdoor
ure 2,.are much the
that lifting
The lifting
permanently
is
of the
Store
upright
vent bending
parts.
ready to be installed.
absorbent
breakers.
STORAGE
If
breakers are not to be
them from
them. If ever5rthing is in
breakers
plates
plates
equipment will not be obstructed.
the circuit breakers
position.
Do
not remove
paper
their shipping cartons and
in their
same as for indoor equipments except
provided
are
should
anchored
They must
of the studs or damage to any
any
A covering of kraft
prevent
will
satisfactory
shipping cartons for storage, Do not re-
switchgear,
at the base of the structure.
be removed after the equipment
so that
passageway
in a clean,
properly
be
protective
dust from
placed
in
service at once, remove
shown in Fig-
at the ends
dry location in an
supported to
the breaker
of
grease
until
other non-
or
they
settling
thoroughly inspect
condition,
replace
on
pre-
are
the
the
move the
shipping
If it is necessary to
time, the
of
vent corrosion
IJncrate
1.
2. Store in a
temperature
vent dirt,
ing
If
3.
the storage
units to
watts of heat in each
switchgear
temporary
ready installed
CAUT|ON:
switchgear.
the
dampness or condensation
members
following
store
precautions
this time.
at
the
equipment for
should be taken to
or deterioration.
the
equipment. Check thoroughly
clean, dry, rodent free
water,
provide protective
and
or other foreign
location
substances
may
location, heaters must be
prevent
moisture damage. Approximately 250
unit is required. On outdoor
this may be accomplished by making a
power
supply connection
in the equipment.
REMOVE
ALL CAR?OJVS
OTHER MISCELLANEOUS PACKING
TERIAL FROM IJVS/DE
ENERGIZING
WIREWAY,
BREAKER
ANY HEATERS.
OR
THE UNITS BEFORE
INSTRUMENT
COMMRTMENT.
A
.
MENT
I
any length
pre-
for damage.
moderate
with
coverings'to
be
encountered
placed
pre-
from enter-
inside
to the heaters al-
AND
MA-
lrl
lrll
llnrl
u4
)
FULL
HEIGHT
WIRE
TROUG
WHEN
in
the
FIG. 3
(0673D0500-265)
front
in
Locotion of skid
of lndoor
Equipment
bolts
(ond
onchor
bohs)
BREAKER
COMPARTMENT
B
BREAKER
COMPARTMENT.
c
(0148A5073-0)
FlG. 4
CAB-E
Side View showing
Comporrmentorion
Page 6

GEK-7 21
01,
Low
oltage
Y
Swifchgeor
PRIMARY
SI{IPPIIG ilCKAGE
SECTIOI{
LOAD CENTER UNIT
SHIPPING PACKAGE
SUBSTATION
LOW VOLTAGE SECTION
SHIPPING PACKAGE
REAKER
UNITS
or3
ol5
(0102C5207-O
FlG.
5
Outline of o typicol lood
Substqtion
DESCRIPTION
General Electric AKD-6 Low Voltage Switchgear
free-standing assembly
Circuit Breakers and other auxiliary
tive devices. It may
double-ended Load Center
Figure 4 is
showing compartmentation, and Figure 5
an outline of a
a typical single-ended Load Center
trating the nomenclature used for all
All of the switching and
metering devices,
formers are mounted in the enclosure. The breaker
are
of the drawout type. The breakers
all
-coupling
self
incorporate
and
proper
compartments and devices is described in the following
paragraphs.
primary
positive
operating
of metal-enclosed units of Power
power
also be a
part
of a single-ended or
Substation.
Unit
side view of a typical
is
Substation
Unit
equipment.
protective
control
fuses
and secondary disconnecting
devices, control and
and instrument trans-
are
and indirect interlocks to insure
sequence. Each of
the individual units,
circuit
an outline of
provided
is a
protec-
unit
illus-
positions
with
contacts
showing nomenclqture
FRONT
ENCLOSURE
The front enclosure
dividual
power
a
and
other
BREAKER
MOUNTING
These breakers are supported
by a rollout track which
attached to the
The drawout mechanism
Figure 19, and its operation is
"Drawout
Cenfer
compartments. These
circuit
protective
COMPARTMENTS_AK BREAKERS_
CODE
Unit
of each
breaker or are used to mount instruments
devices and
2A,
3A,
4A,
is divided into in-
unit
compartments either house
control
OR 5A
components.
within their compartments
part
is
sides of the compartment. See Figure
of the drawout
is shown in an exploded view,
explained
Mechanism Operation,"
mechanism
in
detail under
6.
Page 7

low Voftoge Swifchgeo r, GEK-721 0l
BREAKER
BREAKERS-MOUNTING
These
same
COMPARTMENTS_AKR,
CODE 3A, 4A OR
breakers are supported on a rollout track
manner as the
AK breakers. However, since the
AKRU, AKRT
5A
in
the
rackout mechanism is mounted on the breaker, there are
jackshafts
no
on
both sides of the breaker
mechanism
Note
secondary
secondary
or not
be included at all,.depending
ified. Also note that
shown in Figure
material
A stop link is located on
compartments.
pushing
ally
the compartment
connected
breakers, the latches
pins prevent
all the
set on the tracks.
All
AK or AKR
in the
enclosure. See Figure 7. Racking arms
pins
fastened to
that extra items shown
disconnects,
disconnects) may appear in any compartment
the bracing for the
both sides
in Figures 6 and 7
position
7 may be a
instead of three separate
each
These
a breaker set
when the racking mechanism is in the
position.
the inner house from being manually
prevent
links
on
the
In a compartment made for AKR
rest
that
on the drawout
of the compartment.
switches and
on the equipment spec-
single
pieces.
side
an operator from manu-
tracks
way into the compartment when no
circuit breakers of the
frame engage
the drawout
ground
primary
piece
of
disconnects
of insulating
all AK
all the way into
mechanism
breaker is
same type
(such
sensor
breaker
moved
and
rating
which
have duplicate wiring may be interchanged.
Each breaker compartment has four
illustrated in Figure 18
CONNECIED POSIIION-The
1.
position,
and the door
TESI POSITION-The primary
2.
both
closed.
primary
described below.
and
and secondary
a safe distance, but the secondary
Any
as
3.
4.
breaker test not involving
position.
in
this
tion,
and must be closed before charging the spring
on a manually operated AKR breaker because an open
door
will
DISCONNECIED
secondary
WITHDRAWN
out
equipment.
of
NOTE:
its
ALTHOUGH
PARTMENT
ANY
POSITIOJV,Ijr IS
THE
DOOR ONLY BE OPENED
BREAKER
The door may be
interfere with
POSITION-Neither
contacts
the breaker
are made, The door
POSITION-The
compartment
The door must be open.
ready for removal from the
THE BREAKER
DOOR IUTAY BE
RECOMMENDED THAT
/S IiY THE DISCOIVJVECT
positions.
breaker
contacts are separated
contacts are
power
closed in this
handle travel.
the
breaker
They are
is in operating
contacts made
made.
be made
may
primary
may be closed.
is
posi-
nor the
completely
COM.
OPENED
WHEN
IN
THE
OR
by
WITHDRAWN POSITION.
CAUTION:
DOOR
AND IN THE
NEVER
OPEN THE BREAKER
WHEN THE BREAKER
CONNECTED POSITION.
CLOSED
'S
SECONDARY
DISCONNECTS
KEY
INTERLOCK
TRACK
LINK
ROLLOUT
OPERA
SHAFT
INDICATOR
CURRENT
TRANSFORMER
LOCK
LINK
STOP
ROLLOUT
TRACK
JACK
SHAFT
CHAIN COVER
GROUND
SECONDARY
SENSOR
DISCONNECT
HA,
6
$012645)
Typicol AK
breoker comporlmenl
Page 8

GEK-721 01,
SECONDARY
DISCONNECTS
INNER HOUSE
PADLOCK
INDICATOR
STOP
KEY INTERLOCK
DEVICE
LINK
Low
oltage
V
Swifchgeor
AMMETER
SWITCH
AMMETER
ULUJE
FUSES
INDICATING
LIGHTS
DRAWOUT
PIN
KEY
TRACK LOCK LINK
CURRENT
TRANSFORMER
ROLLOUT TRACK
GROUND SENSOR
SECONDARY
POSITION SWITCH
AND COVER
COVER
BRKR. COMPT. ONLY
BUS
the rear
necessary bus supports for
compartment
compartments
MECHANISM
INTERLOCK SLIDE
DISCONNEC
IN FUSED
REQ'D.
COMPARTMENT
The
bus compartment,
cable compartment, contains
is isolated from the
by barriers. Isolation barriers between the
between
particular
a
7
FlG.
the
front enclosure
of the bus and
all
section.
breaker
and instrument
(8041
585) Typicol AKR
This
and
bus
bus and cable compartments are optional. A typical ar-
rangement with an all-welded
Figure
8. Bolts are used for supports or at connections
aluminum bus
is shown in
which must be made in the field. Bolted copper buses are
optional.
On main breaker and tie
ment may be
divided into an upper and lower section
an optional isolation
section contains
connections in the auxiliary unit,
contains
Optional
sections
the
barriers at tie breakers isolate the two main bus
from each other.
the
main
bus which connects with the other units.
Aluminum buses run
breaker units the bus compart-
barrier. For main
incoming
line bus, fed from
breakers,
the lower section
while
continuouslv from one
the
the
unit to
by
upper
bus
{
iir
breoker comportmenl
another.
made to other equipment
is mad" for
between each
quate
be made from the bars
breakers to
arrangements
vided,
typical terminal arrangement is
the cable compartment of
partment
from above
of conduits leaving the
the normal available space.
At shipping splits,
or where connections
during installation,
unit.
joint.
Copper buses have bolted
the load side of the feeder
at
a bolted
FEEDER
The
CABLE AND BUSWAY COMPARTMENT
rear cable and terminal compartment
room for cable installation. Straight cable runs can
conduits entering above or below. Various
single
of
depending upon the
An add-on unit, 18 inches deep, is
or double cable terminals are
purchaser's
shown
requirements. One
in Figure
available
the 22 inch wide unit. The com-
is
extended when
or
below are used, and
more than
cannot be
unit
two
also when tlre
accommodated in
TEST
SWITCHES
TRIP
FUSES
ooon
INTERLOCK
-
are to be
provision
joints
provides
ade-
pro-
9,
for extending
busway runs
quantity
Page 9

Low
Voltoge Switchgeo
r,
GEK-72101
(8042652)
FlG,
8
Conduits
for
Bus
large
cable compartment
cables
as necessary.
Beside
clude an
of the
connections.
power
enclosed wiring
cable connections,
cable compartment,
Terminal boards
for making control
A neutral bus is
switchgear
bars
a
height of
feet.
ground.
GROUND
designed for
plated
with
about
In most
CAUTION:
equipments the
BUS
connection
IT IS
ESUIPMENT
FOR
SAFETY.
ComDorfment
cables should be near the rear
provide
to
trough on the left side
space
some
providing
provided
are
for bending these
equipments
control
for
in this
(rear
of the
view)
circuit
trough
wiring connections during installation.
provided
in the
cable compartment
four wire systems. It consists
18
areas, and is
inches from
neutral
VERY IMPORTANT
BE ADEQUATELY
installed at
floor
the
bus
GROUNDED
or at about
is insulated
THAT
either
from
in-
on
FlG. 9
$042651)
ground
The
partment
each
equipment for making
ground.
shown on
package,
ping
of
6
OUTDOOR EQUIPMENT
equipment
with a
provided
250
unit.
reduce
A recommended
Where
splits.
Outdoor
walk-in front
watt heater located
These
condensation
Typicol Terminql
bus is
near
bolted to the
the bottom.
A 4/0 connector
location
the floor
AKD-6
the
switchgear
completely
in all
plan
drawing.
switchgear is shipped
ground
bus must
is constructed
enclosed
aisle, Figure
outdoor equipments. There
in the
heaters should
in
be energized
the equipment.
Arrongement
in o
rear of the cable
is included
the
connection to the station
for
this connection
in
be connected at
in
a weatherproof
more than
as
a basic indoor
10. Space
heaters
is one 115v.
bus compartment
at all times
4-high
com-
the ship-
housing
of each
unir
on
is
one
are
ac
to
Page 10

GEK-7 21 0 1, Low V olt oge
Swif
chgeor
t0
FfG.
EQUIPMENT
TO
PRIOR
INSTAII.ATION
Before any installation work is
drawings furnished by G.E. Co. for the
tion. These include arrangement drawings
INSTAIIATION
performed,
particular
(front
view), connection and elementary diagrams,
drawings and a summary
ing information from
furnished
mary and identification number wherever
material
to meet local codes
the equipment, refer to
with
external to
the
(such
the equipment. When request-
of
the factory on
any specific item
the item
possible,
equipment which
as mats, screens, railings, etc.)
may
is not furnished.
LOCATION
In
locating AKD-6
space at the front
mended
and is in
should
air
taken into the
top,
aisle
accordance with N.E.C. Article 110. Local codes
be checked for any special aisle
The equipment should be
is free to
location
a
and rear of the equipment,
space
is shown on
circulate
units at the bottom
good
with
switchgear,
around and above it. Since air
air
provide
floor
the
placed
in an area where
and is exhausted at the
will
provide
flow
adequate aisle
plan
cient operation.
$012659)
Typicol
study all
installa-
plan
and
installation
sum-
by
Any
required
be
The recom-
drawing,
requirements.
clean
more effi-
Outdoor Shipping
FOUNDATION
the
to the floor.
nels
floor, it is recommended that recessed steel
installed by the
The
channels should be embedded in a level concrete
their top surfaces flush with the finished
sential that
switchgear channel be supported
distortion of the switchgear structure,
is
above the floor
switchgear channel must be supported
If other equipment
Section
REQUIREMENTS
Indoor Equipment-Suitable
purchaser
CAUTION:
ECT TO V I B RATIONS, SPECIAL MOU
]
for mounting and
IF THE FOUNDATIO]V
MUST BE PROVIDED TO
means
anchoring the switchgear
PREVENT THE
TRANSMITTAL OF VIBRATIONS
must be
provided
IS
NTI NG
TO THE
ESUIPMENT.
Although the equipment is furnished with built-in
so that it can be mounted directly
floor
channels under
purchaser
for supporting the equipment.
the front and rear
on a smooth, level
channels be
floor. It is
other
prior
to final anchoring, and that
by the finish
level
the mounting channels, the center
by
If
the
floor to avoid
gear
each
steel channels be level and aligned
these
at the same level.
installed in the same
is
channels must
level and
be
aligned
with each other.
SUA-
chan-
switchgear
slab
with
with
the center
is raised
lineup,
by
es-
all
l0
Page 11

Low
oltoge Swifchgeo r, GEK-7 21 0I
Y
FLOOR
STEEL TO BE DRILLEO
(BEFOBE
TAPPEO
lS [{ PLACE),
MAY
8E
USEO.
14
BOLT
0lA.
ANO
STEEL
NUTS
ANCHOA
METHOD OF
ANCHOR SOLTS. FLOOR
BY PUBCHASER.
SHIMS
FOUNDATION
EOUIPMENT
EMAEODEO CHANTIELS
EACH
ENTIRE LEflGTH. CENTER
SUPPORTED.
F€COMMENDED FOR IEVELI'{G PUNPOSES,
FINISH
FROM MOUNTING CHAtrXELS
THE FINISH
CHANilELS.
IS FURNISH€O WITH
OTH€R AflD SHOULD 8E LEVEL OVER THEIR
FLOOR SHOULO
SHOULD BE SET LEVEL
Vr THK. FOFM€D
HAVE
FLOOR
BE HIGHER THAN
OR AFT€R
WELo
OR
ANCHORING
CHANNEIS.
AiiO
DATA
AUILT.IN CHANNELS.
MUST
CHANilEL
CHAilNELS
PITCH AWAY
SLIGHT
AiIO IN
NO CASE SHOULD
MOUNTIflG
ARE
PAD
FINISH
SURFACE
METHOD
ANCHOR BOLTS. FLOOF
WITH
B€
OF ANCHORING
T
CHANNELS
BY PURCBASEN
-
SHIMS
INSERI
OF
METHOO
Foundotion for lndoor Equipment.
FlG.
(0673D0500-265)
t
|
ALTEANATE
ANCXORING
Anchor bolts, floor steel ond olher foundotion moteriol furnished
purchoser
by
Recommended
mounting
the
Figure 11. This information is also sent to the
method of embedding channels and
switchgear to the foundation is shown
purchaser
with other requisition drawings.
Outdoor Equipment-Recommended method
ding channels and mounting the switchgear to
tion is shown
in Figure
Indoor Equipment apply. Outdoor
center
channel in the floor frame
pad
by the
or
other
means.
12.
Otherwise, comments under
equipment
must be supported
which
ANCHORING
The switchgear should be mounted on
as shown in Figures
11 and 12 and securely
top of the channels
them.
embed-
of
fouqda-
the
also has a
anchord
FLOOR
VIEW OF
SIOE
SHOWING
FRONT,
SEARII{G
REAR AiIO
FRAME
OF
SURF^CES
C€NTER CHAITIIELS
FOUNDATION DATA
EOUIPMEXT IS FUFNISHEO
EMBEODEO
CHANNELS SHOULO BE SEI LEVEL
OTH€R ANO
€ACH
EilTINE LEflGTH.
y.
IHICK FORMEO
LEVELING
PURPOSES. FINISH PAD
FlG. t2
(0673D0500-266)
Anchor bolts,
PITCH AWAY
CAS€ SHOULD
THAN MOUNTII{G
floor
FROM MOUN'ING
IHE
sfeel ond
oy
in
to
the channels. One is to use
the holes
shown in the floor
channels of
There are
two methods of anchoring indoor equipment
provided
the
in
the bottom of the €quipment
plan.
Another is to tack
equipment to the foundation channels.
Two suggested methods for anchoring
switchgear
bolt and floor clamp
the
foundation.
NOTE:
MENT
THE
to
BOLTED
UNDER
illustrated
are
to
DO NOT BOLT ORWELDTHE
TO THE FLOOR
SHIPPING PACKAGES HAVB
TOGETHER .4S DESCRIBED
"ASSEMBLY
IVITH
SHOULO
CENTER
CHANNELS
FINISH
CXANNELS.
Foundqtion
other
EUILT-II{ FLOOE FNAI'E.
5E LEVEL OVER
CHANN€L MUST
PAO
ARE
AECOMMET{OEO
SHOULO HAVE
CHANTELS A'{O
BE HIGHER
for
Outdoor
BE SUPPORTEO.
foundolion moteriol furnished
purchoser
inch anchor bolts through
lz
weld the bottom
outdoor AKD-6
in Figure
secure the
12.
Both use an anchor
supporting channel to
CHANNELS UNTIL
ESUIPMENT."
OF
WIT}
THEIA
SLIGHT
IN
EQUIP-
FOn
'{O
Equipment.
as
BEEN
ll
Page 12

GEK-721 01, Low
oltoge
V
Swifchgeor
ASSEMBLY OF EQUIPMENT
Before assembly of
ponents
should be on hand
individual shipping
on the foundation. If there is no transformer
and the equipment has been
middle
both
Unit
its
package
directions. If the equipment
Substation. the transformer section should
pad
in accordance with the instructions
the transformer, and then
NOTE:
WHEN AKD-6
STALLED
TRAIVSFORM E RS
IT IS IMPERATIVE
SURF.ACES BE LEVEL.
Proceed to assemble
1.
The switchgear
foundation
Figure
equipment.
2.
tened together
with the aid of cranes or
I for indoor equipment or Figure
For
Indoor Equipment, the
at
the
equipment
to
packages
facilitate
must be connected
split
on the foundation first
packages
SWITCHGEIR
IN
THE SAME LINEUP WITH
AND OTHE R EqU
THAT ALL MOUNTING
the equipment as follows:
packages
the
shipping splits by bolting
and rear upright channels together.
furnished with the equipment at
transformer
Ilta
the flange to the switchgear
For Outdoor
3,
from
front and fear
the shipping
plates
splice
weather-proofing must be followed as indicated in Figure
14.
proofed,
rubber
port
seal
hardwaie.
place
joining
When
joint
The
This is
seal on each side of the top
batten so that the
on both sides. Bolt
A
by the roof trim.
and switchgear
weather-proofed
rear batten
bolt
The
the transformer,
former
ment. Check
to
see that the
4,
of
adjacent
bars furnished
for
details of splice
mounted
ticularly important
vides
and
them together
gasket
for
flange
Bolt the main buses,
directly
an integral
in
is
the lineup, hardware for connecting
is supplied with the equipment.
Equipment, remove the
of the switchgear base at both ends of
joint
split
as shown in Figure 14.
shipping
in the roof at shipping splits must be weather-
done as shown in Figure 14 by
and assemble the front
packages,
roof sections butt up against this
joint
this
roof
as
rubber
placed
cap is
Joints
and between
shown
seal
Figure
in
at
over this seam and
between transformer throat
shipping splits must be
the shipping
with the furnished
outdoor
an
transformer is furnished with
and hardware
to the
switchgear is supplied
alignment of
weatherproof seal has not
shipping
doors on the outdoor equipment
ground
packages
with the equipment.
bar connections.
on the rear
that this bus
ground
upright channels, It is
for
all the equipment that should
is begun
installation. The
for shipment,
and
part
is
of a Load
of
equipment
should be
jacks
packages
Use
the
end of
special
edge of
togeher, using
14. Install a front and
3/e-16
connecting the trans-
for
buses, and neutral
together using the splice
See Figure
The
be connected since it
all com-
togefher
in
lineup
the
place
assemble
Center
be set on
furnished
I PM E NT,
placed
as
2
should be fas-
3/a-16
the
lifting
procedures
the roof sup-
split
with the equip-
been disturbed.
ground
added.
IS IN-
on the
shown
for
outdoor
the
hardware
packages,
plates
and
placing
7a-16
held
joints
hardware.
buses
13 and
bus is
with
front
rear
and
par-
pro-
the
for
in
14
be connected to
mounted
rear
Iineup, make
to the flexible
shown in
plied
in
the bus'entrance compartment
This
connected
pad
for
on molded insulators
upright
Figures 13 and 14. Connection hardware
with the equipment. The
bar should be reassembled in
at the offset
a
with
proper
All bolted bus
torque values
5. Bolt
specified
switchgear.
equipment.
busway.
in
splits.
under
6.
All shipping supports must
Busway runs
7.
8. Connect control cables
A tag
will indicate
located.
across the split and
blocks as indicated.
a
These
9. Connect
a.
When control
below, they should
above the floor. The control cables may
through
is
installed.
b. Route the
the wiring
ment and connect
in accordance
equipment.
c. If the
top cover
the station
channels.
the necessary connections
connectors furnished
1/z
inch bolt. Consult transforiner instructions
connection
as shown in
procedure.
joints
should be made up using the
or weld the equipment to the foundation as
"Anchoring."
These
Hardware for this
at the top of the
where
control cables to the
the conduits before
control conduits
painted yellow.
are
must be lined up and connected
the
wires are
connected to
conduits enter the switchgear from
control cables from the conduits
trough
with the connection diagrams for the
within the
trol cables should be routed to
and connected
10.
Connect
main
cable connections
identified
ment.
be
cables
at the
Figure
Cable terminals
are
ment.
terminals
they
above
manufacturer's recommendations
as
to indicate their
Adequate electrical
provided
mounted
are
between conduits,
enter
the unit, they
rear
of the cable
9.
at the ends
Check
to see that the
are located
positioned
or below. In
as the instructions
well
to
main
the
are
at each
correctly
all cases, carefully
ground.
Neutral buses are
that are attached to the
If
a transformer is
with the transformer as
present
from the equipment
in
is sup-
portion
Table A.
ground
will
to the transformer
connection bar in
be
shipped
the correct
removed
be
turned
position
ground
proper
from the
to the
joint
is furnished with the
between units at
the
shipping
unit adjacent to the
wires that cross the split are
all
not
tagged
and
the shipping split terminal
switchgear unit as follows:
extend
or after the
should be laid
more than
one inch
pulled
be
switchgear
through
at the side of the cable compart-
the cables to the terminal blocks
enter from above, drill the
available space indicated. Con-
the wiring
the
terminal blocks
cables
are made, the
phase
and
can be lashed to
the
to
mechanical
cables and bus. Where the
units. Before any
cables should be
relationship
clearances
cable supports
trough
as above.
with equip-
compartment as required. See
included
of the bars
with the switchgear, and
in the cable
proper
connection
receive
to
size and
cables
quantity
point,
coming
compart-
and that
follow the
installation
for
contained in
this book.
of cable,
the
in.
and
split
must
of
from
cable
12
Page 13

Low Vohoge
Swifchgeor,
GEK-72101
It is imperative
their
to take
movement
Train
temporary
during short
the
lashing if
weight
cables
that all cables
off
in the
Strip the insulation
not
to
damage
For
copper cables,
insert
the
screws
in
For
aluminum
thoroughly.
strands
Penetrox A.
Insert
in
result
strands.
in
as D50H47
these
channels.
partments,
with a
cables into the
accordance
in the
Bolt
the cable terminal connectors
the cable
connection surfaces,
Lash
the cables
11.
Remove
any strands.
cables
into the
accordance
Immediately
quality
(or
other similar oxide inhibiting compound).
with values
oozing
Wipe off
the excess compound.
compartment.
furnished with
permanently
the lifting
If equipment
brackets
cables.
at the rear cannot be
terminals and studs,
be adequately supported
circuit.
proper
path
to the
required,
to
coat
with values
and cut to the
the
desired dimension,
the
cables with
terminals
shown
and tighten
in Table
wire brush the
after wire
oxide inhibiting
terminals
shown in Table
of compound
brushing, coat the
compound
and tighten the
from between
to
the ends of the bars
A non-oxidizing lubricant
each equipment) can
to the
cable
brackets from the front and
is furnished
with
removed.
prevent
and to
terminals,
proper
length.
being careful
D50H47
grease,
the set
B.
cable strands
such as
set screws
B. This
should
individual
be used
supports.
"add-on"
using
cable
(such
rear
com-
12. Remove all blocking
13. Make
a
finai
inspection to
construction materials,
switchgear.
TORQUE
Wire
Size
6
3
VALUES FOR
Inch-
Pounds
100
100
100
125
tzJ
I
0
at
00
000
0000
200,000
250,000
300,000
125
150
150
200
200
200
250
250
on relays and devlces.
see
that
there are
no
tools,
or other foreign matter left in the
TABTE
B
CABLE TERMINALS
Wire
Size
350,000
400,000
500,000
600,000
700,000
7s0,000
800,000
900,000
1,000,000
1,250,000
1,500,000
1,750,000
2,000,000
Inch-
Pounds
250
250
300
300
300
300
400
400
400
500
500
500
500
TORQUE
VALUES
Bolt
Size Foot
1A_20
16
'll.s-
Yz-13
5/8_tl
TABTE
FOR
LOW VOLTAGE EQUIPMENT
(COPPER
OR ALUMINUM)
Pounds
A
With Prevailin{
With Finished Machine Nut ical
Totque Locknut
And Flat
Flat
And
Washer
Washer And
FIat
Washer
Flat
HARDWARE
Sprin(
Washer
Or
Washer
10
30
42
J)
Washer
OnIy
l3
Page 14

GEK-7
21
01,
Low
V oltoge Swifchgeor
NUT.
REMOVE
PLATE
LIfiING
ANO
SPACER.
AOLT STAYS
PLAC€.
AFTER
EOUIPMENT
(2)
REMovE
SCNEWS
SHIELD To
R€^SSEMBL€
TAP SCREWS.
#10.32 SELF-TAP
AND LOWER EOTTOM
FLoon
rHE
IN
R€MOVING
PLATES
SloE
IS
SET
LrN€.
(2)
SELF-
AilD
SHEET
IN
PLACE
LIFTING
SPACERS
--\
<-4r
ilt \
I II \
#10-32 SELF-TAP scnEws
I ll
III
'
)ll 1 lt
-{++z
-J
SOTTOM
llt-P
E
II
-
IL
SHTELD
8 FT. t0 lH-
\
TILT FRONT OF HOIST
1-Zr
ROLLER
DlA.
CHANNEL. THEN LOWER
TO RAIL.
GROUNO
8US
SPLICE
3
MAIN
BUS
SPLICE
UNOER
{SEE
(SEE
TO ASSEMSLE
UP
FLANGE
FRONT ROLLEAS
NEUTRAL
vlEw
"G")
sPLrcE
3
Or
SPLICE
(sEE
(SEE
VTEW.D)
VIEW.D)
yJ/-,"
I
RACK LOWER BREAKER
A- t
\
/
.I/
IO OISCONNECT POSITION TO RECEIVE
/
-
ANCHOR BOLTS
/
PfHwlofJlH*il"
lf
COMPARTMFNT
*
LOWERIT{G SOTTOM SHIELOS
r sAR BUS 2 8AR
HAROWAFE-v, 8OLTS. NUTS. CoNICAL
NOTES
I ALL SHIPPING SPLIT
OISASSEMBLEO
SHIPPING
NEASSEMBLE TO
2 AUXILIABY UNIT OR
ADAPTEH
MUST 8E REMOVEO FOR CONNECTION TO
TRANSFORMER.
3 GROUND
BUS
NORMALLY SHIPPEO
OF AOJACENI
SIOE
NEUTRAL SPLICE, HAROWARE
(WHEN
FURNISHEOI WILL
ASSEMBLED TO EI'HER SIOE OF
SHIPPING PACKAGES.
HARDWARE TO 8E
BEFORE
PACKAGES ARE
SECURE
AUXILIARY
TOP COVER
ANO
ANO HAROWARE WILL 8E
SPLICE
ASSEMSLEO TO EITHER
SHIPPING
AOJACENT
IN
SET
SHIPPING SPLIT.
UNIT
(2)
REAR
PACKAGES.
AND INSULATOFS
AE
NORMALLY S}IIPPEO
t4
sPLtcE EARS
/-7
It //
'|+\ }.....I.'+-+
-r\\-
BUS 3
ANo FLAT WASHEnS
"F"
vlEw
SPLICE
MAIN BUS
coHDUCroR
PLACE,
COV€RS
i?rr?r,r
ADJACENT
FlG. l3
SPLTCE BARS
-
J-{/ ..1---
AAR AUS
>,
-....fulid4,a
"
ti}{-il
Typtc^LrTlrNsFoFM€R
(0673D0500-265)
r^F
h
il[%*
Assembly
38*'o'r3"o"n*
/*
of Indoor
--
Equipment
npen or rnlues J--
VIEW D
NEUTRAL BUS SPLICE
./-
//
/l
/\
6ft\,fr
ill
r._JlL_-,l
--\.*
-
vrEtv
G
BUS
GROUITD
SPLIC€
u--tt--n
--;-5-"-
ill
r Jll
Tr3 FLAr
c
srrn
REAR
rNsuLAToR
wAsHERs
usrEss
oF FRAME.
Page 15

Horsr
CR^NK
ENLARGEO
(BEASSEMELE
'Utl
-
SPACEF
/&ll
"
ll
VIEW.C
1
,('El*'
\>
J<
AS
SHOWN)
REMOVE
suPPoRrs
RUBSEN
SHIPPING
(YELLOW)
SEAL
Low
I
ROOF
Voltoge
.BATTEN
cAP
Swilchgeo
I
ROOF
CAP
TBIM
r,
GEK-72101
+T.16 HARDWARE
oTY.5OR7
DrscARD
/v llL-l llo. I r/
/u lrfl llo. |
t
90R10%-16
aolTs. WASHERS
A LKW
EACH I I II
srDE FLANGE
TRANSFoRMER
TFANS
]
OPEN I NG
rRANS
il i
r.
L
SHIELOS'
--i
96_16 NUTS
Ilot-'r-Elq,-ll1Ff'|f
&r*pH*-
^lttr"t
,,1,,
',!o'
lt
Lol :o I
iio
"-
,/r. i'
FLANGE
-l
I
"otorrv
\l
)alll
Ypwll'.3..3n
r [-k llll^Gd
'
coNrcAL
WASHER
TYPICAL
CONNECTION
llll^^
llll
llll ,/0- *f
TRANSFOBIIER
-
ifir l.-Jl
l:-l ll
I l^l J
I l,l
rl
lol I ll0
aos
CRANK
PAD
FINISH
SURFACE
3gl,"ltio.,*''
)^
'/
-f
\{.
I
'
mli
,LJ
ENLAR
eM]
/
-
-
J
t:--.-
'll$ow^ae
vrEw
vrE
t
I
. .
'l
e
sEr
'331E'
r ilc:
"
.flliF,".f..
==
=i
NEMOVE
LIFTING
I
I
lu
i
I
I
i
i
PLA'E
!i
=
=
I
SHtPPtNG
/,1-
q
SPLIT
I
i1-
;-At-
Tg-P
REMOVE
LIFTING PLATE
ASSEMBLE
PLATES FRONT
NEAR
)
/
SPLICE
I
AND
, /.spLtcE
':-ts.===-
I AAB
NOTES
1 ALL
SHIPPING
AANENS.
FRONT
TO 8E
DISASSEI/BLEO BEFOBE
SHIPPING PACKAGES
REASSEMALE
2 GNOUNO
NOFMALLY
SIDE OF AOJACENT
NEUTRAL
(WHEN
SHIPPEO ASSEMSLEO
ADJACENT
sAn
BUS
HAROWARE
% BOLTS,
SPLIT HAROWARE.
ROOF RU88ER
ANO REAR
ROOF
ARE
TO SECURE
BUs
SPLICE, INSULATORS
FUBNISHED)
AND
SPLICE
SHIPPED ASSEMELEO
SHIPPING PACKAGES,
WILL BE
TO
SHIPPING PACKAGES
CAP TRIM
gARs
/spltcE
ry #
2 BAR BUS
NUTS,
CONICAL
vtEw,.F..
MAIN
BUS
SPLICE
FOOF
GASKET,
SET IN PLAC€.
SHIPPING
HARDWABE
EITHER
CAP,
AOJACENT
SPLIT,
WILL AE
TO
ETTHER
ANO HAAOWARE
NORMALLY
SIOE OF
FfG.
,SpLtCE
3 8AN BUS
AND FLAT
WASHERS
f 4
@673DO500-266)
SABS
Assembly
SECTION D-D
WPICAL.
FRONT OF
AOJAC€NT
SHIPPING
ARE
SECURE.
STAR
WASHEFS
of
Ourdoor Equipmenr
REAR AFTER
PACKAGES
F
PPHw'^t?tH^"'jl\
B€AR
OF
FBAMES
VIEW H
NEUTRAL
SECTION
AFTER
PACKAGES
/^\ /
,/ \l
//\
E.E
ADJACENT
ARE
.-T
8US SPLICE
SHIPPING
SECURE
BoRBT."iX,o*
Fr ar wAsHERs
t5
Page 16

GEK-721 01, Low
V oltoge
Swifchgeor
ASSEMBLY OF
14.
equipment,
arate carton. To install it, remove
the front of the equipment. Lift the hoist into
of
top
is toward the
on the top of the equipment
the single
is
available at the end of the equipment, the hoist may
assembled
the channel and then
the
stop clip and
straddle the
will
EQUIPMENT
Install the breaker hoist. When supplied
is shipped
this
switchgear
the
rear
on the
wheel
by sliding
positioning
tapered front track. If space
of the equipment is
the hoist side
rear
roller must
hooked under the channel and
positioned
frames immediately in front of the single
be removed. The rear wheel can then be
on the front track. The retaining angle
rear should then
at each end of the front
riding
off the
When a hoist is
shipped mounted and
ping
supports
be
removed as shown in
remove
shipment.
15. Before
breaker
connect
tightness, Refer
Also
check the contact
bar or cluster
accumulated.
a thin film of
before
Check to see that the
compartments. Each
number.
the
summary, the front view drawings, the breaker name-
plate,
ahd
^:-- ^^+^-
Lar Lwrr.
Prrrli
To locate
to the breaker
proper
the
carton, or the mark number on the breaker nameplate. All
identical breakers will
BREAKER INSERTION
ends
at either
the wire that is
placing
compartment for
bars.
Where
to Table A for the
of fingers for foreign matter
Clean these areas if necessary.
D50H47
putting
a breaker in the compartment.
This number is
on the identification card on the breaker ship-
the breaker in the
location
breaker by the identification card on the breaker
(coni.)
with indoor
completely assembled in a sep-
the
lifting
plates
position
that
so
of the equipment. A channel is
the
the end with the single
provided
which serves as the track for
rear of the hoist assembly. If
rear wheel under the top
lifting the front end of the hoist over
restricted,
the front wheels so that they
the
angle which is bolted to
the ends
at
the front wheels
reassembled.
be
of the
provided
secured in
end
track to
track.
of
Stop clips are
prevent
with outdoor equipment, it
place.
The
movable track must
the
hoist
Figure 14. To free
used to keep it in
breakers in the equipment, check each
such
areas on each
breaker is assigned
list on the front
have the
bolted
joints
grease
breakers
shown
proper
joints
in the
exist, check
proper
primary
covers
the
match
on the
breaker sheets of
compartment, refer
view
mark number.
same
provided
the hoist from
yellow
hoist
the
place
primary
the
bolts for
torque values.
disconnect
that may have
Be sure
contact
their respective
part
a
or mark
drawing.
from
roller
space
leg
can
at
ship-
dolly,
during
dis-
that
areas
Find
the
on
be
of
be
test.
Check thoroughly for any
for any dirt or foreign matter
Be
sure that a thin film
disconnects
HOISTING
With the
AND INSERTING AK BREAKERS
inner housing
installine the breaker.
before
NECTED position, proceed
1. Put
be installed.
side of compartment.
3. Rotate handle counter-clockwise
stopped.
the breaker in front of the unit in which
Be sure it is tripped.
2.
Insert
handle on
(Indicator
jackscrew
should
damaged
which
D50H47
of
in the compartment in
as follows:
shaft
read
DISC).
or loose
may
be
grease
located on left hand
until
Inner
parts
and
in the breaker.
present
is
the
on
CON-
it is to
jackscrew
is now
house
is
in the DISCONNECTED position.
4.
Remove handle and
5. Rotate the
is
track to the limit
6. Pay out
slots
on the breaker side frames. See Figure 168.
CAUTION:
PLETELY
CRANK
THE
two track lock links and
of its travel. See Figure 16A.
enough hoist cable to
DO NOT UNWIND
FROM
MUST TURN CLOCKWISE TO HOIST
BREAKER, COUNTER.CLOCKWISE TO
LOWER IT.
Place
7.
(fourth
hoist
of the cable
WARNING:
DU
RI N
8. Raise the breaker until
approximately
9. Pull the remaining track
and lower breaker so the
the slots in the
cable
the
eye
ball from the hooks) and
the
with
DO NOT
TlOlSTlNG
G
one inch above the tracks. See Figure l6D.
hoist. See
track. Remove the liftins device.
ures 16E and F.
10. Push the breaker in against the track stops. Rotate
the two
track
lock
links to
the compartment door. See Figure 16G.
11. Insert handle on
jackscrew
to move breaker into the compartment. Breaker is in CON-
NECTED
tated.
position
(Indicator
when
should read CONN).
compartment door.
open
place
CABLE COM-
DRUM.
just
under the ball nearest
Fieure
STATTD
breaker mounting
UNDER BREAKER
OPE RATION.
the breaker
out to the limit
lock
the breaker in
shaft and rotate clockwise
jackscrew
can
pull
the right
the hooks
in the
OPERATING
the
take
16C.
mounting
slack out
pins
of its travel
pins
drop
See Fie-
place.
Close
no longer be ro-
the
are
into
Before
breaker
'16
installing or operating a breaker,
instruction
manual for
preoperation
to the
refer
inspection and
Page 17

Low
V oltoge Swifchgeo
r,
GEK-7
21
01
HOISTING AND INSERTING AKR AND AKRU BREAKERS
With the
NECTED
l. Put the
installed.
be
2.
yellow
the
sembly. Discard the bolt and tag.
3. Pull inner house
inner housing
position
breaker
Be sure it is tripped.
Open the compartment
head and
in the compartment in
proceed
in
front of
the
shipping tag from the track
forward as far as
as follows:
the
and remove the bolt with
door
unit
possible.
in
which
the CON-
it is to
It is now
in the DISCONNECTED position.
4. Rotate the two track lock links,
track
all the way forward. See Figure 16.{.
5. These
them to
there
When hoisting the non-fused
hooks are
the fused
Pay
hole in the
fused
breakers require a spreader bar
avoid damaging their
are two
positioned
breaker, the hooks
out enough hoist
center of the spreader bar. Figure 17 shows
breaker,
CAUTION:
PLETELY
CRANK MUST TURN CLOCKWISE TO HOIST
THE BREAKER:
in
slots
spreader
each of the breaker's side frames.
in
the forward slots. When
cable to install one hook in the
bar
DO NOT
FROM DRUM,
COUNTER.CLOCKWISE
arc
breaker, the spreader bar's
positioned
are
and hoist
UNWIND CABLE
LOWER IT.
pull
and
chutes. For
when
in the
cable.
COM-
OPERATING
the right
hoisting
hoisting,
hoisting
rear
TO
as-
slots.
11. Engage
rotate
the
end, a high
connect fingers
A couple of turns later, and the stop
position
The
NOTE:
DESIGNED
T
ECT IV E B/RR/ERS I
SEE
BREAKER
the racking handle
the handle clockwise as
requirement
force
on the breaker engage the stationary studs.
indicator will now
ALL BREAKER
FOR
FUTURE USE HAVE PRO-
FIGURE 15.
REMOVAL_AK BREAKERS
N ST ALLED T H E
as in Step 8, and
again
far as
it
will
go.
will be felt as
be encountered.
will
CONN.
show
COMPARTMENTS
Towards
the
REI N,
dis-
l. Trip the breaker.
2. Insert
side
handle
of compartment.
3. Rotate handle
stopped.
a
all
the tracks
BREAKER
(Indicator
4. Remove
5. Rotate the two track lock links and
the way forward. The breaker may
handle and open compartment
by the
REMOVAL-AKR AND AKRU BREAKERS
jackscrew
on
counter-clockwise until
read DISC).
should
lifting
device.
shaft
located on
now
jackscrew
door.
pull
the breaker
be
left
hand
lifted from
is
6. Raise
approximately
7. Pull the remaining
and lower
the
ures 16E and F.
the breaker until the
one inch above
WARNING:
DU
slots
CAUTfON:
FOR/KR
P/ITTS
DO NOT
RI NG HOISTING
breaker so the
in the
track. Remove
THE
BREAKERS ARE ESUIPPED WITH
THAT BRE,4KERS
SO
RECT RATING
TRACKS.
A LOWER
THIS
RATED BREAKER IN A COM-
ST/ND UNDER BREAKER
track out to the limit
TRACKS OF
CANNOT BE SET
PREVEITTS
PARTMENT.
Engage
8.
the racking handle. This is done by
trip button in the breaker
below
shaft.
(if
the two
the
to
it
the right, and inserting the handle on
9. Turn the
it
will
10. Push
handle counter-clockwise
move
in that direction) and remove the handle.
the brea*er in against the track stops.
track lock links to lock the breaker in
compartment
door. See Figure 16G.
breaker mounting
the tracks. See Figure
OPERATION.
breaker mounting
pins
the lifting device. See Fig-
/NNER FiOUSES
AN INCOR-
OF
ON THE
/TTSERTION OF
escutcheon,
sliding the cover
as far
pins
its travel
of
drop into
pushing
jack-
the
as it will
Rotate
place.
Close
are
16D.
the
go
1.
2. Engage the racking handle. This is done by
trip
below it to the right, and inserting the handle on
shaft.
3. Turn the handle counter-clockwise as far as it
If the breaker
charged automatically a few turns before the end of the
action.
4. Remove handle and
.5. Rotate the two track lock links and
all the way forward. The breaker may now be lifted
the tracks
the
Trip
button
(Indicator
breaker.
in the
by
breaker
closing spring is
should
the lifting device.
escutcheon,
fully
read
DISC.)
open compartment door.
sliding
charged, it will be
pull
pushing
the cover
the
will
breaker
the
jack-
dis-
from
I
FIG.
(8042650)
l5
Provision for future
bq rrier
breoker
with
protective
the
go.
17
Page 18

GEK-7
2l
Ol,
Low
oltoge
V
Switchgeor
FlG.
tion,
t6A
open
(8035642)
compodmenl
the
Pull
With
out
innerhouse
door'
trock
right
in
Rotote
comPletelY
DISCONNECTED
trock
lwo
the
lock
posi'
links'
l8
FlG.
l68
(8035640)
Let
out
Hoisl
Coble'
Ploce
hooks
in slots
Page 19

Low
Voltoige
Swifchgeo
r,
GEK-72101
FlG.
l6C
(8035639)
must
Adiusr
be
under
coble
boll
to
bolonce
neorest
ihe
breoker,
hoist
Coble
eye
FlG.
l6D
(803563,
Roise
one
breoker
inch
unril
obove
mounting pins
trocks
ore
obout
t9
Page 20

GEK-7
21
01,
Low
Vohoge
Swif
chgeo
r
FlG.
t5E
(803564.l)
Pull
left
trock
oul
completelv
20
FlG.
t6F
(8035635)
Lower
tne
the
Breoker
Hoist
Coble
into
the
lrock
slots'
Remove
Page 21

Low V
oltage
Switchgeo
r,
GEK-721 0l
FlG. l6G
(8035636)
lhe two
Push the breoker in compleiely
trqck lock links. Close the
door
ond
roiote
i;'l
FIG. 17
.
(8041582)
AKRU or
AKR breoker
coble
ond spreoder
on
hoist
2l
Page 22

GEK-7
21 01, Low
V olt
ge
Switchgeor
o
BREAKER
CTOSING
Manually operated AK
the
120 degrees, and then
position.
required
wise movements and the first three clockwise
of the handle,
70 degrees travel of the fourth clockwise
the spring charged
breaker
through the breaker
complete handle
complete handle
CLOSING MANUALLY OPERATED AKR
Manually
handle and a
the escutcheon. The closing spring must be charged
A complete
handle counter-clockwise
then
three similar cycles of about 50 degrees
indicator should read CHARGED at
breaker can be closed by
CLOSING ELECTRICALLY OPERATED AK
AKR BREAKERS
Electrically operated
control
power.
They may
breaker escutcheon, by a breaker control switch, or by a
relay
in the equipment which houses
some remote
OPERATION
MANUALLY
handle counter-clockwise
closing
such complete movements
Four
to
close the breaker.
the springs are charged. After
A charge indicator, numbered 1 to
closes.
OPERATED
breakers are closed by
clockwise
mechanism is driven over center
back
During the
front escutcheon, moves
movement and indicates the
movements that have been
operated
push
charge
clockwise back to the normal
power,
be
contact. The control switch
location.
AKR
breakers
marked CLOSE on
button
is accomplished by
through
pushing
breakers may be operated by ac
(normally
or
dc
controlled by
a
the breaker, or may be in
BREAKERS
AK
through approximately
fhe normal handle
to
of the handle
four
handle movement,
rotating
counter-clock-
moveroents
approximately
and the
4, viewed
with each
number of
performed.
BREAKERS
are
equipped
either
about 135 degrees and
position
each. The charge
point.
this
the CLOSE button.
OR
station battery) control
pushbutton
relays may
or
with
the
front of
rotating the
or by using
Now the
switch on the
located
be
are
first.
NOTE:
FER
NISHED
FOR FURTHER IiVSIRUCflONS RE-
TITE /NSTRUCTION BOOK FUR-
TO
WITH
TESTING AND
Although
the factory, they must be tested and inspected
before being
equipment has been
tions
the equipment and devices have been tested at
placed
are correct.
All bolted connections and
should be
a
Directions
given
The settings
other relays
must be made by the
setting the relays
The extent
depend on the type and function
which
operation, and
checks.
checked for tightness.
WARNING:
PRIMARY ESUIPMENT
BE COMPLETELY DE-ENERGIZED
?ESTS ON
BEING
,4RE,4S
CONTROL CIRCUITS, ETC, ARE
CONDUCTED. BE
FEEDBACK FROM
OF
CIRCUITS AS
ARE
DISCONNECTED.
for testing
in the instruction book
protective
of
on the
NOTE:
CLL BREAKERS
THE TRIP DEVICES
LEVEL. BEFORE ENERGIZING THE ESUIP-
MENT, CHECK TO SEE THAT ALL TRIP
DEVICES
VALUES,
should be
ARE SET
of the tests on
performed,
switchgear metering,
THE BREAKER.
INSPECTION
in service.
properly
This will insure that the
iostalled, and that all connec-
control wire connections
SURE
THAT
SECONDARY
WELL AS OUTS/DE
relays,
instruments and
furnished for
relays must be
system and therefore these
are
given
purchaser.
General
the Relay Instruction
in
ARE SHIPPED WITH
SET AT THE MINIMUM
AT
THE PROPER
the
equipment
of the equipment. Tests
however,
include circuit breaker
phasing,
the field
in
MUST
WHILE
ALL
SOURCES
meters are
each device.
coordinated
instructions on
as a whole will
and
relay
grounding
settings
Book.
with
MANUAL TRIPPING_AK
A mechanically
operated trip
breaker escutcheon, operates
breaker.
ELECTRIC TRIPPING_AK
A shunt
trip
device is
AKR BREAKERS
OR
button,
mouuted
the trip shaft
OR AKR BREAKERS
an accessory used for electrical
tripping. A normally open auxiliary switch
opens the control circuit after the
22
breaker opens.
on the
to open the
"a" contact
potential
High
tion are
not necessary
carefully followed. If local codes demand
purchaser
should not
For the
times switchgear rating
power
CAUTION:
CONTROL
ANY OTHER DEVICES
PRIMARY
tests
to check
if the
to make high
wishes
exceed 75% of the
circuit
the
plus
the
integrity
installation instructions are
potential
ANSI
factory
ANSI factory
1000 volts.
POTENTIAL IRAiVSFORMERS,
POWER TRAJYSF.ORMERS, AND
CONNECTED TO
CIRCUITS
MUST BE DISCON-
this test or the
tests, the voltage
test
NECTED DURING HIGH POTENTIAL TESTS.
of the insula-
test voltage.
voltage is
two
Page 23

low Volfoge Swifchgeor,
GEK-72101
KEY INTERLOCKS
After initial installation
necessary
propriate
hands of a responsible
schematic included
equipment
correct
is necessary
the interlocking
BREAKER
All
interlock
locks and all
to determine
number
compartments
of operating
since improper
scheme.
OPERATION TEST
keys should
in
the
of
switchgear equipment, all
inserted
be
spare keys should be
person.
the summary
the sequence of
housing all
Refer to the key
furnished with the
keys required.
use of spare keys
AK and AI(R circuit
into the ap-
placed
in
the
interlock
operation and the
precaution
This
will defeat
breakers have a
mary contacts are
tacts
are still
testing
the
into
of the electrical
primary power
service, its
while in this
tripping circuits
The
TEST
mqintenance
TEST
disconnected
engaged. This
circuit. When
control circuit
position
are complete
position
of the
breaker, and should
only for testing breaker
position,
TEST
control
to
make
and functioning
is
not suitable
operation.
in
which
the
breaker
pri-
while the secondary con-
position permits
complete
circuit without energizing
the breaker is first
must be
sure
thoroughly
that
all closing
properly,
for inspection
therefore
be
tested
and
and
used
put
JL--
1J_-
Jl-
-LJ-
j-rr
xrnowrne
-
FOR AI{CHOR]
FlG. l8
(0121C1508)
Side view
of breqker
stock
23
Page 24

GEK-721 01, Low
V oltoge
Swifchgeor
a9
.2'
.tr
(0625E0376)
RACKOUT
MECHANISM
FlG. l9
OPERATION
Rqckoui
AK BREAKERS
part
Part numbers in Figure 19 refer to
Drawing
0673D0500
Sheet 627 Groups 05
The rackout mechanism is operated
handle onto the
the handle. Clockwise
house
and
end of
counter-clockwise
out. Approximately 17 turns of the handle will
breaker
position.
shaft, the slot
pin
square hole in the handle will be engaged with the square
drive end of
breaker must be
inserted.
operated
age on the rackout mechanism
from
end.
in the
also assures
through
24
from the DISCONNECTED
properly
To
engage the handle
in the end of the handle should align
through the
The rackout mechanism
shaft. When the
the
shaft.
open before the operating
When the breaker is
by the
breaker
moved
being
The
pin (105)
back to fully
in the
tube. This slot
that the interlock linkage must be moved
prescribed
a
distance
jackscrew
the
rotation moves
the breaker
rotation moves the
to the CONNECTED
pin
interlocked so that the circuit
is
cross
prevents
closed,
blocks
bar
prevents
and
jackscrew
expose
shaft
rotation of the
before operation
numbers on
or
06.
pushing
by
rotating
and
shaft
into
breaker
move the
jackscrew
the
with
with the
aligned,
is so
handle can be
an interlock link
shaft
mech-
link-
(63)
and
the interlock
the tube
the square shaft
engages in a slot
of the
the
the
the
n
mechonism for AK breokers
anism is
will clear the
engages a trip link on the side of the breaker and holds
trip free
tube
the breaker trip free as
NECTED
into operation before the
and is operable whether or
gaged.
tween the
the TEST to the
can be closed when the rackout handle is disengaged
the
lock tube
position.
in the front of the door
the
indicator
line
can
interlock tube are aligned
engaged. The secondary
gaged
this
possible.
as
is in the retracted
There is also a stationary
and
The
TEST
When the tube is
pin,
a cam surface on the interlock slide
long as the handle is
TEST
breaker thus cannot be closed when
position.
positions.
and the CONNECTED
DISCONNECTED
in the
so
label
jackscrew
that
(75)
marked
is
the interlock linkaee
which
shows the
position
TEST is aligned with
housing. In this
when the
pin
An indicator
house. The TEST
on the indicator
be operated
control
and the
position.
primary
cam
it is
primary
not
aligned
is visible through
pin (105)
and
power
pushed
engaged
in the
moved
back so that it
or the interlock
house which
between the CON-
This stationary cam comes
disconnects have
the rackout
handle is en-
it is be-
positions.
position,
the breaker
with the slot in the inter-
is in the reset
an opening
position
is
reached when
the rackout handle is dis-
power
disconnects are open in
of the breaker in
the line on the
the stationary
position,
and
disconnects
the breaker
the slot in the
(46)
it
holds
parted
From
and
are en-
Page 25

&*-
I n),.i-
llll
ll'j-.-.'-
tp
Low
Vohage
-1#
q.)'
L
,/
FlG. 20
(75E180001)
Rockout mechonism
L
for AKR breqkers
Switchgeo
r,
GEK-72101
DISCONNECTED
The
indicated
ing the end
that
and the
can be closed
by the sight indicator
its
of
when the CONNECTED
interlock tube slot
travel. The adjusting nuts
upon
and CONNECTED
removal
DISCONNECTED position,
jackscrew
the
The motion
at any
point
pin
to match
of the rackout
in the
cycle by reversing the
tation of the handle.
EMERGENCY
If necessary,
the
house
done
by rotating the
been tripped
primary
Ffowever,
far enough
stop
links
automatically
If
it is necessary
when the
tion, the
interference
stop link. It
with masking
this manner.
pushing
aid in
OPERATION
possible
it is
without using the rackout
and
disconnects.
the breaker
to engage
(49,
50) are retracted.
when normal
the breaker manually
cannot be reinserted into
the
track lock
pulling
to insert
rackout mechanism
stop links must
pin
or
the breaker mounting
is recommended
tape
when attempting
The inertia
it onto the
of the breaker can then
primary
positions
and by the
jackscrew
(78)
position
will be
is reached, the
aligned
and the breaker
of the rackout handle. In
it may be necessary
the slot in the interlock
mechanism can
to remove
mechanism.
links
after the
primary
be retracted and held
disconnects
The stop links retract
racking
procedures
the breaker into
is in the
that the
CONNECTED
stop
to insert the breaker
disconnects.
be reversed
direction of
the breaker
breaker has
pin
has
link
be held
be used to
are
reach-
are set so
pin
the
to rotate
tube.
ro-
from
This is
off of the
the house
unless the
are
used.
the house
posi-
until the
passed
the
up
RACKOUT MECHANISM
AKR BREAKERS
Part
numbers in Figure
in
bers
on the breaker itself and a description
mechanism are
the
0673D0500
rackout mechanism for AKR breakers
The
given
The rackout mechanism is operated by
handle
the
house and counter-clockwise rotation moves the breaker
out. Approximately 18 turns of the handle will
breaker from the
position.
breaker
inserted.
operated by the breaker mechanism locks the sliding
over the racking screw in the breaker escutcheon. To insert
the
the sliding cover
insert-:d the cover is held open and the breaker is in a
onto the end
handle.
Clockwise rotation
DISCONNECTED
The rackout mechanism is interlocked so that
must
be open before
When the breaker is closed,
racking
handle the trip button must be depressed, and
pushed
20 refer to sheet and
series
of drawings.
in Maintenance Manual
jackscrew
of the
the operating handle can be
to the right. When the handle is
OPERATION
part
is mounted
and details of this
shaft and rotating
moves the breaker
to the
GEK-7310.
pushing
CONNECTED
the circuit
an interlock link
num-
into
move
cover
the
the
the
trip free condition. As long as the handle is engaged, the
breaker remains trip free.
There is also a
breaker trip
and
TEST
to
the breaker trip shaft
part
in
20,
before the
whether or not the rackout
841-01. This stationary
stationary cam in the house which
free as it is moved between the CONNECTED
positions
primary
by
keeping a lever
in the raised
disconnects have
cam comes into
handle
which is connected
position.
parted
is engaged.
holds
the
See Figure
oper..tion
and is operable
The
breaker
25
Page 26

GEK-7
Low V oltoge Swilchgeor
21 0 l,
thus cannot
the CONNECTED
CONNECTED
the rackout
be closed when it is between
position,
handle is disengaged.
An indicator,636-03,
front of the door,
in the
the house. The
on the
stationary
position.
indicated by
nism reaching
the rackout
stop the
at both
indicator label
breaker
gaged.
gaged
can be
The
and the
DISCONNECTED
The
rotation
ends
mechanism
versing
the direction
CAUTION:
BREAKER
TEST
on the
line
operated
secondary
primary
the sight
the
mechanism
of the
be reversed
can
WHEN
ON THE
SERT/ON,
HOUSE
SIBLE TO
BEFORE PULLING
,,HOISTING
IS PULLED
THE
AKRU BREAKERS"
TEMPT
THE
IS MADE
TRACKS
PARTMENT
THE CONNECTED
IN
NOT GO
WILL
(634-47
TRACK
TO
RACKOUT
ALL
BLOCKED
BE
FIGURE 2O).
IN
LOCK
THE LATCHED
MECHANISM
TION CORRECTLY.
the TEST
positions. From the TEST to
the breaker can
is visible through
which
shows the
position
marked TEST
indicator housing.
when the
control
power
and CONNECTED
indicator
its travel.
end of
(located
of the racking
action. The
of rotation
position
is reached
rackout
power
disconnects
and by the
on the
arms
any
at
of the handle.
motion of
point
MOUNTING
TRACKS
BE SURE
THAT
OUT
AS F/R
DISCONNECTED
THE TRACKS
/]VSERTIJVG
AND
WHILE
1{ND
ON PAGE
TO SET
IT INTO
FUSH
THE
A BREAKER
INNER
be closed when
of the
is aligned
In this
handle
disconnects
are open
rackout
The adjusting
breaker)
at the
in the
AKRTYPE
AN
PRIOR
THE
POSITION
OUT.
AKR
IF AN
17.
THE
HOUSE
POSITION,
BECAUSE
THE WAY
LINKS CANNOT
IN
BY THE
AT THIS
BE
POSITION
WILL
STOP
POINT
ROTATED
AND
NOT
the DIS-
opening
an
breaker in
the
when
with
position,
is disen-
are
positions
mecha-
nuts on
are set to
correct
the rackout
cycle by
IN-
TO
IN]VER
POS-
.4S
SEE
AND
AT-
ON
COM-
IT WILL
IT
L/1VKS
THE
THE
FUNC.
and
line
the
the
en-
in this
are
points
re-
IS
NOTE:
THE
DESCRIBED
PAGE
AKR OR
25 CANNOT
AKRU
FERENCES
ANISMS.
"EMERGENCY
FOR AK-75/
BE PERFORMED
BRE.AKERS
IN THE
DRAWOUT
BREAKERS
lOO
DUE
OPERATION"
OJV
FOR
DIF-
TO
MECH-
KEY INTERTOCKS
KEY INTERIOCKS
Part numbers
in the 0673D0500
bers
The key
and lock
removed
the lock
breaker is rendered trip
sition in the house.
washers
The interlock
from the lock
bolt
The
breaker may be operated
FOR AK BREAKERS
in Figure 21
series of drawings.
interlock is
mounted with
to the
system is designed
is
extended.
refer to sheet
left side
if the breaker
only
When the bolt
free only in the CONNECTED
TEST or DISCONNECTED
lock bolt is extended and the key removed.
The operation of the key interlock should
as follows:
l. With the breaker
trip the breaker.
ually
(622-66)
slide
is with the
in, the lock
to be
rackout operating
bolt
in the CONNECTED
This then allows the
pushed
may
in. The
handle. When the trip
extended
be
The interlock slide may then be allowed to return to its
normal reset
the CONNECTED
the lock
position.
position
bolt is retracted.
The breaker
until
2. If desired, the breaker may be moved
TEST or the DISCONNECTED
removed from the lock.
is
operated for checking
be
In
these
maintenance.
or
(OPTIONAL)
and
one-way screws
two
inner house.
of the
so that
the key
is tripped
is extended,
(closed
positions
preferred
and the
will
the key is returned
tripped)
and
even when
position,
interlock trip
way
key removed.
remain trip free
to either the
position
positions
while
the breaker
part
num-
may be
and
the
po-
in the
the
be checked
man-
this
to do
slide
and
the key
can
is
in
26
FlG.
(Ol2lCl5O7)
2l
Key
IMIERLOCK TRIP SLDE
Interlock
AK breokers
for
522.66
Page 27

P',,
KEY
LOCK
LOCK
{INNER
HOUSE
HoUsE
CAM,mRT
S|DE SHEET
0F 84t-01
Low
Voltoge
Swifchgeor,
GEK-72101
KEY INTERLOCKS
The
key interlock
and lock
removed
the
breaker
sition in
TEST
bolt is
as follows:
ually trip
slide
lock
breaker
until
TEST
is
can
washers
The interlock
from
lock
bolt is
is rendered
the
house.
The
breaker
may
or DISCONNECTED
extended
The
operation
1.
With the
(837-06)
bolt
the
2. If
removed
be operated
breaker
the
breaker.
to
may be
will
remain
key is
desired,
or
the DISCONNECTED
from the
FOR
is
to
the left.
system
the lock
extended.
trip
be
and the
of
the
pushed
be
extended
trip
returned
the
breaker
lock.
for
checking
FlG.
AKR BREAKERS
mounted
is designed
only if the
free
operated
with two
side of the
When
the bolt
only
in the
(closed
positions
so
that the key
breaker is
key removed.
key interlock
in the
CONNECTED position,
This
then
allows the interlock
in.
When the trip
and
the key removed.
free
in
the CONNECTED
and
the lock
may
bolt
be moved
position
In these
positions
or maintenance.
(75C150021)
22
(OPTIONAL)
one-way screws
inner house.
may
tripped
and
is extended,
CONNECTED po-
and
tripped) in
even
when the lock
should
be checked
the
man-
trip
slide is
in, the
The
position
is retracted.
to either
the
while the key
the
breaker
Key Interlock
be
the
for
AKR
breokers
compartment
tached to
being swung
The fuse rollout
compartment
breaker
door
the left side
open
directly
with
which the
this compartment
into
a compartment.
NOTE:
THE
ROLLOUT
TRACTED
RACKED
INTO
is opened.
unless the fuse
is
usually located
the same
See Page
KEY LOCK
An interference
of this
below
fuses
will be
way an AK
panel
rollout is
the compartnient
16.
BOLT
COMPARTMENT
BEFORE
THE
THE
CONNECTED
ROLLOUT
angle
prevent
to
fully withdrawn.
in
a modified
used. It is
breaker
IN THE
MUST BE
CAN BE
POSITION.
is at-
it from
breaker
for tlic
put
into
is inserted
FUSE
RE-
KEY INTERTOCKS
AK
breakers
be
equipped
assembly.
they
are
used
for the
rollout
A hinged
front
When
mounted
element,
panel
of
the fuses
with
breaker.
FOR
that
fuses
fuses
inside
and
made
so that
FUSE
ROLTOUTS
are
used in AKD-6
as an
integral
are required
a
drawout
This
a typical
assembly
perforated
of
model
they
with these
frame
is shown
steel
cannot
(INCLUDED)
switchgear
part
of the
similar
is
known
in Figure
positioned
is
be reached
cannot
breaker
breakers,
to that
as a
if
fuse
23.
the
in
FlG.
(8040045)
23
Fuse
Rollour
used wirh
AK
breokers
27
Page 28

GEK-7 21
01, Low
V
olta
ge
Swifchgeor
ERLOCK SLIDE
r09c2075-31
RIVETS
1o9c2075-26
TRACK
LOCX
LINK
FlG.
ment to
CONNECTED
it is locked
compartment in the normal
companion key interlock is
compartment. Figure
ing devices
extended.
that the racking wrench
shaft, This
(75C15002D
24
There is a key
keep the
position
open. A key interlock
in
this compartment
Note that the interlock slide
prevents
Key
Interlock
interlock system required in
fuse rollout in the CONNECTED or DIS-
unless the
24 shows the
cannot be
the fuse rollout from being racked out
of its compartment. Note also
in Figure 24. This holds the
position
fuse rollout
position
numbers in the
when the lock bolt is
from being
rotating
by
In
Figure
the
24
0673D0500
pulled
the track lock links.
part
numbers refer to sheet and
series of drawings
fqll drawing number is shown.
When the equipment is
breaker
the
rollout,
lock slide
removed.
rollout
the
position.
closed, the intedock
breaker compartment. In order
the associated breaker must
pushed
The key
compartment and
fuse rollout can be racked
in,
the
is then
lock
placed
the lock
for
R HOUSE
Fuse
SIDE SHEET
LOCK MOUNTING
Rollout
comportment
HOLES
the equip-
breaker associated with
is installed in the breaker
position. (See
Page
26) A
installed in the fuse rollout
position
when the key lock bolt is
of
the
interlock-
is held forward so
placed
over
the interlock bracket
lock link in
track
extended and
the
out of
operating
normally
jackscrew
the
shown
the closed
prevents
the
CONNECTED
part
except
when
with the
key is retained in the lock in
to withdraw the fuse
tripped, the
be
bolt
extended,
in
the lock in the fuse
and the
inter-
key
bolt is retracted. Now
out
DISCONNECTED
to the
The operation
checked
ceding
by following
paragraph.
of the key
procedure
the
interlock system should be
outlined in the
pre-
DOOR INTERTOCKS
These interlocks
door
when the breaker
DOOR
INTERLOCK FOR AK BREAKERS
Part numbers
bers in the
0673D0500
This door interlock
on the inner
prevent
opening of the
is
closed.
in Figure 25 refer to
series of drawings.
consists of a link
house side sheet of
the
breaker
compartment
(OPTIONAL)
sheet and
(074-03)
compartment.
part
mounted
num-
A combination torsion, compression spring is mounted on
the
tion.
(640-02),
anism interlock slide
a link operated
in
back. and then
from
back by
use
by
retracted
hole is
By inserting
the link
latch.
be raised
DOOR
bers in the
a
the
link
mounted
When
and the assembly
When the door is closed-with
partment,
bottom of
away from the
the link
Closed"
the
cannot
pivot pin
link
One end of the link engages a clip on the
and
the interlock slide. This
the
When
link
the
pushing
the rackout
raising
the handle while the interlock slide is held
position.
If required, the
provided
can be
With the link
and the door ooened.
TNTERLOCK FOR AKR
Part
numbers in Figure
This door
compartment
(8a4-03),
on the rear
the
door is open, the
the bracket on the
the link
and hook assume
portion
keeper swings
be opened.
and biases the link in a forward
the other end engages
627-46. When the breaker
the breaker cross
by
the door handle cannot
breaker is
actuated by the breaker.
it
handle. The door can then be unlatched
door interlock can be
prevents
open, the interlock slide is released
in. The
preferred
with
bar engages
the slide from
It
way
in the door in front of
a tool such
pushed
0673D0500 series of drawings.
interlock does not
door latch.
spring
of the compartment
is held against
(844-03)
door. When the door is
of Figure
up
a screwdriver
as
back until it is free of the door
held in
this manner,
BREAKERS
26 refer to sheet
operate in conjunction
It consists
(844-35),
and
spring
of a hook
bracket
door. See Figure 26.
pulls
the back of the
an open
breaker
and
positions
the
26. When the
and under
breaker in the
pushes
rotates
closed and latched,
shown
the
hook, and the
direc-
door latch
the
rackout
mech-
is closed,
in a
slot
moving
lifted.
be
now
can
to
defeated.
the
through this
the door latch can
(OPT|ONAL)
and
down on
the top of the
breaker is closed,
moved
be
do this is
A small
interlock
part
(844-04),
(844-05)
the hook,
against
in the
in
link.
hole,
num-
with
door.
com-
link
"Door
door
to
the
all
the
28
Page 29

INTERLOCK
OR
INTERLOCK
o74-03
INTERLOCK
SLIDE
6?7-46
SPRING
LOCK PLATE
622-02
PADLOCK
CUSTOMER
DOOR
LATOH
-
640
02
DOOR LOCKED
Low
V oltoge
DOOR INTERLOCK
BY
Swifchgeo r,
GEK-7
21 01
BREAKER
CLOSED
BREAKER
OPEN
FlG. 25
HOOK
(0121C1509)
844-04
844-03
LINK
KEEPER
ON
BREAKER
Door
Interlock
breokers
ond Podlock
BRACKET
844-O5
DOOR
ACCESS
LOCK
4-35
BRACKET
BREAKER
device for AK
HOLE
ON
DOOR
CLOSED
FlG.
(75CI50023)
26
Door Interlock
for
AKR
breokers
DOOR
OPEN
29
Page 30

GEK-7
21
01,
Low
oltage
V
Swifchgeor
When the
compartment,
rotate away
back
the
be lifted
will
drop into
the door
When
away from
and
be opened.
door is
from
side of
position
the
closed.
the breaker
If required, this
ing a small
door above the bracket.
the
of the hook toward
tool such as
top will move up
held in this
hook
opened.
RACKOUT
These devices
may be
anism
unauthorized
PADLOCK
operation.
DEVICE FOR AK BREAKERS
closed with
the bracket
the door.
the hook contacts
over the
shown
is opened,
the hook, and
door interlock
the
and away from
position,
MECHANISM PADTOCK
are arranged
padlocked
This accessory consists of
is riveted
the
ure 25.
slot in the
the
to the inner
slot of the extension
When one
plate,
jackscrew
cannot be
house side
to three
interlock slide cannot
the
can be locked anywhere
open the compartment
in the device,
interference
closed at will.
PADTOCK
but once
with the door
DEVICE FOR
This accessory
padlock
for
side
unit
occupy the upper
ure 7 for a
when
position,
rackout mechanism can
with this device.
used
out device
sions for locking
shackles.
sheet
pictorial
the inner house is
and tbese are the only two
is furnished. This has
ing the multiple
must be
but
been
opened to
there is
placed
no
position.
in
door in order
consists of two
One of the
and the other
left
corner of
view of the
If more
the ring with six
padlock
put
interference
the breaker
on
ffowever,
a closed
causes
when
breaker
the slope
the keeper, the hook
top of the
in Figure 26,
the keeper
the compartment
can be defeated
a screwdriver
This will
keeper
and will
thereby
swings
through the
push
the
rear of the compartment
the keeper,
the door
in certain
a slotted
on the
padlocks
turned. The
in its travel.
can be unlatched
so that
the rackout
positions
(OPTIONAI)
piece (622-02)
sheet. The slot
interlock
are inserted
rackout mechanism
It
place
to
DEVICES
slide. See
retracted and
be
necessary
is
the
the locks are secured,
and the door
AKR BREAKERS
to the inner
the compartment.
in
the TEST
be locked. Only one
padlocks
function.
padlock
the
with the door
may be opened or
(OPTIONAI)
plates,
each having
plates
is bolted
house. They
device. The
or DISCONNECTED
positions
padlock
are required, a
a single
padlocks,
The compartment
ring and
thus
or lockout
after they have
in the
the link
by insert-
lower
to
there
on
again
holding
down
door can
hole in
part
and the
With the
and
mech-
prevent
which
matches
Fig-
the
into
padlocks
is no
holes
to
to
to the
Fig-
See
holes match
in which the
can be
lock-
provi-
perform-
door
device
on,
NOTE:
MUST
GESTED
TO
PADLOCK SHACKLE
BE FROM
rHrCr(iVESS
DEVICES
FOR
BRElKERS.
MAINTENANCE
periodic
A
obtain
check and
devices and
mum requirement.
operation
permanent
A
The record should
kept.
and tests made,
of the equipment
performed.
were
recognized
National
safety regulations
WARNING:
ING
POWER APPARATUS
LIED UPON
PERSOJVIVEL.
For specific
devices,
to the separate
BRE.AKER
Breakers-Test and inspect
operation
maintenance
the best service
overall maintenance
all connections
Equipment
may require
more frequent
record of all
the date they were
and and any
Maintenance employees
practices,
safety
Electrical Safety
during
SOLID
ENERGIZED
AN
TO PROVIDE
information regarding
such as circuit breakers,
instruction book furnished
AND
INSTRUMENT
as follows:
a. Operate each breaker while
and check all functions.
breakers
positions
closed
WARNING:
normally remain in either the opened or
that
for long
PRIMARY EQUIPMENT MAST
BE COMPLETELY
BEING CONDUCTED.
/REAS OF
CIRCUITS
JRE DISCONNECTED.
Remove the breakers from their compartments
b.
maintenance area.
clean
suggested
in the appropriate
FEEDBACK
AS
WELL
Perform the maintenance
?IIICK,IVESSES
I/+1,
IS
BOTH AK AND AKR
schedule
from
should be
include a list of
3/8,,
TO
/tu!!.THIS
THE SUG-
APPLIES
must be established
the switchgear.
procedure
subject
maintenance work
repairs
the switchgear
for
followed
to highly
maintenance.
periodic
the condition
made,
-or
adjustments
must follow all
such as those
Code and in company
maintenance.
LATIO]Y SURROUIVD-
INSU
contained
CONDACTOR
MUST NEVER
BE RE-
PROTECTION TO
the maintenance of
relays, meters,
for each device.
COMPARTMENTS
all circuit breakers for
in the TEST
periods
particularly
time.
of
This is
DEENERGIZED WHILE
BE
SURE
FROM SECONDARY
/S
OUTS/DE
breaker maintenance
important for
THAT ALL
SOURCES
annual
An
as a
repetitive
should
checks
in the
or other
AND
etc., refer
proper
position
operation
manual.
to
mini-
be
that
to a
30
Page 31

Low
Yohoge Switchgeor,
GEK-72101
WARNING:
PLETELY
WORK
BAS
COMPARTMENTS.
ENERGIZING ANY
SIDE PRIMART
SUCH .eS ?RAIYSFORMERS, TIE
INSTRUMENTS,
DE-ENE
BEFORE
RGIZE EQAIPMBNT COM-
DOING MAINTENANCE
ON ANY DEVICES, CONNECTIONS,
WORK, BREAKER
OR
INSTRUMENT
OR FEEDER CABLE
THIS
CONNECTIONS TO OUT-
SECO,NDART SOURCES,
INCLUDES
TRANSFORMERS
AND RELAYS
Check
and inspect all devices
tioning
tight. Check
BREAKER
ment compartments.
only. Do
compressed air is not recommended.
locks.
signs of abnormal
silvered
properly.
COMPARTMENT
a. Thoroughly clean interior of the breaker
not use
b. Check indicating devices, mechanical and
c. Check
surfaces is
Check that
mounting
primary
of the device.
IJse a
steel
wool or oxide
disconnecting device contacts for
wear or overheating, Discoloration of the
not
ordinarily harmful. These contacts
should be cleaned only by
Before
replacing the
wipe ofr the
a
thin coat of contact lubricant D50H47
and fingers
primary
and to the
breaker, check
disconnecting device contacts. Apply
primary
to see that they
all electrical connections
INTERIORS
vacuum cleaner and clean rags
papers.
wiping with
disconnects
DE-
LINES, ETC.
are func-
are
and instru-
Blowing with
key
inter-
a
lint-free cloth.
the alignment
and
to the house studs
the
on
breaker.
readings.
nance
corded
lar conditions
include the
FEEDER
heating,
nection
Weakening
period
to the next
readings. The
each time, if
temperature and
CABLE AND BUSWAY
a. Inspect
b. Check all bolts that
all
and tighten
bars for
c. Check neutral
mounting
are
OVERALT
where necessary.
bolts
d.
Check that all secondary
tight
and that
SWITCHGEAR
a. Clean and inspect
b. Check to
tural
bolts are
c. Check
door latches
tight.
that
operate
Under normal
operate;
of
Book
PAINT
therefore,
these
devices
for tletailed instructions.
REFINISHING
of the insulation
can be recognized from
readings should
main cable
all connections.
tightness.
bus and
for
tightness.
all control
all
see that all
all breaker
properly.
conditions,
it is important
regularly.
from one mainte-
possible,
be taken under
and the record should
humidity.
COMPARTMENT
connections for signs of over-
hold cable terminals
ground
cabling is intact.
painted
anchor bolts
and instrument
the
Refer
bus
control
wiring connections
surfaces
protective
check
to
to the Relay Instruction
to the,con-
connection and
and retouch
and other struc-
compartment
relays do not
the
operation
the re-
simi-
BUS
COMPARTMENT
Before
formed cover
nished with the equipment.
the following can be
between units if such covers have been fur-
performed,
remove
a. Inspect the buses and connections carefully for
evidence of overheating
supports.
b. Check all connection
and
all bus mounting and
c. Wipe and vacuum
d. Check
breaker studs
partment.
e. After
ground
buses and
checking resistance.
Since definite
sulation
the insulation
through the
cleaning, megger and
and between
connections.
phases
Disconnect
Do not
limits cannot
resistance
values,
or weakening
bolts in the bus
bracing bolts for
clean the buses and supports.
on the bars
structure
bus
of
all
use over a 1500
given
be
a record
of
the
compartment
tightness.
that run from
to the cable com-
record the
insulated
resistance
bars, and all
all control circuits before
volt megger.
for satisfactory in-
must be kept
the
steel
insulating
the
of the
Indoor
Aqualure
an electrostatic
finish damaged
oil
Gray Glidden
02111,
touch-up
of ANSI-61
for
Tie-Cote
Diamond
IC-0702.
rust, scale,
with ANSI-61
Cat.
to
ing
Cat. IC-0702,
switchgear is finished
Paint,
grease.
or
Outdoor
Sand any scratches
using
Semi-gloss
a spray
purposes.
switchgear
gray
the second coat
Lacquer
Vogel ANSI-61
To
refinish damaged
oil
or
Gray
468-E-02111
with Diamond
rising spray
Cat. 478-E-02115,
spray system
areas, remove
is
paint
is ANSI-61
Cat. 468-E-02111
grease.
Glidden Semi-gloss
prime
as a
Vogel
with ANSI-61
which is applied
and is oven baked. To re-
smooth.
paint,
Apply ANSI-61
all loose
Tie-Cote'Lacquer,
can
supplied by the factory
finished
over the
with an
baked finish. The
gray
additional
Glidden Semi-gloss
and the
Gray Acrylic Lacquer
areas, remove
Sand
any scratches
coat,
ANSI-61
cans
supplied
Tie-Cote
and finish
Gray
Acrylic
by the factory.
Gray Glidden
with
rust, scale,
468-E-
Cat.
for
coat
primer
final coat is
Cat.
all loose
smooth.
coat by spray-
paint,
Spray
Lacquer
Lacquer
3r
Page 32

EEilERAT
DrsrRrBuTt0il
EI,ECTRIC C(|.
t0urPtEltT 0lYtsr0il
PtililYtLLE, C0ilt. 06062
GENERAL@ErECTRlc
Printed
in
u.s.A.