Ge 369 User Manual

369 Motor Management Relay
Digital Energy
Instruction Manual
369 Revision: 3.5x
GE Publication Number: GEK-106288S
Copyright © 2011 GE Digital Energy
GE Digital Energy
215 Anderson Avenue, Markham, Ontario, Canada L6E 1B3
Tel: (905) 294-6222, 1-800-547-8629 (North America) Fax: (905) 201-2098
Internet: http://www.gedigitalenergy.com
*1601-0077-BV*
GE Multilin's Quality Management
System is registered to
ISO9001:2000
QMI # 005094
UL # A3775
© 2010 GE Digital Energy Incorporated. All rights reserved.
GE Digital Energy 369 Motor Management Relay instruction manual for revision
3.5x.
369 Motor Management Relay, is a registered trademark of GE Digital Energy Inc.
The contents of this manual are the property of GE Digital Energy Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Digital Energy. The content of this manual is for informational use only and is subject to change without notice.
Part numbers contained in this manual are subject to change without notice, and should therefore be verified by GE Digital Energy before ordering.
Part number: 1601-0077-BV (November 2011)
TABLE OF CONTENTS
Table of Contents
1: INTRODUCTION ORDERING ........................................................................................................................................... 1-1
G
ENERAL OVERVIEW ........................................................................................................... 1-1
O
RDERING ............................................................................................................................ 1-2
A
CCESSORIES ....................................................................................................................... 1-3
F
IRMWARE HISTORY ............................................................................................................ 1-3
PC P
ROGRAM (SOFTWARE) HISTORY ............................................................................... 1-4
369 R
ELAY FUNCTIONAL SUMMARY ................................................................................ 1-5
R
ELAY LABEL DEFINITION ...................................................................................................1-8
2: PRODUCT DESCRIPTION OVERVIEW ........................................................................................................................................... 2-9
UIDEFORM SPECIFICATIONS ............................................................................................ 2-9
G M
ETERED QUANTITIES ........................................................................................................ 2-10
P
ROTECTION FEATURES ...................................................................................................... 2-10
A
DDITIONAL FEATURES .......................................................................................................2-12
SPECIFICATIONS ............................................................................................................................... 2-13
I
NPUTS .................................................................................................................................. 2-13
O
UTPUTS ...............................................................................................................................2-15
M
ETERING ............................................................................................................................. 2-16
C
OMMUNICATIONS .............................................................................................................. 2-17
P
ROTECTION ELEMENTS ...................................................................................................... 2-18
M
ONITORING ELEMENTS .................................................................................................... 2-21
C
ONTROL ELEMENTS ........................................................................................................... 2-22
E
NVIRONMENTAL SPECIFICATIONS .................................................................................... 2-22
L
ONG-TERM STORAGE ......................................................................................................... 2-24
A
PPROVALS/CERTIFICATION ...............................................................................................2-24
T
YPE TEST STANDARDS ...................................................................................................... 2-24
P
RODUCTION TESTS ............................................................................................................ 2-25
3: INSTALLATION MECHANICAL INSTALLATION .....................................................................................................3-27
ECHANICAL INSTALLATION .............................................................................................. 3-27
M
TERMINAL IDENTIFICATION ......................................................................................................... 3-29
369 R
ELAY TERMINAL LIST ................................................................................................ 3-29
269
TO 369 RELAY CONVERSION TERMINAL LIST ........................................................ 3-31
MTM-369 R MPM-369 R T
ERMINAL LAYOUT .............................................................................................................. 3-36
ELAY CONVERSION TERMINAL LIST ........................................................... 3-34
ELAY CONVERSION TERMINAL LIST ........................................................... 3-35
ELECTRICAL INSTALLATION ......................................................................................................... 3-37
T
YPICAL WIRING DIAGRAM ................................................................................................ 3-37
T
YPICAL WIRING .................................................................................................................. 3-37
C
ONTROL POWER ................................................................................................................ 3-38
P
HASE CURRENT (CT) INPUTS ........................................................................................... 3-38
G
ROUND CURRENT INPUTS ............................................................................................... 3-39
Z
ERO SEQUENCE GROUND CT PLACEMENT .................................................................... 3-40
P
HASE VOLTAGE (VT/PT) INPUTS .....................................................................................3-40
B
ACKSPIN VOLTAGE INPUTS ..............................................................................................3-41
RTD I
NPUTS ......................................................................................................................... 3-42
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL TOC–1
TABLE OF CONTENTS
DIGITAL INPUTS ................................................................................................................... 3-42
A
NALOG OUTPUTS ..............................................................................................................3-43
R
EMOTE DISPLAY .................................................................................................................3-43
O
UTPUT RELAYS ..................................................................................................................3-44
RS485 C T T
OMMUNICATIONS ................................................................................................ 3-45
YPICAL TWO-SPEED (LOW SPEED/HIGH SPEED) MOTOR WIRING ............................ 3-47
YPICAL MOTOR FORWARD/REVERSE WIRING ............................................................... 3-49
REMOTE RTD MODULE (RRTD) .................................................................................................... 3-51
M
ECHANICAL INSTALLATION .............................................................................................. 3-51
E
LECTRICAL INSTALLATION .................................................................................................3-53
CT INSTALLATION ............................................................................................................................. 3-54
P
HASE CT INSTALLATION ................................................................................................... 3-54
5 A
MP GROUND CT INSTALLATION ..................................................................................3-55
HGF (50:0.025) G
ROUND CT INSTALLATION ...............................................................3-56
4: USER INTERFACES FACEPLATE INTERFACE .................................................................................................................4-57
ISPLAY ................................................................................................................................. 4-57
D LED I
NDICATORS .................................................................................................................4-57
RS232 P K S
ROGRAM PORT .................................................................................................... 4-58
EYPAD ................................................................................................................................. 4-58
ETPOINT ENTRY .................................................................................................................. 4-59
ENERVISTA 369 SETUP INTERFACE ..........................................................................................4-60
H
ARDWARE AND SOFTWARE REQUIREMENTS .................................................................4-60
I
NSTALLING ENERVISTA 369 SETUP ................................................................................. 4-60
CONNECTING ENERVISTA 369 SETUP TO THE RELAY ...................................................... 4-63
C
ONFIGURING SERIAL COMMUNICATIONS .......................................................................4-63
U
SING THE QUICK CONNECT FEATURE ............................................................................ 4-65
C
ONFIGURING ETHERNET COMMUNICATIONS .................................................................4-65
C
ONNECTING TO THE RELAY .............................................................................................. 4-67
WORKING WITH SETPOINTS AND SETPOINT FILES ........................................................... 4-69
E
NGAGING A DEVICE ........................................................................................................... 4-69
E
NTERING SETPOINTS ......................................................................................................... 4-69
F
ILE SUPPORT ...................................................................................................................... 4-71
U
SING SETPOINTS FILES ..................................................................................................... 4-71
UPGRADING RELAY FIRMWARE ................................................................................................. 4-84
D
ESCRIPTION ........................................................................................................................ 4-84
S
AVING SETPOINTS TO A FILE ............................................................................................ 4-84
L
OADING NEW FIRMWARE ................................................................................................. 4-84
ADVANCED ENERVISTA 369 SETUP FEATURES ................................................................... 4-87
T
RIGGERED EVENTS .............................................................................................................4-87
T
RENDING .............................................................................................................................4-87
W
AVEFORM CAPTURE (TRACE MEMORY) .........................................................................4-89
M
OTOR START DATA LOGGER ...........................................................................................4-91
D
ATA LOGGER ...................................................................................................................... 4-91
M
OTOR HEALTH REPORT ...................................................................................................4-97
P
HASORS .............................................................................................................................. 4-97
E
VENT RECORDER ................................................................................................................4-99
M
ODBUS USER MAP ........................................................................................................... 4-100
V
IEWING ACTUAL VALUES .................................................................................................. 4-100
USING ENERVISTA VIEWPOINT WITH THE 369 RELAY ..................................................... 4-102
P
LUG AND PLAY EXAMPLE .................................................................................................4-102
TOC–2 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
TABLE OF CONTENTS
5: SETPOINTS OVERVIEW ........................................................................................................................................... 5-107
S
ETPOINTS MAIN MENU ..................................................................................................... 5-107
S1 369 SETUP .................................................................................................................................... 5-111
S
ETPOINT ACCESS ............................................................................................................... 5-111
D
ISPLAY PREFERENCES ....................................................................................................... 5-111
369 C
OMMUNICATIONS ..................................................................................................... 5-112
R
EAL TIME CLOCK ............................................................................................................... 5-115
W
AVEFORM CAPTURE .........................................................................................................5-116
D
ATA LOGGER ...................................................................................................................... 5-117
E
VENT RECORDS .................................................................................................................. 5-118
M
ESSAGE SCRATCHPAD ...................................................................................................... 5-118
D
EFAULT MESSAGES ...........................................................................................................5-119
C
LEAR/PRESET DATA .......................................................................................................... 5-120
M
ODIFY OPTIONS ................................................................................................................ 5-121
F
ACTORY SERVICE ............................................................................................................... 5-121
S2 SYSTEM SETUP ............................................................................................................................ 5-122
D
ESCRIPTION ........................................................................................................................ 5-122
CT/VT S M B O C
ETUP ...................................................................................................................... 5-122
ONITORING SETUP ........................................................................................................... 5-125
LOCK FUNCTIONS ............................................................................................................. 5-129
UTPUT RELAY SETUP ........................................................................................................ 5-130
ONTROL FUNCTIONS ........................................................................................................ 5-131
S3 OVERLOAD PROTECTION ....................................................................................................... 5-141
D
ESCRIPTION ........................................................................................................................ 5-141
T
HERMAL MODEL ................................................................................................................ 5-142
O
VERLOAD CURVES ............................................................................................................ 5-144
O
VERLOAD ALARM .............................................................................................................. 5-154
S4 CURRENT ELEMENTS ...............................................................................................................5-155
D
ESCRIPTION ........................................................................................................................ 5-155
S
HORT CIRCUIT .................................................................................................................... 5-155
M
ECHANICAL JAM ............................................................................................................... 5-156
U
NDERCURRENT .................................................................................................................. 5-157
C
URRENT UNBALANCE ....................................................................................................... 5-158
G
ROUND FAULT ...................................................................................................................5-159
S5 MOTOR START/INHIBITS ......................................................................................................... 5-161
D
ESCRIPTION ........................................................................................................................ 5-161
A
CCELERATION TRIP ............................................................................................................5-161
S
TART INHIBITS .................................................................................................................... 5-162
B
ACKSPIN DETECTION ........................................................................................................ 5-163
S6 RTD TEMPERATURE ................................................................................................................... 5-165
D
ESCRIPTION ........................................................................................................................ 5-165
L
OCAL RTD PROTECTION ................................................................................................... 5-165
R
EMOTE RTD PROTECTION ................................................................................................ 5-166
O
PEN RTD ALARM .............................................................................................................. 5-169
S
HORT/LOW TEMP RTD ALARM ....................................................................................... 5-169
L
OSS OF RRTD COMMS ALARM ....................................................................................... 5-170
S7 VOLTAGE ELEMENTS ................................................................................................................ 5-171
D
ESCRIPTION ........................................................................................................................ 5-171
U
NDERVOLTAGE ................................................................................................................... 5-171
O
VERVOLTAGE ...................................................................................................................... 5-172
P
HASE REVERSAL .................................................................................................................5-173
U
NDERFREQUENCY .............................................................................................................. 5-175
O
VERFREQUENCY ................................................................................................................. 5-176
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL TOC–3
TABLE OF CONTENTS
S8 POWER ELEMENTS .................................................................................................................... 5-177
D
ESCRIPTION ........................................................................................................................ 5-177
L
EAD POWER FACTOR ........................................................................................................ 5-178
L
AG POWER FACTOR .......................................................................................................... 5-179
P
OSITIVE REACTIVE POWER ............................................................................................... 5-179
N
EGATIVE REACTIVE POWER ............................................................................................. 5-180
U
NDERPOWER ......................................................................................................................5-182
R
EVERSE POWER .................................................................................................................5-183
S9 DIGITAL INPUTS .......................................................................................................................... 5-184
D
IGITAL INPUT FUNCTIONS ................................................................................................ 5-184
S
PARE SWITCH ..................................................................................................................... 5-186
E
MERGENCY RESTART ......................................................................................................... 5-187
D
IFFERENTIAL SWITCH ........................................................................................................ 5-187
S
PEED SWITCH ..................................................................................................................... 5-188
R
EMOTE RESET .....................................................................................................................5-189
S10 ANALOG OUTPUTS ................................................................................................................. 5-190
A
NALOG OUTPUTS ..............................................................................................................5-190
S11 369 TESTING ............................................................................................................................. 5-192
T
EST OUTPUT RELAYS .........................................................................................................5-192
T
EST ANALOG OUTPUTS .....................................................................................................5-193
S12 TWO-SPEED MOTOR .............................................................................................................. 5-194
D
ESCRIPTION ........................................................................................................................ 5-194
S
PEED 2 OVERLOAD CURVES ............................................................................................ 5-194
S
PEED 2 UNDERCURRENT .................................................................................................. 5-196
S
PEED 2 ACCELERATION .................................................................................................... 5-197
6: ACTUAL VALUES OVERVIEW ........................................................................................................................................... 6-199
CTUAL VALUES MAIN MENU ........................................................................................... 6-199
A
A1 STATUS ........................................................................................................................................... 6-202
M
OTOR STATUS ...................................................................................................................6-202
L
AST TRIP DATA ................................................................................................................... 6-202
D
ATA LOGGER ...................................................................................................................... 6-203
D
IAGNOSTIC MESSAGES ..................................................................................................... 6-203
S
TART BLOCK STATUS ........................................................................................................ 6-204
D
IGITAL INPUT STATUS .......................................................................................................6-204
O
UTPUT RELAY STATUS ...................................................................................................... 6-206
R
EAL TIME CLOCK ............................................................................................................... 6-206
F
IELDBUS SPECIFICATION STATUS .................................................................................... 6-206
A2 METERING DATA ........................................................................................................................ 6-207
C
URRENT METERING ........................................................................................................... 6-207
V
OLTAGE METERING ........................................................................................................... 6-207
P
OWER METERING ..............................................................................................................6-208
B
ACKSPIN METERING .......................................................................................................... 6-208
L
OCAL RTD .......................................................................................................................... 6-209
R
EMOTE RTD ....................................................................................................................... 6-209
O
VERALL STATOR RTD ....................................................................................................... 6-210
D
EMAND METERING ............................................................................................................6-210
P
HASORS .............................................................................................................................. 6-211
A3 LEARNED DATA .......................................................................................................................... 6-213
D
ESCRIPTION ........................................................................................................................ 6-213
M
OTOR DATA .......................................................................................................................6-213
L
OCAL RTD MAXIMUMS .....................................................................................................6-214
R
EMOTE RTD MAXIMUMS .................................................................................................. 6-215
TOC–4 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
TABLE OF CONTENTS
A4 STATISTICAL DATA .................................................................................................................... 6-216
T
RIP COUNTERS ...................................................................................................................6-216
M
OTOR STATISTICS .............................................................................................................6-217
A5 EVENT RECORD .......................................................................................................................... 6-219
E
VENT RECORDS .................................................................................................................. 6-219
M
ODEL INFORMATION ........................................................................................................ 6-220
F
IRMWARE VERSION ........................................................................................................... 6-220
7: APPLICATIONS 269-369 COMPARISON ................................................................................................................. 7-221
AND 269PLUS COMPARISON ................................................................................... 7-221
369
369 FAQS ............................................................................................................................................. 7-223
F
REQUENTLY ASKED QUESTIONS (FAQS) ........................................................................ 7-223
369 DO’S AND DONT’S .................................................................................................................. 7-227
D
OS AND DONTS ............................................................................................................... 7-227
CT SPECIFICATION AND SELECTION ........................................................................................ 7-230
CT S
PECIFICATION ...............................................................................................................7-230
CT S
ELECTION ..................................................................................................................... 7-231
PROGRAMMING EXAMPLE ........................................................................................................... 7-233
P
ROGRAMMING EXAMPLE ................................................................................................... 7-233
APPLICATIONS ................................................................................................................................... 7-239
M
OTOR STATUS DETECTION .............................................................................................. 7-239
S
ELECTION OF COOL TIME CONSTANTS ........................................................................... 7-240
T
HERMAL MODEL ................................................................................................................ 7-242
RTD B
IAS FEATURE ............................................................................................................ 7-243
T
HERMAL CAPACITY USED CALCULATION ........................................................................ 7-244
S
TART INHIBIT ...................................................................................................................... 7-246
T
WO-PHASE CT CONFIGURATION ....................................................................................7-248
G
ROUND FAULT DETECTION ON UNGROUNDED SYSTEMS ........................................... 7-250
RTD C
IRCUITRY ................................................................................................................... 7-251
R
EDUCED RTD LEAD NUMBER APPLICATION ................................................................. 7-251
T
WO WIRE RTD LEAD COMPENSATION ..........................................................................7-253
A
UTO TRANSFORMER STARTER WIRING .......................................................................... 7-253
8: TESTING TEST SETUP ......................................................................................................................................... 8-255
NTRODUCTION .....................................................................................................................8-255
I S
ECONDARY INJECTION TEST SETUP ................................................................................ 8-256
HARDWARE FUNCTIONAL TESTING ......................................................................................... 8-257
P
HASE CURRENT ACCURACY TEST .................................................................................... 8-257
V
OLTAGE INPUT ACCURACY TEST ..................................................................................... 8-257
G
ROUND (1 A / 5 A) ACCURACY TEST ............................................................................ 8-258
50:0.025 G RTD A D
IGITAL INPUTS ................................................................................................................... 8-260
A
NALOG INPUTS AND OUTPUTS ........................................................................................ 8-262
O
UTPUT RELAYS .................................................................................................................. 8-263
ROUND ACCURACY TEST .............................................................................. 8-258
CCURACY TEST ......................................................................................................... 8-259
ADDITIONAL FUNCTIONAL TESTING .......................................................................................8-264
O
VERLOAD CURVE TEST ..................................................................................................... 8-264
P
OWER MEASUREMENT TEST ............................................................................................8-265
V
OLTAGE PHASE REVERSAL TEST ......................................................................................8-265
S
HORT CIRCUIT TEST .......................................................................................................... 8-267
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL TOC–5
TABLE OF CONTENTS
APPENDIX: REVISIONS CHANGE NOTES ................................................................................................................................ A-269
R
EVISION HISTORY .............................................................................................................. A-269
WARRANTY ......................................................................................................................................... A-275
W
ARRANTY INFORMATION ................................................................................................. A-275
INDEX
TOC–6 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
Digital Energy
Multilin

1.1 Ordering

369 Motor Management Relay
Chapter 1: Introduction

Introduction

1.1.1 General Overview

The 369 Motor Management Relay is a digital relay that provides protection and monitoring for three phase motors and their associated mechanical systems. A unique feature of the 369 Relay is its ability to ‘learn’ individual motor parameters and to adapt itself to each application. Values such as motor inrush current, cooling rates and acceleration time may be used to improve the 369 Relay’s protective capabilities.
The 369 Relay offers optimum motor protection where other relays cannot, by using the FlexCurve™ custom overload curve, or one of the fifteen standard curves.
The 369 Relay has one RS232 front panel port and three RS485 rear ports. The Modbus RTU protocol is standard to all ports. Setpoints can be entered via the front keypad or by using the EnerVista 369 Setup software and a computer. Status, actual values and troubleshooting information are also available via the front panel display or via communications.
As an option, the 369 Relay can individually monitor up to 12 RTDs. These can be from the stator, bearings, ambient or driven equipment. The type of RTD used is software selectable. Optionally available as an accessory is the remote RTD module which can be linked to the 369 Relay via a fibre optic or RS485 connection.
The optional metering package provides VT inputs for voltage and power elements. It also provides metering of V, kW, kvar, kVA, PF, Hz, and MWhrs. Three additional user configurable analog outputs are included with this option along with one analog output included as part of the base unit.
The Back-Spin Detection (B) option enables the 369 Relay to detect the flow reversal of a pump motor and enable timely and safe motor restarting. All 369 Relay options are available when ordering the relay from the factory. Field upgrades are only available for the relay when the required hardware is installed in the relay from the factory. Field
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL 1–1
ORDERING CHAPTER 1: INTRODUCTION
upgrades are via an option enabling passcode available from GE Multilin, which is unique to each relay and option. Any hardware modifications made to the relay in the field will void the product warranty and will not be supported by GE Multilin.

1.1.2 Ordering

Select the basic model and the desired features from the selection guide below:
Table 1–1:
369
369
*******
| | | | | | |
||||||
HI
||||||
LO
| | | | |
R
| | | | |
0
||||
M
||||
B
||||
0
| | |
F
| | |
0
||
E
||
P
||
P1
||
D
||
0
|
H
|
0
E Enhanced diagnostics with Enhanced faceplate 0 No Enhanced diagnostics with Basic faceplate
Base unit (no RTD) 50-300 VDC / 60-265 VAC control power 20-60 VDC / 20-48 VAC control power Optional 12 RTD inputs (built-in) No optional RTD inputs Optional metering package Optional backspin detection (incl. metering) No optional metering or backspin detection Optional Fiber Optic Port No optional Fiber Optic Port Optional Modbus/TCP protocol interface Optional Profibus-DP protocol interface Optional Profibus-DPV1 protocol interface Optional DeviceNet protocol interface No optional protocol interfaces Harsh environment option No Harsh environment option
NoteNotes:
1. One Analog Output is available with the 369 base model. The other three Analog
Outputs can be obtained by purchasing the metering or backspin options.
The control power (HI or LO) must be specified with all orders. If a feature is not required, a 0 must be placed in the order code. All order codes have 10 digits. The 369 is available in a non-drawout version only.
Examples: 369-HI-R-0-0-0-0-E: 369 with HI voltage control power and 12 RTD inputs, and enhanced diagnostics 369-LO-0-M-0-0-0-E: 369 relay with LO voltage control power and metering option, and enhanced diagnotics
2. Features available only in Enhanced option (E)
Enhanced faceplate with motor status indicators
Motor Health Report
Enhanced learned data
Motor Start Data Logger
Enhanced event recorder
Security audit trail events
1–2 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
CHAPTER 1: INTRODUCTION ORDERING

1.1.3 Accessories

EnerVista 369 Setup software: Setup and monitoring software provided free with each
relay.
RRTD: Remote RTD Module. Connects to the 369 Relay via a fibre optic or
RS485 connection. Allows remote metering and programming for up to 12 RTDs.
F485: Communications converter between RS232 and RS485 / fibre optic.
Interfaces a PC to the relay.
CT: 50, 75, 100, 150, 200, 300, 350, 400, 500, 600, 750, 1000 (1 A or 5 A
secondaries)
HGF: Ground CTs (50:0.025) used for sensitive earth fault detection on high
resistance grounded systems.
515: Blocking and test module. Provides effective trip blocking and relay
isolation.
DEMO: Metal carry case in which 369 is mounted.
FPC15: Remote faceplate cable, 15'.

1.1.4 Firmware History

FIRMWARE
REVISION
53CMB110.000 Production Release June 14, 1999
53CMB111.000 Changes to Backspin Detection algorithm June 24, 1999
53CMB112.000 Changes to Backspin Detection algorithm July 2, 1999
53CMB120.000
53CMB130.000
53CMB140.000
53CMB145.000 Minor firmware changes June 9, 2000
53CMB160.000
Table 1–2: FIRMWARE HISTORY (Sheet 1 of 2)
BRIEF DESCRIPTION OF CHANGE RELEASE DATE
Capability to work with the Remote RTD module
Improvements to the Remote RTD communications
Changes to Backspin Detection algorithm and improved RS232 communications
October 15, 1999
January 3, 2000
March 27, 2000
Profibus protocol, waveform capture, phasor display, single analog output, demand power and current, power
October 12, 2000
consumption
53CMB161.000 Minor firmware changes October 19, 2000
53CMB162.000 Minor firmware changes
November 30, 2000
53CMB170.000 Autorestart feature added February 9, 2001
53CMB180.000 Modbus/TCP feature added June 15, 2001
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL 1–3
ORDERING CHAPTER 1: INTRODUCTION
Table 1–2: FIRMWARE HISTORY (Sheet 2 of 2)
FIRMWARE
REVISION
53CMB190.000
53CMB201.000
53CMB210.000
53CMB220.000
53CMB230.000
53CMB240.000
53CMB250.000
BRIEF DESCRIPTION OF CHANGE RELEASE DATE
Number of Event Recorders increased to 250; Hottest Overall RTD value added
November 23, 2001
Added Starter Failure, MWhrs as analog output parameter, and Motor Load
April 16, 2004
Averaging feature.
Added support for variable frequency drives; minor changes to Modbus TCP.
Implementation of DeviceNet protocol and starter operation monitor.
Implemented Profibus DPV1, Force Outputs and Protection Blocking.
Custom Curve enhancement, increase range from 0 to 32767 to 0 to 65534.
November 5, 2004
April 11, 2005
September 19, 2005
November 21, 2005
Implementation of start control relay timer setting for reduced voltage starting, additional Modbus address added for starts/hour lockout time remaining, correction to date and time Broadcast
April 28, 2006 command Modbus addresses, fix for latched resets with multiple local/remote assigned relays, fix for repeated “Motor Stopped” and “Motor Running” events.
53CMC310.000
53CMC320.000
53CMC330.000 Added Ethernet Loss of Comms Trip. May 7, 2009
53CMC340.000 Added DeviceNet Loss of Comms Trip. July 7, 2010

1.1.5 PC Program (Software) History

PC
PROGRAM
REVISION
1.10 Production Release June 14, 1999
1.20 Capability to work with the Remote RTD module October 15, 1999
Profibus loss of trip, trip contact seal in undervoltage auto restart, Motor Health Report, Enhanced learned data, motor start data logger, enhanced event recorder,
June 7, 2007 security audit trail events, DeviceNet
enhanced polling.
2-speed motor feature, Datalogger feature, speed of last trip display, latched
March 20, 2008 trip and alarm note.
Table 1–3: SOFTWARE HISTORY
BRIEF DESCRIPTION OF CHANGES RELEASE DATE
1–4 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
CHAPTER 1: INTRODUCTION ORDERING
Table 1–3: SOFTWARE HISTORY
PC
PROGRAM
REVISION
1.30
BRIEF DESCRIPTION OF CHANGES RELEASE DATE
Capability to communicate effectively with version
1.30 firmware
January 3, 2000
1.40 Changes made for new firmware release March 27, 2000
1.45 Changes made for new firmware release June 9, 2000
Profibus protocol, waveform capture, phasor
1.60
display, single analog output, demand power and
October 23, 2000
current, power consumption
1.70 Changes made for new firmware release February 9, 2001
1.80 Changes made for new firmware release June 7, 2001
1.90 Changes made for new firmware release November 23, 2001
2.00 Changes made for new firmware release September 9, 2003
3.01 New features and enhancements August 16, 2004
3.11 Added support for firmware revision 2.1x November 16, 2004
3.20 Changes made for firmware revision 2.2x April 13, 2005
3.30 Changes made for firmware revision 2.3x
September 19, 2005
3.40 Changes made for firmware revision 2.4x November 25, 2005
3.50 Changes made for firmware revision 2.5x May 15, 2006
3.70 Changes made for firmware revision 3.1x June 7, 2007
3.80 Changes made for firmware revision 3.2x March 20, 2008
3.90 Changes made for firmware revision 3.3x May 7, 2009
4.00 Changes made for firmware revision 3.4x July 7, 2010

1.1.6 369 Relay Functional Summary

The front view for all 369 Relay models is shown below, along with the rear view showing the Profibus port, the Modbus/TCP port, and the DeviceNet port .
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL 1–5
ORDERING CHAPTER 1: INTRODUCTION
840702BM.CDR
FIBER OPTIC DATA LINK(F)
For harsh enviroments and or hook up to RRTD
PROFIBUS-DP ( P ) PROFIBUS-DPV1 ( P1 )
BACKSPIN DETECTION(B)
20mV to 480V RMS
3 x RS485 Ports
3 Independent modbus channels
1 ANALOG OUTPUT ( BASE UNIT ) 3 ANALOG OUTPUTS (M,B)
VOLTAGE INPUTS(M)
0-240V wye or delta VT connections.
GROUND CT INPUTS
5A, 1A and 50:0.25 taps
12 RTD INPUTS(R)
Field selectable type
CURRENT INPUTS
3 Phase CT inputs 5A, 1A, taps
CONTROL POWER
HI: 50-300 VDC/60-265 VAC LO: 20-60 VDC / 20-48 VAC
4 OUTPUT RELAYS
Programmable alarm and trip conditions activated by programmable setpoints, switch input, remote communication control
Customer Accessible
Fuse
DIGITAL INPUTS
DISPLAY
40 Character alpha-numeric LCD display for viewing actual values, causes of alarms and trips, and programming setpoints
STATUS INDICATORS LEDs indicate if motor is stopped, starting, running, overloaded or locked out
HELP KEY
Help key can be pressed at any time to provide additional information
KEYPAD
Used to select the display of actual values, causes of alarms, causes of trips, fault diagnosis, and to program setpoints
Rugged, corrosion and flame retardent case.
STATUS INDICATORS
SERVICE LED
4 LEDs indicate when an output is activated. When an LED is lit, the cause of the output relay operation will be shown on the display.
indicates that a self-diagnostic test failed, or that the 369 is in Test Mode .
6
320
1–6 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
FIGURE 1–1: Front and Rear View
CHAPTER 1: INTRODUCTION ORDERING
FIGURE 1–2: DeviceNet Model
FIGURE 1–3: Rear View (Modbus/TCP Model)
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL 1–7
ORDERING CHAPTER 1: INTRODUCTION
CE
g
INPUT POWER:
MODEL: 369-HI-R-B-F-P-0
MAXIMUM CONTACT RATING
250 VAC 8A RESISTIVE 1/4 HP 125VAC 1/2HP 250 VAC
SERIAL No: M53C07000001
FIRMWARE: 53CMC320.000
POLLUTION DEGREE: 2 IP CODE: 50X
50-300 VDC 60-265 VAC 485mA MAX. 50/60Hz or DC
MOD:
12 RTDs:
BACKSPIN
FIBER OPTIC PORT
PROFIBUS
OPTIONS
INSULATIVE VOLTAGE: 2
NONE
OVERVOLTAGE CATAGORY: II
1
7
2
8
3
9
4
10 11
56
12
840350AA.CDR
U
L

1.1.7 Relay Label Definition

1. The 369 Relay order code at the time of leaving the factory.
2. The serial number of the 369 Relay.
3. The firmware installed at the factory. Note that this may no longer be the currently installed firmware as it may have been upgraded in the field. The current firmware revi­sion can be checked in the actual values section of the 369 Relay.
4. Specifications for the output relay contacts.
5. Certifications the 369 Relay conforms with or has been approved to.
6. Factory installed options. These are based on the order code. Note that the 369 Relay may have had options upgraded in the field. The actual values section of the 369 can be checked to verify this.
7. Control power ratings for the 369 Relay as ordered. Based on the HI/LO rating from the order code.
8. Pollution degree.
9. Overvoltage category.
10. IP code.
11. Modification number for any factory-ordered mods.
12. Insulative voltage rating.
1–8 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
Digital Energy
Multilin

2.1 Overview

369 Motor Management Relay
Chapter 2: Product Description

Product Description

2.1.1 Guideform Specifications

Motor protection and management shall be provided by a digital relay. Protective func­tions include:
phase overload standard curves (51)
overload by custom programmable curve (51)
2
•I
t modeling (49)
current unbalance / single phase detection (46)
starts per hour and time between starts
short circuit (50)
ground fault (50G/50N 51G/51N)
mechanical jam / stall
two-speed motor protection
Optional functions include:
under / overvoltage (27/59)
•phase reversal (47)
underpower (37)
power factor (55)
stator / bearing overtemperature with twelve (12) independent RTD inputs (49/38)
backspin detection
Management functions include:
statistical data
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL 2–9
pre-trip data (last 40 events)
ability to learn, display and integrate critical parameters to maximize motor protection
a keypad with 40 character display
flash memory
The relay is capable of displaying important metering functions, including phase volt­ages, kilowatts, kvars, power factor, frequency and MWhr. In addition, undervoltage and low power factor alarm and trip levels are field programmable. The communica­tions interface include one front RS232 port and three independent rear RS485 ports with supporting PC software, thus allowing easy setpoint programming, local retrieval of information and flexibility in communication with SCADA and engineering worksta­tions.

2.1.2 Metered Quantities

Phase Currents and Current Demand Amps Motor Load × FLA Unbalance Current % Ground Current Amps Input Switch Status Open / Closed Relay Output Status (De) Energized RTD Temperature °C or °F R Backspin Frequency Hz B Phase/Line Voltages Volts M Frequency Hz M Power Factor lead / lag M Real Power and Real Power Demand Watts M Reactive Power and Reactive Power Demand Vars M Apparent Power and Apparent Power Demand VA M Real Power Consumption MWh M Reactive Power Consumption/Generation ±Mvarh M
OVERVIEWCHAPTER 2: PRODUCT DESCRIPTION
METERED QUANTITY UNITS OPTION

2.1.3 Protection Features

ANSI/
IEEE
DEVICE
14 Speed Switch • 27 Undervoltage M • 37 Undercurrent / Underpower /M • 38 Bearing RTD R or RRTD • 46 Current Unbalance • 47 Voltage Phase Reversal M • 49 Stator RTD R or RRTD
2–10 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
PROTECTION FEATURES OPTION TRIP ALARM BLOCK
START
CHAPTER 2: PRODUCT DESCRIPTIONOVERVIEW
ANSI/
IEEE
DEVICE
PROTECTION FEATURES OPTION TRIP ALARM BLOCK
50 Short Circuit & Backup
50G/51G
Ground Fault & Ground Fault Backup
••
51 Overload • 55 Power Factor M • 59 Overvoltage M
66
Starts per Hour/Time
Between Starts 74 Alarm • 81 Over/Under Frequency M • 86 Lockout • 87 Differential Switch
General Switch
Reactive Power M
Thermal Capacity
Start Inhibit (thermal capacity
available)
Restart Block (Backspin
Timer)
Mechanical Jam
Acceleration Timer
Ambient RTD R or RRTD
Short/Low temp RTD R or RRTD
Broken/Open RTD R or RRTD
Loss of RRTD
Communications
RRTD
Trip Counter
Self Test/Service
Backspin Detection B
Current Demand
kW Demand M
kvar Demand M
kVA Demand M
Starter Failure
Reverse Power M
Undervoltage Autorestart M or B
START
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL 2–11

2.1.4 Additional Features

OVERVIEWCHAPTER 2: PRODUCT DESCRIPTION
FEATURE OPTION
Modbus/TCP protocol Ethernet interface
E
Profibus-DP rear communication port P Profibus-DPV1 rear communication
port
P1
DeviceNet protocol interface D User Definable Baud Rate (1200-
19200) Flash Memory for easy firmware
updates Front RS232 communication port Rear RS485 communication port Rear fiber optic port F RTD type is user definable R or RRTD 4 User Definable Analog Outputs
(0 to 1 mA, 0 to 20 mA, 4 to 20 mA)
M
Windows based PC program for setting up and monitoring
FIGURE 2–1: Single Line Diagram
2–12 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL

2.2 Specifications

2.2.1 Inputs

CHAPTER 2: PRODUCT DESCRIPTIONSPECIFICATIONS
CONTROL POWER
LO range:............................................................DC: 20 to 60 V DC
AC: 20 to 48 V AC at 50/60 Hz
HI range:.............................................................DC: 50 to 300 V DC
AC: 60 to 265 V AC at 50/60 Hz
Power:..................................................................nominal: 20 VA; maximum: 65 VA
Holdup:................................................................non-failsafe trip: 200 ms; failsafe trip: 100 ms
FUSE
T 3.15 A H 250 V (5 × 20 mm) Timelag high breaking capacity
PHASE CURRENT INPUTS (CT)
CT input (rated):...............................................1 A and 5 A secondary
CT primary:........................................................1 to 5000 A
Range:
for 50/60 Hz nominal frequency: ......0.05 to 20 × CT primary amps
for variable frequency: ...........................0.1 to 20 × CT primary amps
Full Scale: ...........................................................20 × CT primary amps or 65535 A maximum
Frequency:.........................................................20 to 100 Hz
Conversion: .......................................................True RMS, 1.04 ms/sample
Accuracy:
at 2 × CT:....................................................±0.5% of 2 × CT for 50/60 Hz nominal freq.
±1.0% of 2 × CT for variable frequency (for sinusoidal waveforms)
at > 2 × CT:....................................................±1.0% of 20 × CT for 50/60 Hz nominal freq.
±3.0% of 12 × CT or less for variable frequency (for sinusoidal waveforms)
PHASE CT BURDEN
PHASE CT INPUT (A) BURDEN
VA (Ω)
1 0.03 0.03
1A
5 0.64 0.03 20 11.7 0.03 5 0.07 0.003
5A
25 1.71 0.003 100 31 0.003
PHASE CT CURRENT WITHSTAND
PHASE CT WITHSTAND TIME
1s 2s continuous
1 A 100 × CT 40 × CT 3 × CT 5 A 100 × CT 40 × CT 3 × CT
DIGITAL / SWITCH INPUTS
Inputs:..................................................................6 optically isolated
Input type:..........................................................Dry Contact (< 800 Ω)
Function:.............................................................Programmable
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL 2–13
SPECIFICATIONSCHAPTER 2: PRODUCT DESCRIPTION
GROUND CURRENT INPUT (GF CT)
CT Input (rated):...............................................1 A/5 A secondary and 50:0.025
CT Primary: ........................................................1 to 5000 A (1 A/5 A)
Range: .................................................................0.1 to 1.0 × CT primary (1 A/5 A)
0.05 to 25.0 A (50:0.025)
Full Scale: ...........................................................1.0 × CT primary (1 A/5 A)
25 A (50:0.025)
Frequency:.........................................................20 to 100 Hz
Conversion:........................................................True RMS 1.04ms/sample
Accuracy at 50/60 Hz:
for 1 A/5 A: .........................................±1.0% of full scale (1 A/5 A)
for 50:0.025........................................±0.07 A at <1 A
±0.20 A at <25 A Accuracy at variable frequency:
for 1 A tap:.....................................................±1.5% for 40 to 100 Hz
±2.5% for 20 to 39 Hz
for 5 A tap:.....................................................±2% for 40 to 100 Hz
±3% for 20 to 39 Hz
for 50:0.025: .................................................±0.2 A at <1 A
±0.6 A at <25 A
GROUND CT BURDEN
GROUND CT INPUT (A) BURDEN
VA (Ω)
1 0.04 0.036
1A
5 0.78 0.031 20 6.79 0.017 5 0.07 0.003
5A
25 1.72 0.003 100 25 0.003
0.025 0.24 384
50:0.025
0.1 2.61 261
0.5 37.5 150
GROUND CT CURRENT WITHSTAND
GROUND CT WITHSTAND TIME
1s 2s continuous
1 A 100 × CT 40 × CT 3 × CT 5 A 100 × CT 40 × CT 3 × CT 50:0.025 10 A 5 A 150 mA
PHASE/LINE VOLTAGE INPUT (VT) (OPTION M)
VT ratio:...............................................................1.00 to 240.00:1 in steps of 0.01
VT secondary:...................................................240 V AC (full scale)
Range:..................................................................0.05 to 1.00 × full scale
Frequency:.........................................................20 to 100 Hz
Conversion:........................................................True RMS 1.04 ms/sample
Accuracy:...............................................±2.5% of full scale for ≤ 200 V at 20 to 39 Hz
±1% of full scale for 12 to 240 V at > 40 Hz
Burden:................................................................>200 kΩ
Max. continuous: ............................................280 V AC
2–14 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL

2.2.2 Outputs

CHAPTER 2: PRODUCT DESCRIPTIONSPECIFICATIONS
BSD INPUTS (OPTION B)
Frequency: ........................................................1 to 120 Hz
Dynamic BSD range: ....................................20 mV to 480 V RMS
Accuracy:...............................................±0.02 Hz
Burden:................................................................>200 kΩ
RTD INPUTS (OPTION R)
Wire Type:..........................................................3 wire
Sensor Type: .....................................................100 Ω platinum (DIN 43760), 100 Ω nickel, 120 Ω nickel,
10 Ω copper
RTD sensing current: ....................................3 mA
Range:..................................................................–40 to 200°C or –40 to 392°F
Accuracy:...............................................±2°C or ±4°F
Lead resistance:..............................................25 Ω max. per lead for Pt and Ni type;
3 Ω max. per lead for Cu type
Isolation:.............................................................36 Vpk
ANALOG OUTPUTS (OPTION M)
PROGRAMMABLE
OUTPUT
MAX LOAD
MAX OUTPUT
Accuracy:...............................................±1% of full scale
Isolation:.............................................................fully isolated active source
0 to 1 mA 0 to 20 mA 4 to 20 mA
2400 Ω 600 Ω 600 Ω
1.01 mA 20.2 mA 20.2 mA
OUTPUT RELAYS
RESISTIVE
RATED LOAD
CARRY CURRENT
MAX SWITCHING
CAPACITY
MAX SWITCHING V
MAX SWITCHING I
OPERATE TIME
CONTACT
MATERIAL
LOAD (pf = 1)
8 A at 250 V AC 8A at 30VDC
8A 2000 VA
240 W 380 V AC; 125 V DC 8A 3.5A <10 ms (5 ms typical)
silver alloy
LOAD (pf = 0.4)(L/
3.5 A at 250 V AC
3.5 A at 30 V DC
875 VA 170 W
INDUCTIVE
R – 7ms)
This equipment is suitable for use in Class 1, Div 2, Groups A, B, C, D or Non-Hazardous Locations only if MOD502 is ordered.
Hazardous Location – Class 1, Div 2 output rating if MOD502 is ordered: 240 V, 3 A max, as per UL1604. The contact rating is only for Make and carry operations, and shall not be used for breaking DC current.
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL 2–15

2.2.3 Metering

SPECIFICATIONSCHAPTER 2: PRODUCT DESCRIPTION
Explosion Hazard – Substitution of components may impair suitability for Class 1, Div 2.
Explosion Hazard – Do not disconnect equipment unless power has been switched off or the area is known to be Non-Hazardous.
POWER METERING (OPTION M)
PARAMETERACCURAC
Y
(FULL SCALE)
RESOLUTIONRANGE
kW ±2% 1 kW ±32000 kvar ±2% 1 kvar ±32000 kVA ±2% 1 kVA 0 to 65000 kWh ±2% 1 kWh 0 to 999 MWh ±2% 1 MWh 0 to 65535 ±kvarh ±2% 1 kvarh 0 to 999 ±Mvarh ±2% 1 Mvarh 0 to 65535 Power Factor ±1% 0.01 –0.99 to 1.00
Frequency ±0.02 Hz 0.01 Hz
20.00 to
100.00 kW Demand ±2% 1 kW 0 to 32000 kvar Demand ±2% 1 kvar 0 to 32000 kVA Demand ±2% 1 kVA 0 to 65000 Amp Demand ±2% 1 A 0 to 65535
EVENT RECORD
Capacity:.............................................................last 512 events
Triggers:..............................................................trip, inhibit, power fail, alarms, self test,
waveform capture
WAVEFORM CAPTURE
Length:.................................................................3 buffers containing 16 cycles of all current and voltage
channels
Trigger position: ..............................................1 to 100% pre-trip to post-trip
Trigger: ...............................................................trip, manually via communications or digital input
MOTOR START DATA LOGGER
Length: ...............................................................6 Buffers containing 30 seconds of motor start data.
Trigger: ...............................................................Motor Start Status.
Trigger position: .............................................1-second pre-trigger duration.
Logging rate: ...................................................1 sample/200ms.
2–16 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL

2.2.4 Communications

FRONT PORT
Type:.....................................................................RS232, non-isolated
Baud rate: ..........................................................4800 to 19200
Protocol:..............................................................Modbus
BACK PORTS (3)
Type:.....................................................................RS485
Baud rate: ..........................................................1200 to 19200
Protocol:..............................................................Modbus
36V isolation (together)
PROFIBUS (OPTIONS P AND P1)
Type:.....................................................................RS485
Baud rate: ..........................................................1200 baud to 12 Mbaud
Protocol:..............................................................Profibus-DP
Connector Type:..............................................DB9 Female
MODBUS/TCP ETHERNET (OPTION E)
Connector type:...............................................RJ45
Protocol:..............................................................Modbus/TCP
CHAPTER 2: PRODUCT DESCRIPTIONSPECIFICATIONS
®
RTU
®
RTU
Profibus-DPV1
DEVICENET (OPTION D)
DeviceNet CONFORMANCE TESTED™
Connector type:...............................................5-pin linear DeviceNet plug (phoenix type)
Baud rate: ..........................................................125, 250, and 500 kbps
Protocol:..............................................................DeviceNet
Bus-Side Current Draw:...............................85mA (Typical), 100mA (Max)
FIBER OPTIC PORT (OPTION F)
Optional use:.....................................................RTD remote module hookup
Baud rate: ..........................................................1200 to 19200
Protocol:..............................................................Modbus
®
RTU
Fiber sizes: .........................................................50/125, 62.5/125, 100/140, and 200 μm
Emitter fiber type: ..........................................820 nm LED, multimode
Link power budget:
Transmit power: ...........................................–20 dBm
Received sensitivity: ...................................–30 dBm
Power budget:...............................................10 dB
Maximum optical input power: ..............–7.6 dBm
Typical link distance: ...................................1.65 km
Note
Typical link distance is based upon the following assumptions for system loss. As actual losses vary between installations, the distance covered will vary.
Connector loss: ..............................................2 dB
Fiber loss: ..........................................................3 dB/km
Splice loss: ........................................................One splice every 2 km at 0.05 dB loss/splice
System margin: ..............................................3 dB additional loss added to calculations to compensate
for all other losses
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL 2–17
FIELDBUS LOSS OF COMMUNICATION
Pickup: .................................................................No communication
Time delay: ........................................................0.25 to 10 sec in steps of 0.25 sec
Timing accuracy:...................................±250 ms for Profibus

2.2.5 Protection Elements

51 OVERLOAD/STALL/THERMAL MODEL
Curve Shape: ....................................................1 to 15 standard, custom
Curve Biasing: ..................................................unbalance, temperature, hot/cold ratio,
Pickup Level: .....................................................1.01 to 1.25 × FLA
Pickup Accuracy: ............................................as per phase current inputs
Dropout Level:..................................................96 to 98% of pickup
Timing Accuracy:............................................±100 ms or ±2% of total trip time
THERMAL CAPACITY ALARM
Pickup Level: .....................................................1 to 100% TC in steps of 1
Pickup Accuracy: ............................................±2%
Dropout Level:..................................................96 to 98% of pickup
Timing Accuracy:............................................±100 ms
SPECIFICATIONSCHAPTER 2: PRODUCT DESCRIPTION
±300 ms for Ethernet ±250 ms for DeviceNet
cool time constants
OVERLOAD ALARM
Pickup Level: .....................................................1.01 to 1.50 × FLA in steps of 0.01
Pickup Accuracy: ............................................as per phase current inputs
Dropout Level:..................................................96 to 98% of pickup
Time Delay:........................................................0.1 to 60.0 s in steps of 0.1
Timing Accuracy:............................................±100 ms or ±2% of total trip time
50 SHORT CIRCUIT
Pickup Level: .....................................................2.0 to 20.0 × CT in steps of 0.1
Pickup Accuracy: ............................................as per phase current inputs
Dropout Level:..................................................96 to 98% of pickup
Time Delay:........................................................0 to 255.00 s in steps of 0.01 s
Backup Delay: ..................................................0.10 to 255.00 s in steps of 0.01 s
Timing Accuracy:............................................+50 ms for delays <50 ms
±100 ms or ±0.5% of total trip time
MECHANICAL JAM
Pickup Level: .....................................................1.01 to 6.00 × FLA in steps of 0.01
Pickup Accuracy: ............................................as per phase current inputs
Dropout Level:..................................................96 to 98% of pickup
Time Delay:........................................................0.5 to 125.0 s in steps of 0.5
Timing Accuracy:............................................±250 ms or ±0.5% of total trip time
37 UNDERCURRENT
Pickup Level: .....................................................0.10 to 0.99 × FLA in steps of 0.01
Pickup Accuracy: ............................................as per phase current inputs
Dropout Level:..................................................102 to 104% of pickup
Time Delay:........................................................1 to 255 s in steps of 1
Start Delay:........................................................0 to 15000 s in steps of 1
Timing Accuracy:............................................±500 ms or ±0.5% of total time
2–18 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTIONSPECIFICATIONS
46 UNBALANCE
Pickup Level:.....................................................4 to 30% in steps of 1
Pickup Accuracy: ............................................±2%
Dropout Level:..................................................1 to 2% below pickup
Time Delay: .......................................................1 to 255 s in steps of 1
Start Delay:........................................................0 to 5000 s in steps of 1
Timing Accuracy:............................................±500 ms or ±0.5% of total time
50G/51G 50N/51N GROUND FAULT
Pickup Level:.....................................................0.10 to 1.00 × CT for 1 A/5 A CT
0.25 to 25.00 A for 50:0.025 CT
Pickup Accuracy:............................................as per ground current inputs
Dropout Level:..................................................96 to 98% of pickup
Time Delay: .......................................................0 to 255.00 s in steps of 0.01 s
Backup Delay:..................................................0.01 to 255.00 s in steps of 0.01 s
Timing Accuracy:............................................+50 ms for delays <50 ms
±100 ms or ±0.5% of total trip time
ACCELERATION TRIP
Pickup Level:.....................................................motor start condition
Dropout Level:..................................................motor run, trip or stop condition
Time Delay: .......................................................1.0 to 250.0 s in steps of 0.1
Timing Accuracy:............................................±100 ms or ±0.5% of total time
38/49 RTD AND RRTD PROTECTION
Pickup Level:.....................................................1 to 200°C or 34 to 392°F
Pickup Accuracy:................................... ±2°C or ±4°F
Dropout Level:..................................................96 to 98% of pickup above 80°C
Time Delay: .......................................................<5 s
OPEN RTD ALARM
Pickup Level:.....................................................detection of an open RTD
Pickup Accuracy: ............................................>1000 Ω
Dropout Level:..................................................96 to 98% of pickup
Time Delay: .......................................................<5 s
SHORT/LOW TEMP RTD ALARM
Pickup Level:.....................................................<–40°C or –40°F
Pickup Accuracy:................................... ±2°C or ±4°F
Dropout Level:..................................................96 to 98% of pickup
Time Delay: .......................................................<5 s
LOSS OF RRTD COMMS ALARM
Pickup Level:.....................................................no communication
Time Delay: .......................................................2 to 5 s
27 UNDERVOLTAGE
Pickup Level:.....................................................0.50 to 0.99 × rated in steps of 0.01
Pickup Accuracy:............................................as per phase voltage inputs
Dropout Level:..................................................102 to 104% of pickup
Time Delay: .......................................................0.0 to 255.0 s in steps of 0.1
Start Delay:........................................................separate level for start conditions
Timing Accuracy:............................................+75 ms for delays <50 ms
±100 ms or ±0.5% of total trip time
59 OVERVOLTAGE
Pickup Level:.....................................................1.01 to 1.25 × rated in steps of 0.01
Pickup Accuracy:............................................as per phase voltage inputs
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL 2–19
SPECIFICATIONSCHAPTER 2: PRODUCT DESCRIPTION
Dropout Level:..................................................96 to 98% of pickup
Time Delay:........................................................0.0 to 255.0 s in steps of 0.1
Timing Accuracy:............................................±100 ms or ±0.5% of total trip time
47 PHASE REVERSAL
Pickup Level: .....................................................phase reversal detected
Time Delay:........................................................500 to 700 ms
81 UNDERFREQUENCY
Pickup Level: .....................................................20.00 to 70.00 Hz in steps of 0.01
Pickup Accuracy: ............................................±0.02 Hz
Dropout Level:..................................................0.05 Hz
Time Delay:........................................................0.0 to 255.0 s in steps of 0.1
Start Delay:........................................................0 to 5000 s in steps of 1
Timing Accuracy:............................................±100 ms or ±0.5% of total trip time
81 OVERFREQUENCY
Pickup Level: .....................................................20.00 to 70.00 Hz in steps of 0.01
Pickup Accuracy: ............................................±0.02 Hz
Dropout Level:..................................................0.05 Hz
Time Delay:........................................................0.0-255.0 s in steps of 0.1
Start Delay:........................................................0-5000 s in steps of 1
Timing Accuracy:............................................±100 ms or ±0.5% of total trip time
55 LEAD POWER FACTOR
Pickup Level: .....................................................0.99 to 0.05 in steps of 0.01
Pickup Accuracy: ............................................±0.02
Dropout Level:..................................................0.03 of pickup
Time Delay:........................................................0.1 to 255.0 s in steps of 0.1
Start Delay:........................................................0 to 5000 s in steps of 1
Timing Accuracy:............................................±300 ms or ±0.5% of total trip time
55 LAG POWER FACTOR
Pickup Level: .....................................................0.99 to 0.05 in steps of 0.01
Pickup Accuracy: ............................................±0.02
Dropout Level:..................................................0.03 of pickup
Time Delay:........................................................0.1 to 255.0 s in steps of 0.1
Start Delay:........................................................0 to 5000 s in steps of 1
Timing Accuracy:............................................±300 ms or ±0.5% of total trip time
POSITIVE REACTIVE POWER
Pickup Level: .....................................................1 to 25000 in steps of 1
Pickup Accuracy: ............................................±2%
Dropout Level:..................................................96 to 98% of pickup
Time Delay:........................................................0.1 to 255.0 s in steps of 0.1
Start Delay:........................................................0 to 5000 s in steps of 1
Timing Accuracy:............................................±300 ms or ±0.5% of total trip time
NEGATIVE REACTIVE POWER
Pickup Level: .....................................................1 to 25000 kvar in steps of 1
Pickup Accuracy: ............................................±2%
Dropout Level:..................................................96 to 98% of pickup
Time Delay:........................................................0.1 to 255.0 s in steps of 0.1
Start Delay:........................................................0 to 5000 s in steps of 1
Timing Accuracy:............................................±300 ms or ±0.5% of total trip time
37 UNDERPOWER
Pickup Level: .....................................................1 to 25000 kW in steps of 1
Pickup Accuracy: ............................................±2%
2–20 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTIONSPECIFICATIONS
Dropout Level:..................................................102 to 104% of pickup
Time Delay: .......................................................0.5 to 255.0 s in steps of 0.5
Start Delay:........................................................0 to 15000 s in steps of 1
Timing Accuracy:............................................±300 ms or ±0.5% of total trip time
REVERSE POWER
Pickup Level:.....................................................1 to 25000 kW in steps of 1
Pickup Accuracy: ............................................±2%
Dropout Level:..................................................96 to 98% of pickup
Time Delay: .......................................................0.5 to 30.0 s in steps of 0.5
Start Delay:........................................................0 to 50000 s in steps of 1
Timing Accuracy:............................................±300 ms or ±0.5% of total trip time
87 DIFFERENTIAL SWITCH
Time Delay: .......................................................<200 ms
14 SPEED SWITCH
Time Delay: .......................................................0.5 to 100.0 s in steps of 0.5
Timing Accuracy:............................................±200 ms or ±0.5% of total trip time
GENERAL SWITCH
Time Delay: .......................................................0.1 to 5000.0 s in steps of 0.1
Start Delay:........................................................0 to 5000 s in steps of 1
Timing Accuracy:............................................±200 ms or ±0.5% of total trip time
DIGITAL COUNTER
Pickup: .................................................................on count equaling level
Time Delay: .......................................................<200 ms
BACKSPIN DETECTION
Dynamic BSD:...................................................20 mV to 480 V RMS
Pickup Level:.....................................................3 to 120 Hz in steps of 1
Dropout Level:..................................................2 to 30 Hz in steps of 1
Level Accuracy: ...............................................±0.02 Hz
Timing Accuracy:............................................±500 ms or ±0.5% of total trip time

2.2.6 Monitoring Elements

STARTER FAILURE
Pickup level: ......................................................motor run condition when tripped
Dropout level:...................................................motor stopped condition
Time delay: ........................................................10 to 1000 ms in steps of 10
Timing accuracy:............................................±100 ms
CURRENT DEMAND ALARM
Demand period:..............................................5 to 90 min. in steps of 1
Pickup level: ......................................................0 to 65000 A in steps of 1
Pickup accuracy: ............................................as per phase current inputs
Dropout level:...................................................96 to 98% of pickup
Time delay: ........................................................<2 min.
kW DEMAND ALARM
Demand period:..............................................5 to 90 min. in steps of 1
Pickup level: ......................................................1 to 50000 kW in steps of 1
Pickup accuracy: ............................................±2%
Dropout level:...................................................96 to 98% of pickup
Time delay: ........................................................<2 min.
kvar DEMAND ALARM
Demand period:..............................................5 to 90 min. in steps of 1
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL 2–21
Pickup level:.......................................................1 to 50000 kvar in steps of 1
Pickup accuracy:.............................................±2%
Dropout level:...................................................96 to 98% of pickup
Time delay: ........................................................<2 min.
kVA DEMAND ALARM
Demand period: ..............................................5 to 90 min in steps of 1
Pickup level:.......................................................1 to 50000 kVA in steps of 1
Pickup accuracy:.............................................±2%
Dropout level:...................................................96 to 98% of pickup
Time delay: ........................................................<2 min.
TRIP COUNTER
Pickup: .................................................................on count equaling level
Time delay: ........................................................<200 ms

2.2.7 Control Elements

REDUCED VOLTAGE START
Transition Level:..............................................25 to 300% FLA in steps of 1
Transition Time:...............................................1 to 250 sec. in steps of 1
Transition Control:..........................................Current, Timer, Current and Timer
UNDERVOLTAGE AUTORESTART
Pickup/Restoration level: ...........................0.50 to 1.00 × rated in steps of 0.01
Immediate Restart Power Loss Time: ..100 to 500 ms in steps of 100ms
Delay 1 Restart Power Loss Time: .........0.1 to 10 s in steps of 0.1 s, or OFF.
Delay 1 Restart Time Delay: .....................0 to 1200.0 s in steps of 0.2 s
Delay 2 Restart Power Loss Time: ........1 to 3600s in steps of 1s, Off or Unlimited
Delay 2 Restart Time Delay: .....................0 to 1200.0 s in steps of 0.2 s
Time Accuracy: ...............................................± 200ms
SPECIFICATIONSCHAPTER 2: PRODUCT DESCRIPTION
1 to 9 seconds (with loss of control power)

2.2.8 Environmental Specifications

AMBIENT TEMPERATURE
Operating Range: ..........................................-40°C to +60°C
Storage Range: ...............................................-40°C to +80°C
T-Code Rating: .................................................T4A (for MOD 502 only)
NoteNOTE:
2–22 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
For 369 units with the Profibus, Modbus/TCP, or DeviceNet option the operating and storage ranges are as follows:
Operating Range: ..........................................+5°C to +60°C
Storage Range: ...............................................+5°C to +80°C
HUMIDITY
Up to 95% non condensing
DUST/MOISTURE
IP50
VENTILATION
No special ventilation required as long as ambient temperature remains within specifications. Ventilation may be required in enclosures exposed to direct sunlight.
Loading...
+ 264 hidden pages