Ge AF-300A User Manual

GE Drives
l/4 - 5 HP, 200.23OV’ 3-Phase l/4 - 3 HP, 200=24OV, I-Phase
lnsbuctions
GEK-85714A
.:~~~~.~-~~~:*~-~~*~~-~~-~~~. . . . . . ,.\ 2.
***.*.*.*.* cs’~.:‘~~.“~‘~‘.~.~.-.~.-.-.-.-*~.-. i.5. . . .*a pg.* .*.*.*.*.*. >*.>; .*.*.*.*.*.*.*.*.*.*.*. 3
..,~-~,-:;~~~~~~~~~-:~~:~~~~~-.~.~ . . . ..A -
. * . . . . . . . . . . . . . . . . . . . . . . . ,.~.*.*.*.*.*.~.~.~,.*.~.~ *.* *.*.*.*.*. >:.:.: .*.*.*.*.~.‘.*.~.*.*” *.*.* *.*. . .*.*.*.* .‘.*.‘.‘.*.*.~.*.*.*.*
.-~:~.~~~:~~.~:.;.~i.: ~~~~~~~I-~~~~~~~-~s;~.;;;;.~.is;~.--~;~.~.;-.~-.~~~~-~.-.-.~-.~.-.-.~~~~~~-~~~~~~~~~~~~~~~~~~
. . . . . .
.;.:.:.:.-~.
..-...
:: .': -----
:*;.:.:.3:.:
7...-.-.:-
. . . . . .
:yy:y$.*
-.-:.-.'.'.'
>.-.-2...*. <+:.:.:.:.*
. . . . . . .
.~.-.-~-.-.-.-
,....
.- -m-.-.*.-T-
.,..., . . - .% . .:;;i;.:.:. >:.:.>>c. .-.;.ym­+..*<*.*
zg? >y*. .-+' .-:
z:*
‘.~.-.-.-.i~.’ ‘...-~:~~~*~~~:!~~~~:.~~~~~~~~?~~,,,~~~~~,~~..s~~~.~.~:~
~-.-~,-~0~-~~~~~~~~s~~~:-~~~~~~~~s
y. +* .‘:,s\ .‘.....f.......
. . . . . . . . . . . .*
y<ya
-~:y~*-i y&y..* A4 <.-;.>; ­a-i- - -A
-A-s'\ x.:<<<.
<<.-.:.x
-:.:&-.:. :.:.:+:.s +x-x
-.-'-.-.-.\
l . . .*.f.
TM Trademark of General Electric Company, U.S.A.
Those kWucbbns do not purport to cw6f ail details of vafiatims in equipment to cqxxatbn maintenance. Should tbrtbinformatian be desked or should pariicuku problems rnatw should be reloned to Gene& Electric Cotnpmy
\
.y.:.;.;.;<
-.-.a-.-.-. il;&$A
>Sk’.\
.-.,-&-.
-A.:.:*
.y.:.:.:.:
-.-.-.a-.-‘; ‘$g$
. .-‘a-. . :;y::::;:
. . . . .
yy’p
p:.->
-3
.*.:.y.:.:
.-.-.-.-.a
m
,v-:-s
x.:::>;::
.y’y.:<
-.-.a-.-.,
-b.x.-.:.
>-2-3. .*...,..‘..,....
.-z-h*?.-.-.-‘-.-,.-. .~.~..-.-A->.- - * --’ - - - -’ -.-.-.-.‘.-.-.~-.~.-.-.-.-.-.-.-.-.-.~.-.-.-.-.~.~.-.-.-:.-.~.~~
**~*~*~*~~~*~,*~*~,*~~~*,*,*~*~.~~~~*’~~’~~~~:~:‘:~~‘~‘*~* **~~*~~~*~S~*~~S~~*~**.i~.~*~-~~~~~~~~~~~~~~~~
,..... s,.rr,,~r.,,~;.:.:;~.:=-’ ’ -.-t.- * - -.- - *.-.- * - ‘t a.*.-:.* *. .
b ‘. .-.-.-.y -~.-.-.-.-.-.-.-.-.-.~.-.-.,:.:~.:.:.:.:.:.:.:,:.~.:.:.-.:.:.-
.\-‘i-.-. 8~~8~-.~8-.~--~-.-.~- - - -
. . . . . . . . . . . . . . . . . . . . . 1.. . . . . . . . . . . .\-...-.-a
..,~..*~rh,*~S.‘.....~...‘,........ -.
. . , . . . . . . . . . . . . . . . .-. . . .
x-xc-i .:.::.;.:.: :.:.:.:...:.
;<:.p-4 :.:.:.:.:.:. .-.-.-:.-.-
. . . . . .
. . . . . .
. . . . . .
. . . f . .
-... :.:.~.~.:.:~.‘.:.:.:.:-:.:.:.:.:.:.:.:,
. . . . . . . .-. , . . . . . . . . . . .
provide
for overypossibk, cmtingcncy to be met in
ark?
M&h are ruM covered suffkientiy foe the purchasers purposes, the
cowwction with
instaM.bn
/ f
f
@ .
GE Drive Systems
SUPPLEMENT #l
FOR INSTRUCTION MANUAL GEK-85714A
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met during installation, operation, and maintenance. Should &rther information be desired or should particular problems arise that are not covered suficiently for the purchaser’s purpose, the matter should be referred to GE Drive Systems, Salem, Virginia U.S.A.
This supplement contains additional information needed when installing and operating the AF-300A series of inverters. Refer to the information of this supplement in addition to that contained in GEK­85714A for the figures, tables, and paragraphs listed in this supplement.
Table 3: Application of Wiring and Equipment
The recommended wire sizes shown in Table 3 are minimum sizes. Due to variations in installation, check that the recommended wire sizes are adequate for that particular installation. All inverter installa­tions must meet the applicable national (NEC, CEC) and local electrical codes. It is the system engineer’s responsibility to be certain that the inverter installa­tion complies with all applicable electrical codes. (If a system engineer is not involved, it is the user’s respon­sibility.) Only adequately trained persons should install any programmable inverter.
Figure 4-6. Basic Connection Diagram
The 3-phase AC circuit breaker shown in this figure is incorrectly illustrated as three breakers. It is actually a single, 3-pole breaker.
Figure 4-6. Basic Connection Diagram Figures 8-4 and 8-5. Control Block Diagrams
Thermal Relay shown in theses figures is not a stan­dard option kit available from General Electric Drive Systems. Overload protection is not provided by the AF-300A and therefore must be provided by the user. (Typical thermal relay circuit wiring is shown in Figure 4-6.) All inverter installations must meet the appli­cable national (NEC, CEC) and local electrical codes. It is the system engineer’s responsibility to be certain that the inverter installation complies with all appli­cable electrical codes. (If a system engineer is not involved, it is the user’s responsibility.)
Table 10: AC Line Fuses and Fuseholders
Due to variations in installation when mounting fuse­holders and fuses external to the inverter, check that the recommended fuse sizes are correct for that particular installation. When using the recommended fuse sizes, overload protection must be provided by the user in order to comply with most electrical codes. All inverter installations must meet the applicable na­tional (NEC, CEC) and local electrical codes. It is the system engineer’s responsibility to be certain that the inverter installation complies with all applicable electrical codes. (If a system engineer is not involved, it is the user’s responsibility.)
(10/14/94)
Page 1 of 1
AF-300A
Inverter
l/4 l/4
to 5 He 200-230\(, 3-Phase to 3 HP, 200=24OV, 1 -Phase
GEK-85714A
Issue Date: August 1994
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met during installation, operation, and maintenance. Should further information be desired or should particular problems arise that not covered sufficiently for the pur­chaser’s purpose, the matter should be referred to GE Drive Systems, Salem, Virginia, U.S.A.
This document contains proprietary information of General Electric Company, U.S.A. and is furnished to its customers solely to assist that customer in the installation, testing, and/or maintenance of the equipment described. This document shall not be reproduced in whole or in part nor shall its con­tents be disclosed to any third party without the written approval of GE Drive Systems, 1501 Roanoke Boulevard, Salem, Virginia 24153, U.S.A.
Copyright 1994 by General Electric Company, U.S.A.
All
rights reserved.
Printed in the United States of America.

TABLE OF CONTENTS

AF-300A
lnverters GEK-85714
Section
1 .
2 .
3.
4.
5.
Title
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . .
DESCRIPTION, COMPONENT IDENTIF
AND SPECIFICATIONS
General Description Inspection items Upon Delivery TABLE 1: AF-300A lnverter Standard Specifications lnverter Options
INSTALLATION GUIDELINES
Installation Environment Installation Mounting Clearance Dimensions Chart:
WIRING PROCEDURES
Remove Terminal Block Cover
Main Circuit Wiring ..................................................................................
Control Circuit Wiring Optional External Dynamic Braking Resistor Unit Wiring TABLE 2: Terminal Identification/Function TABLE 3: Application of Wiring and Equipment
INVERTER OPERATION
Pre-Operation Inspection Selection of Operating Method Function Code and Data Setting Procedures TABLE 4: Operating Methods Control Circuit Connection and Operation Multi-Step Operations TABLE 5: Function Code Settings*
........................................................................
................................................................................
. . . . . . . . . . . . . . . . . . . . . . . ..*............................................................ 2-7
.............................................................. 3-l
........................................................................ 3-1
..................................................................................
......................................................................
............................................................................
......................................................................
......................................................................
............................................................................
. . . . . . . .
ICAT ‘ION,
............................................................
. . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
............................................................
..............................................................
.......................................... 4-l 0
.................................. 4-l 2
..............................................................
......................................
.............................................................. 5-l
.......................................... 5-4
......................................................
Paae
w
11
2-l
2-1
2-1
3-l
3-2
4-1
4-l
4-l
4-l
.................... 4-8
5-l
5-l 5-l
5-l
5-7
5-9
6 .
7.
*A duplicate of this table
FUNCTION CODE DESCRIPTIONS
TABLE 6: Function Code Descriptions
MAINTENANCE AND INSPECTION
Megger Test Periodic Parts Replacement Inspection Items Measurement Points and Meters
with is also furnished in the back of this instruction (pp. Function Changes I-
2) to record field changes to
............................................................................................
..................................................................
......................................................................................
..........................................................
factory Function Code settings.
....................................................
................................................
....................................................
m
61
6-l
7-l
7-l
7-l
7-l
7-2
AF300A /metiers GEK-85714
TABLE OF CONTENTS
Section
8. TROUBLESHOOTING
9 .
10. PARTS REPLACEMENT
Table #
Title
TABLE 7: Fautt Condition Description and Operation ........................
TABLE 8: Fault Condition Display and Corrective Action ....................
WARRANTY PARTS AND SERVICE 91
Warranty Coverage ................................................................................ 9-l
Out-Of-Warranty Procedures .................................................................. 9-l
Motors
TABLE 9:
lnverter Renewal Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-l
TABLE
and Fuseholders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
...................................................................................................... 9-l
10: AF-300A (200.23OV, 3-Phase) Line Fuses
Title Pagg
.......................................................................... 81
....................................................
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 o-1
AF-300A (200-23OV, 3-Phase and 200.24OV, l-Phase)
LIST OF TABLES
Paw
811 8-3
-
1 o-2
TABLE 1:
TABLE 2:
TABLE 3:
TABLE 4:
TABLE 5:
TABLE 6:
TABLE 7:
TABLE 8:
TABLE 9:
TABLE 10:
AF-300A INVERTER STANDARD SPECIFICATIONS TERMINAL IDENTIFICATION/FUNCTION
APPLICATION OF WIRING AND EQUIPMENT
OPERATING METHODS ................................................................................
FUNCTION CODE SETTINGS FUNCTION CODE DESCRIPTIONS FAULT CONDITION DESCRIPTION AND OPERATION FAULT CONDITION DISPLAY AND CORRECTIVE ACTION AF-300A INVERTER RENEWAL PARTS AF-300A (200.23OV, 3-Phase) AC LINE FUSES AND FUSEHOLDERS
...................................................................... 5-9
....................................................
.............................................................. 6-l
...................................................... 10-l
..................................
............................................ 4-l 2
.............................. 8-l
......................
....
2-4 4-l 0
5-l
8-3
IO-2
LIST OF FIGURES
AF-300A
/metiers GEK-85714
Figure #
Figure 2-l. Figure 2-2. Figure 2-3. Figure 3-l. Figure 3-2. Figure 4-l. Figure 4-2. Figure 4-3.
Figure 4-4.
Figure 4-5.
Figure 4-6. Figure 5-l. Figure 5-2. Figure 5-3. Figure 5-4. Figure 5-5. Figure 5-6. Figure 5-7. Figure 5-8.
Title
NAMEPLATE DATA IDENTIFICATION
KEYPAD PANEL COMPONENT IDENTIFICATION ......................................
TYPICAL INVERTER COMPONENTS
INVERTER MOUNTING CLEARANCE INVERTER EXTERNAL DIMENSIONS
TERMINAL BLOCK COVER
POWER CIRCUIT WIRING CONNECTIONS
WIRING CONNECTIONS FOR OPERATION THROUGH
KEYPAD PANEL
WIRING CONNECTIONS FOR EXTERNAL OPERATION THROUGH CONTROL CIRCUIT TERMINALS
OPTIONAL EXTERNAL DYNAMIC BRAKING RESISTOR UNIT WIRING CONNECTIONS
BASIC CONNECTION DIAGRAM KEYPAD PANEL COMPONENT IDENTIFICATION FACTORY CONNECTIONS COMMON TERMINAL CONNECTION EXAMPLE KEYPAD PANEL OPERATION CONNECTIONS KEYPAD PANEL “RUN” OPERATION EXAMPLE EXTERNAL SIGNAL OPERATION CONNECTIONS EXTERNAL SIGNAL “RUN” OPERATION EXAMPLE MULTI-STEP FREQUENCY OPERATION CONNECTIONS
............................................................................................
.......................................................................... 4-1
. . . . . . . . . . . . . ..I..............................................................
.......................................................................... 5-4
.......................................................... 2-1
.......................................................... 3-l
..........................................................
................................................ 4-2
................................................................ 4-6
..,..,............................,............................. 4-9
...................................... 5-2
......................................
.......................................... 5-5
........................................
....................................
.................................. 5-6
........................ 5-7
2-2
23 - ..........................................................
3-2
4-4
4-8
5-4
5-5 5-6
Figure 5-9. Figure 5-l 0.
Figure 5-l 1.
Figure 7-l. Figure 8-l.
Figure 8-2. Figure 8-3. Figure 8-4. Figure 8-5.
MULTI-STEP FREQUENCY “RUN” OPERATION MULT-STEP ACCELERATION AND DECELERATION
OPERATION CONNECTIONS MULT-STEP ACCELERATION AND DECELERATION “RUN”
OPERATION EXAMPLE MAIN CIRCUIT MEGGER TEST CONNECTIONS MOTOR RUNS BUT SPEED DOES NOT CHANGE
TROUBLESHOOTING CHART
MOTOR ROTATION IS NOT SMOOTH TROUBLESHOOTING CHART . . . . 8-6
MOTOR OVERHEATS TROUBLESHOOTING CHART CONTROL BLOCK DIAGRAM (l/4 TO 1 .O Horsepower) CONTROL BLOCK DIAGRAM (2.0 to 5.0 Horsepower)
. . . . . . . . . . . . . . . . . . . . ..*.....................................*.........
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EXAMPLE ...................... 5-7
5-8
5-8
. . . . . . . . . . ..*.........................
................................
............................
..............................
7-1
8-5
8-6 8-7 8-8
AF300A /metiers GEK-85714
NOTES=
iv
AF300A /metiers
1
m SAFETY PRECAUTIONS
GEK-85714
WARNING, CAUTION AND NOTE
LABELS PLACED ON THE EQUIPMENT
The following format is used on the safety and
informative labels placed on the equipment. Read all labels and follow the directions on them whenever
working on the equipment.
WARN I NG:
practices that may result in personal injury or loss of life if not correctly followed.
Denotes operating procedures and
WARNING labels will be red in color with
black or white letterina.
CAUTION:
practices that, if not strictly observed, may result in
damage to, or destruction of the equipment.
Denotes operating procedures and
CAUTION labels will be amber in color with black lettering.
NOTE:
especially significant in understanding and operating
the equipment.
Notes call attention to information that is
NOTE labels will be white in color with black letterina.
WARNING, CAUTION AND NOTE
PARAGRAPHS WITHIN THIS INSTRUCTION
The following paragraphs list some general safety
reminders and safety recommendations to be followed
when operating or installing this equipment. These
safety precautions will be repeated throughout this instruction book where applicable.
WARNING - STRAIN HAZARD:
lifting practices can cause serious or fatal injury. Lift only with adequate equipment and trained personnel.
Improper
WARNING - ELECTRICAL SHOCK AND
BURN HAZARD:
as oscilloscopes to work on live equipment, the oscilloscope’s chassis should be grounded and a differential amplifier input should be used. Care should be used in the selection of probes and
leads and In the adjustment of the oscilloscope so that accurate readings may be made. See instrument manufacturers instruction book for proper operation and adjustments to the instrument.
When using instrumentssuch
WARNING - FIRE AND EXPLOSION
HAZARD:
mounting inverters in hazardous areas such as locations where flammable or combustible vapors or dusts are present. lnverters should be installed away from hazardous areas, even If used with motors suitable for use in these locations.
WARNING -
HAZARD:
enclosure housings should be grounded in accordance with the National Electric Code and/or applicable local codes.
Fires or explosions might result from
ELECTRICAL SHOCK
All motor bases and equipment
WARNING - MOTOR OVERSPEED
HAZARD:
the inverter could cause the motor to run up to
double its base speed. Never operate the motor
above its top mechanical speed or a catastrophic failure may occur.
With 120 Hz inverter output possible,
WARNING -
HAZARD:
motion. It is the responsibility of the user to insure
that any such motion does not result in an unsafe
condition. Factory provided interlocks and operating limits should not be bypassed or modified.
WARNING ­HAZARD:
FWD-CM or REV-CM terminals connected, the driven motor starts automatically at Power-Up or by pressing the RESET key to reset the inverter.
(This may not occur due to OH2 trip on later
manufactured inverters .)
MECHANICAL MOTION
tnverter systems cause mechanical
MECHANICAL MOTION
When 2-wire control is used with the
WARNING -
HAZARD:
in the External Signal Mode (Function Code 012 and 013). (Pressing STOP may cause OH2 trip.)
WARNING -
HAZARD:
factory-wired, changing Function Code from the factory-set Function Code 010 (Keypad Operation) to Function Code 012 or 013 (External Signal
Operation) without removing the FWD-CM jumper wire will cause the motor to start. (This may not occur due to OH2 trip on later
manufactured inverters .)
1-1
MECHANICAL MOTION
RUN and STOP keys do not function
MECHANICAL MOTION
Because the FWD-CM terminal is
AF-300A
lnvetters
GEK-85714
WARNING - FIRE HAZARD: Use
namic braking resistors that are provided by GE Drive Systems. These are special resistors that have a thermal fuse built in that opens if the resistor gets too hot. This fuse should only open if the DB transistor in the inverter or DB unit fails short circuited. The resistor will need to be re­placed if this happens.
WARNING - FIRE HAZARD: User
vide overload protection for the motor and wiring
because this function is not provided by the AF­300A. See Figure
for typical wiring of an overload relay. Wire size
recommendations shown in Table 3 and fuse size recommendations shown in Table 10 of this In­struction Book are based on overload protection being provided by the user.
CAUTION:
that exceeds the standard specification voltaqe
fluctuation permissible. lf excessive voltaqe is applied
to the inverter, damaqe to the internal components
will
result.
CAUTION:
output terminals (U, V, W). Connect power supply only to the power terminals (Ll, L2, L3).
CAUTION:
brakinq resistor connection terminals (P, DB). Never short-circuit between P-N or P-DB terminals, and do not connect any resistance with a resistance value less than the standard application brakinq resistor.
4-6
“Basic Connection Diagram”
Do not connect power supply voltaqe
Do not connect power supply to the
Do not connect power supplv to the
only dy-
must pro-
CAUTION:
output side of the invetter.
CAUTION:
ground wire connected.
CAUTION:
consult the TROUBLESHOOTING section of this instruction book, and after correctinq the problem, resume operation. Do not reset the alarm automatically by external sequence, etc.
CAUTION:
the inverter terminals or on the control circuit terminals.
CAUTION:
must be provided, either bv motor thermoswitch, motor overload relay, or inverter electronic thermal overload.
CAUTION:
greatly affects inverter the inverter in anv location that exceeds the allowable temperature. Leave theventilation cover attached for temperatures of 40 deqrees C or below, and remove the cover for temperatures of between 40 and 50
deqrees C.
another type of enclosure may be required for safety purposes.
CAUTION:
packet(s)
these packets may become lodqed in the fan or air
passages
Do not connect filter capacitors on the
Do not operate the inverter without the
If the invetter’s Fault Alarm is activated,
Do not perform a meqqer test between
Motor Thermal Overload protection
Because the ambient temperature
life and reliability, do not install
If the cover needs to be removed,
Be sure to remove the desicant drver
when unpackinq inverter. (If not removed
and cause the inverter to overheat.)
CAUTION:
control circuit terminals (except 30A and 30C).
CAUTION:
(forward) and REV-CM (reverse) terminals. Avoid usinq a contactor (ON/OFF) installed on the line side of the inverter for RUN and STOP.
CAUTION:
of the inverter for ON/OFF operation.
CAUTION:
ratinq should be qreater than 1.5 times the inverter HP ratinq, but less than 500 KVA. If the AC power supply transformer is qreater than 500 KVA, install the AC Line Reactor option on the AC power supply to the inverter. A Line Reactor is also required if an SCR Tvpe Controller and/or Power Factor Correction Capacitors are used on the same power lines.
Do not connect power supplv to the
For RUN and STOP, use the FWD-CM
Do not use a switch on the output side
The AC power supplv transformer KVA
CAUTION:
be of heat resistant material because durinq opera­tion, the temperature of the inverter’s coolinq fins rises to approximately 90 deqrees C (194 F).
NOTE:
The mountinq wall for the inverter must
Always read the complete instructions prior to applyingpower or troubleshooting the equipment and follow a// procedures step by step.
NOTE:
The motor chassis should be grounded to earth through a separate ground lead from all other equipment ground leads to prevent noise coupling.
NOTE:
NOTE
l-2
Read and heed a// W’A/WV/NG, CAUTION, and
labels posted on the equipment.
AF300A
lnverters GEK-85714
2. DESCRIPTION, COMPONENT
IDENTIFICATION, AND SPECIFICATIONS,
GENERAL DESCRIPTION
The AF-300ATM inverter is available in l/4 to 5 HP, 200­230 VAC 3-Phase and l/4 to 3 HP, 200-240 VAC
Single-Phase versions. The output of the inverters is 3-phase for running a 3-phase motor whether the input is single-phase or 3-phase. All of the inverters use 32-bit “Digital Signal Processors” (DSP) for muttifunction processing to provide high performance in all applications. completely enclosed (except for the cooling fan) construction for improved performance in adverse environments. All the inverters are furnished with
detachable wiring lead-in plate for access so that wiring can be easily accomplished. (See Figure 2-3 for inverter external component identification.)
lnverter operation and code function setting is
performed from the “Keypad Panel” that features a 3-
Position, 7-segment LED display. Five operation
keys: STOP key, Program (Shift) Key, RUN Key, and
the Increment and Decrement Keys (for frequency/
speed adjustment) control the inverter. (See Figure
2-2 for Keypad Panel component identification and
function.)
The AF-300A inverters feature
General data and specifications for each individual inverter are listed on the nameplate attached to the inverter (see Figure 2-l for nameplate example). See
TABLE 1 for a complete listing of all AF-300A inverter
specifications,
INSPECTION ITEMS UPON DELIVERY
Upon receipt of your inverter, inspect equipment for
the following items:
a
1. Check the nameplate to insure that the specifications correspond to those ordered.
2. Inspect the unit for any damage that may have occurred during shipment.
-- If there are any problems or questions regarding
the above, contact the distributor from which the inverter was purchased.
TM - AF-3OOA is a trademark of General Electric Company, USA.
Figure 2-l.
NAMEPLATE DATA IDENTIFICATION
2-l
AF300A /metiers
GEK-85714
Function indication
Program key (Shift
Up/Down keys
key)
Figure
1
2-2. KEYPAD PANEL
.
1 Stop key (Reset
COMPONENT IDENTIFICATION
Data indication
key)
Run key
KEY DESCRIPTIONS
PROGRAM (SHIFT) Key
selection key. Press to select Programming Mode and first digit of Function Code will blink, Press to advance selection to the next Function Code
the disired one is reached. Any data changes are
automatically set when key is pressed to advance
to another Function Code.
UP/DOWN Keys
- These keys increase or decrease
the frequency (or speed) of the inverter when in the
Operating Mode. When in Program Setting Mode, they change the Function Code or Data Code values.
RUN Key
- Key is used for starting operation. This key does not function when Data Code is set for external (control terminal) operation (Function Code 012 and 013).
STOP (RESET) Key
operating normally and Resets any Fault Trips
when inverter has stopped abnormally. The STOP function of this key causes the inverter to trip on
OH2 when Function Code 01 is set to REMOTE
(012 or
013).
When the inverter trips, the motor will
coast to stop.
- Programming Mode
until
- Stops inverter when it is
INDICATOR DESCRIPTIONS
FUNCTION INDICATOR
indicated by the second
the
Programming
Mode*. When in the Operating Mode, setting frequency, output frequency , and alarm messages are indicated.
DATA INDICATOR
- Data Code is indicated by the first and second digits when in the Programming Mode*. When in the Operating Mode, setting frequency, output frequency, and alarm messages are indicated.
*When looking at Function Codes 00 through 04, the data is in the first digit and the Function Code is in the second and third digits. Function Codes 7 through f, the data is in the first and second digits and the Function Code is in the third digit.
- Function Code is
and third digits when in
When looking at
2-2
l/4 to 1.0 HP Units
AF300A /metiers GEK-85714
VENTILATION HOLE BLIND PLA’TE
VENTILATION HOLE BLIND PLATE
MOUNTING HOLE
VENTILATION HOLE
BLIND PLATE
CABLE INLET PLATE
RUBBER BUSHING (PROVIDED LOOSE)
NAME PLATE
7
pCABLE INLET
PLATE
SCREW
TERMINAL COVER
FOR&
Figure 2-3.
L-
NAM
: PLATE
LCOOLING
FAN
2 to 5 HP Units
TYPICAL INVERTER COMPONENTS
2-3
RUBBER BUSHING (PROWED LOOSE)
AF300A
/metiers GEK-85714
TABLE 1: AF-300A INVERTER STANDARD SPECIFICATIONS
ITEM
3=Phase, 200-230V lnverter HP Standard Applicable
Motors - 230V (KVV)
OUTPUT:
Rated Capacity-230V (KVA) Rated Output Current-230V (Amps) Rated Output Voltage (*I) Rated Output Frequency Overload Current Rating
POWER SUPPLY:
Rated input AC Voltage
Allowable
Control System Output Frequency Range
Fluctuations
I
l/4 l/2 1.0
0.2 0.4 0.8
0.57
1.10 1.90 3.00 4.20
1.5 3.0 5.0 3-Phase, 3-Wire Type, 200-230 VAC 50 Hertz, 60 Hertz, 100 Hertz, 120 Hertz 150% for 1 minute duration (inverse time characteristic)
3-Phase, 3-Wire Type, 200-230 VAC, 50/60 Hertz 170 - 253 VAC; Voltage Unbalance - +/-3%; Frequency - +/-50/o Sinusoidal PWM Control
I
0.5 - 120 Hertz
I
SPECIFICATION
2.0 3.0 5.0
1.5 2.2 3.7
6.50
8.0 11 17
I
f
I
I
1
1
1
1 -Phase, 200-240V lnverter HP
Standard Applicable Motors - 230V (KW)
OUTPUT:
Rated Capacity-230V (KVA) Rated Output Current-230V (Amps) Rated Output Voltage (*I) Rated Output Frequency Overload Current Rating
POWER SUPPLY:
Rated input AC Voltage Allowable Fluctuations Control System Output Frequency Range
l/4
l/2 1.0 2.0 3.0
0.2
0.4 0.8 1.5 2.2
0.57
1.10 1.90 3.00 4.20
1.5
3.0 5.0 8.0 11
3-Phase, 3-Wire Type, 200-240 VAC
I
50 Hertz, 60 Hertz, 150% for 1 minute duration (inverse time characteristic)
1 -Phase, 2-Wire Type, 200-240 VAC, So/60 Hertz
170 - 257 VAC; Frequency - +/-5%
I
Sinusoidal PWM Control
I
0.5 - 120 Hertz
I
100 Hertz, 120 Hertz
1
1
1
1
1
(*l)
It is not possible for output voltage to exceed power supply voltage.
2-4
AF-300A lnverters GEK-85714
TABLE 1: AF-300A INVERTER STANDARD SPECIFICATIONS (continued)
ITEM
lnverter HP
CONTROL:
Frequency Temperature Fluctuation
Frequency Setting Resolution
Output Frequency Resolution
Voltage/Frequency Characteristic (V/F)
Torque Boost
Braking Torque (Regenerative)
Braking Torque (DC injection)
Acceleration/Deceleration Time
(200=23OV, 3-Phase) (200=24OV, 1 -Phase)
SPECIFICATION
l/4 l/2 1 .o 2.0 3.0 5.0 l/4 l/2 1.0 2.0 3.0
Analog Setting - Maximum frequency +/-0.2% (at 25OC, +/-1gOC)
Digital Setting - Maximum frequency +/-0.01% (at 25OC, +/-1oOC)
Analog Setting - 0.1 Hz (up to maximum frequency of 99.9 Hertz)
Digital Setting - 0.02Hz (at maximum frequency of 60 Hertz)
0.01 Hertz (both analog and digital setting)
4 Patterns Available
16 Patterns Available
Regenerate to DC Bus capacitor (external DB resistor is available only for inverters rated 2 HP or above).
Time - 0.1 to 10 seconds; Voltage - 0 to 10%; Starting Freq. - 0.5 to 60 Hertz
0.2 to 300 seconds (at 60 Hz) independently adjustable
OPERATION:
Frequency Setting Signal
Frequency setting device or voltage input: O-10 VDC, 4-20mA DC. (Selectable from Jumper SW6.)
input Signals
Fonnrard command, reverse command, multi-frequency setting, coast-to-stop command, external alarm signal, and alarm reset signal.
Output Signals
PROTECTIVE FUNCTIONS (“2):
Fault; 30A, 30C Normally Open Contact - 250 VACO.3 A @ cos theta > 0.3
Stall prevention, overcurrent, momentary power failure, undervoltage, over­voltage, inverter overheating, external alarm.
Protective Enclosure and Cooling
*
( 2)
WARNING - FIRE HAZARD:
NEMA 1 (self cooled)
User must provide overload protection for the motor and wiring because
NEMA 1 (forced air cooled)
this function is not provided by the AF-300A. See Figure 4-6 “Basic Connection Diagram” for typical wiring
of an overload relay. Wire size recommendations shown In Table 3 and fuse size recommendations shown in Table 10 of this Instruction Book are based on overload protection being provided by the user.
2-5
AF-300A
ltwerters GEK-85714
TABLE 1: AF-300A INVERTER STANDARD SPECIFICATIONS (continued)
ITEM
lnverter HP
(200=23OV, 3-Phase) (200=24OV, 1 -Phase)
Frequency Meter Output Signal
Keypad Panel Running Display
Keypad
Panel Setting Display
Keypad Panel Fauit Display
Charge LED (CRG)
CONDITION:
installation
Ambient Temperature
Location
SPECIFICATION
l/4 l/2 1.0 2.0 3.0 5.0 l/4 l/2 1 .o 2.0 3.0 ---
Analog - 0 to + 10 VDC (adjustment range of 6.5 to 10.5 VDC)
Setting Frequency and Output Frequency.
Function Code and Setting Data.
OCl - acceleration overcurrent; OC2 - deceleration overcurrent; OC3 ­constant speed overcurrent; LU (LV) - undervoltage; OU (OV) - overvottage; OH1 - inverter overheat; OH2 - external alarm; Err - error.
Indicates DC Link voltage is present
Indoor, less than 1000 meters (3281 feet) elevation, not in contact with corrosive gas, oil mist or dust, and out of direct sunlight. Motor wiring should be less than 66 feet, otherwise wire separation of 4 inches may be
required.
-10 to +WC (+ 14 to + 122oF) (remove ventilation covers if temperature is over +40% [ + 1040F]). (-20 to
+650C (-5
to +
1500F]
storage temp.)
Humidity
Vibration
EFFICIENCY AND LOSS*:
Loss (W)
Efficiency (%) Constant Torque Load:
Base Speed Full
0.75 Base Speed Full
0.5 Base Speed Full Load
0.25 Base Speed Full Load
Efficiency (%) Pump or Fan:
0.8
Base Speed 64%
Load
Load
Load
0.6 Base Speed 36% Load
0.4 Base Speed 16% Load
APPROXIMATE WEIGHT: Kgs
Lbs
*Applies to 200-23OV, 3-Phase inverters only.
20 to 90% relative humidity (without dew condensation).
0.6G
or less.
o-0
25 40 75
w-0
95.8 97.7
-00
96.1 97.3 96.0 95.4 96.6
o-0
94.5 96.2 94.5 95.2 95.5
0-a
90.0
91.7 90.8 91.2 91.7
-00
95.1 96.2 97.0 96.5 95.9
m-0
90.2
91.0 92.9 91.5 94.6
o-0
80.1 80.8 82.8 84.0 91 .O
1.3 1.6 2.1
2.9 3.5 4.6 7.3 7.5 7.7
105 170
96.2
97.1 96.5
3.3 3.4 3.5
2-6
AF-300A Catalog Numbers
AF-300A lnveflers
GEK-85714
(200=23OV, 3=Phase, SO/SO Hertz)
HP Rating
0.25 6VAF323F25A- (1) 0.25
0.5 6VAF323F50A- (1) 0.5
1.0 6VAF323OOlA- (1) 1.0
2.0 6VAF323002A- (1) 2.0
3.0 6VAF323003A- (1) 3.0
5.0 6VAF323005A- (1) (1) The two character positions following a dash in the catalog number designate the following:
No dash or characters
Al
A2 - lnverter is UL listed and CSA approved.
Catalog No.
--
--
--
--
--
--
- inverter is not UL listed or CSA approved.
- lnverter is UL listed only.
INVERTER OPTIONS
Various options are availableforthe AF-300A Inverter. These options can be ordered from the supplier of the inverter per the GE Catalog Number shown on the chart within this paragraph. The General Electric Company “6Vn catalog numbers are coded as shown in the following Examples:
NOTE:
(200.24OV, 1 -Phase, HP Rating Cataloq No.
Option charts are divided into horsepower
50/60
Hertz)
6VAF321 F25A- (1) 6VAF321 F50A- (1) 6VAF321OOlA- (1) 6VAF321002A- (1) 6VAF321003A- (1)
--
--
--
--
--
related and non-horsepower related items. Check the horsepower of the inverter before ordering options to be sure the correct option is ordered.
Example: (Non-HP Related Items)
GVKAAA3AANN*
6V
- General Electric Standard Drives
K
- Option Kit AAA - Applicable Series (1, 2, or 3 characters) 3 - AF-300 Family of inverters AA - Option Abreviation NN - Option Size/Length (if applicable)
*A = alphabetical character, N = Numerical char.
Example: (HP Related Items)
6VKA3NAANN*
6V - General Electric Standard Drives
K
- Option Kit AAA - Applicable Series 3 - AF-300 Family of inverters
N - Voltage
AA - Option Abreviation
NN - Horsepower Rating (2 or 3 characters)
I
2-7
AF-300A
lnverters GEK-85714
AF-300A NON-HORSEPOWER
RELATED OPTIONS
Description
Speed Potentiometer 6VKAB3SP RFI Reactor 6VKABC3RF
GE Catalog Number
Description
DB Resistor (2 HP and Above)
AF=300A HORSEPOWER
RELATED OPTIONS
GE Cataloq Number
6VKB32BR05
OPTIONAL AC LINE REACTORS (ACR)
CAUTION:
the Inverter, AC Power Supply Transformer qreater than this is to be used, install a Line Reactor (must be purchased seperately) on the line side of the Inverter. A Line Reactor is also required if an SCR type controller and/or power factor correction
The AC Power Supply Transformer KVA ratinq should be qreater than 1.5 times the HP ratinq of
but
not qreater than IO times the HP ratinq of the lnverter or 500 KVA (whichever is qreater).
capacitors
are used on the same power lines.
If an
AC Line Reactors for AF-300A lnverters
(200=23OV,
HP WA Input Part #
0.25 0.598
05 . 1.195
10 . 1.992
2.0 3.187
3.0 4.382
5.0 6.772
NOTE:
sure that the peak (non-saturating) current rating of the reactor is greater than 2.8 times the input current rating of the inverter.
If reactors are supplied by others, be
3=Phase, SO/SO Hz)
Inductance
Amps lin uH)
1.5 FB003
3.0 FB004
5.0
8.0
11 FAOOI 17 FAOOI
104X220
FBOO5 FAOOI
6300
4000 2500
950
950 950
AC Line Reactors for AF-300A lnverters
(200-24OV,
HP WA Input Part #
0.25
1 1.081 1 2.6
0.5
1 2.162 1 5.2 1 FBO05 1 2500
1 .O 1 3.617 1 8.7
2.0 1 5.778 1 13.9 1 FAOOI
3.0 7.940
NOTE:
sure that the peak (non-saturating) current rating of the reactor is greater than 2.8 times the input current rating of the inverter.
If reactors are supplied by others, be
1 -Phase, SO/SO Hz)
104X220
1 FBO04 1 4000
1 FAOOI
19.1 FA002
Inductance (in uH) Amps
1 950 1 950
485
2-8
Loading...
+ 46 hidden pages