Gaylord C-5000 Service Manual

THE
GAYLORD VENTILATOR
EFFECTIVE DA TE 4-05
TECHNICAL MANUAL
FOR THE “CG” & “RG” SERIES
WATER-WASH VENTILATORS
WITH
MODEL C-5000 COMMAND CENTER
GAYLORD INDUSTRIES
1-800-547-9696 • 503-691-2010 • FAX: 503-692-6048 • email: info@gaylordusa.com
AN ILLINOIS T OOL WORKS COMPANY
GAYLORD INDUSTRIES
10900 S.W . AVER Y STREET • TUALATIN, OREGON 97062 U.S.A.
1-800-547-9696 • 503-691-2010 • FAX: 503-692-6048
To Our Customers. . . Congratulations on your recent purchase of a Gaylord
Ventilator. We are proud to be able to provide you with a quality product that incorporates the latest engineering concepts and is a result of over 50 years of experience in the foodservice kitchen exhaust indus- try .
If you have other Gaylord equipment such as a Gay- lord Heat Reclaim Unit, Quencher Fire Protection Sys- tem, or Roof Top Air Handling Equipment, etc., please refer to the corresponding supplementary equipment manuals.
If you have further questions, please call us toll free at 1-800-547-9696. We are more than happy to help.
Sincerely,
Edson C. Gaylord President/CEO
COMMERCIAL KITCHEN EXHAUST SYSTEMS • FIRE PROTECTION • HEAT RECLAIM • UTILITY DISTRIBUTION • ROOF TOP UNITS • POLLUTION CONTROL
TABLE OF CONTENTS
"CG" SERIES PRINCIPLE OF OPERATION............................................................................................. 3-5
"RG" SERIES PRINCIPLE OF OPERATION............................................................................................. 6-8
INTERNAL FIRE PROTECTION ................................................................................................................ 7 -8
DAILY OPERATION .................................................................................................................................... 9
PREVENTIVE MAINTENANCE ................................................................................................................. 10
DETERGENT PUMP OPERATION ............................................................................................................ 1 1
DETERGENT FOR THE WASH SYSTEM ................................................................................................. 12
MODEL C-5000 SERIES COMMAND CENTER - INSTRUCTIONS.........................................................13-15
ENGINEERING DATA ...........................................................................................................................16-17
TROUBLE-SHOOTING:
EXHAUST..................................................................................................................................... 18
GREASE EXTRACTION ............................................................................................................... 18
EXHAUST FAN............................................................................................................................. 18
C-5000 COMMAND CENTER ....................................................................................................... 1 9
FIRE CYCLE ................................................................................................................................ 1 9
WASH SYSTEM .......................................................................................................................... 19
BACKFLOW PREVENTOR .......................................................................................................... 20
VACUUM BREAKER ................................................................................................................... 2 0
RP DEVICE.................................................................................................................................. 2 0
DRAINS........................................................................................................................................ 21
C-5000 STATUS LIGHT CHART.................................................................................................... 21
MEASURING INLET SLOT VELOCITY ..................................................................................................22-24
OPTIONAL CONTINUOUS COLD WATER MIST ....................................................................................... 25
PARTS LISTS:
MODEL GPC-5000 SERIES CONTROL CABINET........................................................................ 26
MODEL GPC-5000-RP SERIES CONTROL CABINET .................................................................. 2 7
MODEL GPC-5000-RP-S SERIES CONTROL CABINET .............................................................. 28
OPTIONAL CONTINUOUS COLD WATER MIST .......................................................................... 29
MODEL GPC-5000 SERIES CONTROL........................................................................................ 30
DAMPER CONTROL SWITCH...................................................................................................... 3 1
DETERGENT PUMP .................................................................................................................... 3 2
MISCELLANEOUS VENTILATOR PARTS .................................................................................... 33
WIRING DIAGRAMS .............................................................................................................................34-41
STANDARD VENTILATOR MODELS ........................................................................................................ 42
METRIC CONVERSION CHART................................................................................................................ 43
START-UP INSPECTION REPORT ........................................................................................................... 44
LIMITED WARRANTY .....................................................................................................Inside back cover `1
1
PATENTS
U.S. PATENT NUMBERS
3,247,776; 3,611,909; 3,785,124; 3,788,041;
4,072,143; 4,266,529; 4,281,635; 4,356,870
Other U.S. Patent applications pending.
U.S. Trademark Registration 800,820.
AUSTRALIA PATENT NUMBERS
481,510; 465,037
BRAZIL PATENT APPLICATION PENDING
CANADA PATENT NUMBERS
744,166; 759,710; 926,689; 940,761;
1,004,155; 1,086,126; 1,139,151; 968,559
Canada Patent application pending.
FRANCE PATENT NUMBERS
7,227,217; 7,332,718; 2,351,362
France Patent applications pending.
France Trademark: 740,296
GERMANY PATENT NUMBERS
2,346,196; 1,604,173; 3,152,501
German Patent application pending.
GREAT BRITAIN PATENT NUMBERS
1,350,857; 1,396,065; 1,558,537
JAPAN PATENT NUMBERS
650,269; 797,637; 917,077; 1,045,507;
726,884; 1,580,556
Japan Patent application pending.
Japan Trademark registration 874,453
NEW ZEALAND PATENT NUMBERS
162,024; 167,964
New Zealand Trademark #B 95557
SWEDEN TRADEMARK
120,229
SWITZERLAND PATENT NUMBERS
560,358
© Copyright 2005, Gaylord Industries
ALL RIGHT RESERVED. NO PART OF THIS BOOK MAY BE REPRO­DUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM BY AN ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORD­ING MEANS OR OTHERWISE WITHOUT THE WRITTEN PERMISSION OF GAYLORD INTERNATIONAL COPYRIGHT 2005.
The manufacturer reserves the right to modify the materials and specifications resulting from a continuing program of product improvement or the availability of new materials.
Additional Copies $15.00
2
"CG" SERIES VENTILATOR PRINCIPLE OF OPERATION
GREASE EXTRACTION
The Gaylord “CG” Series Ventilator extracts up to 95% of the grease, dust and lint particles from the airstream passing through it, when operated and maintained in accordance with design specifications.
The hot, contaminant-laden air rising from the cooking surface merges with the higher velocity air that wipes the front of the cooking equipment and extends, like an air blanket, from the front edge of the cooking equipment to the air inlet of the ventilator. As the air moves through the ventilator at a high speed, it is forced to make a series of turns around four baffles. As the high velocity air turns around each baffle, the heavier­than-air particles of grease, dust and lint are thrown out of the airstream by centrifugal force. The extracted grease, dust and lint are collected in the interior of the ventilator, remaining out of the airstream until removed daily by the wash cycle.
Baffle #1
This baffle, located at the air entrance of the ventilator, is of airplane wing type construction, and in its normally open position, acts as the primary extracting baffle. (Refer to Figure
1) This baffle is hinged at each end and, in case of fire, is automatically closed by thermostatic action. There is a small sloped grease collecting gutter on the back side of the damper which drains off liquefied grease, preventing it from re-entrain- ing into the airstream.
Baffle #2
This baffle is located on the interior back wall of the ventilator and is a stainless steel pipe, equipped with brass spray nozzles on 8" to 10" centers. (Refer to Figure 1) During the wash cycle, hot detergent water is released through the nozzles. If the ventilator’s automatic fire control system is activated, fire smothering water spray is also released through the spray nozzles.
Baffle #3
This baffle is located on the back of the inspection doors. This baffle is also a grease collecting gutter, collecting grease, dust and lint extracted by the ventilator - preventing the contami­nants from dropping back into the high velocity airstream.
Baffle #4
This baffle is located on the interior back wall of the ventilator and is a stainless steel pipe equipped with brass spray nozzles on 8" to 10" centers. Baffle #4 is inter-connected with baffle #2, and performs washing and fire protection functions simultaneously with baffle #2.
NOTE: Some ventilators may be equipped with optional “Custom Air” baffles (shown dotted) which reduces the exhaust volume where the baffle occurs.
NOTE: Some ventilators may be equipped with optional continuous cold water mist. Refer to Page 25 for details.
FIG. 1
GREASE EXTRACTION
3
"CG" SERIES VENTILATOR PRINCIPLE OF OPERATION
WASH CYCLE
The wash cycle is activated each time the exhaust fan is shut off by pushing the “Start Wash” button on the Command Center or, if equipped with optional time clock (“TC” Series), as programmed on the clock. The “Wash On” light is illuminated each time the wash cycle comes on, and hot, detergent injected water is released into the interior of the ventilator for the time set on the wash timer.
This hot detergent water washes the day’s grease, dust and lint accumulation from the interior of the ventilator flushing it down to the main gutter which slopes to a pre-flushed drain which leads to the building drain system. Spray nozzles are located on 8" to 10" centers on the two wash pipes (BAFFLES) mounted on the interior back wall of the ventilator. (Refer to Figure 3) At the end of the wash cycle, the water is automatically shut off, and the interior of the ventilator is clean
- ready for the next day’s operations. There are three standard wash cycle times that are set
depending upon the type of cooking equipment being used.
COMMAND CENTER MODEL C-5000 SERIES
The settings are 3 minutes for light-duty equipment, 5 minutes for medium-duty equipment, and 9 minutes for heavy-duty equipment. However, adequate cleaning is dependent upon water pressure, water temperature, daily grease accumula- tion, the length of the wash cycle, frequency of wash cycle and the type of detergent being used. It may be necessary to increase the wash time to the next higher setting to achieve proper cleaning.
SPRAY NOZZLES
PRE-FLUSH LINE
HOT DETERGENT WATER SPRAY
MAIN GUTTER DRAIN LINE
FIG. 2
VENTILATOR CONTROL CABINET
MODEL GPC-5000 SERIES
FULL LENGTH HINGED INSPECTION DOORS
FIG. 3
WASH CYCLE
4
"CG" SERIES VENTILATOR PRINCIPLE OF OPERATION
FIRE QUENCHING WATER SPRAY
WATER BARRIER FIRE DAMPER
BAFFLE IN CLOSED POSITION
DRAIN LINE
DAMPER CONTROL SWITCH IS ACTIVATED CLOSING FIRE DAMPER BAFFLE AND SHUTTING OFF EXHAUST FAN
RESET HANDLE SURFACE FIRE
PROTECTION NOZZLE (OPTIONAL)
350°F THERMOSTAT
INTERNAL FIRE MODE
Automatic internal fire protection is accomplished by the action of the thermostats, which are located at the point where the ductwork joins the ventilator. When the temperature of the conveying airstream, which must pass over the thermostats, reaches 350°F (177°C), the system is activated, and the following occurs:
1. The hinged, grease-extracting fire damper baffle at the air inlet of the ventilator closes — stopping the combustion­supporting, natural draft through the ventilator. (Refer to Figure 6)
2. The exhaust fan serving the ventilator is shut off, stopping the combustion-supporting, mechanically induced draft. The supply fan is also shut off.
3. Fire-smothering water spray is released into the interior of the ventilator through the cleaning system.
4. The “Fire” light on the Command Center illuminates.
Water will run until the thermostat cools below 350°F (177°C), and then continue for a 5 minute cool down cycle. The water may be shut off prior to the end of the 5 minute cool down cycle by pushing the “Cancel” button located inside the electrical compartment of the control cabinet. After the water has shut off, the dampers can be reset by pushing the reset handle on the damper control switch (Refer to Figure 5), and the exhaust fan(s) re-started by pushing the “Start Fan” button on the Command Center.
EXTERNAL FIRE MODE
A break glass fire switch is optional (see Figure 4) and if provided, would normally be located at the exit of the kitchen. Pulling the fire switch shuts off the supply fan and starts the exhaust fan if it was off, releases fire smothering water spray into the interior of the ventilator and the “Fire” light on the Command Center flashes. During this time, the fire damper remains open, and the exhaust fan remains on to help remove smoke, heat, etc. If the fire intensified and the thermostat reached 350°F, the fire damper would then close and the exhaust fan would shut off.
To resume normal operations, open the fire switch and flip the toggle switch to the position marked “normal”. Replace the glass rod and close the cover.
FIG. 4
BREAK GLASS FIRE SWITCH
C-1357A SERIES
TESTING INTERNAL FIRE MODE
The internal fire protection system may be tested periodically by pushing the “Fire Test Switch” which is located inside the electrical compartment of the control cabinet. Pushing this switch duplicates thermostatic action.
CAUTION: Before pushing the “Fire Test Switch”, check to see if the internal fire protection system is tied to the building alarm system.
TO RESUME NORMAL OPERATION
1. To discontinue the 5 minute cool down cycle at any point
during the cycle, push the “Cancel” button located inside the electrical compartment.
2. Reset all damper control switches.
3. Push the “Start Fan” button on the Command Center.
SURFACE FIRE PROTECTION
The Gaylord Ventilator may be equipped with surface fire protection either dry or wet chemical, or the Gaylord Quencher System. In the event of a fire, the surface fire protection system would normally be activated and discharged prior to the ventilator’s internal fire protection. These systems may be intertied with the ventilator control cabinet to activate the External Fire Mode. If the fire is unusually severe or the surface fire protection system malfunctions, the ventilator’s internal fire protection system would activate, thus providing a second level of defense.
FIG. 5
DAMPER CONTROL SWITCH
C-61 SERIES
5
FIG. 6
FIRE CYCLE
CAUTION:
In case of severe fire and the thermo­stats located in the duct collar are activated, and as a precautionary measure, it is recommended that the thermostats be replaced.
"RG" SERIES VENTILATOR PRINCIPLE OF OPERATION
GREASE EXTRACTION
The Gaylord Royal “RG” Series Ventilator extracts up to 95% of the grease, dust and lint particles from the airstream passing through it, when operated and maintained in accordance with design specifications.
The hot, contaminant-laden air rising from the cooking surface merges with the higher velocity air that wipes the front of the cooking equipment and extends, like an air blanket, from the front edge of the cooking equipment to the air inlet of the ventilator. As the air moves through the ventilator at a high speed, it is forced to make a series of turns around three baffles. As the high velocity air turns around each baffle, the heavier-than-air particles of grease, dust and lint are thrown out of the airstream by centrifugal force. The extracted grease, dust and lint are collected in the interior of the ventilator, remaining out of the airstream until removed daily by the wash cycle.
Baffle #1
This baffle is located at the air inlet of the ventilator and is formed as part of the inspection door. There is a small grease collecting gutter on the back side of the baffle which drains off liquefied grease, preventing it from re-entraining into the airstream.
Baffle #2
This baffle is on the interior back wall of the ventilator and includes a square stainless steel pipe, equipped with brass spray nozzles on 8" to 10" centers. During the wash cycle, hot detergent water is released through the nozzles. If the ventilator’s automatic fire control system is activated, fire smothering water spray is also released through the spray nozzles.
Baffle #3
This baffle is located on the back of the inspection door. NOTE: Some ventilators may be equipped with optional
Custom Air” baffles (shown dotted) which reduces the ex­haust volume where the baffles occur.
NOTE: Some ventilators may be equipped with optional continuous cold water mist. Refer to Page 25 for details.
FIG. 7
GREASE EXTRACTION
6
"RG" SERIES VENTILATOR PRINCIPLE OF OPERATION
WASH CYCLE
The wash cycle is activated each time the exhaust fan is shut off by pushing the “Start Wash” button on the Command Center or, if equipped with optional time clock (“TC” Series), as programmed on the clock. The “Wash On” light is illuminated each time the wash cycle comes on, and hot, detergent injected water is released into the interior of the ventilator for the time set on the wash timer.
This hot detergent water washes the day’s grease, dust and lint accumulation from the interior of the ventilator flushing it down to the main gutter which slopes to the pre-flushed drain which leads to the building drain system. Spray nozzles are located on 8" to 10" centers on the wash pipe mounted on the interior back wall of the ventilator. (Refer to Figure 9) At the end of the wash cycle, the water is automatically shut off, and the interior of the ventilator is clean - ready for the next day’s operations.
There are three standard wash cycle times that are set depending upon the type of cooking equipment being used.
On fuse link activated ventilators, water will continue to run until it is shut off by the hand valve located inside the ventilator control cabinet. The fire damper must then be reset by replacing the fuse links. IMPORTANT NOTE: All replacement fuse links must be UL Listed and rated for 280°F (138°C).
The hand valve may then be reopened and the exhaust fan may then be re-started by pushing the “Start Fan” button on the Command Center.
FIRE DAMPER
The settings are 3 minutes for light-duty equipment, 5 minutes for medium-duty equipment, and 9 minutes for heavy-duty equipment. However, adequate cleaning is dependent upon water pressure, water temperature, daily grease accumula- tion, the length of the wash cycle, frequency of wash cycle and the type of detergent being used. It may be necessary to increase the wash time to the next higher setting to achieve proper cleaning.
COMMAND CENTER MODEL C-5000 SERIES
FIG. 8
VENTILATOR CONTROL CABINET
MODEL GPC-5000 SERIES
INTERNAL FIRE MODE
The ventilator is equipped with a spring loaded fire damper located at the duct collar. The internal fire protection system is automatically activated whenever the fuse link or optional electrical thermostat reaches 280°F (138°C). Upon activa­tion the following occurs:
HOT DETERGENT WATER SPRAY
SPRAY NOZZLES
DRAIN LINE
HINGED INSPECTION DOOR
FIG. 9
AUTOMATIC WASH CYCLE
1. The fire damper closes — stopping the combustion­supporting, natural draft through the ventilator. (Refer to Figure 13)
2. The exhaust fan serving the ventilator is shut off, stopping the combustion-supporting, mechanically in­duced draft. The supply fan is also shut off.
3. Fire-smothering water spray is released into the interior of the ventilator through the cleaning system.
4. The “Fire” light on the Command Center illuminates.
FIG. 10
DAMPER CONTROL SWITCH
MODEL C-61-GXB-RG
USED WITH FUSE LINK
ACTIVATED SYSTEMS
7
"RG" SERIES VENTILATOR PRINCIPLE OF OPERATION
INTERNAL FIRE MODE (CONTINUED)
On thermostatically activated systems, the water will run until the thermostat cools below 280°F (138°C), and then continue for a 5 minute cool down cycle. The water may be shut off prior to the end of the 5 minute cool down cycle by pushing the “Cancel” button located inside the electrical compartment of the control cabinet. After the water has shut off, the dampers can be reset by pulling the reset handle on the damper control switch (Refer to Figure 11), and the exhaust fan(s) restarted by pushing the “Start Fan” button on the Command Center.
FIG. 11
DAMPER CONTROL SWITCH
MODEL C-61-GXSH-RG
USED WITH THERMOSTATICALLY
ACTIVATED SYSTEMS
EXTERNAL FIRE MODE
A break glass type fire switch is optional and if provided, would normally be located at the exit of the kitchen. Pulling the fire switch shuts off supply fan and starts the exhaust fanif it was off, releases fire smothering water spray into the interior of the ventilator, and the “Fire” light on the Command Center flashes. During this time, the fire damper remains open, and the exhaust fan remains on to help remove smoke, heat, etc. If the fire intensified and the fuse link or thermostat reach 280°F(138°C), the fire damper would then close and the exhaust fan would shut off.
To resume normal operations, open the fire switch and flip the toggle switch to the position marked “normal”. (Refer to Figure
12) Replace the glass rod and close the cover.
TESTING INTERNAL FIRE MODE
The internal fire protection system may be tested periodically by pushing the “Fire Test Switch” which is located inside the electrical compartment of the control cabinet. Pushing this switch will cause the following:
Thermostatically Activated Fuse Link Activated
1. Water turns on and 1. Water turns on and will run for 5 minutes. will run for 5 minutes.
2. Exhaust fan shuts off. 2. Exhaust fan shuts off.
3. Damper closes. 3. Fire light illuminates.
4. Fire light illuminates.
CAUTION: Before pushing the “Fire Test Switch”, check to see if the internal fire protection system is tied to the building alarm system.
TO RESUME NORMAL OPERATION
1. To discontinue the 5 minute cool down cycle at any point during the cycle, push the “Cancel” button located inside the electrical compartment.
2. Reset all damper control switches, if thermostatically operated.
3. Push the “Start Fan” button on the Command Center.
SURFACE FIRE PROTECTION
The Gaylord Ventilator may be equipped with surface fire protection either dry or wet chemical, or the Gaylord Quencher System. In the event of a fire, the surface fire protection system would normally be activated and discharged prior to the ventilator’s internal fire protection. These systems may be intertied with the ventilator control cabinet to activate the External Fire Mode. If the fire is unusually severe or the surface fire protection system malfunctions, the ventilator’s internal fire protection system would activate, thus providing a second level of defense.
FIRE DAMPER IN CLOSED POSITION MELTED 280°F FUSE LINK
FIG. 12
BREAK GLASS FIRE SWITCH
C-1357A SERIES
FIRE QUENCHING WATER SPRAY
DRAIN LINE
8
FIG. 13
FIRE CYCLE
HINGED INSPECTION DOOR
(OPTIONAL) SURFACE FIRE PROTECTION NOZZLE
DAILY OPERATION
DAILY OPERATION
All functions of the ventilator, such as starting the exhaust fan, starting the wash cycle, etc., are controlled by the Command Center located on the control cabinet. Refer to Pages 13 through 15 for detailed instructions on the operation of the Command Center.
COMMAND CENTER MODEL C-5000 SERIES
FIG. 14
VENTILATOR CONTROL CABINET
MODEL GPC-5000 SERIES
Starting the Exhaust Fan
To start the exhaust fan push the “Start Fan” button on the Command Center. If the Command Center is equipped with a time clock (“TC” Series control), it may be programmed to start automatically at any desired time. (Refer to programming instructions on Page 15 for automatic operations.) The “Fan On” light will illuminate when the exhaust fan is running. It is important to start the exhaust fan before turning on the cooking equipment.
Stopping the Exhaust Fan and Starting the Wash Cycle
CAUTION: The cooking equipment must be shut off prior to
shutting off the exhaust fan. Failure to do this will cause excessive heat buildup and could cause the surface fire protection system to discharge.
1. To start the wash cycle push the “Start Wash” button on the Command Center. If the Command Center is equipped with a time clock (“TC” Series control), it may be programmed to start automatically at any desired time. Refer to programming instructions on Page 15 for auto- matic operations. When the wash cycle is activated the “Wash On” light illuminates and the following occurs:
A. The exhaust fan shuts off.
However, adequate cleaning is dependent upon water pressure, water temperature, daily grease accumula­tion, the length and frequency of the wash cycle, and the type of detergent being used. Refer to wash timing instructions on Page 14 for setting the length of the wash cycle.
NOTE: Some control cabinets are equipped with a low detergent switch. If so equipped, the “Wash On” light will flash if the detergent tank is empty or if the detergent pump is malfunctioning and detergent is not pumping.
2. After the wash cycle is completed, wipe the exposed front surface of the baffle at the air inlet of the ventilator, as well as other exposed exterior surfaces. (Refer to Figure 15)
3. The ventilator is now clean. The exhaust fan may be restarted by pushing the “Start Fan” button on the Command Center.
In very heavy cooking operations it may be necessary to wash the ventilator(s) more than once a day. If equipped with a time clock (Model C-5000-TC Series) the Command Center is capable of being programmed to start the wash cycle several times within a 24-hour period. Refer to programming instruc- tions on Page 15.
NOTE: For proper operation of the wash system:
Water Pressure 40 psi min. - 80 psi max.
(2.8Kg/cm2 - 5.6Kg/cm2)
Water temperature 140°F min. - 180°F max.
(60°C min. - 82°C max.)
NOTE: The ventilator wash system is designed to remove daily accumulations of grease within the extraction chamber. If the ventilator is not washed a minimum of once during a cooking day, a grease buildup could accumulate which the wash system cannot remove. If this occurs, it is recommended that the ventilator be put through several wash cycles by pushing the “Start Wash” button on the Command Center. If this does not remove the grease, it will be necessary to remove the grease manually by using a scraping tool, such as a putty knife, or retain the services of a commercial hood cleaning service to steam clean or pressure wash the system.
WARNING: Some commercial hood cleaning services blow a fire retardant chemical into hood and duct systems. Fire retardant chemicals should never be applied to any portion of The Gaylord Ventilator. If retardant is applied to the ventilator, it must be removed.
B. Hot detergent water is automatically released into the
interior of the ventilator for the length of time set on the wash timer. The length of the wash cycle may be set for 3 different wash times, 3 minutes for light-duty equipment, 5 minutes for medium-duty equipment, and 9 minutes for heavy-duty equipment.
9
PREVENTIVE MAINTENANCE
PREVENTIVE MAINTENANCE
The following should be checked periodically in order to keep The Gaylord Ventilator operating at design efficiency:
Weekly
1. The detergent tank should be checked at least weekly and kept full with a recommended detergent. (Refer to Page 12)
Monthly
1. The detergent system fittings should be checked at least monthly. This is an airtight system and fittings should be tight. (For complete details refer to the Detergent Pump section on Page 12.)
2. At least monthly, at the conclusion of a wash cycle, open the inspection doors of the ventilator and check to ensure that the interior has been cleaned of grease, dust, and lint. (Refer to Figure 15) If overall cleaning appears to be inadequate, refer to “Trouble-Shooting of the Wash Sys- tem”, Page 19.
3. The main grease gutter of the ventilator should be checked at least monthly to remove any foreign material such as paper towels, order chits, etc.
Every Six Months
1. Exhaust fan(s) should be checked every six months for belt tightness, belt alignment, and lubrication of necessary moving parts.
NOTE: A blue lithium based grease is best suited for high heat and speed bearing lubrication.
2. Check for proper velocity at air inlet slot. Refer to Pages 22 through 24 for method of checking velocity.
3. Test the "Internal Fire Mode" (electrically activated dampers only) to check for proper damper closure. Refer to page 5. Reset damper when test is complete.
4. Detergent tank and foot valve should be cleaned every six months.
NOTE: Annual and semi-annual inspections are recommended by the NFPA, Standard No. 96, Chapter 8. Factory trained service agencies are certified by Gaylord Industries, Inc. to perform these inspections. For the name and phone number of your nearest agent call 1-800-547-9696.
INSPECTION AND CLEANING REQUIREMENTS
The 1998 edition of NFP A-96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations) require that hoods, ducts and exhaust fans be inspected by a properly trained, qualified and certified company or person(s) in accordance with the following table.
Upon inspection, if found to be contaminated with deposits from grease-laden vapors, the entire exhaust system shall be cleaned by a properly trained, qualified, and certified copany or person(s) acceptable to the authority having jurisdic- tion in accordance.
When a vent cleaning service is used, a certificate showing date of inspection or cleaning shall be maintained on the premises. After cleaning is completed, the vent cleaning con- tractor shall place or display within the kitchen area a label indicating the date cleaned and the name of the servicing company . It shall also indicate areas not cleaned.
ELUDEHCSNOITCEPSNIMETSYSTSUAHXE
snoitarepognikoocleufdilosgnivressmetsySylhtnoM
gnikoockowrogniliorbrahc,gnikoocruoh-42
sretnec
sahcussnoitarepognikoocemulov-hgihgnivressmetsyS
snoitarepognikoocemulov-etaredomgnivressmetsyS yllaunnaimeS
sahcus,snoitarepognikoocemulov-wolgnivressmetsyS
roinesro,sessenisublanosaes,spmacyad,sehcruhc
ylretrauQ
yllaunnA
FIG. 15
10
DETERGENT PUMP OPERATION
DESCRIPTION
The Gaylord Ventilator detergent pump is an integral part of the wash-down system of The Gaylord Ventilator. The pump is located within the control cabinet unless otherwise specified. (Refer to schematic on Pages 26 through 29.)
OPERATION
The detergent pump is started when the wash cycle begins. The pump draws detergent up from the detergent tank, pushing it through the copper tubing and into the hot water line serving the ventilator.
NOTE: Some control cabinets are equipped with a low detergent switch. If so equipped, the “Wash On” light will flash if the detergent tank is empty or if the detergent pump is malfunctioning and detergent is not pumping.
Initial Operation
To prime and operate the pump for the first time, it is recommended that water be used instead of detergent to prevent detergent from spilling in case of leaks at the system’s fittings.
Priming The Pump
The detergent pump is self-priming. Push the pump test switch, located on the junction box of the motor, and hold down until liquid climbs up the vinyl tubing and fills the pump head. The pump will be operating properly when both upper and lower poppet checks can be seen moving up and down slightly. If the pump does not self-prime, an air lock may have developed within the pump head and the following action should be taken:
1. Hold down pump test switch and loosen top cap slightly to allow air to be pushed out. Repeat as necessary until liquid climbs up tube and fills pump head.
2. If the pump still does not work properly, check the following: A. Foot valve should be clean and immersed in the liquid. B. Check all fittings to ensure an airtight system. C. Poppet checks within the foot valve, pump head and
brass check valve should be clean and operating freely.
D. Detergent lines should be free and clear.
DETERGENT FLOW
Detergent flow is initially factory set according to the pipe size of the control cabinet (refer to chart). Generally, the factory setting will be sufficient to provide adequate cleaning of the ventilator. However, adequate cleaning is dependent upon a number of factors:
1. Temperature of hot water 5. Frequency of wash
2. Water pressure cycle
3. Daily grease accumulation 6. Type of detergent
4. Wash cycle time
PREVENTIVE MAINTENANCE
As with any piece of fine equipment, a reasonable amount of care must be taken to keep it in good working order:
1. Caution should be taken not to spill detergent on the exterior of the pump.
2. A periodic check should be made of all fittings to guarantee their tightness.
NOTE: The detergent pump motor has sealed bearings and will not require lubrication.
)lairepmI(
lortnoC tenibaC
eziSepiP
"2/11#2.36.91.21.615.35.229.4
"4/32#1.56.514.31.627.55.639.7
"13#0.68.719.36.925.64.141.9
"4/11
"2/11&
lortnoC tenibaC
eziSepiP
)mm(
511#590.582.55.8574.52.41566.59.91
022#051.164.38.31277.61.32970.173.23
523#771.625.87.51678.82.62522.157.63
23
04&
yrotcaF
maC
gnitteS
4#3.68.811.43.138.68.346.9
yrotcaF
maC
gnitteS
4#681.655.86.61629.87.72692.183.83
reP.zO ta.niM ISP04
retaW
erusserP
sretiL
.niMreP
ta
8.2 mc/gk
setuniM3setuniM5setuniM9
.zO
.laG
reP
reP
yaD
.oM
)cirteM(
setuniM3setuniM5setuniM9
sretiL
sretiL
reP
reP
yaD
.oM
TRAHCNOITPMUSNOCTNEGRETED
HTGNELELCYCHSAW
.zO
.laG
.zO
reP
reP
yaD
.oM
TRAHCNOITPMUSNOCTNEGRETED
HTGNELELCYCHSAW
sretiL
sretiL
reP
reP
yaD
.oM
.laG
reP
reP
yaD
.oM
sretiL
sretiL
reP
reP
yaD
.oM
Depending upon these factors, it may be necessary to adjust the detergent flow. Adjustment may be accomplished by changing the cam to a different size. To change the cam:
1. Loosen Allen set screw on brass cam.
2. Remove cam and replace with next size as required.
3. Cam #1 minimum setting. Cam #4 maximum setting. NOTE: Cams are available from Gaylord Industries or your
Gaylord Certified Service Agency.
FIG. 16
11
DETERGENT FOR THE WASH SYSTEM
FORMULA G-510 is the only cleaner recommended by Gay­lord Industries for use in the washdown system of The Gaylord Ventilator. FORMULA G-510 is a concentrated colloid cleaner specially formulated to remove the daily accumulation of grease inside The Gaylord Ventilator without damaging the rubber and synthetic parts of the detergent pumping system. FORMULA G-510 is biodegradable, safe for kitchen person­nel, and has a variety of uses.
DILUTION OF FORMULA G-510 FOR VENTILATOR CLEANING
Normal Cleaning
For ventilators covering cooking equipment such as broilers, griddles, fryers, or any other heavy grease producing equip­ment, fill the detergent tank with full strength FORMULA G-510.
Light-Duty Cleaning
For ventilators covering light grease producing equipment such as ovens, kettles, steamers and ranges, fill the detergent tank with a mixture of one part FORMULA G-510 to one part water.
Cleaning the Ventilator Exterior
Mix one part FORMULA G-510 to twenty parts water in hand spray bottle. Spray on and wipe off. NOTE: Once a day, this same solution should be used to clean the front of the fire damper and main grease extracting baffle.
FOR OTHER CLEANING JOBS
The colloidal action of FORMULA G-510 makes it a cleaner especially well-suited for use in kitchens. The colloids break up dirt and grease into millions of tiny particles that constantly repel each other. These particles cannot recombine or redeposit on a surface and are, therefore, easily washed away. FORMULA G-510 is biodegradable and contains no harsh chemicals, yet offers outstanding performance on the tough- est cleaning jobs.
Use a mixture of one part FORMULA G-510 to twenty parts water for:
VINYL/PLASTIC/WALLS...Removes dirt, grease, food deposits and fingerprints.
REFRIGERATORS...Removes dirt, spilled milk, blood, mildew and objectionable odors.
RESTROOMS...Add a disinfectant to clean all fixtures, walls, floors, etc.
Use a mixture of one part FORMULA G-510 to five parts water for extremely heavy grease build-up, such as on the floor and on equipment around deep-fryers. Spray on and rinse or wipe off. For extremely soiled areas, gentle agitation, followed by a soaking period, will result in more thorough cleaning.
DON’T be afraid to experiment with FORMULA G-510 because it contains no phosphates, nitrates, enzymes, sulfates, sul- fonates or silicates.
LIMITED WARRANTY
G-510 CHEMICAL DIVISION warrants that FOR­MULA G-510 will not cause cleansing agent dam­age to the rubber and synthetic parts of the injection pump (“O” rings, diaphragms, washers, tubing, and other such parts) used with The Gaylord Ventilator, Heat Reclaim Unit, or Pollution Control Equipment. G-510 CHEMICAL DIVISION’S obligation under this warranty and any warranties implied by law shall be limited to repairing or replacing, at its option, any of said parts which G-510 CHEMICAL DIVISION’S examination shall disclose to its satisfaction to have been damaged by the use of FORMULA G-510 for the life of the detergent pumping system. This warranty shall not cover damages caused by any other detergent. The use of any other detergent shall void this warranty.
All repairs and replacement parts under this war- ranty shall be F.O.B. G-510 CHEMICAL DIVISION’S factory. The owner shall pay the necessary freight and delivery charges; also removal and installation costs. Any federal, state or local taxes are also extra. Requests for repairs or replacement parts should be made to G-510 CHEMICAL DIVISION, P.O. Box 1149, Tualatin, Oregon 97062-1149.
This is the sole warranty with respect to FORMULA G-510. G-510 CHEMICAL DIVISION MAKES NO OTHER WARRANTY OF ANY KIND WHATSEVER, EXPRESSED OR IMPLIED, AND ALL IM­PLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID OBLIGATION ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS AGREEMENT. G-510 CHEMICAL DI­VISION SHALL NOT BE RESPONSIBLE FOR INCI­DENTAL OR CONSEQUENTIAL DAMAGES RE­SULTING FROM A BREACH OF THIS WARRANTY.
IMPORTANT
If a cleansing agent other than FORMULA G-510 is used with The Gaylord Ventilator injection pump, it is recommended that a warranty similar to the above be obtained from the manufac­turer of said product.
For more information contact:
20/10 Products
P.O. Box 7609 Salem, Oregon 97303
1-800-286-2010 FAX: 503-363-4296 email:twentyten@juno.com
12
A Subsidiary of Gaylord International, Inc.
TUALATIN, OR 97062-8549
FAN ON FIRE WASH ON
START WASH
START
FAN
OPERATING INSTRUCTIONS
1. Push Start Fan before turning on cooking equipment.
2. At the end of the day, or whenever cooking is com-
pleted, push Start Wash. This will turn off the exhaust fan
and begin a timed wash cycle. NOTE: 24 hour kitchens
must push Start Wash at least once a day or as needed
for proper cleaning.
3. To set the length of time for the wash cycle, open this
cabinet door and set the toggle switches for either Light-
duty, Medium or Heavy-duty cooking equipment.
Extreme cooking loads may require more than one wash
cycle per day.
NOTE: If the Command Center is a S, TC or RSPC Series,
refer to additional operating instructions inside this panel.
COMMAND CENTER
C-5000-S-TC
MODEL
LOW DETERGENT
1. If Wash On light flashes detergent is low.
FIRE CONDITION
1. A flashing fire light indicates the control is in an External Fire Mode - exhaust fan on, fire damper open, and water wash
nozzles on.
2. A solid fire light indicates the control is in an Internal Fire Mode - exhaust fan off, fire damper closed, and water wash
nozzles on.
GAYLORD INDUSTRIES, INC.
MODEL C-5000 SERIES COMMAND CENTER - INSTRUCTIONS
MODEL C-5000 SERIES COMMAND CENTER ­GENERAL
The Model C-5000 Series Command Center controls all of the functions of the Gaylord Water-Wash Ventilator.
The C-5000 Series Command Center is available in four basic models. They are:
Model Description of Operation
C-5000 ...................... Manual start fan and start wash
C-5000-TC ................ Programmable time clock opera-
tion of the start fan and start wash functions
C-5000-S .................. Manual start fan and start wash
functions with sequence wash feature
C-5000-TC-S ............ Programmable time clock opera-
tion of the start fan and start wash functions with sequence wash feature
The model number of your control is indicated on the Command Center label. Refer to Figure 17.
STARTING THE FAN AND WASH CYCLE
The Model C-5000 and C-5000-S Command Centers start fan and start wash functions are the same. To start the exhaust fan push the “Start Fan” button and to start the wash cycle push the “Start Wash” button. The exhaust fan automatically shuts off when the “Start Wash” button is pushed.
Models C-5000-TC and C-5000-TC-S include a time clock which can be programmed to start the fan and wash cycle at any desired time. (Refer to programming instructions on Page 15.) However both of these Command Centers may also be operated manually by pushing the “Start Fan” or
“Start Wash” buttons. SETTING WASH CYCLE TIME FOR MODELS C-5000
AND C-5000-TC COMMAND CENTERS
To set the length of the wash cycle, open the electrical compartment. At the bottom of the control chassis is a three position toggle switch labeled Wash 1 (refer to Fig.17). Set the toggle switch for either 3, 5 or 9 minutes for light, medium or heavy duty equipment as required (refer to “Recom­mended Wash Time” chart on page 14 . Upon activation of the wash cycle, the detergent injected hot water will wash the interior of the extraction chamber for the length of time selected and then shut off.
FAN ON FIRE WASH ON
START
FAN
WASH TIMES SWITCH POSITION
3 MIN. LIGHT-DUTY COOKING EQUIPMENT UP 5 MIN. MEDIUM-DUTY COOKING EQUIPMENT CENTER 9 MIN. HEAVY-DUTY COOKING EQUIPMENT DOWN
WASH 1 WASH 2 WASH 3 WASH 4 WASH 5 WASH
FORM NO. C5CB
IF LIGHT FLASHES DETERGENT
IS LOW
START
WASH
MFG. BY:
GAYLORD INDUSTRIES, INC.
P.O. BOX 1149 TUALATIN, OR 97062
C-5000-S-TC
MODEL NO. ______________ VOLTAGE ________________
120vac
CANCEL
SWITCH
FORM NO. C5CA
DELAY TIMES
1 MIN. SHORT 15 MIN. MEDIUM 30 MIN. LONG
DELAY
FIRE
TEST
SWITCH
FIG.17 FIG.18
13
Loading...
+ 33 hidden pages