GE AIR F24, GE AIR F34, GE AIR F41 Service Manual

Page 1
1
GE Consumer & Industrial Appliances
Split System Air Conditioner
Model numbers:
GE AIR F24 GE AIR F34 GE AIR F41
Page 2
2
Page 3
3
Page 4
4
IInnttrroodduuccttiioonn aanndd FFeeaattuurrees
s
MMooddeell RReemmaarrkkss
GE AIR F24 1PH 230V 50Hz R407C
Page 5
5
MMooddeell
RReemmaarrkkss
GE AIR F34
3PH 400V 50Hz R407C
Page 6
6
MMooddeell
RReemmaarrkkss
GE AIR F41
3PH 400V 50Hz R407C
Page 7
7
Model GE AIR F24 Function Cooling Heating Power (Phase-Frequency-Voltage) 1Ph 50Hz 230V Tot a l C a pa c i t y (W) 7000 8500 Rated power (W) 3000 3050 Rated current (A) 14.6 15.1 Air flow volume (m3/h) 1170 Dehumidify volume (L/h) 2.3 C.O.P/EER (W/W) 2.3 2.79
Model GE AIR F24 IN Fan motor speed (r/min) (H/M/L) 1360/1280/1240 Output power of motor(W) 100 Fan type-piece Centrifugal Fan-4 Diameter-length (mm) ф125×134 Evaporator Aluminum fin-copper tube Pipe diameter ф7
Row-fin distance (mm) 3-1.6
Extended area of heat exchange (I×H×L) 1.042×0.19 Swing motor model MP35CA Power of motor (W) 4
Fuse (A) PCB5A Transformer 0.2A
Sound (pressure level) dB(A) ≤47 Dimension (W/D/H) (mm) 1300×188×600 Dimension of package (W/D/H) (mm) 1414×248×724
Indoor unit
Net weight/gross weight (kg) 32/36 Model GE AIR F24 OUT Input Power 2900 2950 Running Current 14.2 14.7 Compressor Model C-RN220H5B
Compressor Type Rotary Type
LRA(A) 75 Compressor Overload Protector Type Internal Inherent Protector Throttle Method Capillary Starting Method Capacitor
Range of working temperature( )℃ 7≤T≤43℃℃
Condenser Aluminum fin-copper tube Pipe diameter ф9.52 Row-fin distance (mm) 2-1.8 Extended area of heat exchange (I×H×L)mm
725×813
Fan motor speed (rpm) 60/780 Fan type-piece Axial Flow Fan-1 Fan Diameter (mm) Ф450
Defrosting Method Auto
Sound (pressure level) dB(A) ≤58 Dimension (W/D/H) (mm) 950×412×840 Dimension of package (W/D/H) (mm) 1100×450×920 Net weight/gross weight (kg) 75/87
Outdoor Unit
Refrigerant/Refrigerant Charge (kg) R407C/2.5 Length 5
Liquid Pipe (mm) Ф9.52(3/8”) Outer
Diameter
Gas Pipe (mm) Ф 16(5/8”) Height (m) 5
Connecting
Pipe
Max. Distance
Length (m) 10
Page 8
8
Model GE AIR F34 GE AIR F41 Function Cooling Heating Cooling Heating Power (Phase-Frequency-Voltage) 3Ph - 400V - 50Hz 3Ph - 400V - 50Hz Tot a l C a pa c i t y (W) 10000 11500 12000 13000 Rated power (W) 4400 4400 5000 4600 Rated current (A) 7.5 7.5 8.3 7.8 Air flow volume (m3/h) 2100 2200 Dehumidify volume (L/h) 2.6 3.4 C.O.P/EER (W/W) 2.27 2.61 2.4 2.83
Model GE AIR F34 IN GE AIR F41 IN Fan motor speed (r/min) (H/M/L) 1140/1070/980 1110/1000/900 Output power of motor(W) 150 150 Fan type-piece Centrifugal Fan-4 Centrifugal Fan-4 Diameter-length (mm) ф145×175 ф155×175 Evaporator Aluminum fin-copper tube Aluminum fin-copper tube Pipe diameter ф7 ф7
Row-fin distance (mm) 3-1.6 3-1.6
Extended area of heat exchange (I×H×L)
1.34×0.25 1.34×0.25
Swing motor model MP35CA MP35CA Power of motor (W) 4 4 Fuse (A) PCB5A Transformer 0.2A PCB5A Transformer 0.2A Sound (pressure level) dB(A) ≤52 ≤55 Dimension (W/D/H) (mm) 1590×238×695 1590×238×695 Dimension of package (W/D/H) (mm) 1770×330×830 1714×330×830
Indoor unit
Net weight/gross weight (kg) 42/53 42/51 Model GE AIR F34 OUT GE AIR F41 OUT Compressor Model C-SBN303H8A C-SBN353H8A Input Power 4250 4250 4850 4450 Running Current 6.9 7 7.6 7.1
Compressor Type Rotary Type Rotary Type
LRA(A) 42 55 Compressor Overload Protector Type Internal Inherent Protector Internal Inherent Protector Throttle Method Capillary Capillary Starting Method Capacitor Capacitor
Range of working temperature( )℃ 2≤T≤43℃℃ 2≤T≤43℃℃
Condenser Aluminum fin-copper tube Aluminum fin-copper tube Pipe diameter ф9.52 ф9.52 Row-fin distance (mm) 2-1.4 2-1.8 Working Area mm2 813×930 725×1218 Fan motor speed (rpm) 920 840 Fan type-piece Axial Flow Fan-1 Axial Flow Fan-2 Fan Diameter (mm) Ф482 Ф450
Defrosting Method Auto Auto
Sound (pressure level) dB(A) ≤62 ≤63 Dimension (W/D/H) (mm) 1040×410×840 1250×950×412 Dimension of package (W/D/H) (mm) 1100×450×880 1295×1110×450 Net weight/gross weight (kg) 90/105 112/133
Outdoor Unit
Refrigerant/Refrigerant Charge (kg) R407C/3.1 R407C/3.4 Length 5 5
Liquid Pipe (mm) Ф12(1/2”) Ф12(1/2”) Outer
Diameter
Gas Pipe (mm) ф19(3/4”) ф19(3/4”) Height (m) 5 5
Connecting
Pipe
Max. Distance
Length (m) 10 10
Page 9
9
CCoommppoonneenntt NNaammee
Applicable to GE AIR F24/ GE AIR F34
Indoor unit Swing Assy.
Air outlet
Decorative panel
Air inlet Water outlet
Front grill
Remote controller
Outdoor Unit
Air outlet
Connecting pipe
Air outlet grill
Drainage pipe
Air outlet
Page 10
10
Applicable to GE AIR F41
Indoor unit
Swing Assy. Air outlet
Decorative panel
Air inlet Water outlet
Front grill
Remote controller
Outdoor Unit
Air outlet grill
Air outlet
Connecting pipe
Air outlet grill
Air outlet
Drainage pipe
Page 11
11
OOvveerraallll aanndd IInnssttaalllliinngg DDiimmeennssiioon
n
Overall and Installing Dimension of Indoor Unit
Applicable to GE AIR F24 IN
Overall dimension
Installing dimension
Page 12
12
Applicable to GE AIR F34 IN/ GE AIR F41 IN
Page 13
13
Overall and Installing Dimension of Outdoor Unit
Applicable to GE AIR F24 OUT/ GE AIR F34 OUT
Unit: mm
Bolt Nut
Wrench
Page 14
14
Applicable to GE AIR F41 OUT
Unit: mm
Bolt Nut
Wrench
Page 15
15
SSyysstteemm DDiiaaggrraamm
System Diagram for Cooling-and-Heating Unit
Capillary
4-way valve
Evaporator Condenser
Gas-liquid
Cooling separator Compressor Heating
Switch on the power to start the unit. Low-pressure refrigerant vapor from evaporator is absorbed into the compressor, where it is compressed into high-temp. and high-pressure gas. The gas refrigerant is then diverted to condenser, where it is liquidized after heat exchange with outdoor air. After that, the liquidized refrigerant flows through capillary for decrease of temperature and pressure and then enters into evaporator, where it becomes low-temp. and low-pressure refrigerant vapor after heat exchange with indoor air to be regulated. This process is repeated in cycle to achieve the purpose of cooling. (Under heating mode, the 4-way valve will change the flow of refrigerant, so that the condenser absorbs heats and the evaporator gives out heats, thus to achieve the purpose of heating).
Page 16
16
GE AIR F24
GE AIR F34
66EElleeccttrriiccaall DDiiaaggrraamm
Page 17
17
GE AIR F41
In case of any change in the Electrical Diagram shown above, please follow the drawing on cabinet.
Page 18
18
T
preset
T
p
reset
T
preset
T
p
reset
CCoonnttrroolllleerr aanndd RReemmoottee CCoonnttrroolllleerr FFuunnccttiioonn MMaannuuaall aan
ndd OOppeerraattiinngg IInnssttrruuccttiioonnss
Controller and Remote Controller Function Manual
7.1.1 Temperature Parameters
Indoor preset temperature (T
preset
)
Indoor ambient temperature (T
amb.
)
Outdoor condenser temperature (T
cond.
)
7.1.2 Basic Functions
Once started under any mode, the compressor will not be stopped within 6 minutes with the change of ambient temperature. Once stopped, it cannot be restarted unless after 3-minute lag.
7.1.2.1 Cooling Mode
When T
amb.≥Tpreset
+1, the unit will run under cooling mode, in which case the compressor and outdoor fan will be
started, the indoor fan will run at preset speed and the swing will run as preset.
When T
amb.≤Tpreset
-1, the compressor and outdoor fan will be stopped and the indoor fan will run at preset speed.
When T
preset
-1℃<T
amb.
< T
preset
+1, the unit will maintain its original operating status.
Under cooling mode, the temperature can be set within a range from 16 to 30℃. The initial value is 25.
T
amb
Start cooling
Maintain original operating status
6 min. 3 min. 6 min. Stop cooling
Compressor
Outdoor fan
Indoor fan Run at preset speed
Run Stop
7.1.2.2 Dehumidifying Mode
When T
amb.≥Tpreset
+2 , the unit will run under coo ling mode, in which case the compressor and outdoor fan will be
started, the indoor fan will run at low speed.
When T
preset
-2 ≤T
amb.≤Tpreset
+2 , the compressor, indoor unit and outdoor unit will run 6 minutes and stop 4
minutes in repeated cycle, while the indoor fan will run at low speed.
When T
amb.
< T
preset
-2 , the compressor and outdoor fan will be stopped, and the indoor ran will keep running at low
speed.
¾ Under dehumidifying mode, the temperature can be set within a range from 16 to 30 . The init ial value is 25 .
T
amb
Start cooling
Run under dehumidifying mode
6 min. 4 min. 6 min. 4 min. Stop cooling
Compressor
Outdoor fan
Indoor fan Low speed
Run Stop
Page 19
19
T
preset
T
p
reset
7.1.2.3 Heating Mode
When T
amb.≤Tpreset
-1 , the unit will run under heating mo de, in which case the 4-way valve, compressor and
outdoor fan will be started, while the indoor fan will run at preset speed under preset cold air prevention condition.
If T
amb.≥Tpreset
+1 , the compressor and outdoor fan will be stopped, the 4-way valve is still energized and the indoor
fan will run at low speed for 10 seconds before it is stopped.
When T
preset
-1 <T
amb.
< T
preset
+1 , the unit will maintain its original operating status.
¾ Under heating mode, the temperature can be set within a range from 16 to 30 . The initial value is 25 .℃℃ ¾ If the unit is switched off under heating mode or switched to another mode, the 4-way valve will be de-energized 2
minutes after the compressor is stopped.
Start cooling
Ambient temperature T
amb
Maintain original operating status
6 min. 3 min. 6 min. Stop cooling
Compressor
Outdoor fan
Indoor fan
5 minutes
Preset speed
5 minutes
Preset speed
Louver valve
Run Stop
7.1.2.3.1 Cold Air Prevention Condition
The compressor will start at heat mode, indoor fan will not operate. After 5Min or if the outlet temperature is high, the indoor fan will run at preset speed. The indoor fan will no longer be stopped once it is started. Once running at preset speed, it will be impossible to change the speed of the indoor fan.
7.1.2.3.2 Defrosting Conditions
When the condenser is detected to have frost, the system will enter into defrosting mode, in which case the 4-way
valve, indoor fan and outdoor fan will be stopped.
When it is detected that the frost in condenser is completely eliminated, the 4-way valve and outdoor fan will be
started simultaneously, while the indoor fan will start to run under preset cold air prevention condition.
10 min.
Compressor
Outdoor fan Indoor fan
3min.
Preset speed
Run Stop
7.1.2.4 Fan Mode
Indoor fan will run at preset speed
Auto Speed Low Speed Medium Speed High Speed
The temperature can be set within a range from 16 to 30 . The initial value is 25 .℃℃
7.1.2.5 Auto Mode
Under this mode, the system will automatically select its run mode (cooling, dehumidifying, heating or fan) depending on ambient temperature.
¾ Once a mode is started, the unit will run at least 30 seconds before it can run the status of auto mode depending on
ambient temperature.
7.1.3 AUTO ON/OFF and Sleep Function
7.1.3.1 Sleep
If the controller is under cooling or dehumidifying mode, the preset temperature will be increased by 1 one hour
after running under sleep mode and will be increased by another 1 after two hours. The temperature will increased by 2 within two hours. After that, the unit will run at this temperature.
Page 20
20
T
preset
T
preset
T
preset
T
preset
T
preset
T
preset
Set the Temperature T
preset
1 hours 2 hours Over 2 hours
If the controller is under heating mode, the preset temperature will be decreased by 1 one hour after running under
sleep mode and will be decreased by another 1 after two hours. The temperature will decreased by 2 within two℃℃
hours. After that, the unit will run at this temperature.
1 hours 2 hours Over 2 hours
Set the Temperature T
preset
No sleep function under fan mode or auto mode.
7.1.3.2 AUTO ON
You can set AUTO ON function when the unit is under standby status. Upon the time of AUTO ON, the controller will
run under preset mode. The time interval for AUTO ON is 0.5h, and can be set within 0.5 - 24 hours.
7.1.3.3 AUTO OFF
You can set AUTO OFF function when the unit is under ON status. Upon the time of AUTO OFF< the system will be
switched off. The time interval for AUTO OFF is 0.5h, and can be set within 0.5 - 24 hours.
7.1.4 Other Control
7.1.4.1 Swing Control
You can switch on or off the swing by pressing the SWING key. The swing is valid only when the indoor fan is running.
7.1.4.2 Buzzer Control
When the controller is energized or receives valid key-press signal, the buzzer will give a beep.
7.1.4.3 Automatic Control of Indoor Fan Speed
Under this mode, the indoor fan will automatically select its speed, i.e. high, medium or low, depending on ambient temperature. Once a speed is activated, the indoor fan will run at least 30 seconds before it can switch over to other conditions.
7.1.5 Protection
7.1.5.1 Indoor Antifreeze Protection
If E2 is displayed under cooling mode, the compressor, outdoor fan and indoor fan will be stopped, and the swing
motor will maintain its original status. When evaporator temperature is higher than 6 and the compressor has been
stopped for 4 minutes, the display will resume and the controller will run under preset mode.
Under dehumidifying mode (i.e. run 6 minutes and stop 4 minutes), if it is detected within 3 minutes successively that
the tube temperature is lower than -2 after the compressor has been running for 3 minutes, the c ompressor and
outdoor unit will be stopped, the indoor fan will run at low speed, and E2 will be displayed. When tube temperature is
higher than 6 and the compressor has been stopped for 4 minutes, the display will resume and the controller will
run under preset mode.
7.1.5.2 Compressor High-pressure Protection
If high-pressure protection is detected within 3 seconds successively, all loads will be closed, all key-press and remote control signals will be shielded, and E1 will be displayed. When it is detected within 6 seconds successively that the compressor has released high-pressure protection, shielding of key-press signal will be removed but E1 will be still displayed. To clear off E1 display, you have to press ON/OFF key to switch off the unit and press it again to restart.
7.1.5.3 Compressor Low-pressure Protection
When it is detected that the low-pressure switch is off, the complete unit will be stopped and be automatically
restarted after 3 minutes. If E3 is displayed, the unit cannot be restarted automatically, in which case you have to press ON/OFF key to switch off the unit and press this key again to restart.
Page 21
21
If it is detected that the low-pressure switch is off when the compressor is stopped, the complete unit will be stopped,
E3 will be displayed and the unit cannot be restarted automatically. You have to press ON/OFF key to switch off the unit and press this key again to restart.
7.1.5.4 Exhaust Pipe High-temp. Protection
After the compressor is started, if the exhaust temperature is too high or exhaust sensor is in short circuit (or open
circuit), the unit will be stopped when the indoor ambient temperature reaches the preset value.
After the compressor is stopped for 3 minutes, the complete unit will be restarted when the exhaust temperature is
resumed to normal.
In case of above issue, the complete unit cannot resume its operation and E4 will be displayed. You have to press
ON/OFF key to switch off the unit and press this key again to resume operation under preset mode.
7.1.5.5 Indoor Overtemperature Protection
If it is detected that the evaporator tube temperature is too high under heating mode, the outdoor fan will be stopped.
When the evaporator tube temperature resumes to normal, the outdoor fan will be started.
7.1.5.6 Low-voltage Protection
If the current is detected over 22A as the compressor is started, the unit will be stopped when indoor ambient
temperature reaches preset value. The compressor will automatically resume to its original operating status after it is stopped for 3 minutes. If E5 is displayed, the compressor cannot resume to its original operating status automatically, in which case you have to press ON/OFF key to switch off the unit and press this key again.
7.1.5.7 Fault Code and Definition
Fault Code Definition
E1 Compressor High-pressure Protection
E2 Indoor Antifreeze Protection
E3 Compressor Low-pressure Protection
E4 Exhaust Pipe High-temp. Protection
E5 Low-voltage Protection
7.1.5.8 Compulsory Cooling (Heating) Mode
If no valid key-press upon first energization:
From the remote controller, you can press temperature selection key (+) to enter into compulsory heating mode, in
which case all the keys on front panel and remote controller will be shielded, all loads will be started and the indoor
fan will run at high speed. If it is detected that ambient temperature is in open circuit or higher than 105 , or that evaporator temperature is in open circuit or higher than 105 , the buzzer will beep. After five minutes, the unit will be
stopped and enter into normal standby status.
From the remote controller, you can press temperature selection key (-) to enter into compulsory cooling mode, in
which case all the keys on front panel and remote controller will be shielded, all loads except the 4-way valve will be started and the indoor fan will run at high speed. If it is detected that ambient temperature is in open circuit or higher
than 105 , or that evaporator temperature is in open circuit or higher than 105 , the buzzer will beep. After five ℃℃
minutes, the unit will be stopped and enter into normal standby status. The functions stated in 1 and 2 are only for test purpose. Compulsory heating function is not available for cooling-only unit.
7.1.5.9 Indicator
Power indicator: It is bright when energized and black when de-energized. It will blink under indoor antifreeze
protection, compressor high-pressure protection, low-voltage protection and defrosting.
Cooling indicator: It is bright under cooling mode, dehumidifying mode, auto cooling mode or auto dehumidifying
mode. It is black under other modes.
Heating indicator: It is bright under heating mode and auto heating mode. It is black under other modes
7.1.5.10 Power-OFF Memory Function
Memory function includes the mode, swing, preset temperature, preset fan speed, Auto ON/OFF (If the power is cut off before the preset time for AUTO ON/OFF, the timer will count the time again once the power is resumed. If the power is cut off after the preset time for AUTO ON/OFF, the unit, once energized again, will run under the mode after preset AUTO OFF time). Once energized again after any de-energization, the unit can be automatically restarted according to the memory.
Page 22
22
Description and Function of Remote Controller Keys
Notes:
z Make sure that there is no obstruction between remote controller and signal receiving window. z Do not fall off or throw the remote controller. z Do not let any liquid flow into remote controller, or expose the remote controller under direct
sunshine or extreme hot temperature.
SWING key One press of this key will enable the guide louver to swing at a specific angle. Another press will stop the
g
uide louver.
TEMP. key Each press of (+) key will increase the preset temperature by 1 . Each press of (-) key will decrease the preset temperature by 1 . Under “ “ mode, the indoor temperature can be adjusted to any value between 16~30 .
MODE key The run mode will change sequentially as below with each press of MODE key.
Auto
FAN ke y Each press of this key will change the fan speed sequentially as below:
Auto Fan
Note: The fan speed is not adjustable under Mode.
Cooling mode
Dehumidifying mode
Fan mode
Heating Mode
ON/OFF key Press this key to start the air conditioner. Press it again to stop the air conditioner.
Page 23
23
Description and Function of Remote Controller Keys (After opening the rear cover)
Note: This remote controller is for general use and applicable to multiple types (functions)
of air conditioner. AIR, HUMID, LIGHT, ANION and SAVE buttons are not used for these
models.
LCD display Display the information selected by each key
SLEEP key Press this key to enter into sleep mode and press it again to exit sleep mode. Note: There is no sleep function under Auto or Fan mode.
AUTO OFF key Pressing this key when the unit is running, you can set the AUTO OFF time from 0 to 24 hours.
Cancel the AUTO
ON/OFF
Lamp indicator Press this key to switch on the lamp.
Press it again to switch off the lamp.
AUTO ON key Pressing this key when the unit is stopped, you can set the AUTO ON time from 0 to 24 hours. Each press of this key will increase the time by
0.5 hour.
Cancel the
AUTO ON/OFF
Page 24
24
Battery cover
Installation of Remote Controller Batter
z Operating Guideline
General Procedures:
1. Switch on the power and press ON/OFF key to start the air conditioner.
2. Press MODE key to select your desired run mode.
3. Press SWING key to enable the guide louver to swing at a specific angle. Press it again to stop the swing.
4. Press FAN key to set the fan speed.
5. Press +/- key to set your desired temperature.
Optional Procedures:
6. Press SLEEP key from remote controller to set the sleep mode.
7. Press AUTO ON/OFF key and then press +/- key to set the timer.
Note: When auto mode is selected, the air conditioner will automatically select an appropriate run mode
according to the indoor temperature, making the environment comfortable.
z Replacement of Remote Controller Battery
Two pieces of 7# alkali dry batteries are used in the remote controller.
1. Slide the battery cover of remote controller downward. Remove the old batteries and replace with two pieces of new batteries (Take care that the polarity shall be correct)
2. Close the battery cover of remote controller.
Note:
z Do not use new batteries together with old
batteries, or use different types of batteries together.
z To avoid leakage of liquid and damage to the
remote controller, please take out the batteries if you will not use the remote controller in several weeks.
z Operate the remote controller within effective
range.
z Keep the remote controller at least 1 meter
away from television set or sound equipment.
RESET key
Insert two 7# batteries.
Page 25
25
Screw
(Fig
8-3
)
DDiissaasssseemmbbllyy aanndd AAsssseemmbbllyy PPrroocceedduurrees
s
Disassembly Procedures of Indoor Unit GE AIR F24 IN, F34 IN & F41
Disassemble Front Grill Sub-Assy
Manually push the clasp of front grill sub-assy downward to open the front grill. (Fig 8-1)
(Fig 8-1)
Clasp
Disassemble Left and Right Panels
Use screwdriver to screw off the screws shown in the position, and then move the panels toward the direction of arrow to Disassemble the left and right decorative panels. (Fig 8-2)
Screw (Fig 8-2)
Disassemble Electric Box Assy
A. Use screwdriver to twist off the two screws
shown in the figure and remove the electric box cover (8-3);
B. Use screwdriver to twist off the screw shown in
the figure, remove the capacitor support, and disconnect the cables (refer to Figure 8-4);
C. Use screwdriver to twist off the four screws (2
screws at each side), remove the electric box sub-assy, and disconnect the cables (refer to Figure 8-5);
(Fig 8-4) Screw Screw (Fig 8-5)
Page 26
26
Operating Procedures / Photos
Disassemble Front Panel Assy
Use screwdriver to screw off the six screws shown in the figure (two screws at the left, right and rear sides respectively), remove the front panel assy toward the direction shown in the figure to remove it (refer to figures 8-6, 8-7).
Screw Screw
(Fig 8-6) (Fig 8-7)
Disassemble Guide Louver Sub-assy
First remove the guide louver from the fitting position of the guide louver support, then remove the two ends of the guide louver from the fitting position of the swing motor. (Fig 8-8)
Support Motor fitting position (Fig 8-8)
Disassemble Water Tray Sub-assy
Use screwdriver to screw off the three screws shown in the figure so as to remove the water tray sub-assy (refer to Figure 8-9).
Screw
(Fig 8-9)
Page 27
27
Operating Procedures / Photos
Disassemble Mounting Plate Sub-assy of Swing Louver
Use screwdriver to screw off the screws at both ends of the mounting plate sub-assy of swing louver. Take the mounting plate sub-assy of swing louver apart from the guide louver support. (Fig 8-10)
Screw Support
(Fig 8-10)
Disassemble Evaporator Assy
Use screwdriver to screw off the screw shown in the figure. Remove the tube-exit clamp sub-assy of evaporator. (Fig 8-11)
Use screwdriver to screw off the screw shown in the figure and remove the evaporator assy. Handle with care. (Fig 8-12Fig 8-13)
(Fig 8-11) Screw Screw (Fig 8-12)
Screw
(Fig 8-13)
Disassemble Air Outlet Rear Side Plate Sub-assy
First remove the velvet sheet and the left and right side plate cushions at the air outlet; then use screwdriver to screw off the screw shown in the figure. (Fig 8-14)
Screw
(Fig 8-14)
Page 28
28
Operating Procedures / Photos
Disassemble Mounting Plate Sub-assy of Swing Motor
Use screwdriver to screw off the screw shown in the figure. (Fig 8-15)
(Fig 8-15) Screw
Disassemble Left and Right Side Plate Foam Sub-ass
Left Side Plate Foam Sub-assy
Right Side Plate Foam Sub-assy
Follow the shown direction to remove the left and right side plate foam sub-assy. (Fig 8-16)
(Fig 8-16)
Disassemble Fan Motor Assy
Press downward the clasps fitting the front and rear propeller housings, then pull upward to remove the front propeller housing (refer to Figure 8-17).
Hold the clasp position of the rear propeller housing and pull upward to remove the rear propeller housing (refer to Figure 8-18).
Use special tool to screw off the two holding screws at the coupling, move the coupling toward the fan until the coupling and shaft sub-assy can be removed; use special tool to remove the holding screw fixing the fan to remove the fan (refer to Figure 8-19).
Clasp Position (Fig 8-17) Holding Screw
(Fig 8-18)
(Fig 8-19)
Page 29
29
Operating Procedures / Photos
Disassemble Bearing Mounting Plate
Use screwdriver to screw off the four screws at the bearing mounting plate. (Fig 8-20)
Screw
(Fig 8-20)
Disassemble Motor
Use screwdriver to screw off the screw shown in the figure to remove the motor clamp and the motor fixing hoop. (Fig 8-20)
Screw (Fig 8-20)
Disassemble Motor Mounting Plate Sub-assy
Use screwdriver to screw off the screw at the motor mounting plate to remove the motor mounting plate sub-assy. (refer to Figure 8-21).
Motor Mounting Plate Sub-assy
Screw
(Fig 8-21)
Page 30
30
Operating Procedures / Photos
Disassemble Supporting Plate of Motor Support
Use screwdriver to screw off the screws connecting the supporting plate of motor support and the rear side plate sub-assy with the motor support. (Fig 8-22)
Tapping Screw
(Fig 8-22)
Disassemble Left and Right Mounting Plates
Use tool to remove the bolts (2 X M8, 2 X M6) fixing the left and right mounting plates. (Fig. 8-23)
Mounting Plate
M8 Bolt M6 Bolt (Fig 8-23)
Disassemble Motor Support
Use screwdriver to screw off the screws at the rear support base plate and at the both sides of the support as shown in the figure to remove the motor support. (refer to Fig. 8-24、8-25).
(Fig 8-24)
Screw
(Fig 8-25)
Page 31
31
Disassembly Procedures of Indoor Unit
Operating Procedures / Photos Applicable to the models: GE AIR F34 IN/ GE AIR F41 IN
Disassemble Front Grill Sub-Assy
Use tool to push the clasp 1 of front grill sub-assy downward to open the front grill. (Fig 8-26)
Front Panel Clasp 1
(Fig 8-26)
Disassemble Left and Right Decorative Panels
Screw off the screw in the decorative panel, and then manually pull toward the direction of arrow to remove the left and right decorative panels. (Fig 8-27)
Screw (Fig 8-27)
Disassemble Electric Box Assy
Use screwdriver to twist off the two screws at the electric box and manually pull the electric box cover upward to remove the electric box. (Fig 8-28)
Use screw driver to loosen the two screws at upper and two screws at lower. Remove the capacitor board (As shown in Fig. 8-29) Use screwdriver to twist off the two upper screws and the two lower screws and remove the capacitor support. Use screwdriver to screw off the screw shown in Figure 5 and disconnect the cables to remove the electric box sub-assy. (Fig 8-30)
Screw
(Fig 8-28)
Screw
(Fig 8-29)
Screw
(Fig 8-30)
Page 32
32
Operating Procedures / Photos
Disassemble Front Panel Assy
Screw off the screws at the front and at the two sides. Remove the front panel sub-assy. (Fig 8-31)
Front
Panel Sub-assy
Screw
(Fig 8-31)
Disassemble Guide Louver Sub-assy
First remove the guide louver from the fitting position of the guide louver support, then remove the two ends of the guide louver from the fitting position of the swing motor. (Fig 8-32)
(Fig 8-32)
Disassemble Water Tray Sub-assy
Use screwdriver to screw off the nut with washer at the middle of water tray. (Fig 8-33)
Use screwdriver to screw off the two side screws of the auxiliary water tray. Pull the auxiliary water tray and the water tray upward to remove them. (Fig 8-34)
Disassemble Mounting Plate Sub-assy of Swing Louver
Water Tray
Nut with Washer
(Fig 8-33)
Auxiliary Water Tray
Screw
(Fig 8-34)
Use screwdriver to screw off the screws at both ends of the mounting plate sub-assy of swing louver. Take the mounting plate sub-assy of swing louver apart from the guide
louver support. (Fig 8-35)
Screw (Fig 8-35)
Page 33
33
Operating Procedures / Photos
Disassemble Evaporator Assy
Use screwdriver to screw off the two screws at the tube-exit plate of evaporator. Remove the tube-exit plate of evaporator. (Fig 8-36)
Use screwdriver to screw off the screw shown in the figure to remove the evaporator. (Fig 8-37)
Tapping Screw
Tube-exit Plate of Evaporator
)
Tapping Screw
Disassemble Left and Right Mounting Plates
(Fig 8-37)
First remove the flocking fabrics and the left and right side plate cushions at the air outlet; then use screwdriver to screw off the screw shown in the figure. (Fig 8-38)
Screw
(Fig 8-38)
Disassemble Mounting Plate Sub-assy of Swing Motor
Use screwdriver to screw off the screw shown in the figure. (refer to Figure 8-39).
Screw
(Fig 8-39)
Page 34
34
Operating Procedures / Photos
Disassemble Mounting Plate
Sub-assy of Swing Motor
Left Side Plate Foam Sub-assy
Right Side Plate Foam Sub-assy
Use screwdriver to screw off the screw shown in the figure. (Fig 8-40)
Disassemble Fan Motor Assy
(Fig 8-40)
Press downward the clasps fitting the front and rear propeller housings, then pull upward to remove the front propeller housing (refer to Figure 8-41).
Hold the clasp position of the rear propeller housing and pull upward to remove the rear propeller housing (refer to Figure 8-42).
Use special tool to screw off the two holding screws at the coupling, move the coupling toward the fan until the coupling and shaft sub-assy can be removed; use special tool to remove the holding screw fixing the fan to remove the fan (refer to Figure 8-43).
(Fig 8-41) (Fig 8-42)
Clasp Position Holding Screw
Clasp Position
Disassemble Bearing Mounting Plate
Use screwdriver to screw off the four screws at the bearing mounting plate. (Figure 8-44).
Disassemble Motor
Use screwdriver to screw off the screw shown in the figure to remove the motor clamp and the motor fixing hoop.(Figure 8-45)
Screw Screw
(Fig 8-44) (Fig 8-45)
Page 35
35
Operating Procedures / Photos
Disassemble Motor Mounting Plate Sub-assy
Use screwdriver to screw off the six screws at the motor mounting plate to remove the motor mounting plate sub-assy. (Fig 8-46)
Motor Mounting Plate Sub-assy
(Fig 8-46)
Tapping Screw
Disassemble Supporting Plate of Motor Support
Use screwdriver to screw off the screws connecting the supporting plate of motor support and the rear side plate sub-assy with the motor support. (Fig 8-47)
Disassemble Left and Right Mounting Plates
Tapping Screw (Fig 8-47)
Use tool to remove the bolts (2 X M8, 2 X M6) fixing the left and right mounting plates. (Fig 8-48)
Disassemble Motor Support
Use screwdriver to screw off the screws at the rear support base plate and at the both sides of the support as shown in the figure to remove the motor support.
(Fig 8-48)
Right Mounting Plate Bolt
Left Mounting Plate
Tapping Screw
Bolt
(Fig 8-49)
Page 36
36
Disassembly Procedures of Outdoor Unit
Operating Procedures / Applicable Models: GE AIR F24 OUT / GE AIR F34 OUT
Disassemble Front Side Plate
Screw off the four screws around the front side plate to remove the front side plate. (Fig 8-50)
Front side plate
Screw
(Fig 8-50)
Disassemble Top Cover
Screw off the tapping screws around the top cover, and then pull the top cover upward to remove it. (Fig 8-51)
Screw
Top Cover
(Fig 8-51)
Disassemble Rear Grill
Screw off the four screws around the rear grill to remove the rear grill. (Fig 8-52)
Screw
Rear Grill
(Fig 8-52)
Page 37
37
Operating Procedures / Photos
Disassemble Housing
Use screwdriver to screw off the screws around the cabinet to remove the housing. (8-53)
Screw
Housing
(Fig 8-53)
Disassemble Electric Box Screw
Use screwdriver to screw off the screws fixing the electric box, and pull the electric box to remove it. (Fig 8-54)
Electric Box
Communication Ceiling Type Unit Electric Box
Screw
(Fig 8-54)
Disassemble Right Side Plate
Use screwdriver to screw off the screws at the right side plat, condenser side plate, gas valve and liquid valve, and then pull the right side plate sub-assy upward to remove it. (Fig 8-55)
Screw
Right Side Plate
(Fig 8-55)
Page 38
38
Operating Procedures / Photos
Disassemble Axial Flow Fan
Use spanner to remove the nut at the fan to remove the axial flow fan. (Fig 8-56)
Nut
Axial Flow Fan
(Fig 8-56)
Disassemble Outdoor Motor Motor
Screw off the four tapping screws fixing the motor, pull out the motor lead-out cable plug, and remove the motor. Screw off the two tapping screws fixing the motor support, and pull the motor support upward to remove it. (Fig 8-57)
Screw Fixing the Motor
Motor Cable
Motor Support
Fixing Screw
(Fig 8-57)
Disassemble 4-Way Valve
Only Heating and Cooling Unit has such valve
Screw off the holding nut of the 4-way valve coil and remove the coil. Use wet cotton cloth to wrap the 4-way valve, unsold the four soldering points connecting the 4-way valve, and remove the 4-way valve. Be quick during the unsoldering process, pay attention to keep the wrapping cloth wet and do not allow the soldering flame to burn the compressor lead-out cable. (Fig 8-58)
4-Way Valve
Soldering Point
(Fig 8-58)
Page 39
39
Operating Procedures / Photos
Disassemble Capillary
Unsold the soldering points at the capillary, the valve and the condenser to remove the capillary. Pay attention not to allow the soldering slag to block the capillary.
(Fig 8-59)
Capillary
Disassemble Valve
Unscrew the two screws fixing the gas valve, unsolder the soldering point between the gas valve and the return-air duct and remove the gas valve (note: when unsoldering the soldering point, use wet cloth to completely wrap the gas valve to prevent valve body from being harmed by high temperature). Unscrew the two screws fixing the liquid valve, unsolder the soldering point connecting the liquid valve and the fork type pipe, and remove the liquid valve. (Fig 8-60)
Liquid Valve Screw Gas Valve
Disassemble Compressor
Firstly unsolder the pipes connecting the compressor, and then unscrew the three foot nuts at the compressor to remove the compressor. (Fig 8-61)
Foot Nut
Page 40
40
Disassembly Procedures of Outdoor Unit
Operating Procedures/ / Applicable Models: GE AIR F41 OUT
Disassemble Rear Grill
Screw off the tapping screws at the rear side plate, valve support chassis and condenser side plate to remove the rear grill. (Fig 8-62)
Rear Grill
Screw
Disassemble Top Cover Plate Screw
Screw off the tapping screws around the top cover, and then pull the top cover upward to remove it. (Fig 8-63)
Top Cover
Disassemble Front Side Plate
Screw off the three tapping screws at the front side plate, and then pull the front side plate upward to remove it. (Fig 8-64)
Front Side Plate
Screw
Page 41
41
Operating Procedures / Photos
Disassemble Housing
Unscrew the screws around the housing to remove it.
(Fig 8-65)
Screw
Housing
Disassemble Electric Box
Unscrew the screws around the electric box sub-assy to remove it. (Fig 8-66)
Screw
Communication Cassette Type Unit Electric Box
Screw
Disassemble Right Side Plate
Unscrew the screws around the right side plate to remover the right side plate. (Fig 8-67)
Right Side Plate
Screw
Page 42
42
Operating Procedures / Photos
Disassemble Axial Flow Fan
Use spanner to twist off the nut of the fan and remove the fan.
(Fig 8-68)
Nut
Nut
Disassemble Outdoor Motor
Screw off the four tapping screws fixing the motor, pull out the motor lead-out cable plug, and remove the motor. Screw off the two tapping screws fixing the motor support, and pull the motor support upward to remove it. (Fig 8-69)
Motor
Screw Fixing the Motor
Motor Support
Fixing Screw
Disassemble 4-Way Valve
Screw off the holding nut of the 4-way valve coil and remove the coil. Use wet cotton cloth to wrap the 4-way valve, unsold the four soldering points connecting the 4-way valve, and remove the 4-way valve. Be quick during the unsoldering process, pay attention to keep the wrapping cloth wet and do not allow the soldering flame to burn the compressor lead-out cable. (Fig 8-70)
4-Way Valve
Page 43
43
Operating Procedures / Photos
Disassemble Valve
Unscrew the screw fixing the valve, unsolder the connecting pipe of the valve, and remove the valve.
(Fig 8-71)
Screw Liquid Valve Screw
Gas Valve
Disassemble Capillary
Unsolder the soldering points between the capillary and other pipes to remove the capillary. (Fig 8-72)
Capillary
Disassemble Compressor
Unscrew the foot screw of the compressor and unsolder the connecting pipe to remover the compressor. (Fig 8-73)
Foot Nut
Page 44
44
99 CCaarree aanndd MMaaiinntteennaannccee
Warning
z Be sure to stop the unit and plug out the power before cleaning your air
conditioner. Otherwise, electric shock may happen.
z Never splash water on the indoor unit, this may cause the risk of
electric shock.
z Volatile liquids such as thinner or gasoline will cause damage to the
appearance of air conditioner. (Only use soft dry cloth or wet cloth soaked with neutral detergent to clean the indoor unit).
9.1 To clean the filter
Remove the filter and clean with vacuum cleaner. If
very dirty, wash with warm water (below 45) that is
added with neutral detergent. Fully dry the filter before reinstallation.
Suggestion: Too dirty filter will reduce air inflow and result in system overload, causing 6% more consumption of power. Therefore, it is quite necessary to clean the filter regularly.
9.2 To clean the equipment and components
Use dry and soft cloth or vacuum cleaner to clean the air conditioner and remote controller. If wet cloth is used, please wipe it dry after cleaning.
Warning: Never expose the front grill or air filter directly under the sun. Never clean it with hot
water over 45℃ or dry it on fire, (as this will cause decoloring, fire or deformation).
9.3 When using the air conditioner
Check for any foreign articles that may obstruct the air into or out of the indoor and outdoor unit. If the unit is operating without air filter, dust will deposit and cause trouble to the unit. Generally, be sure to install filter before operating the unit. Check the drainage pipe for bend or damage. Check the equipment for normal and correct installation.
9.4 When the air conditioner is out of service
Pull off the plug and disconnect the power. Clean the filter, equipment and components. Start the fan for 2 to 3 hours to clean and dry the inside of the equipment.
Page 45
45
Air –conditioning unit
cannot be started
Trip of circuit breaker or burn-out of fuse
Check insulation resistance for grounding; Confirm if air-conditioning unit has electrical leakage or is short-circuited
When set short-circuiter as ON , it trips immediately
When air-conditioning unit is powered on, there is no action (when the unit is plugged in, buzzer does not sound and there is no action after using the remote controller to start the unit)
Remote controller does not receive signal (when unit is powered on, buzzer shall sound, unless buzzer is damaged)
No power
supply
Check and secure the plug to ensure firm contact
Power plug is not firmly seated or connection is poor
Replace controller fuse
Controller fuse burned out
Secure line connections; measure output voltage of transformer and replace transformer if it is incorrect
Connection line of transformer is loose or suffers from poor plugging, or there is transformer failure
Replace controller
Controller is damaged
Batteries of remote controller are running out of
p
owe
r
Remote controller failure
Receiving head is loose or plug connection is
poor
Receiving head is damaged
Replace battery
First press “AUTO” key of manual switch. If there is no action check according to the above method; if the operation is normal after pressing the key, recheck to see if the mounting position of receiving head and the line connections are correct; if they are correct, replace receiving head or remote controller.
Check power voltage. If the voltage is 10% than rated voltage, check the cause, and improve the power supply conditions such as adding regulated power supply.
When turning the air-conditioning unit to the ONstatus, trip of circuit breaker occurs several minutes later
Failure of air-conditioning unit or component insulation failure, short circuit or electricle leakage owing to insulation puncture after heating, measure insulation resistance or check the components one by one to find the ones with failure; failure of circuit breaker itself, replace it.
Power voltage is too low
10 Trouble-Shooting
Page 46
46
Poor cooling (heating)
effect
Set temperature is not appropriate
Adjust the set temperature
Check if the cooling (heating) load is appropriate
Check the forecasted cooling (heating) load
Failure of
refrigerant flow
Leakage of refrigerant or insufficient refrigerant
Check leakage, carry out vacuum-pumping after repairing leakage and charge refrigerant according to requirements
Leakage between internal high pressure and low pressure sections of compressor
Replace compressor
4-way valve failure
Replace 4-way valve
Partial block in capillary Replace capillary
Block in cooling system
Observe the condensation condition of evaporator or the reading of high pressure meter to judge if the system is blocked; deal with the system accordingly
Poor thermal insulation of connecting pipe between indoor unit and outdoor unit
The thermal insulation of big pipe and small pipe shall be separate and sound; joint and bare position of copper pipe shall also have thermal insulation
Insufficient air
circulation volume
Block in outdoor heat exchanger
Wash away dust on surface of heat exchanger
Block in air filte
r
Clean filter
Fan speed was set too lo
w
Set fan speed as high or medium
Fan speed turns
Capacitor
is dama
g
ed
Replace
ca
p
cito
r
Motor is
damaged
Replace
moto
r
Mounting position of outdoor unit is inappropriate
Outdoor unit shall be installed in a
p
lace with good ventilation
Outdoor temperature is too high
Install proper weather screen; it is suggested to replace air-conditioner unit with one of higher capacity in case the best available cooling effect does not satisfy needs
Indoor space is not sufficiently closed, or people enters or leave the room frequently, or there is heating equipment operating in the room
Keep the indoor space as closed as possible, do not use electrical appliance
g
enerating large amount of heat
Page 47
47
Indoor fan motor burned out or there is wire breakage or failure of overheating protecto
r
Replace fan motor or components with failure
The internal overheating protector frequently breaks as overheating is caused by abnormity of motor
Replace fan motor
Wrong line connection
Correctly connect lines according to electrical diagram
Open circuit or damage of fan capacitor
Replace it withfan capacitor of the same model and spec
When air supply mode is selected, the fan does not o
p
erate
Outdoor fan motor is damaged
Replace fan motor
Wrong line connection
Correctly connect lines according to electrical diagram
Outdoor fan capacitor is damaged
Replace fan capacitor
When in cooling or heating mode, compressor operates but outdoor fan does not operate
Compressor failure Replace Compressor
Operating capacitor of compressor is damaged
Replace capacitor
Voltage is too low or too high
It is suggested to equip voltage regulator
Wrong line connection
Correctly connect lines according to electrical diagram
When in cooling or heating mode, outdoor fan operates but compressor does not o
p
erate
Failure of protector itself
Use universal meter to check if contacts of compressure not overheated are conducting; replace protector in case of non-conducting conditions
Insufficient or too much refrigerant
Adjust refrigerant amount
Capillary is blocked so air intake temperature is too high
Replace capillary
Compressor does not operate smoothly (seized or jammed), air discharge valve is damaged
Replace Compressor
Failure of protector itself
Replace protector
Compressor is overheated so protector is activated
To rque of swing motor is insufficient
Wrong line connection
Fisrtly check if line connections have fault, if no, replace components at failure position
Controller is damaged (IC2003 is damaged, swing relay cannot close
Swing louver does not run
Page 48
48
In case of the following protection or failures, the indoor unit shall display corresponding codes, which
are explained as follows:
Code Explanation
E1
Compressor High-pressure Protection
E2
Indoor Antifreeze Protection
E3
Compressor Low-pressure Protection
E4
Exhaust Pipe High-temp. Protection
E5
Low-voltage Protection
Fan of indoor unit touches other positions
Adjust fan position
Foreign articles inside the indoor unit
Remove foreign articles
Vibration of compressor is violent
Adjust support foot mat of compressor, tighten loose bolts
Abnormal sound and vibration
Pipes of outdoor unit bump togethe
r
Separate bumping pipes
Metal plates bump together inside the unit
1. Tighten connection screws
2. Attach vibration damping gum between metal plates
Indoor fan bumps cabinet
Adjust fan position
Abnormal sound from inside compressor
Replace Compressor
Abnormal electromagnetic noise from 4-way valve when in heating operation
Internal short circuit of solenoid valve
,
replace solenoid valve
Water leakage
Block or breakage of drainage pipe
Replace drainage pipe
The refrigerant pipe joint is not wrapped firmly
Wrap and bind it again firml
y
Loading...