GAZ lomain KGL P Series, lomain KGM P Series Installation, Operation And Maintenance Instructions

Battery Installation,
Operation and
Maintenance Instructions
NEXT GENERATION OF BATTERIES
Visit us at www.enersys.com
1. Receiving the battery
Cells must not be stored in their packaging, therefore, unpack the battery immediately upon receipt. Do not tilt the package or turn it upside down. The battery cells are equipped with a blue plastic transport plug.
battery cells will be delivered filled and charged. The battery is ready for installation. Replace the transport plug with the red vent cap included in the accessories just before use (see section 7).
The battery must not be charged with the transport plug installed as this can damage the battery.
2. Storage
The rooms provided for storing the batteries must be clean, dry, cool (+10°C to +30°C) and well ventilated. Cells must not be stored in the transport packaging and must not be exposed to direct sunlight or UV-radiation.
If the cells are delivered in plywood boxes, open the boxes before storage and remove the packing material on the top of the cells. If the cells are delivered on pallets, remove the packing material on the top of the cells.
Filled
cells can be stored up to 12 months from the day of
delivery.
Storage of filled cells at a temperature above +30°C will result in a loss of capacity of approximately 5% per 10 degrees per year. It is very important that the cells are sealed with the plastic transport plugs tightly in place. This is to be checked after receiving the goods. In case of electrolyte loss during transport, refill the cell up to the “MAX” mark with genuine electrolyte before storage.
3. Installation
The installation should be carried out in accordance with the requirements of IEC 62485-2:2010, Part 2 “Safety Requirements
for secondary batteries and battery installations – Part 2: Stationary batteries” . For non-stationary installations, specific standards may
also apply.
3.1 Location
Install the battery in a dry and clean room. Avoid exposure to direct sunlight and heat. The battery will give the optimal performance and maximum service life if the ambient temperature range is between +10°C and +30°C.
3.2 Ventilation
During the last phase of charging, battery gases are released (a mixture of oxygen and hydrogen). Ventilation is necessary, even if the generation of gas is very low during float charging.
Compliance with local regulations as to ventilation may be necessary for certain applications. If there are no special regulations, standard IEC 62485-2:2010, Part 2 must be met.
3.3 Setting up
Always follow the assembly drawings, circuit diagrams and other separate instructions. In the case of parallel string connection only use battery cells of the same capacity, design and age up to a maximum of two parallel strings. For parallel connection of more than two strings, please contact the manufacturer for technical approval. Use nickel-plated cable lugs for cable connections.
The transport plugs must be replaced with the red vent caps included in the accessories.
Tighten the terminal screws with corresponding tightening torque as per table 1.
It is recommended to use a calibrated torque wrench.
Table 1: Torque loading for terminal screws:
2
Warning!
The gases emitted during charging are explosive. The electrolyte (potassium hydroxide, KOH) is highly corrosive. Exposed metal parts of the battery always conduct a voltage and are electrically active parts. Precautions in accordance with IEC 62485-2:2010 must be observed.
Shield eyes Read instructions
Shield eyes Read instructions
Contains lead
Clean all acid splash in eyes or on skin with plenty of clean water. Then seek medical help. Acid on clothing is to be washed with water
Warning: Risk of fire, explosion, or burns. Do not disassemble, heat above 60ºC, or incinerate. Avoid any short circuit. Metallic parts under voltage on the battery, do not place tools or items on top of the battery
Care for your safety
No smoking, no naked flames, no sparks
Shield eyes Read instructions
Electrical hazard Danger Re-cycle scrap batteries.
Contains lead
Electrolyte is corrosive
Clean all acid splash in eyes or on skin with plenty of clean water. Then seek medical help. Acid on clothing is to be washed with water
Warning: Risk of fire, explosion, or burns. Do not disassemble, heat above 60ºC, or incinerate. Avoid any short circuit. Metallic parts under voltage on the battery, do not place tools or items on top of the battery
Shield eyes Read instructions
Contains lead
Contains lead
Warning: Risk of fire, explosion, or burns. Do not disassemble, heat above 60ºC, or incinerate. Avoid any short circuit. Metallic parts under voltage on the battery, do not place tools or items
Care for your safety
No smoking, no naked flames, no sparks
Shield eyes Read instructions
Observe the instructions for use and place them visibly close to the battery! Work only on batteries after receiving instruction from qualified personnel!
When working on batteries wear safety glasses and protective clothing. All metallic personal objects, such as rings, watches, bracelets etc. shall be removed before starting work on the battery! Only use insulated tools! Comply strictly with the accident prevention regulations and your national Health and Safety standards as well as IEC 62485-1:2010
Electrolyte is harmful to skin and eyes. Therefore, after an accidental contact with the electrolyte flood the eyes immediately with large quantities of clean water for an extended period of time of at least 15 minutes. In all cases, consult a doctor immediately! Clothing contaminated with electrolyte should be washed in water immediately!
Warning: Risk of fire, explosion, or burns! Avoid any short circuit! Metallic parts of the battery are always under voltage on the battery, do not place tools or items on top of the battery!
Electrolyte is highly corrosive!
Cells are heavy! Make sure they are safely installed! Only use suitable transport equipment!
No smoking! Do not allow naked flames, embers or sparks near the battery due to the risk of explosion or fire!
The Installation, Operation and Maintenance Instructions must be strictly observed.
Non-compliance with the Installation, Operation and Maintenance Instructions, use of nongenuine spares and the usage of other than by EnerSys/GAZ specified parts, use of additives to the electrolyte and unauthorised tampering will invalidate any entitlement to warranty.
Used batteries with this symbol are recyclable products and have to be put into a recycling system. Used batteries must be disposed of as special waste in accordance with all standards.
WARNING!
Never use sulphuric acid or
acidic water.
Acid will damage the battery!
Male terminal Female terminal
M10 : 8 Nm
Connectors and terminals should be protected by a thin layer coating of anti-corrosion grease.
M8 : 20-25 Nm
M10 : 25-30 Nm
Ni-Cd
Cd
3
3.4 Electrolyte
The electrolyte for
NiCd batteries consists of a diluted potassium hydroxide (KOH) solution (specific gravity 1.20 kg/litre +/-0.01 kg/litre) with a lithium hydroxide component, in accordance with IEC 60993:1989. The potassium hydroxide solution is prepared in accordance with factory regulations. The specific gravity of the electrolyte does not indicate the state of charge of the battery. The specific gravity changes very little during charging and discharging, and has limited relationship to the temperature.
When checking the electrolyte levels, a variation in level between cells is not unusual and is due to the different quantity of gas held in the separators of each cell. Before the battery is put into service for the first time, check that the electrolyte level is not lower than 10mm below the “MAX” mark. There is usually no need to adjust it.
If the electrolyte level is lower than the “MIN” level during service, the battery should not be disconnected from the charger for a time longer than 12 hours.
If visual inspection is not possible, due to restricted view, use an electrolyte level testing tube to check the electrolyte level. For further instructions, please contact your GAZ/EnerSys representative.
GAZ
cells fulfil the requirements of IEC 62259:2003, para
7.9 for gas recombination efficiency.
3.5 Commissioning
The following instructions are valid for commissioning between +20°C and +30°C. For different conditions please contact GAZ. Charging with constant current is the preferred method.
If a site test is requested, it must be carried out in accordance with IEC 62259:2003.
According to IEC 62259:2003, 0.1 C
5
A is also expressed as 0.1 It A.
The reference test current It is expressed as:
Example:
0.1 It A means: 10 A for a 100 Ah battery or 50 A for a 500 Ah battery
3.5.1 Commissioning with contant current
cells stored up to 6 months:
A commissioning charge is normally not required and the cells are ready for service. If full performance is necessary immediately, a commissioning charge of 10 hours at 0.1 I
t
A is recommended. This procedure is carried out without the red low-pressure vents installed.
During the charge the temperature should be checked (see section 5).
cells stored for more than 6 months up to 1 year:
A commissioning charge of 15 hours at 0.1 I
t
A is necessary. This procedure is carried out without the red low-pressure vents installed.
During the charge the temperature should be checked (see section 5).
3.5.2 Commissioning with constant voltage
A commissioning charge is normally not required and the cells are ready for service. If the charger´s maximum voltage setting is too low to supply constant current charging, divide the battery into two parts and charge them individually.
cells stored up to 6 months:
A commissioning charge is normally not required and the cells are ready for service. If full performance is necessary immediately, a commissioning charge of 20 hours at 1.65 V/cell with current limited to 0.1 I
t
A is recommended.
This procedure is carried out without the red low-pressure vents installed.
During the charge the temperature should be checked (see section 5).
cells stored more than 6 months and up to 1 year:
A commissioning charge of 30 hours at 1.65 V/cell with current limited to 0.1 I
t
A is necessary.
This procedure is carried out without the red low-pressure vents installed.
During the charge the temperature should be checked (see section 5).
In the case of variable charging conditions, please consult your GAZ
®
representative.
3.5.3 Commissioning at ambient temperature above +30°C
Constant current charging is the only appropiate method for commissioning under such temperature conditions. During the whole process the electrolyte temperature must be monitored. The electrolyte temperature should never exceed +45°C. On exceeding +45°C the charging should be temporarily interrupted until the electrolyte temperature drops to +40°C.
Duration: 20 hours
Charging current: 0.1 I
t
A
In case of any interruption during the commissioning process, the total charge time must be extended by the duration of the downtime.
4. Charging in operation
Do not open or remove the low pressure vent caps during operation. The charging current limit should be 0.1 It A maximum in general.
In order to reduce the water consumption it is recommended, but not obligatory to adjust the charge voltage.
Operation in high temperature area (>35°C): Temperature coefficient of -2 mV/K
Operation in low temperature areas (<20°C): Temperature coefficient of -3mV/K
Recommended charging voltages for ambient temperatures from +20°C to +35°C are:
Two step charge
Float charge: 1.40-1.42 V/cell Boost charge: 1.45-1.46 V/cell Current limitation: 0.1 I
t
A
Single step charge
Charging voltage: 1.42-1.44 V/cell Current limitation: 0.1 I
t
A
5. Periodic maintenance
GAZ® cells require a minimum amount of maintenance. In order to maintain maximum performance, the following is recommend:
Standard service inspection:
In a regular twelve month period, carry out a check-up under normal float conditions. Depending on site location, local regulations, or special application requests, these check-ups can vary in frequency or period.
When performing the standard service inspections please be sure to carry out the following:
• General appearance and cleanliness of all the batteries and the battery room.
The battery must be kept clean using only water. Do not use a
wire brush or solvents/additives of any kind. Ventilation must fulfill the requirements of section 3.2.
Cn Ah
1h
I
t
A=
Loading...
+ 7 hidden pages