GE
Lighting
AlbeoTM LED Luminaire
Modular High & Low Bay Lighting
(ABV1-series)
Features
5 year limited warranty
•
• Damp location rated
BEFORE YOU BEGIN
Read these instructions completely and carefully.
WARNING/AVERTISSEMENT
RISK OF ELECTRIC SHOCK
• Turn power off before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL or IEC approved wire for input/output connections.
Minimum size 18 AWG.
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des ls approuvés par UL ou IEC pour les entrées/sorties de
connexion. Taille minimum 18 AWG.
Installation Guide
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation. CAN ICES-3 (A)/NMB-3(A)
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense.
Save These Instructions
Use only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.
Prepare Electrical Wiring
Electrical Requirements
The LED driver must be supplied with 120-480 VAC, 50/60 Hz per product label and connected to an
individual properly grounded branch circuit, protected by a 15 or 20 ampere circuit breaker.
Grounding Instructions
The grounding and bonding of the overall system shall be done in accordance with National Electric
Code (NEC) Article 600 and local codes.
imagination at work
Unit Installation
Provide at least 12” of clearance from the top of the xture to any ceiling or surface above.
Carefully unpack unit and properly inspect for defects before installing. Wear work gloves to prevent dirt and oil from being
1
transferred to the luminaire.
Choose a mounting method: chain or cable, rod mount, or pendant mount . (Chain or cable is covered here. Other options are
2
covered in the section Optional Mounting Methods).
Attach to
Fixture Weight
structural member
ABV1-series
LED Modules
Max. Weight (lbs.)
120/277V 347/480V
1 7 10
2 13 18
Chain or Cable Mounting: Please follow all UL, NEC and
3
minimum load rating guidelines when selecting and
installing a cable or chain.
NOTE: When selecting chain, a joint in a circular chain
link shall be welded. A joint in a chain link of another
shape shall not be located within 30 degrees of the
vertical unless welded.
Electrical Connections (120/277V)
Hang two chains/cables from a structural member of
4
the ceiling. Fixture must be supported independently
of an outlet box. Loop chain/cable through the
mounting slots next to each xture end. Chain/cable
mounting locations must be in the slots closest to the
xture end-cap.
Loosen screws to remove power access plate.
1
A) Conduit
Option 2: power input from side – Remove knockout in
3 4
endcap and A) install 1/2” conduit, or B) install AC power
cord with strain relief. Plug unused hole on power
access plate with appropriate tting
B) Power cord
A) Conduit
Option 1: power input from top – A) Install 1/2” conduit,
2
or B) install AC power cord with strain relief into power
access plate.
Connect the green (ground), black (line) and white
(neutral) wires of the AC line to the similarly colored
wires of the xture’s power supply using UL listed
connectors. Place all connections and exposed wire
inside of xture and reattach power access plate.
B) Power cord