GE ACM1O, ACM1l, ACM12 Use and Care Guide

Page 1
Contents
RoomAk
Conditioner
Adapter Plug Air Direction
Care and Cleaning Condenser Coils
Control Settings Electrical Requirements
Energy Saver Energy-Saving Tips
Extension Cords Grille and Cabinet
Models ACM1O
ACM1l ACM12
4,5
3
5
6 2
6 6
3 4
2 3
6
Grounding Model and Serial Numbers
Problem Solver Repair Service
Safety Instructions Warranty
GEAmwer Center
Back Cover
m
80f1626.2000
3 2
7 7
2
Page 2
Help us
Importit Safety
help you...
Before conditioner, read this book carefully.
It is intended to help you operate and maintain your new air conditioner properly.
Keep it handy for answers to your questions.
If you don’t understand something or need more help, write (include your phone number):
Consumer Affairs GE Appliances Appliance Park Louisville, KY 40225
Write down the model and serial numbers.
You’ll find them on a label on the frame of the air conditioner behind the air filter.
These numbers are also on the Consumer Product Ownership Registration Card that came with your air conditioner. Before sending in this card, please write these numbers here:
Model Number
Serial Number
Use these numbers in any correspondence or service calls concerning your air conditioner.
usiW
your air
Imtructiom
Men using
exercise basic safety precautions, including the following:
Use this
intended purpose as
this Use and Care Book.
* This* conditioner must be properly installed in accordance with the Instillation Instructions
before
instructions on
Never unplug
by pulling on the power cord.
Always grip plug straight out from
Repair
elatric
all have damaged.
shows along its plug or connector end.
SAW
this appliance, always
app~ance ody
for
described in
it is used. See
your air
grounding
page
3.
fi~y
the
receptacle.
conditioner
and pull
or replace immediately
service cords that
become
frayed or otherwise
Do
not use a cord that
cracb
or abrasion damage
length
or at either the
T~E
ib
~STRUCTIONS
Ene~y-saving
Keep the air filter clean. (See
instructions on page 6.)
. For most efficient cooling, keep the ventilation control in the “closed” position except when you want to allow a small amount of outdoor air to enter the room or exhaust air, smoke or odors from the room.
Don’t let the room get too hot. Whenever possible, turn the unit on before the room heats up. When heat is “stored up” in walls, furniture, rugs and draperies, your air conditioner takes longer to produce the desired comfort condition.
Keep windows and doors closed. Cool, dry air escapes when they’re open.
Keep furnace floor registers and
cold air returns closed. can easily escape through them.
Don’t let drapes or furniture block the front of the unit and restrict air flow when it is operating.
It’s best to operate your air conditioner at high speed during extremely hot weather.
Keep the outdoor condenser coil clean. (See page 6.)
. Turn the air conditioner off before vacations or extended absences from home.
tips
Cold
air
If you received a
dam~ed
air conditioner . . .
Immediately contact the dealer (or builder) that sold you the air conditioner.
Save time and money. Before you request service . . .
Check the Problem Solver on page 7. It lists causes of minor operating problems that you can correct yourself.
2
Page 3
Electrical
Safety—IMPO~~T...pleme
Read Carefully.
How
to connect
electricity
For
~rsonal safety, thisappliance
properly grounded. Electrical
H5-volt
volt a.c., 60 hz grounded outlet protected with a 15 amp time delay fuse or circuit breaker.
The power cord on these models has a three-prong (grounding) plug that mates with a standard three-prong (grounding) wall outlet (Fig. 1) to minimize the possibility of electric shock hazard from these appliances.
Where a standard two-prong wall outlet is encountered. it is personal responsibdi~ and to have it replaced with a properly grounded three-prong wall outlet.
230/208-volt models
own single branch circuit supplying 230/208-volt a.c., protected with a time delay fuse or circuit breaker. This is recommended for best performance and to prevent overloading house wiring circuits, which could cause a possible fire hazard from overheating wires.
The power cord on these models has a 230/208-volt perpendicular, tandem or large tandem type plug that mates respectively with a
models require a
PREFERRED , METHOD
$-.
: >
yk
Fig. 1
/
DO NOT, UNDER
cmcmsTANcm, OR WW
(GROUND) PRONG
T~
POWER
m~
be
requiremen~
115/120-
\
aQ
~
f’
.
.
\\
n
INSURE PROPER
GROUNO
EXISTS
BEFORE USE
vour
;bligation
Am
CUT
m mmD
~OM
CORD.
require their
230/208-volt perpendicular, tandem or large tandem type wall outlet. These types of outlets are available at
PERPENDICULAR TYPE WALL OUTLET
LINE CORO PLUG
REQUIRES 20 AMP TIME
TANOEM
LINE CORO PLUG
REQUIRES 15 AMP TIME
@o
LARGE
LINE CORO PLUG
REQUIRES 30 AMP TIME
Whether
f15-volt
is important to have the wall
outle~
qualified electrician if there is any doubt as to whether a proper ground exists.
Use of adapter plug
(~-volt modek
Because of potential safety hazards under certain conditions, we
strongly recommend against use of an adapter plug.
if you still elect to use an adapter, where local codes permit, a TEMPORARY may be made to a properly grounded two-prong wall outlet by use of a
UL listed adapter (Fig. 2) available
at most local hardware stores.
mos~
hardware stores.
@@
230/208-VOLT
OR CIRCUIT BREAKER PROTECTION
WB
230/208-VOLT
TYPE
OR CIRCUIT BREAKER PROTECTION
-0
(’
\
e
230/20B-VOLT
TANOEM
TYPE WALL OUTLET
OR CIRCUIT BREAKER PROTECTION
your air conditioner is a
or a 230/208-volt unit, it
and circuit checked by a
MATCHING
OELAY
FUSE
MATCHING
WALL OUTLET
OELAY
FUSE
mm
MATCHING
OELAY
FUSE
The aligned-with the larger
outlet to provide proper polarity in the connection of the power cord.
CAUTION: Attaching the adapter ground terminal to wall outlet cover screw does not ground the appliance
udess
insulati,
through house wiring. You should have the circuit checked by a electrician to make sure the outlet
is properly grounded.
When disconnecting the power cord
from the adapter,
adapter with one hand. If this is not
done, the adapter ground terminal is
very likely to break with repeated use.
Should the adapter ground terminal break,
appliance until a proper ground has again been established.
Use of
Because of potential safety
hazards under certain conditions,
we
use of an extension cord.
if you stall
cord, it is absolutely necessary that
only)
However,
CONNE~ION
it be a type appliance extension cord and
that the current carrying rating of
the cord in amperes be equal to or
greater than the branch circuit size
shown on the rating nameplate of
the appliance. Such extension cords
are obtainable through your local
service organization.
TEMPORARY METHOD
(ADAPTER PLUGS NOT
PERMITTEOINCANAOA) %
larger
slot in the
cover screw is
and
e~nsion
stron@y
recommend against the
elat
UL listed 3-wire grounding
adauter
must be
sl~t
in the
meti,
and not
wdl
outlet is grounded
qudifid
always hold
M N~
USE
cords
However,
to use an extension
I
wdl
tie
the
3
Page 4
Opemting
Your Air Conditioner Controls
LOW
COOL
SELECTOR
1
THERMOSTAT
10
VENTILATION
Selector Switih
OFF
turns air conditioner off.
*FAN
ONLY
operation without cooling.
*Forfan
Saver Switch must be in the
NORMALposition.
LOW COOL
low fan speed operation.
MED
COOL permits cooling with
medium fan speed operation.
HIGH COOL
high fan speed operation.
permits low fan speed
only operation, Energy
permits cooling with
permits cooling with
Thermos@t
When you turn the Thermostat Control to the desired setting, the thermostat will automatically control the temperature of the indoor air. The higher the number selected, the cooler the indoor air will be.
Control
Ventilation Control
When the slide switch is at the
CLOSED position, the vent door
is closed and only the air inside the room can be circulated and conditioned.
Slide the switch to the left to the
OPEN position and the vent door
opens to allow a small amount of
outdoor air to enter the room.
Slide the switch to the right to the
EXHAUST position and the vent
door opens to allow air, smoke or
odors to be exhausted from the
room.
*Ene~y
The Energy Saver Switch controls
the fan operation. When it’s in the
NORMAL position, the fan will
circulate room air continuously.
When it’s in the SAVE position,
the fan will automatically
and off with the compressor.
Forfan only operation, Energy
Saver Switch must be in the
NORMAL position.
Saver Switih
SAVE
m
ENERGY SAVER
NoRMAL
cycle
on
4
Page 5
For normal cooling
For nighttime operation
To adjust air direction
1.
Set the Selector Switch at
HIGH COOL.
2. Set the Thermostat Control at the desired number (usually 5-7 is a good starting position). If room temperature is not satisfactory after a reasonable time, set the Thermostat Control at a higher number for a cooler room or at a lower number for a warmer room.
For maximum cooling
1.
Set the Selector Switch at
HIGH COOL.
2. Set the Thermostat Control at 10.
3. Set the Ventilation Control at CLOSED.
For quieter operation
1.
Set the Selector Switch at
LOW COOL. When the Thermostat Control is set
on 9 or 10 and the Fan is set on low speed, moisture may freeze on the coils and prevent the unit from cooling. If this happens, set the Fan at high speed and set the Thermostat Control to a lower number.
2. Set the Thermostat Control at desired number.
During the cooler evening hours, we recommend that you set the Selector Switch at LOW COOL for very quiet operation and the Thermostat Control at mid-range (5 or 6).
For extreme temperatures
For greatest economy and best performance, we suggest that you set the Selector Switch at HIGH COOL in extremely hot weather.
For ventilation
Whether controls are set for cooling or fan operation only, setting the Ventilation Control at OPEN allows a small amount of outside air to enter the room. Setting it at EXHAUST lets room air be exhausted to the outside. This is helpful in removing stale air, smoke or odors from the room, and permits outdoor air to enter through normal openings in the house. However, cooling is reduced when this control is set at OPEN or EXHAUST, so we
su~est
you don’t keep it there
especially in hot, humid weather.
effwtiveness
long—
The up-and-down air direction louvers
controlled by fingertip pressure on the louvers. They regulate air discharge upward, downward or straight out.
Two
side air direction louvers
separate tabs to let you direct discharged air to the right, to the left, or straight ahead.
UP-AND-DOWN
AIR DIRECTION
are together and are
separate banks of side-to-
have
SIDETO-SIDE
AIR DIRECTION
3. Set the Ventilation Control at CLOSED.
Note: When the Energy Saver Switch is at the SAVE position, changes in the sound level may be more noticeable than when it’s at the NORMAL position.
5
Page 6
Care and Cleaning
USER MAINTENANCE INSTRUCTIONS
Turn air conditioner off and remove plug from before cleaning.
wall
outlet
Grilles & Cabinet
Wipe front grille with a clean cloth lightly dampened with mild liquid
dishwashing
with mild soap or detergent and lukewarm water.
detergent. Wash cabinet
Condemer Coik
These coils on the weather side of the unit should be checked periodically and cleaned if clogged with dirt or soot from the atmosphere.
If extremely soiled, they may need to be steam cleaned, a service available through your GE service outlet.
Air Filter
The foam air filter behind the inlet grille should be washed at least every 30 days or as often as it needs cleaning.
FILT-ER
To remove the filter, grasp the front grille with both hands, pull down and forward to free clips at top of grille from frame of chassis, and lift up to free slots in bottom of grille from hooks at base of chassis. Then pull the filter off the two tabs on the back of the grille.
Vacuum the filter on the dirty side or wash it with running water. Run water through from the cleaner side of the filter to drive out accumulated dust and lint. Shake to dry. Replace filter on tabs on grille and reinstall grille.
6
Page 7
-
m
~,
-
Questiom?
Use This
fioblem
Solver
PROBLEM AIR CONDITIONER
DOES NOT OPERATE AIR CONDITIONER
“DOES N~ COOL ASIT SHOULD”
OPERATING SOUNDS
WATER
DMPPING
OUTSIDE
POSSIBLE CAUSE AND REMEDY
. Not plugged
IfpluggM
cumin,
restrict air flow.
Thermostat Control may not be
Highest setting should provide maximum cooling. When at SAVE, temperature range in room will vary more.
Air filter dirty, should be cleaned at least every 30 days. See instructions,
Room may have
for it to cool down.
Cold air maybe escaping through open furnace floor registers and cold air
o
Vent control maybe set at
at EXHAUST position, allowing cool air to be exhausted from the room.
The~os&t click,
This is normal.
o F~ ~ns continuously norrnd.
When Energy Saver Switch is set at SAVE fan cycles on =d off with
compressor.
G
Excess water may overflow in excessively hot
in.
Plug
in, fuse could
blinds
or
furniture blocking the top or the front of the air
~e~ very
a
may have
have
hot when
me~llic
sound,
when
been bumped loose bY ~cutimcl~~er
blown
OPEN ~sition, allowing
or circuit breaker may
set
high enough.
airconfitioner
may behe~rd when
Selector Switch
is in COOL or
~rn
knob
was
hot outside
compressor
and humid
Energy
first
weather. This is normal.
or
Rmitumt
have tripped.
conditioner
to
ahighernurnber.
Saver Switch is set
page 6.
turned on.
tirto enter the
FAN
position. This is
cycles
AIIow time
on
will
remrns.
rOO~;
and
off.
or
WATER DRIPPING INSIDE
WATER IN BASE PAN (ON OUTDOOR SIDE)
If you need more help... call, toll free: GE Answer
8M.6262W
consumer information service
Center@-
. Air conditioner water
dismsd.
This is normal
petiod
in very humid areas. Moisture removed from indoor air drains to
where it is picked up by a fan and thrown against the outdoor condenser
If You Need Service
To obtain service, see your warranty on the back page of this book.
We’re proud of our service and want you to be pleased. If for some reason you are not happy with the service you receive, here are three steps to follow for further help.
FIRST, contact the people who serviced your appliance. Explain
why you are not pleased. Inmost cases, this will solve the problem.
NEXT, if you are still not pleased, write all the details-including your phone number—to:
must
be installed level or tilted slightly to the
fora
short period in
Manager, Consumer Relations GE Appliances Appliance Park Louisville, Kentucky 40225
areas
with
outside forpmwr
littie
humidity; norm~ for a longer
rearof
coil.
FINALLY, if your problem is still not resolved, write:
Major Appliance Consumer Action Panel 20 North Chicago, Illinois 60606
Wacker
cabinet
Drive
7
Page 8
YOUR GENERAL ELECTRIC ROOM AIR CONDITIONER
WARRANTY
Save proof of original purchase date such as your sales slip or cancelled check to establish warranty period.
I
WHAT IS COVERED
FULL ONE-YEAR WARRANTY For one year from date of original
purchase, we will provide, free of charge, parts and service labor in your home to repair or replace
any part of conditioner that fails because
of a manufacturing defect. FULL FIVE-YEAR WARRANTY
For five years from the date of
original purchase, we will provide, free of charge, parts and service labor in your home to repair or replace
mfrigemting system
condenser, evaporator and all connecting tubing) that fails because of a manufacturing defect.
For each of the above warranties:
Transportation expense to and from a service shop and shop service labor if required will be free of charge.
the
any pan
room air
of
the
sealed
(the compressor,
This warranty is extended to the original purchaser and any succeeding owner for products purchased for use in the states, Hawaii and Washington,
In Alaska the warranty is the same except that it is LIMITED because you must pay to ship the product to the service shop or for the service technician’s travel costs to your home.
All warranty service will be provided by our Factory Service Centers or by our authorized Customer servicers during normal working hours.
Look in the White or Yellow Pages of your telephone directory for GENERAL ELECTRIC COMPANY, GENERAL ELECTRIC FACTORY SERVICE, GENERAL
HOTPOINT
GENERAL ELECTRIC CUSTOMER CARE@ SERVICE.
FACTORY SERVICE or
48
mainland
D.C.
Care”
ELECTRIC-
WHAT
Service trips to teach you how to
use the product.
Read your Use and Care material.
If you then have any questions about operating the product, please contact your dealer or our Consumer Affairs office at the address below, or call, toll free:
GE Answer
800.626.2000 consumer information service
IS
NOT COVERED
Improper installation.
If you have an installation problem, or if the air conditioner
is of improper cooling capacity for the intended use, contact your dealer or installer. You are
responsible for providing adequate electrical connecting facilities.
Center@
Some
states do not allow the exclusion
may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
To know what your legal rights are in your state, consult your local or state consumer affairs office or your state’s Attorney General.
If further help is needed concerning this warranty, write:
Manager—Consumer Affairs, GE Appliances, Louisville, KY 40225
s
Replacement of fuses or
resetting of circuit breakers.
s
In commercial locations labor necessary to move the unit to a location where it is accessible for
service by an individual technician.
or limitation of incidental or consequential damages, so the above limitation or exclusion
Warrantor: General Electric Company
Failure of the product resulting from
modifications to the product or due to unreasonable use including failure to provide reasonable and necessary maintenance.
. Failure due to corrosion on models not corrosion-protected.
Damage to the product caused
by improper power supply voltage, accident, fire, floods or acts of God.
IS NOT
WARRANTOR FOR CONSEQUENTIAL DAMAGES.
RESPONSIBLE
Pub.
6-86
No.
49-7200
ACM1O ACM1l ACM12
Loading...