10900 S.W. AVERY STREET • TUALATIN, OREGON 97062 U.S.A.
AN ILLINOIS T OOL WORKS COMPANY
GAYLORD INDUSTRIES
10900 S.W . AVER Y STREET • TUALATIN, OREGON 97062 U.S.A.
1-800-547-9696 • 503-691-2010 • FAX: 503-692-6048
To Our Customers. . .
Congratulations on your recent purchase of a Gaylord
Ventilator. We are proud to be able to provide you
with a quality product that incorporates the latest
engineering concepts and is a result of over 50 years
of experience in the foodservice kitchen exhaust indus-
try .
If you have other Gaylord equipment such as a Gay-lord Heat Reclaim Unit, Quencher Fire Protection Sys-tem, or Roof Top Air Handling Equipment, etc., pleaserefer to the corresponding supplementary equipmentmanuals.
If you have further questions, please call us toll free at1-800-547-9696.We are more than happy to help.
Sincerely,
Edson C. GaylordPresident/CEO
COMMERCIAL KITCHEN EXHAUST SYSTEMS • FIRE PROTECTION • HEAT RECLAIM • UTILITY DISTRIBUTION • ROOF TOP UNITS • POLLUTION CONTROL
TABLE OF CONTENTS
"CG" SERIES PRINCIPLE OF OPERATION............................................................................................. 3-5
"RG" SERIES PRINCIPLE OF OPERATION............................................................................................. 6-8
INTERNAL FIRE PROTECTION ................................................................................................................ 7 -8
ALL RIGHT RESERVED.NO PART OF THIS BOOK MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY
FORM BY AN ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING MEANS OR OTHERWISE WITHOUT THE WRITTEN PERMISSION
OF GAYLORD INTERNATIONAL COPYRIGHT 2005.
The manufacturer reserves the right to modify the materials and specifications resulting from a continuing
program of product improvement or the availability of new materials.
Additional Copies $15.00
2
"CG" SERIES VENTILATOR PRINCIPLE OF OPERATION
GREASE EXTRACTION
The Gaylord “CG” Series Ventilator extracts up to 95% of the
grease, dust and lint particles from the airstream passing
through it, when operated and maintained in accordance with
design specifications.
The hot, contaminant-laden air rising from the cooking
surface merges with the higher velocity air that wipes the front
of the cooking equipment and extends, like an air blanket, from
the front edge of the cooking equipment to the air inlet of the
ventilator. As the air moves through the ventilator at a high
speed, it is forced to make a series of turns around four baffles.
As the high velocity air turns around each baffle, the heavierthan-air particles of grease, dust and lint are thrown out of the
airstream by centrifugal force. The extracted grease, dust and
lint are collected in the interior of the ventilator, remaining out
of the airstream until removed daily by the wash cycle.
Baffle #1
This baffle, located at the air entrance of the ventilator, is of
airplane wing type construction, and in its normally open
position, acts as the primary extracting baffle. (Refer to Figure
1) This baffle is hinged at each end and, in case of fire, is
automatically closed by thermostatic action. There is a small
sloped grease collecting gutter on the back side of the damper
which drains off liquefied grease, preventing it from re-entrain-
ing into the airstream.
Baffle #2
This baffle is located on the interior back wall of the ventilator
and is a stainless steel pipe, equipped with brass spray
nozzles on 8" to 10" centers. (Refer to Figure 1) During the
wash cycle, hot detergent water is released through the
nozzles. If the ventilator’s automatic fire control system is
activated, fire smothering water spray is also released through
the spray nozzles.
Baffle #3
This baffle is located on the back of the inspection doors. This
baffle is also a grease collecting gutter, collecting grease, dust
and lint extracted by the ventilator - preventing the contaminants from dropping back into the high velocity airstream.
Baffle #4
This baffle is located on the interior back wall of the ventilator
and is a stainless steel pipe equipped with brass spray
nozzles on 8" to 10" centers. Baffle #4 is inter-connected with
baffle #2, and performs washing and fire protection functions
simultaneously with baffle #2.
NOTE: Some ventilators may be equipped with optional“Custom Air” baffles (shown dotted) which reduces theexhaust volume where the baffle occurs.
NOTE: Some ventilators may be equipped with optionalcontinuous cold water mist. Refer to Page 25 for details.
FIG. 1
GREASE EXTRACTION
3
"CG" SERIES VENTILATOR PRINCIPLE OF OPERATION
WASH CYCLE
The wash cycle is activated each time the exhaust fan is shut
off by pushing the “Start Wash” button on the Command
Center or, if equipped with optional time clock (“TC” Series), as
programmed on the clock. The “Wash On” light is illuminated
each time the wash cycle comes on, and hot, detergent
injected water is released into the interior of the ventilator for
the time set on the wash timer.
This hot detergent water washes the day’s grease, dust and
lint accumulation from the interior of the ventilator flushing it
down to the main gutter which slopes to a pre-flushed drain
which leads to the building drain system. Spray nozzles are
located on 8" to 10" centers on the two wash pipes (BAFFLES)
mounted on the interior back wall of the ventilator. (Refer to
Figure 3) At the end of the wash cycle, the water is
automatically shut off, and the interior of the ventilator is clean
- ready for the next day’s operations.
There are three standard wash cycle times that are set
depending upon the type of cooking equipment being used.
COMMAND CENTER
MODEL C-5000
SERIES
The settings are 3 minutes for light-duty equipment, 5 minutes
for medium-duty equipment, and 9 minutes for heavy-duty
equipment. However, adequate cleaning is dependent upon
water pressure, water temperature, daily grease accumula-
tion, the length of the wash cycle, frequency of wash cycle and
the type of detergent being used. It may be necessary to
increase the wash time to the next higher setting to achieve
proper cleaning.
SPRAY NOZZLES
PRE-FLUSH LINE
HOT DETERGENTWATER SPRAY
MAIN GUTTERDRAIN LINE
FIG. 2
VENTILATOR CONTROL CABINET
MODEL GPC-5000 SERIES
FULL LENGTH
HINGED INSPECTION
DOORS
FIG. 3
WASH CYCLE
4
"CG" SERIES VENTILATOR PRINCIPLE OF OPERATION
FIRE QUENCHINGWATER SPRAY
WATER BARRIERFIRE DAMPER
BAFFLE IN CLOSEDPOSITION
DRAIN LINE
DAMPER CONTROL SWITCH
IS ACTIVATED CLOSING
FIRE DAMPER BAFFLE
AND SHUTTING OFF
EXHAUST FAN
RESET HANDLE
SURFACE FIRE
PROTECTION NOZZLE
(OPTIONAL)
350°F THERMOSTAT
INTERNAL FIRE MODE
Automatic internal fire protection is accomplished by the
action of the thermostats, which are located at the point where
the ductwork joins the ventilator. When the temperature of the
conveying airstream, which must pass over the thermostats,
reaches 350°F (177°C), the system is activated, and the
following occurs:
1. The hinged, grease-extracting fire damper baffle at the air
inlet of the ventilator closes — stopping the combustionsupporting, natural draft through the ventilator. (Refer to
Figure 6)
2. The exhaust fan serving the ventilator is shut off, stopping
the combustion-supporting, mechanically induced draft.
The supply fan is also shut off.
3. Fire-smothering water spray is released into the interior of
the ventilator through the cleaning system.
4. The “Fire” light on the Command Center illuminates.
Water will run until the thermostat cools below 350°F (177°C),
and then continue for a 5 minute cool down cycle. The water
may be shut off prior to the end of the 5 minute cool down cycle
by pushing the “Cancel” button located inside the electrical
compartment of the control cabinet. After the water has shut
off, the dampers can be reset by pushing the reset handle on
the damper control switch (Refer to Figure 5), and the exhaust
fan(s) re-started by pushing the “Start Fan” button on the
Command Center.
EXTERNAL FIRE MODE
A break glass fire switch is optional (see Figure 4) and if
provided, would normally be located at the exit of the kitchen.
Pulling the fire switch shuts off the supply fan and starts the
exhaust fan if it was off, releases fire smothering water spray
into the interior of the ventilator and the “Fire” light on the
Command Center flashes. During this time, the fire damper
remains open, and the exhaust fan remains on to help remove
smoke, heat, etc. If the fire intensified and the thermostat
reached 350°F, the fire damper would then close and theexhaust fan would shut off.
To resume normal operations, open the fire switch and flip thetoggle switch to the position marked “normal”. Replace theglass rod and close the cover.
FIG. 4
BREAK GLASS FIRE SWITCH
C-1357A SERIES
TESTING INTERNAL FIRE MODE
The internal fire protection system may be tested periodically
by pushing the “Fire Test Switch” which is located inside the
electrical compartment of the control cabinet. Pushing this
switch duplicates thermostatic action.
CAUTION: Before
pushing the “Fire Test Switch”, check to see if the internal
fire protection system is tied to the building alarm system.
TO RESUME NORMAL OPERATION
1. To discontinue the 5 minute cool down cycle at any point
during the cycle, push the “Cancel” button located inside
the electrical compartment.
2.Reset all damper control switches.
3.Push the “Start Fan” button on the Command Center.
SURFACE FIRE PROTECTION
The Gaylord Ventilator may be equipped with surface fire
protection either dry or wet chemical, or the Gaylord Quencher
System. In the event of a fire, the surface fire protection
system would normally be activated and discharged prior to
the ventilator’s internal fire protection. These systems may beintertied with the ventilator control cabinet to activate theExternal Fire Mode. If the fire is unusually severe or the surfacefire protection system malfunctions, the ventilator’s internalfire protection system would activate, thus providing a secondlevel of defense.
FIG. 5
DAMPER CONTROL SWITCH
C-61 SERIES
5
FIG. 6
FIRE CYCLE
CAUTION:
In case of severe fire and the thermostats located in the duct collar are
activated, and as a precautionary
measure, it is recommended that
the thermostats be replaced.
"RG" SERIES VENTILATOR PRINCIPLE OF OPERATION
GREASE EXTRACTION
The Gaylord Royal “RG” Series Ventilator extracts up to 95%
of the grease, dust and lint particles from the airstream passing
through it, when operated and maintained in accordance with
design specifications.
The hot, contaminant-laden air rising from the cooking surface
merges with the higher velocity air that wipes the front of the
cooking equipment and extends, like an air blanket, from the
front edge of the cooking equipment to the air inlet of the
ventilator. As the air moves through the ventilator at a high
speed, it is forced to make a series of turns around three
baffles. As the high velocity air turns around each baffle, the
heavier-than-air particles of grease, dust and lint are thrown out
of the airstream by centrifugal force. The extracted grease,
dust and lint are collected in the interior of the ventilator,
remaining out of the airstream until removed daily by the wash
cycle.
Baffle #1
This baffle is located at the air inlet of the ventilator and is
formed as part of the inspection door. There is a small grease
collecting gutter on the back side of the baffle which drains off
liquefied grease, preventing it from re-entraining into the
airstream.
Baffle #2
This baffle is on the interior back wall of the ventilator and
includes a square stainless steel pipe, equipped with brass
spray nozzles on 8" to 10" centers. During the wash cycle, hot
detergent water is released through the nozzles. If the
ventilator’s automatic fire control system is activated, fire
smothering water spray is also released through the spray
nozzles.
Baffle #3
This baffle is located on the back of the inspection door.
NOTE: Some ventilators may be equipped with optional
“Custom Air” baffles (shown dotted) which reduces the exhaust volume where the baffles occur.
NOTE: Some ventilators may be equipped with optionalcontinuous cold water mist. Refer to Page 25 for details.
FIG. 7
GREASE EXTRACTION
6
"RG" SERIES VENTILATOR PRINCIPLE OF OPERATION
WASH CYCLE
The wash cycle is activated each time the exhaust fan is shut
off by pushing the “Start Wash” button on the Command
Center or, if equipped with optional time clock (“TC” Series), as
programmed on the clock. The “Wash On” light is illuminated
each time the wash cycle comes on, and hot, detergent
injected water is released into the interior of the ventilator for
the time set on the wash timer.
This hot detergent water washes the day’s grease, dust and
lint accumulation from the interior of the ventilator flushing it
down to the main gutter which slopes to the pre-flushed drain
which leads to the building drain system. Spray nozzles are
located on 8" to 10" centers on the wash pipe mounted on the
interior back wall of the ventilator. (Refer to Figure 9) At the
end of the wash cycle, the water is automatically shut off, and
the interior of the ventilator is clean - ready for the next day’s
operations.
There are three standard wash cycle times that are set
depending upon the type of cooking equipment being used.
On fuse link activated ventilators, water will continue to run
until it is shut off by the hand valve located inside the
ventilator control cabinet. The fire damper must then be
reset by replacing the fuse links. IMPORTANT NOTE: All
replacement fuse links must be UL Listed and rated for 280°F
(138°C).
The hand valve may then be reopened and the exhaust fan
may then be re-started by pushing the “Start Fan” button on
the Command Center.
FIRE DAMPER
The settings are 3 minutes for light-duty equipment, 5 minutes
for medium-duty equipment, and 9 minutes for heavy-duty
equipment. However, adequate cleaning is dependent upon
water pressure, water temperature, daily grease accumula-
tion, the length of the wash cycle, frequency of wash cycle and
the type of detergent being used. It may be necessary to
increase the wash time to the next higher setting to achieve
proper cleaning.
COMMAND CENTER
MODEL C-5000SERIES
FIG. 8
VENTILATOR CONTROL CABINET
MODEL GPC-5000 SERIES
INTERNAL FIRE MODE
The ventilator is equipped with a spring loaded fire damper
located at the duct collar. The internal fire protection system
is automatically activated whenever the fuse link or optional
electrical thermostat reaches 280°F (138°C). Upon activation the following occurs:
HOT DETERGENTWATER SPRAY
SPRAYNOZZLES
DRAIN LINE
HINGED INSPECTION
DOOR
FIG. 9
AUTOMATIC WASH CYCLE
1. The fire damper closes — stopping the combustionsupporting, natural draft through the ventilator. (Refer
to Figure 13)
2. The exhaust fan serving the ventilator is shut off,
stopping the combustion-supporting, mechanically induced draft. The supply fan is also shut off.
3. Fire-smothering water spray is released into the interior
of the ventilator through the cleaning system.
4. The “Fire” light on the Command Center illuminates.
FIG. 10
DAMPER CONTROL SWITCH
MODEL C-61-GXB-RG
USED WITH FUSE LINK
ACTIVATED SYSTEMS
7
"RG" SERIES VENTILATOR PRINCIPLE OF OPERATION
INTERNAL FIRE MODE (CONTINUED)
On thermostatically activated systems, the water will run until
the thermostat cools below 280°F (138°C), and then continue
for a 5 minute cool down cycle. The water may be shut off prior
to the end of the 5 minute cool down cycle by pushing the
“Cancel” button located inside the electrical compartment of
the control cabinet. After the water has shut off, the dampers
can be reset by pulling the reset handle on the damper control
switch (Refer to Figure 11), and the exhaust fan(s) restarted by
pushing the “Start Fan” button on the Command Center.
FIG. 11
DAMPER CONTROL SWITCH
MODEL C-61-GXSH-RG
USED WITH THERMOSTATICALLY
ACTIVATED SYSTEMS
EXTERNAL FIRE MODE
A break glass type fire switch is optional and if provided, would
normally be located at the exit of the kitchen. Pulling the fire
switch shuts off supply fan and starts the exhaust fanif it was
off, releases fire smothering water spray into the interior of the
ventilator, and the “Fire” light on the Command Center
flashes. During this time, the fire damper remains open, and
the exhaust fan remains on to help remove smoke, heat, etc.If the fire intensified and the fuse link or thermostat reach280°F(138°C), the fire damper would then close and theexhaust fan would shut off.
To resume normal operations, open the fire switch and flip the
toggle switch to the position marked “normal”. (Refer to Figure
12) Replace the glass rod and close the cover.
TESTING INTERNAL FIRE MODE
The internal fire protection system may be tested periodically
by pushing the “Fire Test Switch” which is located inside the
electrical compartment of the control cabinet. Pushing this
switch will cause the following:
Thermostatically ActivatedFuse Link Activated
1. Water turns on and1. Water turns on and
will run for 5 minutes.will run for 5 minutes.
2. Exhaust fan shuts off.2.Exhaust fan shuts off.
3. Damper closes.3.Fire light illuminates.
4.Fire light illuminates.
CAUTION: Before pushing the “Fire Test Switch”, check to
see if the internal fire protection system is tied to the building
alarm system.
TO RESUME NORMAL OPERATION
1.To discontinue the 5 minute cool down cycle at any pointduring the cycle, push the “Cancel” button located insidethe electrical compartment.
2.Reset all damper control switches, if thermostaticallyoperated.
3.Push the “Start Fan” button on the Command Center.
SURFACE FIRE PROTECTION
The Gaylord Ventilator may be equipped with surface fire
protection either dry or wet chemical, or the Gaylord Quencher
System. In the event of a fire, the surface fire protection
system would normally be activated and discharged prior to
the ventilator’s internal fire protection. These systems may be
intertied with the ventilator control cabinet to activate the
External Fire Mode. If the fire is unusually severe or the surface
fire protection system malfunctions, the ventilator’s internal
fire protection system would activate, thus providing a second
level of defense.
FIRE DAMPER IN CLOSED POSITION
MELTED 280°F FUSE LINK
FIG. 12
BREAK GLASS FIRE SWITCH
C-1357A SERIES
FIREQUENCHING
WATER SPRAY
DRAIN LINE
8
FIG. 13
FIRE CYCLE
HINGED INSPECTION
DOOR
(OPTIONAL) SURFACE
FIRE PROTECTION
NOZZLE
DAILY OPERATION
DAILY OPERATION
All functions of the ventilator, such as starting the exhaust fan,
starting the wash cycle, etc., are controlled by the Command
Center located on the control cabinet. Refer to Pages 13
through 15 for detailed instructions on the operation of the
Command Center.
COMMAND CENTER
MODEL C-5000
SERIES
FIG. 14
VENTILATOR CONTROL CABINET
MODEL GPC-5000 SERIES
Starting the Exhaust Fan
To start the exhaust fan push the “Start Fan” button on the
Command Center. If the Command Center is equipped with a
time clock (“TC” Series control), it may be programmed to start
automatically at any desired time. (Refer to programming
instructions on Page 15 for automatic operations.) The “Fan
On” light will illuminate when the exhaust fan is running. It is
important to start the exhaust fan before turning on the cooking
equipment.
Stopping the Exhaust Fan andStarting the Wash Cycle
CAUTION: The cooking equipment must be shut off prior to
shutting off the exhaust fan. Failure to do this will causeexcessive heat buildup and could cause the surface fireprotection system to discharge.
1.To start the wash cycle push the “Start Wash” buttonon the Command Center. If the Command Center isequipped with a time clock (“TC” Series control), it may be
programmed to start automatically at any desired time.
Refer to programming instructions on Page 15 for auto-
matic operations. When the wash cycle is activated the“Wash On” light illuminates and the following occurs:
A. The exhaust fan shuts off.
However, adequate cleaning is dependent upon water
pressure, water temperature, daily grease accumulation, the length and frequency of the wash cycle, and
the type of detergent being used. Refer to wash timing
instructions on Page 14 for setting the length of the
wash cycle.
NOTE: Some control cabinets are equipped with a
low detergent switch. If so equipped, the “Wash On”light will flash if the detergent tank is empty or if the
detergent pump is malfunctioning and detergent is not
pumping.
2.After the wash cycle is completed, wipe the exposed front
surface of the baffle at the air inlet of the ventilator, as well
as other exposed exterior surfaces. (Refer to Figure 15)
3.The ventilator is now clean. The exhaust fan may be
restarted by pushing the “Start Fan” button on the
Command Center.
In very heavy cooking operations it may be necessary to wash
the ventilator(s) more than once a day. If equipped with a time
clock (Model C-5000-TC Series) the Command Center iscapable of being programmed to start the wash cycle severaltimes within a 24-hour period. Refer to programming instruc-tions on Page 15.
NOTE: For proper operation of the wash system:
Water Pressure40 psi min. - 80 psi max.
(2.8Kg/cm2 - 5.6Kg/cm2)
Water temperature140°F min. - 180°F max.
(60°C min. - 82°C max.)
NOTE: The ventilator wash system is designed to remove dailyaccumulations of grease within the extraction
chamber. If the ventilator is not washed a minimum of once
during a cooking day, a grease buildup could accumulate
which the wash system cannot remove. If this occurs, it is
recommended that the ventilator be put through several wash
cycles by pushing the “Start Wash” button on the Command
Center. If this does not remove the grease, it will be necessary
to remove the grease manually by using a scraping tool, such
as a putty knife, or retain the services of a commercial hood
cleaning service to steam clean or pressure wash the system.
WARNING: Some commercial hood cleaning services blow
a fire retardant chemical into hood and duct systems. Fire
retardant chemicals should never be applied to any portion of
The Gaylord Ventilator. If retardant is applied to the ventilator,
it must be removed.
B. Hot detergent water is automatically released into the
interior of the ventilator for the length of time set on the
wash timer. The length of the wash cycle may be set
for 3 different wash times, 3 minutes for light-duty
equipment, 5 minutes for medium-duty equipment,
and 9 minutes for heavy-duty equipment.
9
PREVENTIVE MAINTENANCE
PREVENTIVE MAINTENANCE
The following should be checked periodically in order to keep
The Gaylord Ventilator operating at design efficiency:
Weekly
1. The detergent tank should be checked at least weekly and
kept full with a recommended detergent. (Refer to Page 12)
Monthly
1. The detergent system fittings should be checked at least
monthly. This is an airtight system and fittings should be
tight. (For complete details refer to the Detergent Pump
section on Page 12.)
2. At least monthly, at the conclusion of a wash cycle, open
the inspection doors of the ventilator and check to ensure
that the interior has been cleaned of grease, dust, and lint.
(Refer to Figure 15) If overall cleaning appears to be
inadequate, refer to “Trouble-Shooting of the Wash Sys-
tem”, Page 19.
3. The main grease gutter of the ventilator should be checked
at least monthly to remove any foreign material such as
paper towels, order chits, etc.
Every Six Months
1. Exhaust fan(s) should be checked every six months for belt
tightness, belt alignment, and lubrication of necessary
moving parts.
NOTE: A blue lithium based grease is best suited for high
heat and speed bearing lubrication.
2. Check for proper velocity at air inlet slot. Refer to Pages 22
through 24 for method of checking velocity.
3. Test the "Internal Fire Mode" (electrically activated
dampers only) to check for proper damper closure. Refer
to page 5. Reset damper when test is complete.
4. Detergent tank and foot valve should be cleaned every six
months.
NOTE: Annual and semi-annual inspections are
recommended by the NFPA, Standard No. 96, Chapter 8.
Factory trained service agencies are certified by Gaylord
Industries, Inc. to perform these inspections. For the name
and phone number of your nearest agent call 1-800-547-9696.
INSPECTION AND CLEANING REQUIREMENTS
The 1998 edition of NFPA-96 (Standard for Ventilation Control
and Fire Protection of Commercial Cooking Operations)
require that hoods, ducts and exhaust fans be inspected by a
properly trained, qualified and certified company or person(s)
in accordance with the following table.
Upon inspection, if found to be contaminated with deposits
from grease-laden vapors, the entire exhaust system shall be
cleaned by a properly trained, qualified, and certified company or person(s) acceptable to the authority having jurisdic-tion in accordance.
When a vent cleaning service is used, a certificate showingdate of inspection or cleaning shall be maintained on thepremises. After cleaning is completed, the vent cleaning con-tractor shall place or display within the kitchen area a labelindicating the date cleaned and the name of the servicingcompany. It shall also indicate areas not cleaned.
The Gaylord Ventilator detergent pump is an integral part of the
wash-down system of The Gaylord Ventilator. The pump is
located within the control cabinet unless otherwise specified.
(Refer to schematic on Pages 26 through 29.)
OPERATION
The detergent pump is started when the wash cycle begins.
The pump draws detergent up from the detergent tank, pushing
it through the copper tubing and into the hot water line serving
the ventilator.
NOTE: Some control cabinets are equipped with a low
detergent switch. If so equipped, the “Wash On” light will
flash if the detergent tank is empty or if the detergent pump is
malfunctioning and detergent is not pumping.
Initial Operation
To prime and operate the pump for the first time, it is
recommended that water be used instead of detergent to
prevent detergent from spilling in case of leaks at the system’s
fittings.
Priming The Pump
The detergent pump is self-priming. Push the pump test
switch, located on the junction box of the motor, and hold down
until liquid climbs up the vinyl tubing and fills the pump head.
The pump will be operating properly when both upper and lower
poppet checks can be seen moving up and down slightly. If the
pump does not self-prime, an air lock may have developed
within the pump head and the following action should be taken:
1. Hold down pump test switch and loosen top cap slightly to
allow air to be pushed out. Repeat as necessary until liquid
climbs up tube and fills pump head.
2. If the pump still does not work properly, check the following:
A. Foot valve should be clean and immersed in the liquid.
B.Check all fittings to ensure an airtight system.C.Poppet checks within the foot valve, pump head and
brass check valve should be clean and operating freely.
D.Detergent lines should be free and clear.
DETERGENT FLOW
Detergent flow is initially factory set according to the pipe sizeof the control cabinet (refer to chart). Generally, the factorysetting will be sufficient to provide adequate cleaning of theventilator. However, adequate cleaning is dependent upon a
number of factors:
1. Temperature of hot water5.Frequency of wash
2. Water pressurecycle
3. Daily grease accumulation6.Type of detergent
4. Wash cycle time
PREVENTIVE MAINTENANCE
As with any piece of fine equipment, a reasonable amount of
care must be taken to keep it in good working order:
1. Caution should be taken not to spill detergent on the
exterior of the pump.
2. A periodic check should be made of all fittings
to guarantee their tightness.
NOTE: The detergent pump motor has sealed bearings and
will not require lubrication.
)lairepmI(
lortnoCtenibaC
eziSepiP
"2/11#2.36.91.21.615.35.229.4
"4/32#1.56.514.31.627.55.639.7
"13#0.68.719.36.925.64.141.9
"4/11
"2/11&
lortnoCtenibaC
eziSepiP
)mm(
511#590.582.55.8574.52.41566.59.91
022#051.164.38.31277.61.32970.173.23
523#771.625.87.51678.82.62522.157.63
23
04&
yrotcaF
maC
gnitteS
4#3.68.811.43.138.68.346.9
yrotcaF
maC
gnitteS
4#681.655.86.61629.87.72692.183.83
reP.zOta.niMISP04
retaW
erusserP
sretiL
.niMreP
ta
8.2mc/gk
setuniM3setuniM5setuniM9
.zO
.laG
reP
reP
yaD
.oM
)cirteM(
setuniM3setuniM5setuniM9
sretiL
sretiL
reP
reP
yaD
.oM
TRAHCNOITPMUSNOCTNEGRETED
HTGNELELCYCHSAW
.zO
.laG
.zO
reP
reP
yaD
.oM
TRAHCNOITPMUSNOCTNEGRETED
HTGNELELCYCHSAW
sretiL
sretiL
reP
reP
yaD
.oM
.laG
reP
reP
yaD
.oM
sretiL
sretiL
reP
reP
yaD
.oM
Depending upon these factors, it may be necessary to adjust
the detergent flow. Adjustment may be accomplished by
changing the cam to a different size. To change the cam:
1. Loosen Allen set screw on brass cam.
2. Remove cam and replace with next size as required.
3. Cam #1 minimum setting. Cam #4 maximum setting.
NOTE: Cams are available from Gaylord Industries or your
Gaylord Certified Service Agency.
FIG. 16
11
DETERGENT FOR THE WASH SYSTEM
FORMULA G-510 is the only cleaner recommended by Gaylord Industries for use in the washdown system of The Gaylord
Ventilator. FORMULA G-510 is a concentrated colloid cleaner
specially formulated to remove the daily accumulation of
grease inside The Gaylord Ventilator without damaging the
rubber and synthetic parts of the detergent pumping system.
FORMULA G-510 is biodegradable, safe for kitchen personnel, and has a variety of uses.
DILUTION OF FORMULA G-510 FOR
VENTILATOR CLEANING
Normal Cleaning
For ventilators covering cooking equipment such as broilers,
griddles, fryers, or any other heavy grease producing equipment, fill the detergent tank with full strength FORMULA
G-510.
Light-Duty Cleaning
For ventilators covering light grease producing equipment such
as ovens, kettles, steamers and ranges, fill the detergent tank
with a mixture of one part FORMULA G-510 to one part water.
Cleaning the Ventilator Exterior
Mix one part FORMULA G-510 to twenty parts water in hand
spray bottle. Spray on and wipe off. NOTE: Once a day, this
same solution should be used to clean the front of the fire
damper and main grease extracting baffle.
FOR OTHER CLEANING JOBS
The colloidal action of FORMULA G-510 makes it a cleaner
especially well-suited for use in kitchens. The colloids break
up dirt and grease into millions of tiny particles that constantly
repel each other. These particles cannot recombine or
redeposit on a surface and are, therefore, easily washed away.
FORMULA G-510 is biodegradable and contains no harsh
chemicals, yet offers outstanding performance on the tough-
est cleaning jobs.
Use a mixture of one part FORMULA G-510 to twenty parts
water for:
VINYL/PLASTIC/WALLS...Removes dirt, grease,food deposits and fingerprints.
REFRIGERATORS...Removes dirt, spilledmilk, blood, mildew and objectionable odors.
RESTROOMS...Add a disinfectant to clean allfixtures, walls, floors, etc.
Use a mixture of one part FORMULA G-510 to five parts water
for extremely heavy grease build-up, such as on the floor and
on equipment around deep-fryers. Spray on and rinse or wipe
off. For extremely soiled areas, gentle agitation, followed by
a soaking period, will result in more thorough cleaning.
DON’T be afraid to experiment with FORMULA G-510 because
it contains no phosphates, nitrates, enzymes, sulfates, sul-
fonates or silicates.
LIMITED WARRANTY
G-510 CHEMICAL DIVISION warrants that FORMULA G-510 will not cause cleansing agent damage to the rubber and synthetic parts of the injection
pump (“O” rings, diaphragms, washers, tubing, and
other such parts) used with The Gaylord Ventilator,
Heat Reclaim Unit, or Pollution Control Equipment.
G-510 CHEMICAL DIVISION’S obligation under this
warranty and any warranties implied by law shall be
limited to repairing or replacing, at its option, any of
said parts which
G-510 CHEMICAL DIVISION’S examination shall
disclose to its satisfaction to have been damaged by
the use of FORMULA G-510 for the life of the
detergent pumping system. This warranty shall not
cover damages caused by any other detergent. Theuse of any other detergent shall void this warranty.
All repairs and replacement parts under this war-ranty shall be F.O.B. G-510 CHEMICAL DIVISION’Sfactory. The owner shall pay the necessary freightand delivery charges; also removal and installationcosts. Any federal, state or local taxes are alsoextra. Requests for repairs or replacement partsshould be made to G-510 CHEMICAL DIVISION,P.O. Box 1149, Tualatin, Oregon 97062-1149.
This is the sole warranty with respect to FORMULAG-510. G-510 CHEMICAL DIVISION MAKES NOOTHER WARRANTY OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE
WHICH EXCEED THE AFORESAID OBLIGATION
ARE HEREBY DISCLAIMED AND EXCLUDED
FROM THIS AGREEMENT. G-510 CHEMICAL DIVISION SHALL NOT BE RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM A BREACH OF THIS WARRANTY.
IMPORTANT
If a cleansing agent other than FORMULA G-510 is used with
The Gaylord Ventilator injection pump, it is recommended that
a warranty similar to the above be obtained from the manufacturer of said product.
1.Push Start Fan before turning on cooking equipment.
2.At the end of the day, or whenever cooking is com-
pleted, push Start Wash. This will turn off the exhaust fan
and begin a timed wash cycle. NOTE: 24 hour kitchens
must push Start Wash at least once a day or as needed
for proper cleaning.
3.To set the length of time for the wash cycle, open this
cabinet door and set the toggle switches for either Light-
duty, Medium or Heavy-duty cooking equipment.
Extreme cooking loads may require more than one wash
cycle per day.
NOTE:If the Command Center is a S, TC or RSPC Series,
refer to additional operating instructions inside this panel.
COMMAND CENTER
C-5000-S-TC
MODEL
LOW DETERGENT
1. If Wash On light flashes detergent is low.
FIRE CONDITION
1. A flashing fire light indicates the control is in an External Fire
Mode - exhaust fan on, fire damper open, and water wash
nozzles on.
2. A solid fire light indicates the control is in an Internal FireMode - exhaust fan off, fire damper closed, and water wash
nozzles on.
GAYLORD INDUSTRIES, INC.
MODEL C-5000 SERIES COMMAND CENTER - INSTRUCTIONS
MODEL C-5000 SERIES COMMAND CENTER GENERAL
The Model C-5000 Series Command Center controls all of
the functions of the Gaylord Water-Wash Ventilator.
The C-5000 Series Command Center is available in four
basic models. They are:
ModelDescription of Operation
C-5000 ...................... Manual start fan and start wash
C-5000-TC ................ Programmable time clock opera-
tion of the start fan and start wash
functions
C-5000-S .................. Manual start fan and start wash
functions with sequence wash
feature
C-5000-TC-S ............ Programmable time clock opera-
tion of the start fan and start wash
functions with sequence wash
feature
The model number of your control is indicated on the
Command Center label. Refer to Figure 17.
STARTING THE FAN AND WASH CYCLE
The Model C-5000 and C-5000-S Command Centers start
fan and start wash functions are the same. To start the
exhaust fan push the “Start Fan” button and to start the
wash cycle push the “Start Wash” button. The exhaust fan
automatically shuts off when the “Start Wash” button is
pushed.
Models C-5000-TC and C-5000-TC-S include a time clock
which can be programmed to start the fan and wash cycle at
any desired time. (Refer to programming instructions on
Page 15.) However both of these Command Centers may
also be operated manually by pushing the “Start Fan” or
“Start Wash” buttons.
SETTING WASH CYCLE TIME FOR MODELS C-5000
AND C-5000-TC COMMAND CENTERS
To set the length of the wash cycle, open the electrical
compartment. At the bottom of the control chassis is a three
position toggle switch labeled Wash 1 (refer to Fig.17). Set
the toggle switch for either 3, 5 or 9 minutes for light, medium
or heavy duty equipment as required (refer to “Recommended Wash Time” chart on page 14 . Upon activation of
the wash cycle, the detergent injected hot water will wash the
interior of the extraction chamber for the length of time
selected and then shut off.
FAN ON FIRE WASH ON
START
FAN
WASH TIMES SWITCH POSITION
3 MIN. LIGHT-DUTY COOKING EQUIPMENT UP
5 MIN. MEDIUM-DUTY COOKING EQUIPMENTCENTER
9 MIN. HEAVY-DUTY COOKING EQUIPMENT DOWN
WASH 1 WASH 2 WASH 3 WASH 4 WASH 5 WASH
FORM NO. C5CB
IF LIGHT FLASHES DETERGENT
IS LOW
START
WASH
MFG. BY:
GAYLORD INDUSTRIES, INC.
P.O. BOX 1149TUALATIN, OR 97062
C-5000-S-TC
MODEL NO.______________VOLTAGE________________
120vac
CANCEL
SWITCH
FORM NO. C5CA
DELAY TIMES
1 MIN. SHORT
15 MIN. MEDIUM
30 MIN. LONG
DELAY
FIRE
TEST
SWITCH
FIG.17FIG.18
13
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.