This document provides information regarding the operation and maintenance of Blackmer®
Global Dispenser Pumps (GDPs) as used in Gilbarco
This document also provides step-by-step instructions for kit installation. It is recommended
that kits be installed by a Gilbarco Authorized Service Contractor (ASC).
Blackmer GDP pumps must only be installed in systems that have been designed by
qualified engineering personnel. The system must conform to all applicable local and
national regulations and safety standards. This manual must be kept with the pump.
Blackmer® Global Dispenser Pump Operation,
Maintenance and Kit Installation Manual
®
self-contained products.
IMPORTANT INFORMATION
MDE-4096C
April 2008
Intended Users
This document is intended for Gilbarco ASCs.
Table of Contents
TopicPage
Introduction1
Important Safety Information4
Installation6
Operation7
Maintenance8
Repair Kits19
Pump Parts List21
Troubleshooting29
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 1
Page 2
Introduction
Required Tools
The following tools are required for the installation of the kit:
• 5 mm Allen® wrench
• 1/4-inch Allen wrench
• Heavy snap ring pliers
• Ratchet wrench
• 16 mm socket
• 13 mm or 1/2-inch socket
• Rubber mallet
• Torque wrench
Required Reading
Before servicing the pump, the technician must read, understand, and follow this document.
Failure to do so may adversely effect the safe use and operation of the equipment.
Related Documents
Document Number TitleGOLD Library
MDE-3802Encore® and Eclipse® Site Preparation
MDE-2833Pumps and Dispensers Site PreparationSite Prep
MDE-2530Pump and Dispenser Installation ManualAdvantage® and Legacy® models
MDE-3985Encore Installation ManualEncore and Eclipse
Manual
Encore and Eclipse
Pump Model Identification
The pump model identification plate is located on the rear cover. The pump model number
begins with M00955B. For example, M00955B207 is a complete model number.
Abbreviations and Acronyms
TermDescription
ASCAuthorized Service Contractor
cmHgcentimeter of mercury
CWClockwise
CCWCounterclockwise
GDPGlobal Dispenser Pump
gpmgallons per minute
inHginch of mercury
lbspound-force
lpmliters per minute
mmmillimeter
N/ANot applicable
NmNewton-meter
OIMLInternational Organization of Legal Metrology*
Opt.Optional
Page 2MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 3
TermDescription
PCVPressure Control Valve
psipounds per square inch
RPMRevolutions Per Minute
StdStandard
UHFUltra High Flow
* OIML Switch (optional) monitors air to fuel mix and is used primarily in
Europe.
Introduction
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 3
Page 4
Important Safety Information
Important Safety Information
This section introduces the hazards and safety precautions
associated with installing, inspecting, maintaining or servicing
this product. Before performing any task on this product, read
this safety information and the applicable sections in this
manual, where additional hazards and safety precautions for
your task will be found. Fire, explosion, electrical shock or
pressure release could occur and cause death or serious
injury, if these safe service procedures are not followed.
Preliminary Precautions
You are working in a potentially dangerous environment of
flammable fuels, vapors, and high voltage or pressures. Only
trained or authorized individuals knowledgeable in the related
procedures should install, inspect, maintain or service this
equipment.
Emergency Total Electrical Shut-Off
The first and most important information you must know is
how to stop all fuel flow to the pump/dispenser and island.
Locate the switch or circuit breakers that shut off all power to
all fueling equipment, dispensing devices, and Submerged
Turbine Pumps (STPs).
!
WARNING
!
The EMERGENCY STOP, ALL STOP, and
PUMP STOP buttons at the cashier’s station
WILL NOT shut off electrical po wer to th e pump/
dispenser. This means that even if you activate
these stops, fuel may continue to flow
uncontrolled.
Read the Manual
Read, understand and follow this manual and any other
labels or related materials supplied with this equipment. If you
do not understand a procedure, call a Gilbarco Authorized
Service Contractor or call the Gilbarco Support Center at
1-800-800-7498. It is imperative to your safety and the safety
of others to understand the procedures before beginning
work.
Follow the Regulations
Applicable information is available in National Fire Protection
Association (NFPA) 30A; Code for Motor Fuel Dispensing
Facilities and Repair Garages, NFPA 70; National Electrical
Code (NEC), Occupational Safety and Hazard Association
(OSHA) regulations and federal, state, and local codes. All
these regulations must be followed. Failure to install, inspect,
maintain or service this equipment in accordance with these
codes, regulations and standards may lead to legal citations
with penalties or affect the safe use and operation of the
equipment.
Replacement Parts
Use only genuine Gilbarco replacement parts and retrofit kits
on your pump/dispenser. Using parts other than genuine
Gilbarco replacement parts could create a safety hazard and
violate local regulations.
Safety Symbols and Warning Words
This section provides important information about warning
symbols and boxes.
Alert Symbol
You must use the TOTAL ELECTRICAL SHUTOFF in the case of an emergency and not the
console’s ALL STOP and PUMP STOP or
similar keys.
Total Electrical Shut-Off Before Access
Any procedure that requires access to electrical components
or the electronics of the dispenser requires total electrical
shut off of that unit. Understand the function and location of
this switch or circuit breaker before inspecting, installing,
maintaining, or servicing Gilbarco equipment.
Evacuating, Barricading and Shutting Off
Any procedure that requires access to the pump/dispenser or
STPs requires the following actions:
• An evacuation of all unauthorized persons and vehicles
from the work area
• Use of safety tape, cones or barricades at the affected
unit (s)
• A total electrical shut-off of the affected unit (s)
This safety alert symbol is used in this manual and
on warning labels to alert you to a precaution which must be
followed to prevent potential personal safety hazards. Obey
safety directives that follow this symbol to avoid possible
injury or death.
Signal Words
These signal words used in this manual and on warning
labels tell you the seriousness of particular safety hazards.
The precautions below must be followed to prevent death,
injury or damage to the equipment:
DANGER: Alerts you to a hazard or unsafe practice
!
which will result in death or serious injury.
WARNING: Alerts you to a hazard or unsafe practice
!
that could result in death or serious injury.
CAUTION with Alert symbol: Designates a hazard or
!
unsafe practice which may result in minor injury.
CAUTION without Alert symbol: Designates a hazard
or unsafe practice which may result in property or
equipment damage.
Working With Fuels and Electrical Energy
Prevent Explosions and Fires
Fuels and their vapors will explode or burn, if ignited. Spilled
or leaking fuels cause vapors. Even filling customer tanks will
cause potentially dangerous vapors in the vicinity of the
dispenser or island.
Page 4MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 5
Important Safety Information
No Open Fire
Open flames from matches, lighters, welding
torches or other sources can ignite fuels and their vapors.
No Sparks - No Smoking
Sparks from starting vehicles, starting or using power tools,
burning cigarettes, cigars or pipes can also ignite fuels and
their vapors. Static electricity, including an electrostatic
charge on your body, can cause a spark sufficient to ignite
fuel vapors. Every time you get out of a vehicle, touch the
metal of your vehicle, to discharge any electrostatic charge
before you approach the dispenser island.
Working Alone
It is highly recommended that someone who is capable of
rendering first aid be present during servicing. Familiarize
yourself with Cardiopulmonary Resuscitation (CPR) methods,
if you work with or around high voltages. This information is
available from the American Red Cross. Always advise the
station personnel about where you will be working, and
caution them not to activate power while you are working on
the equipment. Use the OSHA Lockout/ Tagout procedures. If
you are not familiar with this requirement, refer to this
information in the service manual and OSHA documentation.
Working With Electricity Safely
Ensure that you use safe and established practices in
working with electrical devices. Poorly wired devices may
cause a fire, explosion or electrical shock. Ensure that
grounding connections are properly made. Take care that
sealing devices and compounds are in place. Ensure that you
do not pinch wires when replacing covers. Follow OSHA
Lockout/T agout requirements. S t ation employees and service
contractors need to understand and comply with this program
completely to ensure safety while the equipment is down.
Hazardous Materials
Some materials present inside electronic enclosures may
present a health hazard if not handled correctly. Ensure that
you clean hands after handling equipment. Do not place any
equipment in the mouth.
!
WARNING
The pump/dispenser contains a chemical known to the
State of California to cause cancer.
In an Emergency
Inform Emergency Personnel
Compile the following information and inform emergency
personnel:
• Location of accident (for example, address, front/back of
building, and so on)
• Nature of accident (for example, possible heart attack, run
over by car, burns, and so on)
• Age of victim (for example, baby, teenager, middle-age,
elderly)
• Whether or not victim has received first aid (for example,
stopped bleeding by pressure, and so on)
• Whether or not a victim has vomited (for example, if
swallowed or inhaled something, and so on)
WARNING
!
Gasoline ingested may cause unconsciousness
and burns to internal organs.
Do not induce vomiting.
Keep airway open.
Oxygen may be needed at scene.
Seek medical advice immediately.
WARNING
!
Gasoline inhaled may cause unconsciousness
and burns to lips, mouth and lungs.
Keep airway open.
Seek medical advice immediately.
WARNING
!
Gasoline spilled in eyes may cause burns to eye
tissue.
Irrigate eyes with water for approximately 15
minutes.
Seek medical advice immediately.
WARNING
!
Gasoline spilled on skin may cause burns.
Wash area thoroughly with clear water.
Seek medical advice immediately.
IMPORTANT: Oxygen may be needed at scene if gasoline
has been ingested or inhaled. Seek medical advice
immediately.
WARNING
!
Lockout/Tagout
Lockout/Tagout covers servicing and maintenance of
The pump/dispenser contains a chemical known to the
State of California to cause birth defects or othe r
reproductive harm.
machines and equipment in which the unexpected
energization or start-up of the machine(s) or equipment or
release of stored energy could cause injury to employees or
personnel. Lockout/Tagout applies to all mechanical,
hydraulic, chemical or other energy, but does not cover
electrical hazards. Subpart S of 29 CFR Part 1910 - Electrical
Hazards, 29 CFR Part 1910.333 contains specific Lockout/
Tagout provision for electrical hazards.
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 5
Page 6
Installation
Installation
Inlet Fittings
The Blackmer GDP is shipped without inlet fittings. Appropriate inlet fittings must be
installed on site.
Configuration Table
The following table lists three possible inlet configurations.
Sl. NoInlet Configuration
11-1/2” NPT x 1-3/4” LG. SCH. 80 NIPPLE and 1-1/2” NPT 150# Union (Gilbarco part
21-1/2” NPT x 1-3/4” LG. SCH. 80 NIPPLE and 1-1/2” NPT 300# Union (Gilbarco part
33-Bolt Flange with flexible connector (order Gilbarco kit number K94194)
Installing the Fittings
To install the fittings, proceed as follows:
numbers R11493-50 and K12179)
numbers R11493-50 and Q10846-08)
1 Apply a pipe sealant (that is approved for use with petroleum products) to the threads.
CAUTION
Do not use Teflon® tape. Teflon tape may shred off and get caught within
components.
2 Hand-tighten, and then wrench-tighten approximately by another 3 turns. The pump body is
aluminum.
CAUTION
Do not overtighten inlet fittings. The pump body is made of aluminum.
Overtightening may strip pump threads.
3 Check for leaks (refer to the section “Troubl esho oting Table” on page 29).
Page 6MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 7
Operation
PCV Adjustment
Pressure Control Valves (PCVs) must be set to the desired single hose operation pressure. A
retaining ring must be in place at all times during PCV adjustment.
Note: Numbers within parentheses in the procedural steps in the manual refer to the numbers
!
WARNING
Not using a retaining ring can release hazardous pressure that can
cause personal injury or property damage.
Always ensure that the retaining ring is in place before making the PCV
adjustment.
Take appropriate safety precaution s. Failure to do so may result in
personal injury or property damage.
mentioned in the referenced figures.
Operation
To set the proper PCV operation pressure, proceed as follows:
1 To increase the pressure setting, turn the PCV cover (13) inward or clockwise (CW) using a
16 mm socket wrench (see Figure 3 on page 11).
2 T o decrease the pressure setting, turn the PCV cover (13) outward or counterclockwise (CCW)
using a 16 mm socket wrench (see
Figure 3 on page 11).
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 7
Page 8
Maintenance
Maintenance
Maintenance shall be performed by qualified technicians only. Follow procedures and
warnings as presented in this manual.
Notes:1) Before removing plugs or covers, ensure that approved container and absorbent
Draining Pump
Figure 1: Typical Plug Location
IMPORTANT INFORMATION
materials are ready to contain any released fuel.
2) Follow all safety procedures for working around fuel and fuel vapors.
Plug, Left Side
Casing (11)
Plug, Lower Right Face (11)
Front Head Cap Screw
To drain the bulk of the fluid from the pump, proceed as follows:
Note: Residual fluid may remain in the pump.
1 Put the approved tray in place to collect the fuel.
Plug, Upper
Face (11)
2 Remove the plug (11) on the upper face of the head, directly to the right of the strainer cover
(19). This port may be used to monitor vacuum (see
Page 8MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Figure 1).
Page 9
3 Remove the plug (11) on the lower right face of the head (9). Fluid will be emptied by
removing this plug. Fluid must be properly contained during draining procedure.
Note: Pump contains up to 0.5 liters of fluid. Do not use this port to monitor system pressure.
4 If sump drainage is desired, remove the plug (11) near the mounting hole on the left side of
pump casing (1).
5 Manually turn the pump pulley counterclockwise (CCW) to aid in fluid removal.
6 Properly dispose of all fluid drained from pump.
7 After pump is drained, replace all plugs (11) using a non-hardening pipe sealant.
Note: Do not use Teflon tape.
Strainer/Check Valve Removal
Check valves (if equipped) should be replaced only if pump is experiencing frequent prime
loss, indicating that the check valve is not functioning. Check valve should be installed when
tank check valve is not available. Always use strainers with or without check valves. Strainer
must be kept clean to ensure proper operation and pump life.
Maintenance
To remove the strainer/check valve, proceed as follows:
1 Lower pump fluid level by removing the plug (1 1) located at the right of the strainer cover an d
rotating the pump shaft counterclockwise (CCW) approximately 10 turns (see
Figure 2 on
page 10).
Note: Removing the plug allows air to enter.
2 Remove the three strainer cover screws (21).
3 Remove the strainer cover (19). Inspect cover O-Ring (18) for damage. If damaged, discard
O-Ring and replace with new O-Ring.
4 Carefully pull out strainer (17). Keep strainer in a horizontal position to avoid contaminating
pump with strainer debris. It may be necessary to use a small tool to gently hook the inside of
the metal strainer end cap.
5 If equipped, remove the inlet check valve assembly (16). Inspect for cracked or otherwise
damaged O-Rings. Replace if damaged.
6 Lift dome strainer (25) out from the bore located behind the check valve assembly. Inspect
strainer for damage. Clean and/or replace, if necessary.
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 9
Page 10
Maintenance
Strainer/Check Valve Installation
To install the strainer/check valve, proceed as follows:
1 If equipped with the check valve option, insert the dome strainer (25) into the bore (see
Figure 2).
Figure 2: Strainer/Check Valve
Optional Dome
Strainer (25)
Optional
Check
Valve (16)
Screws (21)
Strainer Cover (19)
Strainer (17)
Strainer Support
O-Ring (18)
2 Clean the debris from the check valve, especially at the O-Ring seats.
3 Lubricate O-Ring before installing check valve assembly.
4 Insert the check valve assembly (16) or check cap (30) into corresponding pump bore as
shown (see
Figure 2). Press the assembly squarely over receiving cylindrical surface until O-
Ring seats firmly over the surface and holds assembly in position.
5 Insert new or cleaned strainer (17) into bore, over check valve assembly.
6 Clean debris from strainer cover O-Ring groove and install O-Ring (18). If O-Ring does not
stay in place, use a small amount of all purpose grease to hold the O-Ring in groove.
7 Install strainer cover (19) with screws (21). Hand tighten, alternating between each screw to
keep the cover parallel to the casing face. Torque the screws to 150 in. lbs (17 Nm). Do not
overtighten. Overtightening may cause damage to screw or casing.
8 Replace the plug (11) in the hole located to the right of the strainer cover (see Figure 1 on
page 8).
Page 10MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 11
PCV Removal
1 Drain the pump following the procedure provided in the section “Draining Pump” on page 8.
2 Remove the snap ring (15) (see Figure 3).
3 Using a 16 mm socket wrench, turn the valve cover (13) outward or counterclockwise (CCW)
4 Remove the spring (12) and valve (10).
5 If the valve does not come out with the spring, use needle nose pliers to remove it from the
Maintenance
CAUTION
Excessive wear on the PCV can cause improper pump performance, including
flow loss or excessive or low discharge pressure.
To remove the PCV, proceed as follows:
until completely removed.
bore.
PCV Installation
To install the PCV, proceed as follows:
1 Inspect valve (10) for damage or excessive wear. Replace if necessary.
2 Install PCV in the reverse order of removal (see Figure 3).
Figure 3: PCV
Snap Ring (15)
Valve Cover (13)
Valve (10)
Spring (12)
Cover O-Ring (14)
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 11
Page 12
Maintenance
3 Apply a light application of grease on the cover of the O-Ring (14) to prevent the O-Ring from
being damaged during installation.
Modification of PCV or failure to correctly install all components of the PCV will void
any regulating agency recognition applicable to this pump.
4 When the pump is operating at full speed, the discharge pressure must not exceed 50 psi (3.5
bar) with any discharge restriction (fully open to fully close discharge). If the pressure exceeds
50 psi (3.5 bar), refer to
Pump Cartridge Removal
CAUTION
Damage or excessive wear to pump cartridge can cause low suction,
low flow, lock-up or excessive noise.
IMPORTANT INFORMATION
“PCV Adjustment” on page 7.
Note: Avoid introducing contamination into the unit during disassembly or installation of the
cartridge. Keep Parts clean.
To remove the pump cartridge, proceed as follows:
Note: Refer to the appropriate exploded view of pump and see Figure 7 on page 15.
1 Drain the pump following the procedure provided in the section “Draining Pump” on page 8.
2 Remove belt and pulley.
3 Remove strainer, check valve, and PCV. Refer to “Strainer/Check Valve Removal” on page 9
and “PCV Removal” on page 11 for disassembly instructions.
4 Remove the 10 head capscrews (5).
5 Slightly rotate the head (9) counterclockwise (CCW) around pump cartridge to provide
exposed edges to grasp.
6 Remove head (9) from pump casing.
7 If the pump cartridge (7) comes off with head, remove by rotating and pulling the cartridge
from the head bore (see
Figure 7 on page 15).
8 If the cartridge remains in the pump casing, grasp the shaft and/or liner and pull while slightly
turning back and forth. If necessary, gently tap around the circumference with a rubber mallet
to loosen the cartridge assembly. Ensure that you keep it coaxial with the bore.
Page 12MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 13
CAUTION
Do not pry the cartridge out against the side walls, as this will damage
the gasket seal surface.
Pump Cartridge Installation
Preliminary Steps
CAUTION
To prevent O-Ring damage, break corner on the pump body and cover
at cartridge insertion point, as shown in Figures4through6. Ensure
that you remove any residual matter after you complete this procedure,
as this may cause the pump to fail or wear prematurely.
Maintenance
Figure 4: Pump Cover
Using a file or sand paper ,
break corner as shown
(See Figure 6 on page 14)
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 13
Page 14
Maintenance
Figure 5: Pump Body
Using a file or
sand paper, break
corner as shown
(See Figure 6)
Figure 6: Breaking Corner
0.060” Max.
35°
Note: This figure represents a rough
approximation.
To install the pump cartridge, proceed as follows:
1 Install the wave spring (6) in the cartridge bore with the dowel pin hole exposed by the gap in
the wave spring (see
Figure 7 on page 15).
Page 14MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 15
Figure 7: Pump Cartridge
Head Gasket (8)
Maintenance
Direction of
Pump Cartridge
Insertion
Pump
Cartridge (7)
Wave Spring (6)
2 Lightly grease the O-Rings and the bore in which they fit using silicone grease.
3 Align the pump cartridge dowel pin with the dowel pin hole and slide in the pump cartridge
(7). If dowel pin is in the hole, you should be able to rotate the cartridge very lightly back and
forth and feel the positive stops. The wave spring deflection will also be felt when the
cartridge is pressed in axially.
4 Insert provided guides into screw holes. The guides will orient gasket as well as hold it in
position.
5 Install the head gasket (8). If needed, apply a thin film of motor oil onto the mating surface to
affix areas of the gasket that do not retain their position.
IMPORTANT INFORMATION
Ensure that you have completed the steps described in the “Preliminary Steps” section
on page 13, before you proceed to step 6.
6 Carefully install the head (9) over the cartridge. Push head in until it comes approximately
1/4-inch from the casing face.
7 Carefully replace guides with head screws, threading each of them in a few turns.
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 15
Page 16
Maintenance
8 Alternating between the four screws closest to the shaft, draw in the head approximately one
turn on the screw at a time in order to keep the head parallel to the casing.
Notes:1) It is recommended that you t ighten a lternately opposing b olts on th e other side of the
cover instead of tightening the adjacent bolts.
2) Screws will become very tight if faces are not kept parallel. If necessary, return to
9 Once the head is fully drawn in, torque the four screws to 200 in. lbs (23 Nm).
10 Before tightening the remaining head screws, check that the pump shaft turns freely and
uniformly. If so, tighten the remaining screws to 200 in. lbs (23 Nm) and check that the pump
shaft turns freely and uniformly.
11 Reinstall inlet check valve, strainer, and PCV as per previous instructions.
12 Reinstall belt and pulley (see step 1 on page 32).
13 Purge the unit of air and check for leaks.
Sump Float Removal
Pump will have poor suction or sump overflow if sump float mechanism is worn or damaged.
To remove the sump float, proceed as follows:
1 Drain the pump by following the procedure pertained in the section “Draining Pump” on
page 8.
step 3 and check to ensure that the cartridge pin is still aligned with the hole.
2 Remove the pump from the dispenser per dispenser installation instructions.
3 Remove the ten sump cover screws (5) (see Figure 8 on page 17).
4 Lift off the sump cover (4) and gasket (3). Inspect the gasket and replace, if worn or damaged.
5 The sump return float mechanism should operate freely. At full down position, the float valve
should center and seat against the rubber seal surface. If it does not seat, or parts are worn or
damaged, remove the sump float assembly and replace.
Notes:1) The sump overflow float mechanism (if present) should operate freely. The float valve
should center and seat against the rubber seal surface when float is lifted straight up.
2) Either the sump float assembly (2) or the sump overflow float mechanism (23) can be
removed by removing the two sump base mounting screws (24).
Page 16MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 17
Sump Float Installation
To install the sump float, proceed as follows:
1 Install the sump return float assembly (2) or sump overflow float assembly (23), holding the
mount to the casing with one finger and inserting the two screws (24) with the other hand.
Ensure that the rubber washer has not fallen out and is properly seated in the recess of the float
assembly mount (see
Figure 8: Sump Float Assembly
Maintenance
Figure 8).
Sump Overflow Float Assy. Option (23)
Sump Cover Screws (5)
Sump Cover (4)
Gasket (3)
Sump Return Float Assy. (2)
Mounting Screws (24)
2 Tighten the screws (24) to a torque of 18 in. lbs (2 Nm).
3 Check float mechanism. It should operate freely. At full down position, the sump return float
valve should center and seal against the rubber seal surface. The sump overflow float assembly
should seat when the float is fully elevated.
4 Install the sump cover gasket (3). Correctly position the gasket onto all sealing surfaces.
5 Lower the sump cover (4) gently into place over the gasket with the pins aligned, while
ensuring that you do not move the gasket.
6 Install and tighten the center-most sum cover screw (5) to 200 in. lbs (23 Nm).
7 Install the remaining sump cover screws and tighten to 200 in. lbs (23 Nm), alternating in a
cross pattern.
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 17
Page 18
Maintenance
OIML Switch Removal
To remove OIML switch, proceed as follows:
1 Cut and remove tamper resist wire.
2 Using a wrench, rotate the OIML Switch assembly (22) in a counterclockwise (CCW)
direction and remove it (see
CAUTION
Do not allow debris to fall into open port.
OIML Switch Installation
To install the OIML switch, proceed as follows:
1 Apply a very thin film of thread sealing compound onto the thread, beginning at about 3 mm
from the end.
Figure 9 on page 21).
CAUTION
Thread sealing tape is not advised as it may cause contamination.
2 Rotate the OIML switch assembly (22) threads in a clockwise (CW) direction into the sump
vent port by hand and tighten firmly with wrench (see
Figure 9 on page 21).
CAUTION
Do not allow debris to fall into open port.
3 Secure new tamper resist wire through appropriate holes in the switch body and pump casing
tab.
Page 18MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 19
Repair Kits
Table of Kits
Repair Kits
The following table lists fourteen repair kits.
Note: Kits listed specifically as Ultra High Flow (UHF) are for Ultra High Flow products
manufactured in Europe only.
Gilbarco
Kit NumberKit Description
M00955K001Inlet Strainer Kit-Std Pump (see note 1)17Strainer 1X
M00955K002Inlet Strainer Kit-UHF17Strainer, UHF1X
M00955K003Check Valve Kit (see note 1)16Check Valve Assembly1XX
1. Not available for models M00955B102 and M00955B201.
2. Excludes model M00955B705 and UHF.
3. Includes only model M00955B705.
4. Available when sump vent location discharges from the standard vent location on top of the GDP unit. Not available when the alternate
vent location on the rear cover is used.
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 19
1. Not available for models M00955B102 and M00955B201.
2. Excludes model M00955B705 and UHF.
3. Includes only model M00955B705.
4. Available when sump vent location discharges from the standard vent location on top of the GDP unit. Not available when the alternate
vent location on the rear cover is used.
Page 20MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 21
Pump Parts List
Figure 9: Pump Models 102 and 201
Optional
24
Pump Parts List
23
21
19
Optional
18
17
16
15
Optional
22
11
13
14
12
5
11
2
4
3
10
24
6
20
7
8
9
11
5
1
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 21
Page 22
Pump Parts List
Pump Models 102 and 201
The following is a list of parts for pump models M00955B102 and M00955B201 (see Figure 9
on page 21 for the exploded view of the pump assembly). This parts list is for reference only.
Refer to “Repair Kits” on page 19 for replacement parts.
* Included in one or more repair parts kits.
** Not a saleable item.
Page 22MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 23
Figure 10: Pump Model 206
Pump Parts List
21
19
18
Optional
16
17
Optional
Optional
25
11
22
Optional
11
24
23
5
24
6
7
1
2
4
3
15
14
13
12
10
20
8
9
11
5
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 23
Page 24
Pump Parts List
Pump Model 206
The following is a list of parts for pump model M00955B206 (see Figure 10 on page 23 for the
exploded view of the pump assembly). This parts list is for reference only. Refer to “Repair
* Included in one or more repair parts kits.
** Not a saleable item.
8948761
(Std)*
8948501
Assembly (Opt)
Page 24MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 25
Optional
16
Optional
25
Figure 11: Standard Flow Pump Model
Optional
24
Optional
22
29
11
11
23
Pump Parts List
Optional
11
21
19
18
17
30
15
14
13
12
10
2
24
28
3
1
6
7
20
8
26
11
9
5
5
4
27
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 25
Page 26
Pump Parts List
Standard Flow Pump Models
The following is a list of parts for the standard flow pump models M00955B107,
M00955B207, M00955B705 and M00955B707 (see
view of the pump assembly). This parts list is for reference only. Refer to “Repair Kits” on
* Included in one or more repair parts kits.
** Not a saleable item.
**1
8948401
7023321
8948301
8948501
Page 28MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 29
Troubleshooting
This section provides troubleshooting and maintenance information for pumps.
Maintenance must be performed by qualified technicians only. Follow the appropriate
procedures and warnings as presented in this manual.
Troubleshooting Table
The following table contains a list of troubleshooting symptoms and probable causes.
SymptomProbable Cause
Pump not priming or excessive
time to prime
Reduced Capacity (Flow)• Pump speed too low
Noise• Inlet Restriction of:
Leakage
1 Port• Loose piping
2 Weep Hole• Damaged shaft seal O-Ring
3 Head or Sump Gasket• Damaged gasket
4 Sump Overflow• Excessively foamy fuel
Motor/Belt Overheating• Pump cartridge locked up
* This applies only to units equipped with the overflow check valve option.
Troubleshooting
IMPORTANT INFORMATION
• Suction line obstruction
• Air leak in suction line
• Clogged strainer (refer to “Strainer/Check Valve Removal” on
page 9 and “Strainer/Check Valve Installation” on page 10)
• Pump speed too low (check motor, pulleys and belt)
• Damaged or missing strainer cover O-Ring (refer to “Strainer/
Check Valve Removal” on page 9 and “Strainer/Check Valve
Installation” on page 10)
• PCV open, worn or not seated properly (refer to “PCV
Removal”and “PCV Installation” on page 11)
• Air leak in suction lines
• Restriction in suction lines
• Excessive system pressure (flow loss to PCV)
• PCV open, worn or not seated properly
• Worn or damaged pump cartridge
a. Inlet piping
b. Clogged strainer
• Excessive pump speed
• Pump inadequately fastened to the base plate
• Misaligned pulleys
• Improperly anchored piping
• PCV setting too high
• Excessive time with closed discharge line
• Damaged pump cartridge
• Excessive system pressure
• Improperly applied pipe thread sealant
• Damaged shaft seal
• Improperly torqued mounting screws
• Failure of sump float mechanism
• Failure of sump overflow check valve*
• PCV stuck closed
• Excessive speed
• Improper belt tightening or alignment
• Defective or damaged motor
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 29
Page 30
Troubleshooting
Checking Pump Vacuum
!
WARNING
You are working in a potentially dangerous environment of flammable fuels and
vapors.
Fire or explosion could result in severe injury or death if you do not follow safe
procedures.
Read and follow all safety precautions as outlined in the section“Important
Safety Information”onpage 4.
CAUTION
Do not use Teflon tape. Teflon tape may shred off and get caught within
components.
CAUTION
Ensure that fittings are properly tightened and check for leaks.
To check pump vacuum, proceed as follows:
1 Remove 1/4-inch NPT plug from the side of the strainer extrusion on pump face (see
Figure 13).
2 Install a long 1/4-inch pipe nipple by screwing into pump in order to extend beyond pump
pulley.
Figure 13: Pump Vacuum
Vacuum Port
Vacuum Gauge
Pipe Nipple
3 Attach the vacuum gauge into the pipe.
Page 30MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 31
Checking the Pump Pressure
To check the pump pressure, proceed as follows:
1 Remove the feedline filter from the manifold (see Figure 14).
2 Screw on filter cap (R18896-G1) modified with a 1/4-inch NPT tapped hole.
3 Attach the pressure gauge into the hole on the filter cap.
IMPORTANT INFORMATION
When testing is complete, replace the filter cap with the filter.
Figure 14: Pump Pressure Test Set-up
Troubleshooting
Fuel
Filter
Manifold
Filter
Cap
Pressure
Gauge
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 31
Page 32
Troubleshooting
Pump Performance Test
1 Check the belt tension.
!
CAUTION
Tighter belt tensions can cause pump and motor bearing wear and premature failure.
Loose belts may result in lower flow or excessive belt wear.
The recommended belt tension is 45-55 lbs. (200-244 Newtons).
Notes: 1) The proper belt tension is the lowest tension at which the belt will not slip.
2) Operate the unit with both pressure and vacuum gauges attached. Use an approved
container to collect fuel. Clean spills promptly.
Belts and pulleys can pinch fingers and hands. Injuries may result.
Avoid placing fingers or hands between belts and pulleys.
Never turn power on to fit belt on pulley.
2 Run pump in by-pass with all nozzles closed and record pressure.
3 Run pump in full flow with all nozzles wide-open and record pressure and vacuum. Use a stop
watch to record flow rate in gpm or lpm.
4 If necessary, check the pump speed with a rpm photo-tachometer. Blackmer GDP nominal
Standard Flow3-8 / 7.6-20.320-35 / 1.3-2.417-20 / 64-7622-38 / 1.5-2.6
Notes:
1. Pressures, vacuum and flow will vary depending upon installation factors, fuels and hardware configurations.
2. For UHF pump ranges, contact Gilbarco.
Discharge
Pressure
psi/bar
Flow Rate
gpm/lpm
Nozzles Closed
Discharge Pressure
psi/bar
Page 32MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008
Page 33
This page is intentionally left blank.
Troubleshooting
MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008Page 33
Page 34
Troubleshooting
The Advantage® Series, Encore®, Eclipse®, Gilbarco®, and Legacy® are registered trademarks of Gilbarco Inc. Allen® is a registered
trademark of Industrial Fasteners, Inc. Blackmer
®
is a registered trademark of Dover Corporation. Teflon® is a registered trademark of E.I.