Setup are trademarks or registered trademarks of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin Inc. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-9086-AN (June 2017)
Storage
Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow
the storage temperature range outlined in the Specifications.
To avoid deterioration of electrolytic capacitors, power up units that are stored in a deenergized state once per year, for one hour continuously.
This product cannot be disposed of as unsorted municipal waste in the European
Union. For proper recycling return this product to your supplier or a designated
collection point. For more information go to www.recyclethis.info.
Note
GENERAL SAFETY PRECAUTIONS - 350
• Failure to observe and follow the instructions provided in the equipment manual(s)
could cause irreversible damage to the equipment and could lead to property
damage, personal injury and/or death.
• Before attempting to use the equipment, it is important that all danger and caution
indicators are reviewed.
• If the equipment is used in a manner not specified by the manufacturer or
functions abnormally, proceed with caution. Otherwise, the protection provided by
the equipment may be impaired and can result in Impaired operation and injury.
• Caution: Hazardous voltages can cause shock, burns or death.
• Installation/service personnel must be familiar with general device test practices,
electrical awareness and safety precautions must be followed.
• Before performing visual inspections, tests, or periodic maintenance on this device
or associated circuits, isolate or disconnect all hazardous live circuits and sources
of electric power.
• Failure to shut equipment off prior to removing the power connections could
expose you to dangerous voltages causing injury or death.
• All recommended equipment that should be grounded and must have a reliable
and un-compromised grounding path for safety purposes, protection against
electromagnetic interference and proper device operation.
• Equipment grounds should be bonded together and connected to the facility’s
main ground system for primary power.
• Keep all ground leads as short as possible.
• At all times, equipment ground terminal must be grounded during device
operation and service.
• In addition to the safety precautions mentioned all electrical connections made
must respect the applicable local jurisdiction electrical code.
• Before working on CTs, they must be short-circuited.
• LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL) Class
1M. Class 1M devices are considered safe to the unaided eye. Do not view directly
with optical instruments.
• This product uses optical electronic devices (line or point sensors) to sense arc
flash fault conditions. It is recommended to follow proper housekeeping measures
and establish a regularly scheduled preventive maintenance routine to ensure
proper device operation.
• This product itself is not Personal Protective Equipment (PPE). However, it can be
used in the computation of site-specific arc flash analysis when the arc flash
option is ordered. If a new appropriate Hazard Reduction Category code for the
installation is determined, the user should follow the cautions mentioned in the arc
flash installation section.
• This guide is intended to provide protective relay application guidance to mitigate
arc flash incident energy. This guide does not endorse energized work. This guide
does not claim that protective relaying can totally protect personnel from the
dangers of an arc flash. The only way to completely prevent injury from arc flash
events is to de-energize the equipment and properly follow safe lockout/tagout
procedures to ensure the equipment remains de-energized.
Safety words and definitions
The following symbols used in this document indicate the following conditions
Note
Indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
Note
Indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
Note
Indicates a hazardous situation which, if not avoided, could result in minor or
moderate injury.
Note
Indicates practices not related to personal injury.
For further assistance
For product support, contact the information and call center as follows:
GE Grid Solutions
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Worldwide telephone: +1 905 927 7070
Europe/Middle East/Africa telephone: +34 94 485 88 54
North America toll-free: 1 800 547 8629
Fax: +1 905 927 5098
Worldwide e-mail: multilin.tech@ge.com
Europe e-mail: multilin.tech.euro@ge.com
Website: http://www.gegridsolutions.com/multilin
Voltage ..........................................................................................................................................4 - 8
Power .............................................................................................................................................4 - 9
Energy ...........................................................................................................................................4 - 9
Current Demand.......................................................................................................................4 - 10
Power Demand..........................................................................................................................4 - 10
A. APPENDIXWarranty................................................................................................................................A - 1
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUALv
vi350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
GE
Grid Solutions
350 Feeder Protection System
Chapter 1: Introduction
Overview
Introduction
The 350 is a microprocessor-based relay for primary and backup over-current protection
of medium and low voltage distribution feeders. The relay is also suitable for providing
over-current and backup protection for small and medium size motors, transformers,
generators, and distribution bus-bars. The small footprint and the withdrawable option
make the 350
combination of proven hardware, a variety of protection and control features, and
communications, makes the relay ideal for total feeder protection and control. Equipped
with serial (RS485), USB, and Ethernet ports with the possibility of adding redundancy
(IEC62439, PRP and HSR), and a wide selection of protocols such as Modbus, DNP3.0, IEC
60870-5-103, 60870-5-104, IEC61850 GOOSE, OPC-UA, the 350
for MCCs and PCCs, SCADA and inter-relay communications. The 350
excellent transparency with respect to power system conditions and events, through its
four-line 20-character display, as well as the EnerVista 3
Conveniently located LEDs provide indication of relay operation, alarm, and pickup, as well
as breaker, and relay status.
The 350 relay provides the following key benefits:
•Withdrawable small footprint – saves on rewiring and space. (non-draw out version is
also available)
•Multiple protection groups with the added flexibility of switching through a wide
selection of overcurrent protection and control features.
•Fast setup (Quick Setup) menu for power-system setup and a simple overcurrent
protection configuration.
•Large four-line LCD display, LEDs, and an easy-to-navigate keypad.
•Multiple communication protocols for simultaneous access when integrated into
monitoring and control systems.
relay ideal for panel mounting on either new or retrofit installations. The
relay is the best-in-class
relay provides
Series Setup program.
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL1–1
DESCRIPTION OF THE 350 FEEDER PROTECTION SYSTEMCHAPTER 1: INTRODUCTION
Description of the 350 Feeder Protection System
CPU
Relay functions are controlled by two processors: a Freescale MPC5554 32-bit
microprocessor measures all analog signals and digital inputs and controls all output
relays; a Freescale MPC520B 32-bit microprocessor controls all the Ethernet
communication protocols.
Analog Input and Waveform Capture
Magnetic transformers are used to scale-down the incoming analog signals from the
source instrument transformers. The analog signals are then passed through a 960 Hz low
pass anti-aliasing filter. All signals are then simultaneously captured by sample and hold
buffers to ensure there are no phase shifts. The signals are converted to digital values by a
12-bit A/D converter before finally being passed on to the CPU for analysis.
Both current and voltage are sampled thirty-two times per power frequency cycle. These
‘raw’ samples are scaled in software, then placed into the waveform capture buffer, thus
emulating a fault recorder. The waveforms can be retrieved from the relay via the
EnerVista 3
Frequency
Frequency measurement is accomplished by measuring the time between zero crossings
of the Bus VT phase A voltage. The signals are passed through a low pass filter to prevent
false zero crossings. Sampling is synchronized to the Va-x voltage zero crossing which
results in better co-ordination for multiple 350
Phasors, Transients, and Harmonics
Current waveforms are processed four times every cycle with a DC Offset Filter and a
Discrete Fourier Transform (DFT). The resulting phasors have fault current transients and all
harmonics removed. This results in an overcurrent relay that is extremely secure and
reliable; one that will not overreach.
Processing of AC Current Inputs
The DC Offset Filter is an infinite impulse response (IIR) digital filter, which removes the DC
component from the asymmetrical current present at the moment a fault occurs. This is
done for all current signals used for overcurrent protection; voltage signals bypass the DC
Offset Filter. This filter ensures no overreach of the overcurrent protection.
The Discrete Fourier Transform (DFT) uses exactly one sample cycle to calculate a phasor
quantity which represents the signal at the fundamental frequency; all harmonic
components are removed. All subsequent calculations (e.g. RMS, power, etc.) are based
upon the current and voltage phasors, such that the resulting values have no harmonic
components.
Protection Elements
Protection elements are processed up to four times every cycle to determine if a pickup
has occurred or a timer has expired. The protection elements use RMS current/voltage,
based on the magnitude of the phasor. Hence, protection is impervious to both harmonics
and DC transients.
NOTE:
Arc Flash protection elements are processed up to 8 times every cycle.
Series Setup software for display and diagnostics.
relays on the same bus.
1–2350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 1: INTRODUCTIONDESCRIPTION OF THE 350 FEEDER PROTECTION SYSTEM
898742A7.CDR
A350 RELAYY
TRIP
BUS
LOAD
3
1
52
CLOSE
50G/
51G
50P50N
79
22
21
METERING
TRANSIENT RECORDER
EVENT RECORDER
FAULT REPORT
51N51P
50_2
111
49
1
27X
59P27P
59X
59_259N81U81O
CLP
50BF
1
11
1
1122
MONITORING
BUS VT
67P
1
1
51_2
67N
1
CTS
25
51G/SG 67G/SG50G/SG
I/I
12
27_1
1
86
VTFF
1
24
32N
2
32
50P HS
1
1
50G/SG
HS
AF
SENSORS
Figure 1-1: Functional block diagram
Table 1-1: ANSI device numbers and functions
ANSI Code61850 Logical Node Description
24PVPHVolts per Hertz
25RSYN1Synchrocheck
27_1psseqPTUV1Positive Sequence Undervoltage
27PphsPTUV1, phsPTUV2,
2nd Harmonic Blocking
Arc Flash Detector
Ambient Temperature
Breaker Control
Breaker Health
Breaker Maintenance
CT Failure Detection
Data Logger
Demand (in metering)
Digital Counters
DNP 3.0 Communications
Event Recorder
Fault Report
Flexcurves
HSR Communications
IEC 60870-5-103 Communications
IEC 60870-5-104 Communications
IEC 61850 Communications
IEC 61850 GOOSE Communications
Lockout (86)
Logic Elements
Metering: current, voltage, power, PF, energy, frequency, 2nd harmonics
Modbus User Map
Modbus RTU Communications
Modbus TCP Communications
Non-volatile Latches
OPC-UA Communications
1–4350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 1: INTRODUCTION350 ORDER CODES
ACTUAL VALUES
COMMANDS
SETPOINTS
MAINTENANCE
ACTUAL VALUES
A1 STATUS
A2 METERING
A3 RECORDS
A4 TARGET MESSAGES
QUICK SETUP
RELAY STATUS
NOMINAL FREQUENCY
PH CT PRIMARY
PH CT SECONDARY
VT SEC. VOLTAGE
VT RATIO
AUX VT SECONDARY
AUX VT RATIO
PH TOC FUNCTION
NTRL TOC FNCTN
PH IOC1 FUNCTION
NTRL IOC1 FNCTN
▼
SETPOINTS
S1 RELAY SETUP
S2 SYSTEM SETUP
S3 PROTECTION
S4 CONTROLS
S5 INPUTS/OUTPUTS
▼
MAINTENANCE
M1 RELAY INFO
M3 BKR MAINTENANCE
M5 RELAY MAINT
M6 FACTORY SERVICE
M4 BKR MONITOR
▼
898756A3.cdr
[S]GND CT SECONDARY
S6 MONITORING
M7 TESTING
QUICK SETUP
[S]GND CT PRIMARY
VT CONNECTION
[S]GND TOC FUNCTION
[S]GND IOC1 FNCTN
Description
Output Relays
PRP Communications
Relay Maintenance
Remote Inputs (32)
Setpoint Groups (2)
Test Mode
Transient Recorder (Oscillography)
Trip and Close Coil Monitoring
User Curves
User-programmable LEDs
Virtual Inputs (32)
Virtual Outputs (32)
Figure 1-2: Main Menu structure
350 order codes
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL1–5
The information to specify a 350 relay is provided in the following order code figure.
350 ORDER CODESCHAPTER 1: INTRODUCTION
350 **** ***** ***
Interface350||||||||||| | 350 Feeder Protection System
User InterfaceE |||||||||||English without programmable LEDs
L |||||||||||English with programmable LEDs
Phase Currents
a
a. Phase Current options PX/P0 and Ground Current options GX/G0 are only available with the non-drawout Case Design N.
PX|||||||||| No CT
P0||||||||| | 1 A or 5 A configurable phase current inputs
P1||||||||| | 1 A 3-phase current inputs
P5||||||||| | 5 A 3-phase current inputs
Ground Currents
b
b. Ground Currents G1/G5 and S1/S5 must match the corresponding P1/P5 Phase Currents (i.e. 5A and 1A must not be mixed).
Ground Current GX requires PX Phase Current, and is only available with Case N, Current Protection N, Other Options V, and Input/Output E.
Ground Current G0/S0 must match the P0 Phase Current, and is only available with the non-drawout Case Design N.
GX |||||||||No CT
G0 |||||||||1 A and 5 A configurable ground current input
G1 |||||||||1 A ground current input
G5 |||||||||5 A ground current input
S0 |||||||||1 A or 5A configurable sensitive ground current input
S1 |||||||||1 A sensitive ground current input
S5 |||||||||5 A sensitive ground current input
Power SupplyL ||||||||24 to 48 V DC
H|||||||| 125 to 250 V DC/120 to 230 V AC
Input/Output
c
c. Input/Output option A is only available with the non-drawout Case Design N
Case DesignD |Protection Relay with drawout design
N| Protection Relay with non-drawout design
X| Protection Relay (drawout design) with no chassis
Harsh EnvironmentNNone
HHarsh Environment Conformal Coating
Figure 1-3: Order Codes
1–6350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 1: INTRODUCTION350 ORDER CODES
NOTE
897800AF-A1.fm
AFC **
AF System ComponentE|Sensor Fiber Extension (black sensor fiber with two single
bulkhead connectors, used with loop sensors)
L|Loop Sensor with transparent sensor fiber
P|Point Sensor with black sensor fiber
Sensor Fiber LengthXXSensor fiber length:
01 to 35 meters for Point Sensors and Extensions
01 to 70 meters for Loop Sensors
NOTE:
FASTPATH:
FASTPATH:
Features related to each order number are subject to change without notice.
Arc Flash System
The 350 protection relay with Input/Output option “A” supports up to 4 Arc Flash sensors,
which are ordered separately so that the connected sensor fiber lengths can be
customized.
The total sensor fiber length connected to each loop sensor must not exceed 70 meters of
single sensor fiber. Black sensor fiber is duplex, and must be doubled in calculations.
For example, a loop sensor with a 25 meter transparent sensor fiber plus a sensor fiber
extension of 10 meters would have a total of 2 x 10m + 25m = 45m of single sensor fiber.
The total sensor fiber length connected to each point sensor must not exceed 35 meters of
black (duplex) cable.
NOTE:
NOTE:
FASTPATH:
Generally each loop sensor is used with a sensor fiber extension, in order to minimize
exposure to ambient light when running the sensor fiber between cabinets. A duplex
sensor fiber extension connects the relay to the loop sensor, and can be gently pulled
apart to connect to the loop sensor connectors if they are not adjacent. Consider your
installation needs carefully when ordering sensor and extension lengths.
Empty chassis
The 350 protection relay chassis used with a drawout relay is available separately, for use
as a partial replacement or in test environments. Many features are supported by the
cards and ports within the chassis, as is reflected in the chassis order code.
The chassis order code and drawout relay order code must match exactly.
A drawout relay cannot be used in a chassis with different order code options.
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL1–7
350 ORDER CODESCHAPTER 1: INTRODUCTION
NOTE
350 CH ******
Phase CurrentsP1 |||||1 A 3-phase current inputs
P5 |||||5 A 3-phase current inputs
Ground Currents
a
a. Ground current options G1/G5 must match the corresponding P1/P5 Phase currents
G1 ||||1 A ground current input
G5 ||||5 A ground current input
S1 ||||1 A sensitive ground current input
S5 ||||5 A sensitive ground current input
Other OptionsN|||No selection
D| | | Neutral and Ground Directional Overcurrent Protection: 67N(1), 67G/SG(1), 60CTS
M| | | Voltage, Power, and Energy Metering, 60CTS
R
||||||Phase, Neutral, and Ground Directional Overcurrent Protection: 67P(1), 67N(1),
67G/SG(1), 32N(2), VTFF + Voltage, Power, and Energy Metering, 60CTS
1–8350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Other accessories
•1819-0103 350 Retrofit Kit for 735
•1819-0102 350 Retrofit Kit for IAC Relay
•1819-0101 350 Retrofit Kit for MDP Relay
•1819-0100 350 Retrofit Kit for S1/S2 Cut-Out
•18L0-0075 3 Series Depth reducing collar - 1.375”
•18L0-0076 3 Series Depth reducing collar - 3.00”
•18L0-0080 3 Series IP20 Kit
•3S-NDO-STCONKIT 3 Series NDO straight terminal block kit
•0804-0458 USB A-B configuration cable - 6’
Refer to the 3 Series Retrofit Instruction Manual for the retrofit of Multilin MI, MII, MLJ, and
TOV relays.
CHAPTER 1: INTRODUCTIONSPECIFICATIONS
NOTE
NOTE
Specifications
NOTE:
NOTE:
Specifications are subject to change without notice.
To obtain the total element operating time, i.e. from the presence of a trip condition to
initiation of a trip, add 8 ms output relay time to the operate times listed below, with the
exception of Arc Flash SSR loads.
Password security
PASSWORD SECURITY
Master Password: ...............................................8 to 10 alpha-numeric characters
Settings Password:.............................................3 to 10 alpha-numeric characters for local and remote
access
Control Password:...............................................3 to 10 alpha-numeric characters for local and remote
access
Protection
BROKEN CONDUCTOR (I1/I2 OR 46BC)
Minimum operating positive current:........ 0.05 to 1.00 x CT in steps of 0.01 x CT
Maximum operating positive current:....... 0.05 to 5.00 x CT in steps of 0.01 x CT
Pickup level:........................................................... 20.0% to 100.0% in steps of 0.1%
Dropout level:........................................................ 97% to 98% of the pickup level
Pickup time delay: .............................................. 0.000 to 65.535 s in steps of 0.001 s
Timer accuracy: .................................................. ± 3% of delay setting or ± ¾ cycle (whichever is greater)
from pickup to operate
Operate time:........................................................ <30 ms at 60 Hz
WATTMETRIC GROUND FAULT (32N)
Measured power:................................................ zero sequence
Number of elements: ........................................ 1
Characteristic angle: ......................................... 0º to 359º in steps of 1°
Pickup threshold:................................................. 0.001 to 1.200 pu in steps of 0.001 pu
Pickup level accuracy:...................................... ± 2% or ± 0.03 pu, whichever is greater
Hysteresis:.............................................................. 3% or 0.001 pu, whichever is greater
Pickup delay:......................................................... Definite T ime (0.00 to 600 .0 s in steps of 0.1 s), Inverse T ime,
or Flexcurve
Inverse time multiplier:..................................... 0.01 to 2.00 in steps of 0.01
Curve timing accuracy:.................................... ± 3.5% of operate time or ± ¼ cycle (whichever is greater)
from pickup to operate
Operate time:........................................................ <30 ms at 60 Hz
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL1–9
Operational Delay: ............................................. 20 to 30 ms
NOTE:
The selection of the “P” or “R” option from “350 OTHER OPTIONS” in the order code table,
will enable the Phase directional element. The polarizing voltage used for this element is
the line voltage.
GROUND DIRECTIONAL (67G)
Directionality: ....................................................... Co-existing forward and reverse
Operating:............................................................... Ground Current (Ig)
Operational Delay: ............................................. 20 to 30 ms
NOTE:
The selection of the “D” option from “350 OTHER OPTIONS” in the Order Code table, will
enable the Ground Directional element with voltage polarizing 3V
measured from the
0
Vaux voltage input.
NOTE:
The selection of the “P”, “R”, or “W” option from “350 OTHER OPTIONS” in the order code
table, will enable the Ground directional element. The polarizing voltage used for this
element is the computed V0 from the measured phase voltage inputs.
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL1–11
SPECIFICATIONSCHAPTER 1: INTRODUCTION
NOTE
NEUTRAL DIRECTIONAL (67N)
Directionality: ....................................................... Forward and reverse
Operational Delay:............................................. 20 to 30 ms
NOTE:
The selection of the “D” option from “350 OTHER OPTIONS” in the Order Code table, will
enable the Neutral Directional element with voltage polarizing 3V
calculated using phase voltages (VTs must be
0
connected in “Wye”)
-3V
measured from Vaux input (3V0 provided by an
0
external broken delta connection).
G
measured from the
0
Vaux voltage input.
The selection of “P”, “R”, or “W” option from “350 OTHER OPTIONS” in the Order Code table,
will enable the Neutral Directional elements with voltage polarizing V
computed from the
0
measured phase voltage inputs.
The ground polarizing current, IG, is available for selection in both cases.
THERMAL OVERLOAD (49)
Current:.................................................................... RMS current - max (Ia, Ib, Ic)
Pickup Accuracy: ................................................ per current inputs
Timing Accuracy:................................................ See graph below
Figure 1-5:
The graph shows the trip time error with respect to the ratio of cable load and thermal
model pickup setting. With a smaller I/Ipkp ratio, the time error tends to be higher, as
accumulated through the logarithmic formula, the measurement error, and the time of
measurement. For higher I/Ipkp ratios, the time to trip is substantially more accurate. Each
point on the graph represents a trip time error, with the I/Ipkp ratio kept constant during
the test.
Bend Radius: ......................................................... 35 mm minimum
Product Type:........................................................ Class 1 Laser product
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL1–13
SPECIFICATIONSCHAPTER 1: INTRODUCTION
NOTE
Metering
PARA METERACCURACY
3-Phase Real Power (MW or kW)±1% of full scale0.1 MW± 100000.0 kW
3-Phase Reactive Power (Mvar or kvar) ±1% of full scale0.1 Mvar± 100000.0 kvar
3-Phase Apparent Power (MVA or kVA) ±1% of full scale0.1 MVA± 100000.0 kVA
3-Phase Positive Watthour (MWh)±1% of full scale±0.001 MWh50000.0 MWh
3-Phase Negative Watthour (MWh)±1% of full scale±0.001 MWh50000.0 MWh
3-Phase Positive Varhour (Mvarh)±1% of full scale±0.001 Mvarh50000.0 Mvarh
3-Phase Negative Varhour (Mvarh)±1% of full scale±0.001 Mvarh50000.0 Mvarh
Power Factor±0.050.01-0.99 to 1.00
Frequency±0.05 Hz0.01 Hz40.00 to 70.00 Hz
NOTE:
Negative values (-) represent lead and positive values (+) represent lag.
(full scale for
CT Input is 3 x CT)
RESOLUTIONRANGE
CURRENTS
Parameters:...........................................................Phase A, Phase B, Phase C, Neutral, Ground, Sensitive
Ground, Positive Sequence, Negative Sequence, Zero
Sequence, and 2nd Harmonic
Accuracy: ...............................................................See the Inputs section in Chapter 1: Specifications
VOLTAGES
Parameters:...........................................................Wye VTs: AN, BN, CN, Negative Sequence, Zero Sequence
and Auxiliary
Delta VTs: AB, BC, CA, Negative Sequence, Zero Sequence
and Auxiliary
Accuracy: ...............................................................See the Inputs section in Chapter 1: Specifications
Data capture
TRANSIENT RECORDER
Buffer size: .............................................................3 s
No. of buffers:.......................................................1, 3, 6
No. of channels:................................................... 14
Sampling rate:......................................................4, 8, 16, or 32 samples per cycle
Data storage:........................................................ RAM - battery backed-up
FAULT RECORDER
Number of records:............................................ 1
Content:................................................................... Date and Time, first cause of fault, phases,
Contact Input
Virtual Input
Logic Element
Element Pickup/Trip/Dropout/Alarm
Contact input state
Contact output state
Virtual input state
Logic element state
Currents: Ia, Ib, Ib, Ig/Isg, In - magnitudes and angles
Voltages: Van, Vbn, Vcn, Vab, Vbc, Vca, Vaux - magnitudes
and angles
System frequency
1–14350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 1: INTRODUCTIONSPECIFICATIONS
EVENT RECORDER
Number of events:..............................................256
Header: ....................................................................relay name, order code, firmware revision
Content:...................................................................event number, date of event, cause of event,per-phase
current, ground current, sensitive ground current, neutral
current, per-phase voltage (VTs connected in “Wye”), or
phase-phase voltages (VTs connected in “Delta”), system
frequency, power, power factor, thermal capacity
Data Storage:........................................................Retained for 3 days
CLOCK
Setup:........................................................................Date and time
Daylight Saving Time
IRIG-B:.......................................................................Auto-detect (DC shift or Amplitude Modulated)
Amplitude modulated: 1 to 10 V pk-pk
DC shift: 1 to 10 V DC
Input impedance: 40 kOhm ± 10%
Accuracy with IRIG-B:....................................... ± 1 ms
Accuracy without IRIG-B:................................± 1 min / month
Control
LOGIC ELEMENTS
Number of logic elements: .............................16
Trigger source inputs per element: ............2 to 8
Block inputs per element: ...............................2 to 4