Other brand or product names shown may be
trademarks or registered trademarks of their
respective holders.
Non-registered trademarks
Consola
™
Infinity
™
TopKAT™
All Gasboy computer programs (including software on diskettes and within memory chips) and documentation are copyrighted by, and shall remain the property of, Gasboy. Such
computer programs and documents may also contain trade secret information. The duplication, disclosure, modification, or unauthorized use of computer programs or
documentation is strictly prohibited, unless otherwise licensed by Gasboy.
Federal Communications Commission (FCC) Warning
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy, and if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential
area is likely to cause harmful interference in which case the user will be re quired to correct the inte rference at his own exp ense. Changes or modifications not expressly approved by
the manufacturer could void the user’s authority to operate this equipment.
Approvals
Trademarks
This document is subject to change without notice.
E-mail: literature@gasboy.com · Internet: http://www.gasboy.com 2014 GASBOY. All Rights Reserved.
Page ivMDE-4331M Atlas® Fuel Systems Installation Manual · September 2014
PurposeIntroduction
Certain special alternative fuels, such as E85 and additives, can degrade pump/dispenser
performance or integrity if the dispensers are not designed for use with such fuels.
Additionally, converting to certain standard fuels (gasoline, diesel, kerosene, and so on)
from alternative fuels, such as those with ethanol (E85), methanol, or biodiesel, or from
alternative fuels to standard fuels can degrade dispenser performance or integrity. Similar
effects can also occur when converting units to different standard fuel types. As per
Underwriters Laboratories (UL
®
) 87A requirements, nozzles dispensing E85 fuel and
Diesel Exhaust Fluid (DEF) must not be used to dispense any other type of fuel such as
gasoline.
Leaks and potential environmental hazards can result or components may fail
prematurely.
To avoid these issues, follow the guidelines provided for dispensing E85 fuel and DEF in
this manual.
CAUTION
The unit is shipped with the hose elbow facing upward. Ensure to install the unit with the
hose elbow facing downward.
CAUTION
1 – Introduction
Purpose
This manual provides step-by-step instructions for installing Atlas® pumps and dispensers.
This manual does not include site preparation instructions. For site preparation instructions,
refer to MDE-4333 Atlas Fuel Systems Site Preparation Manual.
Intended Users
This manual is intended for Authorized Service Contractors (ASCs) who will be involved in
the installation of Atlas pumps and dispensers.
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014 Page 1-1
IntroductionGeneral Description
General Description
Atlas Commercial Electronic Series
Gasboy® Atlas dispensing units are UL-listed and are available in a self-contained (suction
pump) or remote-controlled (dispenser) package. Both packages offer a variety of models that
are available as single-hose outlets or dual-hose outlets (with single or dual product
capability). Following self-contained models are available:
• Standard Flow (SF) models up to 15 GPM, 56 LPM, 12 IPM
• High Flow (HF) models up to 22 GPM, 83 LPM, 18 IPM
™
• Single-hose Super-Hi
• Single-hose Ultra-Hi
Flow (SHF) models up to 40 GPM, 151 LPM, 33 IPM
™
Flow (UHF) models up to 50 GPM, 189 LPM, 42 IPM
The rate of delivery for remote-controlled packages varies base
pump, as well as the choice of the hanging hardware, including the nozzle type. The delivery
rate of both packages also varies depending on installation conditions and additional
accessories.
The difference between commercial and retail pumps/dispensers can be visually identified.
Commercial pumps/dispensers have only one visual port for gallons/liters on a side(s), while
retail pumps/dispensers have visual ports for both gallons/liters and cost per gallon/liter.
The Atlas series pumps/dispensers offer the following features:
9862KX• Bottom Inlet: 1-inch British Standard Pipe Parallel
• Inlet: 1-1/2-inch National Pipe Taper (NPT) female
threads
• Discharge: 1-inch NPT female threads (can be
reduced to 3/4-inch with bushing)
• Motor: (self-contained) 3/4 HP continuous duty
• Inlet: 1-1/2-inch NPT female threads
• Discharge: 1-inch NPT female threads
• Motor: (self-contained) 3/4 HP continuous duty
• Inlet: 2-inch NPT female threads
• Discharge: 1-inch NPT female threads
• Motor: (self-contained) (2) 3/4 HP continuous duty
• Discharge: 1-inch NPT female threads
• Motor: (self-contained) 1-1/2 HP continuous duty
• Discharge: 3/4-inch NPT female threads
(BSPP) female threads
• Side Inlet: 1-inch BSPP male threads
• Discharge: 1-inch BSPP male threads
d on the size of the submersible
™
PLUS option factory mounted on top
Page 1-2MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014
Atlas Model CodesIntroduction
Atlas Commercial Mechanical Series
Atlas commercial mechanical series dispensing units are UL-listed and are available in a
self-contained (suction pump) packag
e or remote-controlled (dispenser) package. Both
packages offer a variety of models that are available as single-hose outlets or dual-hose outlets
(with single or dual product capability). Following self-contained models are available:
• Standard speed, up to 15 GPM/56 LPM
• High speed, up to 22 GPM/83 LPM
• As a single-hose model with high capacity spee
d up to 26 GPM/99 LPM.
Note: DEF unit is a standard speed unit.
e
The rate of delivery for remote-controlled packages varies bas
d on the size of the submersible
pump and plumbing to the dispenser . The d elivery rate of both packages also varies depending
on installation conditions and additional accessories.
All models of the Atlas commercial mechanical series offer mechanical non-computers,
complete with electric resets. Mechanical pump registers display the total volume for a
delivery. All non-computers read up to 999.9 gallons/liters.
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014 Page 1-3
IntroductionShipping Weight
DEF freezes at approximately 11 °F (-11.5 °C). Power to the dispenser and heater must
always remain ON in cold weather. If power is lost and the temperature drops below this
point within the DEF cabinet, the system must be inspected for freeze damage before
restart.
CAUTION
Shipping Weight
The Atlas shipping weights listed below are approximate values, as shipping weights vary for
different models:
• Standard, Hi, and Super-Hi Dispenser: 315 lbs
• Standard, Hi, and Super-Hi Pump: 325 lbs
• Ultra-Hi Combo Pump with Satellite Piping: 503 lbs
• Ultra-Hi Dual Dispenser with Satellite Piping: 414 lbs
•TopKAT
PLUS with Receipt printer: 41 lbs
• Atlas DEF 9872KXTW1 Dispenser: 361 lbs
• Atlas DEF 9872KXWWTWI Dispenser: 355 lbs
Operating Environment
EnvironmentRange
Relative Humidity20 to 95% non-condensing
Minimum Ambient Temperature-22 °F (-30 °C)
Maximum Ambient Temperature131 °F (55 °C)
Operating Environment - Special Considerations for DEF Dispensers
MDE-4255 Gasboy Warranty Policy Statement for USA and Canada• Domestic Warranty and Owners
MDE-4333 Atlas Fuel Systems Site Preparation ManualGasboy Atlas Pumps/Dispensers
MDE-4334 Commercial and Retail Series Atlas Start-up/Service Manual Gasboy Atlas Pumps/Dispensers
MDE-4363 Atlas Fuel Systems Owner’s ManualGasboy Atlas Pumps/Dispensers
MDE-5013 TopKAT PLUS Installation ManualGasboy Series 1000/ Fleetkey & Topkat
PT-1949Commercial and Retail Series Atlas Pump and Dispenser
PT-1950Atlas Recommended Spare Parts ListGasboy Atlas Pumps/Dispensers
PT-1960Gasboy Fleet Plus Recommended Spare PartsGasboy Fleet PLUS System
PT-1963Gasboy Illustrated Spare Parts ManualGasboy Fleet PLUS System
Manual
spensers with Electronic and Mechanical Displays
DEF Di
Electronic and Mechanical Unit
s Manual
Illustrated Par
t
s
s Diagnostic
SM
Library
Gasboy Q, A&E Series Pumps/Dispensers
Gasboy Parts List & Wiring Diagrams
Gasboy Parts List & Wiring Diagrams
Manuals
•
Gasboy Safety & Warranty Docs
• Gasboy Policy Documents
Gasboy Atlas Pumps/Dispensers
Abbreviations and Acronyms
TermDescription
ASCAuthorized Service Contractor
ASTAboveground Storage Tank
ASTMAmerican Society for Testing and Materials
BSPPBritish Standard Pipe Parallel
CFNCash Flow Network
CPUCentral Processing Unit
D-BoxDistribution Box
DEFDiesel Exhaust Fluid
DIPDual In-line Package
E-CALElectronic Calibration
FMSFuel Management System
GFIGround Fault Interrupter
®
GOLDGilbarco
GPMGallons per Minute
HDPEHigh Density Polyethylene
HFHigh Flow
J-boxJunction Box
LANLocal Area Network
LPMLiters per Minute
Online Documentation
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014 Page 1-5
IntroductionCommon Terms Used
TermDescription
LSDLeast Significant Digit
MSDMost Significant Digit
NCWMNational Conference on Weights and Measures
®
NEC
NFPANational Fire Protection Association
NPTNational Pipe Taper
NTEPNational Type Evaluation Program
PCBPrinted Circuit Board
SFStandard Flow
SHFSuper-Hi Flow
STPSubmersible Turbine Pump
TFR-ISO Top Front Right Isometric
UHFUltra-Hi Flow
ULUnderwriters Laboratories
USTUnderground Storage Tank
W&MWeights and Measures
WANWide Area Network
National Electrical Code
Common Terms Used
TermDescription
ComboThis unit is configured as master on one side a
Dispenser A dispensing device that receives fuel under pressure fro
underground)] through a Submersible Turbine Pump (STP) or from an Aboveground Storage Tank (AST)
using an aboveground pump located at the tank.
GradeFuel that is dispensed a
ListedProducts bearing the authorized listing mark of UL as the manufacturer
the product complies with UL’s requirements and is in accordance with terms of the UL’s Listing and
Follow-Up Service agreement.
MasterThis unit dispenses fuel to one saddle t
PumpA dispensing device that utilizes a self-contained pumping unit and motor to move fuel from a
tank using suction.
ProductFuel in the storage tank.
SatelliteA dispensing unit that receives the product from a master un
both saddle tanks on a vehicle to be filled at the same time.
UreaUrea is a non-flammable liquid chemical from a sepa
reduce emissions to nitrogen and water. Urea is used in DEF.
Warranty
nd has an assigned pr
ank and to a
nd satellite on the other.
m the Underground Storage Tank [UST (if
ice.
’s declaration, which implies that
second saddle tank through a satellite unit.
it and
registers at the master unit, allowing
rate tank that chemically interacts with exhaust to
storage
For information on warranty, refer to MDE-4255 Gasboy Warranty Policy Statement for USA
and Canada. If you have any warranty related questions, contact Gasboy’s Warranty
Department at its Greensboro, N.C. location.
Page 1-6MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014
2 – Important Safety Information
Notes: 1) Save this Important Safety Information section
in a readily accessible location.
2) Although DEF is non-flammable, diesel is
flammable. Therefore, for DEF cabine ts that are
attached to diesel dispensers, follow all the
notes in this section that pertain to flammable
fuels.
This section introduces the hazards and safety precautions
associated with installing, inspecting, maintaining or servicing
this product. Before performing any task on this product, read
this safety information and the applicable sections in this
manual, where additional hazards and safety precautions for
your task will be found. Fire, explosion, electrical shock or
pressure release could occur and cause death o r serious injury,
if these safe service procedures are not followed.
Preliminary Precautions
You are working in a potentially dangerous environment of
flammable fuels, vapors, and high voltage or pressures. Only
trained or authorized individuals knowledgeable in the related
procedures should install, inspect, maintain or service this
equipment.
Emergency Total Electrical Shut-Off
The first and most important in formation you must know is how
to stop all fuel flow to the pump/dispenser and island. Locate
the switch or circuit breakers that shut off all power to all fueling
equipment, dispensing devices, and Submerged Turbine
Pumps (STPs).
The EMERGENCY STOP, ALL STOP, and
PUMP STOP buttons at the cashier ’s station
WILL NOT shut off electrical power to the
pump/dispenser. This means that even if you
activate these stops, fuel may continue to flow
uncontrolled.
You must use the TOTAL ELECTRICAL
SHUT-OFF in th e cas e of an emerge nc y a nd not
the console’s ALL STOP and PUMP STOP or
similar keys.
!
WARNING
!
Total Electrical Shut-Off Before Access
Any procedure that requires access to electrical component s or
the electronics of the dispenser requires total elect rical shut off
of that unit. Understand the function and location of this switch
or circuit breaker before inspecting, installing, maintaining, or
servicing Gasboy equipment.
Evacuating, Barricading and Shutting Off
Any procedure that requires access to the pump/dispenser or
STPs requires the following actions:
• An evacuation of all unauthorized persons and vehicles from
the work area
• Use of safety tape, cones or barricades at the affected unit(s)
• A total electrical shut-off of the affected unit(s)
Read the Manual
Read, understand and follow this manual and any other labels
or related materials supplied with this equipment. If you do not
understand a procedure, call a Gasboy Authorized Serv ice
Contractor or call the Gasboy Support Center at
1-800-444-5529. It is imperative to your safety and the safe ty of
oth
e
rs to understand the procedures before beginning work .
Follow the Regulations
Applicable information is available in National Fire Protection
Association (NFPA) 30A; Code for Motor Fuel Dispensing
Facilities and Repair Garages, NFPA 70; National Electrical
Code (NEC), Occupatio nal Safety and Health Administration
(OSHA) regulations and federal, state, and local codes. All
these regulations must be followed. Failure to install, inspect,
maintain or service this equipment in accordance with these
codes, regulations and standards may lea d to leg al citation s
with penalties or affect the safe use and operation of the
equipment.
Replacement Parts
Use only genuine Gasboy replacement p art s and re trofit kits on
your pump/dispenser. Using parts other than genuine Gasboy
replacement parts could create a safety hazard and violate
local regulations.
Safety Symbols and Warning Words
This section provides important information about wa rn ing
symbols and boxes.
Alert Symbol
This safety alert symbol is used in this manual and on
warning labels to alert you to a precaution which must be
followed to prev
ent potential personal safety hazards. Obey
safety directives that follow this symbol to avoid possible injury
or death.
Signal Words
These signal words used in this manual and on warning labels
tell you the seriousness of particular safety hazards. The
precautions below must be followe d to prevent death, injury or
damage to the equipment:
DANGER: Al
erts yo
u to a hazard or unsafe practice
which will result in death or serious injury.
WARNING: Alerts
you to a hazard or unsafe practice
that could result in death or serious injury.
CAUTION with Alert symbol: Designates a hazard or
un
safe practice which may result in minor injury.
CAUTION w
i
thout Alert symbol: Designates a hazard or
unsafe practice which may result in property or
equipment damage.
Working With Fuels and Electrical Energy
Prevent Explosions and Fires
Fuels and their vapors will explode or burn, if ignited. Spilled or
leaking fuels cause vapors. Even filling customer tanks will
cause potentially dangerous vapors in the vicinity of the
dispenser or island.
DEF is non-flammable. Therefore, expl
osion and fire safety
warnings do not apply to DEF fluid lines.
!
!
!
Important Safety Information
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014Page 2-1
Important Safety Information
The pump/dispenser contains a chemical known to the
State of California to cause cancer.
WARNING
!
The pump/dispenser contains a chemical known to the
State of California to ca use birth defects or other
reproductive harm.
WARNING
!
Gasoline/DEF ingested may cause
unconsciousness and burns to internal organs.
Do not induce vomiting. Keep airway open.
Oxygen may be needed at scene. Seek medical
advice immediately.
DEF generates ammonia gas at high er temperatures.
When opening enclosed panels, allow the unit to air out to
avoid breathing vapors.
If respiratory difficulties develop, move victim away from
source of exposure and into fresh air. If symptoms persist,
seek medical attention.
WARNING
!
WARNING
!
Gasoline inhaled may cause unconsciousness
and burns to lips, mouth and lungs.
Keep airway open.
Seek medical advice immediately.
WARNING
!
Gasoline/DEF spilled in eyes may cause burns to
eye tissue.
Irrigate eyes with water for approximately
15 minutes.
Seek medical advice immediately.
WARNING
!
Gasoline/DEF spilled on skin may cause burn s.
Wash area thoroughly with clear water.
Seek medical advice immediately.
WARNING
!
DEF is mildly corrosive. Avoid cont act with eyes , skin, and
clothing. Ensure that eyewash stations and safety
showers are close to the work location. Seek medical
advice/recommended treatment if DEF spills into eyes.
WARNING
!
No Open Fire
Open flames from matches, lighters, welding torches or
other sources can ignite fuels and their vapors.
No Sparks - No Smoking
Sparks from starting vehicles, starting or using power tools,
burning cigarettes, cigars or pipes can also ig nite fuels and their
vapors. Static electricity, including an electrostatic charge on
your body, can cause a spark sufficient to ignite fuel vapors.
Every time you get out of a vehicle, touch the metal of your
vehicle, to discharge any electrostatic charge before you
approach the dispenser island.
Working Alone
It is highly recommended that someone who is capab l e of
rendering first aid be present during servicing. Familiarize
yourself with Cardiopulmonary Resuscitation (CPR) methods, if
you work with or around high voltages. This informa tion is
available from the American Red Cross. Always advise the
station personnel about where you will be working, and caution
them not to activate power while you are working on the
equipment. Use the OSHA Lockout/Tagout procedures . If you
are not familiar with this requirement, refer to this information in
the service manual and OSHA documentation.
In an Emergency
Inform Emergency Personnel
Compile the following information and inform emergency
personnel:
• Location of accident (for example, address, front/back of
building, and so on)
• Nature of accident (for example, possible heart attack, run
over by car, burns, and so on)
• Age of victim (for example, baby, teenager, middle-age,
elderly)
• Whether or not victim has received first aid (for example,
stopped bleeding by pressure, and so on)
• Whether or not a victim has vomited (for example, if
swallowed or inhaled something, and so on)
Working With Electricity Safely
Ensure that you use safe and established practices in working
with electrical devices. Poorly wired devices may cause a fire,
explosion or electrical shock. Ensure that grounding
connections are properly made . Take care that sealing devices
and compounds are in place. Ensure that you do not pinch wires
when replacing covers. Follow OSHA Lockout/Tagout
requirements. Station employees and service contractors need
to understand and comply with this program complete ly to
ensure safety while the equipment is down.
Hazardous Materials
Some materials present inside electronic enclosures may
present a health hazard if not handled correctly . Ensure that you
clean hands after handling equipment. Do not place any
equipment in the mouth.
IMPORTANT: Oxyg en may be needed at scene if gasoline has
been ingested or inhaled. Seek medical advice immediately.
Lockout/Tagout
Lockout/Tagout covers servicin g and maintenance of machines
and equipment in which the unexpecte d energization or sta rt-up
of the machine(s) or equipment or release of stored energy
could cause injury to employees or personnel. Lockout/Tagout
applies to all mechanical, hydraulic, chemical, or other energy,
but does not cover electrical hazards. Subpart S of 29 CFR Part
1910 - Electrical Hazards, 29 CFR Part 1910.333 contains
specific Lockout/Tagout provision for electric al haz ards.
Hazards and Actions
WARNING
Spilled fuels, accidents involving pumps/dispensers, or uncontrolled fuel flow create a
serious hazard.
Fire or explosion may result, causing serious injury or death.
Follow established emergency procedures.
DEF is non-flammable. However it can create a slip hazard. Clean up spills promptly.
!
Collision of a Vehicle with UnitFire at IslandFuel Spill
The following actions are recommended regarding these hazards:
Important Safety Information
• Do not go near a fuel spill or allow anyone else in the area.
• Use station EMERGENCY CUTOFF immediately . Turn off all system circuit breakers to the island(s).
• Do not use console E-STOP, ALL STOP, and PUMP STOP to shut off power. These keys do not
remove AC power and do not always stop product flow.
• Take precautions to avoid igniting fuel. Do not allow starting of vehicles in the area. Do not allow
open flames, smoking or power tools in the area.
• Do not expose yourself to hazardous conditions such as fire, spilled fuel or exposed wiring.
• Call emergency numbers.
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014Page 2-3
*DEF dispensers located outside the 20 feet area are unclassified.
Notes: 1) Not applicable to DEF-only dispensers.
2) DEF is not flammable and does not generate explosive vapors. For any requirements, consult local regulatory agencies. For
example, units dispensing DEF and diesel must follow the flammable fuel regulatory requirements.
20’
18”
Unclassified
18”
Vapor Barrier
20’
DEF
18”
18”
18”
48”
Division 1
Division 2
Division 2
Division 2*
18”
18”
18”
Division 1
Division 2
Dispenser Without Vapor
Barrier Construction
Dispenser with Vapor
Barrier Construction
Class 1 Division 1
(Hazardous Location)
Class 1 Division 2
(Hazardous Location)
Vapor Areas
Fuel Containing
Components
3 – Hazardous Locations
Classifying Hazardous Locations
Any activity (such as smoking or drilling) that can cause an explosion must be done well
outside the vapor area.
Figure 3-1 is b
Figure 3-1: Hazardous Locations Diagram
sed on National Fire Protection Association (NFPA) 30A and NFPA 70®.
a
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014 Page 3-1
Hazardous LocationsImportant Considerations for DEF Dispensers
Applicable during installation and operation of the dispenser: DEF freezes at
approximately 11 °F (-11.5 °C). Power to the dispenser and heater must always remain
ON in cold weather. If power is lost and the temperature dro ps below this point, the
system must be inspected for freeze damage before restart. For sites that experience
occasional power losses or for sites that are located in very cold climates, it is
recommended that a backup power generator be used to maintain constant power to the
dispenser. Do not use any additives to lower the freezing point of DEF. Additives of any
type must not be used in DEF.
Prolonged storage at temperatures above 77 °F (25 °C) can impair the quality of DEF
and reduce its shelf life.
CAUTION
DEF is mildly corrosive. It can corrode components that are made from incompatible
material(s) and reduce their integrity. The use of incompatible material(s) may lead to
leaks and spills, and can contaminate and degrade the DEF. When dispensing DEF,
verify with the manufacturer if the material of all plumbing components are compatible
with the DEF being dispensed.
CAUTION
Do not use prover cans meant for engine fuel with DEF or vice versa. Use stainless steel
prover cans for DEF. DEF and engine fuel must not be mixed with each other or be
contaminated by each other. Otherwise, damage to a vehicle’s engine or pollution control
devices can occur. DEF crystallizes as its water base evaporates. Pouring out liquid will
not guarantee that no corrosive DEF remains in the prover can. DEF must not be
contaminated with diesel fuel, contaminants, or other fluids or materials. Such
contamination can cause serious damage to vehicle catalytic converters.
CAUTION
Important Considerations for DEF Dispensers
• Conventional fluid handling precautions are also applicable to DEF.
• Avoid contact with eyes, skin, and clothing. Ensure that
eyewash stations and safety
showers are close to the work location.
• DEF is mildly corrosive and non-flammable.
• Clean the DEF spill with water and dry the area wit
h clean rags, especially areas that
contain metallic parts. Spilt DEF can be slippery and will corrode certain types of metallic
parts. Wear eye protection and rubber gloves during any cleanup activity.
• DEF is heavier than gasoline. Be aware that prover cans, containers filled with DEF, and
so on, will be
considerably heavier than gasoline.
Page 3-2 MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014
PurposeControl Lines for Atlas Electronic Series
4 – Control Lines for Atlas Electronic Series
Purpose
This section is provided to familiarize the installer with control inputs and outputs that are
available for the Atlas electronic series dispensing unit. It is recommended that installers read
these descriptions to obtain a better working knowledge of the unit to guide them in planning
the site wiring. For specific wiring diagrams and installation notes, refer to “Installation”
on page 6-1.
Grounding
Atlas electronic series units may be provided for
use with 230 VAC power for international
applications. The operating voltage for control lines to these units is shown in parentheses as
(230 VAC International).
If you are connecting the Atlas electronic series unit to a Gasboy Fuel Management System
(FMS), refer to the following documents:
Document
NumberTitleGOLD Library
MDE-4298CFN Series Site Controller III Installation Manual Gasboy CFN Series
MDE-4319TopKAT Fuel Management System Installation ManualGasboy Series 1000/Fleetkey &
MDE-4811Islander PLUS and ICR PLUS Installation ManualGasboy Fleet PLUS System
MDE-4813CFN Plus Installation ManualGasboy Fleet PLUS System
MDE-5013TopKAT PLUS Installation ManualN/A
TopKAT
To ensure proper operation of the equipment and required safety factors, a good ground line
must be provided. A ground wire (preferably green) must be connected between the ground
wire of the system and the main electrical service panel. One earth ground connection is
required per unit. The ground rod must be a solid, corrosion-resistant conductor and must be
installed at the main electrical panel as per the National Electrical Code (NEC). It must be
properly tied into the ground bus strip of the panel. It is recommended that n eutral and g round
bus strips be bonded together (unless prohibited by local codes).
Ground Fault Interrupter (GFI) breakers are required for DEF
only units installed on and with
a skid tank platform because of no underground piping, AC power in potentially wet area, and
a potential for earth ground to become broken if skid tank moves.
A GFI works by having a sensor that detects changes in current to the load, by comparing the
current owing to and from the load. A drop off in the current equivalent to about 5 mA, turns
off all power by tripping a relay within the GFI within a few hundredths of a second.
When powering a dispenser with a GFI, any device that the dispenser supplies power must
have its return to the same neutral as the dispenser. For example, the STP control relay.
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014 Page 4-1
Control Lines for Atlas Electronic SeriesMicro Feed
Micro Feed
The micro feed is a 115 VAC (230 VAC international) input required to power the
microprocessor of the register’s electronics. This power must always remain on and must be
on a separate breaker from control lines (control/pump motor feed or control/submersible
feed - side 1, side 2). It must also be on a separate
electrical noise and allow separate control of lights. In a site configuration using multiple
dispensing units, the power for microprocessors of up to eight units can be supplied by one
breaker (except cold weather DEF units). This line also supplies power to the optional
T opKAT PLUS. If this unit is equipped with a TopKAT PLUS option, for wiring requirements
and information, refer to MDE-5013 TopKAT PLUS Installation Manual.
breaker from fluorescent lights to reduce
The cold weather DEF unit’s internal heater ca
circuit. These units must not share breakers with other dispenser.
n share the micro feed AC line and neutral
Micro Neutral
The micro neutral is a return line for AC from the microprocessor of the dispensing unit to the
breaker panel. This line also serves as the return for the optional TopKAT PLUS.
Auth/Pump Motor Feed (Self-contained Pumping Units)
The auth/pump motor feed is a 115 VAC (230 VAC international) input that is required to
power and authorize the auth control line. This line is used to provide authorization for the
self-contained pumping unit (when enabled, refer to MDE-4334 Atlas Start-up/Service Manual). If this line is controlled by an FMS using solid state relays, a resistor assembly must
be installed between the auth feed line and feed neutral to prevent false triggering of the
authorization input. The resistor assembly is 8.2 K Ohm, 10 W (part number C05818) for
115/230 VAC domestic; and 30 K Ohm, 10 W (part number C06683) for 230 VAC
international wiring.
Note: The auth/pump motor feed is not r
The auth/pump motor feed line is used to powe
installed). The power used to control the pump is also provided by this line. It is possible to
combine control lines for twins and supply them from one breaker. However, the gauge of the
wire must be adjusted to handle the load of two motors. The reset complete signal used for
external monitoring of the pump also originates from the auth/pump motor feed line.
Two auth/pump motor feed lines are provided for twins.
equired for the TopKAT PLUS system.
r slow flow and fast flow valves (when
Page 4-2 MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014
External ValveControl Lines for Atlas Electronic Series
External Valve
The external valve line is used to directly power an anti-siphon valve mounted on top of an
AST . The valve must operate at the same voltage as the pump motor and the current draw must
not exceed 1 A, or the valve must be switched through an external relay controlled by the
external valve line. Do not connect two or more external valve lines together. If more than one
pump is drawing from the tank, separate anti-siphon valves must be installed, or each external
valve line must operate an external relay, which then operates the valve.
Neutral Feed
The neutral feed is the AC current return line back to the breaker panel for all attached devices
(pump motor, reset motor, and solenoid valves).
Auth Input Dispensers
The auth input is a 115 VAC (230 VAC international) input that is required to power and
authorize the auth control line. This line is used to provide authorization for the dispensing
unit (when enabled, refer to MDE-4334 Atlas Start-up/Service Manual). If this line is
controlled by an FMS using solid state relays, a resistor assembly must be installed between
the auth feed line and feed neutral to prevent false triggering of the authorization input. The
resistor assembly is 8.2 K Ohm, 10 W (part number C05818) for 115/230 VA C domestic and
30 K Ohm, 10 W (part number C06683) for 230 VAC international wiring. Cash Flow
Network (CFN) systems require the resistor assembly only when they are used with the Atlas
commercial electronic pump/dispenser operating in standalone mode. Operating the Atlas
commercial electronic unit in standalone mode with a CFN system requires an optional
mechanical pump control unit. This line also supplies power, which is switched to slow flow
and fast flow valves along with the switch detect signal. Two lines are provided for twins.
If the Atlas commercial electronic unit is to be controlled t
special care must be taken in the wiring of submersible control lines when a common
submersible is used for more than 1-hose outlet. For more information, refer to “Submersible
Units with Standard Submersible Starter Drive (Subm Starter Drive)
Power for the submersible start drive line originates from the AUTH input. The submersible
starter relay line in standard remote dispensers is not capable of directly powering a
submersible pump. A starter relay must be used. Control lines for twin remote dispensers can
be combined together and powered by one breaker if individual control of each side is not
required. In site configuration using multiple remote dispensers, power for control lines of up
to 8-hose outlets (eight singles or eight twins) can be supplied from one breaker.
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014 Page 4-3
Control Lines for Atlas Electronic SeriesSubmersible Starter Drive (Subm Starter Drive)
Units with Submersible Pump Drive Relay Option
Power for the submersible pump drive line originates from the motor feed input. Units
equipped with optional relays for direct submersible pump drive can be connected directly to
submersible pumps up to 3/4 HP at 115 VAC, or 1-1/2 HP at 230 VAC. The gauge of this wire
must be determined according to the size of the motor, the voltage at which the motor will be
powered, and the distance from the breaker panel to the pump.
Submersible Starter Drive (Subm Starter Drive)
The submersible starter drive is a 115 VAC (230 VAC International) output used to control a
submersible starter relay. Two lines are provided for twins. This line is capable of supplying
300 mA of AC current to control the coil of the submersible motor contactor (starter relay).
This is sufficient for directly connecting to popular models, but if in doubt, check the contactor
(relay) manufacturer’s data sheet for the sealed VA rating. Divide the sealed VA by the coil
voltage to determine the current. This line must not be connected directly to the submersible
pump, shorted to any conduit or chassis metal, or incorrectly wired; otherwise, the Central
Processing Unit (CPU) Printed Circuit Board (PCB) will be instantly damaged. This line must
be left capped when not in use. To avoid accidental damage, follow checks before applying
power.
Note: When multiple dispensers are used to contr
pump, and the Atlas commercial electronic unit is controlled (authorized) through the
auth/pump motor feed line (as in the case of some FMSs), it is important that lines from
the Atlas commercial electronic unit to the submersible equipment be isolated from
each other. This can be accomplished by running submersible control lines through a
secondary set of relay contacts in the FMS. If a secondary set of contacts is not
available, external control re lays must be used between the Atlas commercial electr onic
unit and the submersible starter relay or pump. Another option is to provide a separate
submersible starter relay for each hose outlet. In no case must the submersible drive
lines from the Atlas commercial electronic unit be tied together.
ol a common submersible starter relay or
Submersible Pump Drive (Subm Pump Drive)
The submersible pump drive is not available on all Atlas models for remote dispensers, and is
active only when submersible drive relays are supplied. The submersible drive is a
115/230 VAC (230 VAC international)
submersible pump. When connected directly to the submersible pump, the motor size cannot
exceed 3/4 HP at 115 VAC, or 1-1/2 HP at 230 V AC. Two lines are provided for twins. In cases
where both lines control the same starter relay or pump, they can be combined. This line is
also used to control an external valve used on AST installations.
Note: For situations where more
to the note in “Submersible Starter Drive (Subm Starter Drive)”.
output used to control the submersible starter relay or
than one-hose outlet uses the same submersible pump, refer
Page 4-4 MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014
Reset Complete (Switch Detect)/Slow FlowControl Lines for Atlas Electronic Series
Reset Complete (Switch Detect)/Slow Flow
The reset complete/slow flow is a 115 VAC (230 VAC international) output used to indicate
that the reset process is complete and the unit is ready to dispense the product. It may be
required when used with an FMS. It may also be used to control a remote (satellite)
slow flow valve. Two lines
are provided for twins.
In addition to the internal load of the slow flow valve,
maximum of 170 mA AC to the satellite valve and FMS. When you are connecting it to a
non-Gasboy satellite or FMS, ensure that this limit is not exceeded. This line must not be
shorted to any conduit or chassis metal, incorrectly wired, used to control both stages of a
satellite valve, or be connected to equipment requiring more than 170 mA AC from this line to
operate; otherwise, the CPU PCB will be instantly damaged. This line must be left capped
when not in use. To avoid accidental damage, follow checks before applying power.
Fast Flow Valve
The fast flow valve is a 115 VAC (230 VAC International) line that can be used to control a
remote (satellite) fast flow valve. Two lines are provided for twins. In addition to the internal
load of the fast flow valve, this line is capable of supplying 170 mA AC to the satellite valve.
When connected to a non-Gasboy satellite, ensure that this limit is not exceeded. This line
must not be shorted to any conduit or chassis metal, incorrectly wired, used to control both
stages of a satellite valve, or be connected to equipment requiring more than 170 mA from this
line to operate; otherwise, the CPU PCB will be instantly damaged. This line must be left
capped when not in use. To avoid accidental damage, follow checks before applying power.
Phase 2 Feed
this line is capable of supplying a
The phase 2 feed is a hot feed, which is the opposite phase of pump motor feed. This line and
pump motor feed are used for 230 VAC domestic motor applications. If connected to
equipment requiring control of the authorization input, phase 2 feed must be switched through
a separate relay to prevent false triggering of the authorization signal.
Slow/Fast Satellite Return
The slow/fast satellite return lines are used only in units that come equipped with satellite
piping. They are used in applications where the remote dispenser and satellite may not
dispense the product at the same time. These lines are not connected internally as they leave
the factory . Four lines ar e provided for twins. These lines must not be shorted to any conduit or
chassis metal, or be connected to equipment requiring more than 170 mA from each line to
operate; otherwise, the CPU PCB will be damaged instantly. These lines must be left capped
when not in use. To avoid accidental damage, follow checks before applying power.
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014 Page 4-5
Control Lines for Atlas Electronic SeriesLight Feed
V+ (24 VDC Maximum)
Pulser #1 Input (100 mA Maximum)
Pull-up Resistors not
supplied with 9800
Pulser #1 Input (100 mA Maximum)
FMS
Ground
Pulse 1
Pulse 2
Return
Black
White
Green
Gasboy 9800 Pump I/F PCB
Leave Capped in
9800 Junction Box
(J-box)
TLP627
U4
P1
Red
Light Feed
The light feed is a 115 VAC input required to power fluorescent lights. In a site configuration
using multiple remote dispensers (or pumps), the power for lights of up to eight units can be
supplied by one breaker. It is recommended that this be on a separate breaker from the
micro/heater feed to reduce electrical noise and allow separate control
of lights.
Light Neutral
The light neutral is a return line for AC current from lights to the breaker panel. When a
separate breaker is not used to control lights, the light neutral is attached to the micro neutral.
Pulser
When the dispensing unit includes the optional pulser interface, a pulser output is provided.
This pulser output provides a DC output that indicates the quantity of product dispensed. The
pulse rate can be configured by a sealable Dual In-line Package (DIP) switch for rates of 1, 10,
100, 250, or 500 pulses per gallon, or 1, 10, 100, or 250 pulses per liter. For the Atlas
commercial electronic pump, pulse rates are 1, 10, 100, 250, or 500 pulses per gallo n, or 1, 10,
or 100 pulses per liter.
The output is an open collector transistor capable of sinking up to 100 m A DC at voltages up
to 24 VDC. The
DC ground for the circuit comes from the FMS. Since the transistor switches
between ground and high impedence, the installer must provide a voltage reference when the
transistor is in the high impedence state. This reference voltage is provided by a pull-up
resistor installed at the FMS between the pulser input and reference voltage. The value of this
resistor is calculated based on the voltage and current requirements of the FMS pulser circuit.
Figure 4-1: Pulsers
Page 4-6 MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014
RS-485Control Lines for Atlas Electronic Series
In the main J-box, the optional pulser interface is supplied with eight wires. On Ultra-Hi units,
a separate DC J-box with six wires is supplied. The unused wires in the J-box must be
individually capped.
RS-485
When the dispensing unit includes the optional RS-485 interface, RS-485 lines are provided.
This interface allows you to connect a Gasboy CFN series system directly to the Atlas
commercial electronic series dispensing unit. These lines must be capped individually when
not in use. The RS-485 interface is included with the TopKAT PLUS option.
Local Area Network (LAN)/Wide Area Network (WAN)
When the dispensing unit includes the optional T opKAT PLUS, lines for communication to the
TopKAT PLUS are provided. These lines allow you to communicate directly to the TopKAT
PLUS through a LAN/WAN connection. For more information on LAN/WAN wiring, refer to
MDE-5013 TopKAT PLUS Installation Manual.
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014 Page 4-7
Control Lines for Atlas Electronic SeriesLocal Area Network (LAN)/Wide Area Network (WAN)
This page is intentionally left blank.
Page 4-8 MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014
PurposeControl Lines for Atlas Mechanical Series
5 – Control Lines for Atlas Mechanical Series
Purpose
This section is provided to familiarize the installer with control inputs and outputs that are
available for the Atlas mechanical series dispensing unit. It is recommended that installers
read these descriptions to obtain a better working knowledge of the unit to guide them in
planning the site wiring. For specific wiring diagrams and installation notes, refer to
“Installation” on page 6-1.
Grounding
The Atlas mechanical series may be provided fo
applications. The operating voltage for control lines to these units is shown in parentheses as
(230 VAC international).
If you are connecting the Atlas mechanical unit to a Gasboy FMS, refer to the following
documents:
Document
NumberTitleGOLD Library
MDE-4298CFN Series Site Controller III Installation ManualGasboy CFN Series
MDE-4319TopKAT Fuel Management System Installation Manual Gasboy Series 1000/Fleetkey & TopKAT
MDE-4811Islander PLUS and ICR PLUS Installation Manual Gasboy Fleet PLUS System
MDE-4813CFN Plus Installation ManualGasboy Fleet PLUS System
MDE-5013TopKAT PLUS installation ManualGasboy Series 1000/Fleetkey & TopKAT
To ensure proper operation of the equipment and required safety factors, a good ground line
must be provided. A ground wire (preferably green) must be connected between the unit’s AC
J-box ground lug and main electrical service panel. One earth ground connection is required
per unit. The ground rod must be a solid, corrosion-resistant conductor that must be installed at
the main electrical panel as per the NEC. It must be properly tied into the ground bus strip of
the panel. It is recommended that the neutral and ground bus strips be bonded together (unless
prohibited by local codes).
r use with 230 VAC power for international
GFI breakers are required for DEF only units installed on and
because of no underground piping, AC power in potentially wet area, and a potential for earth
ground to become broken if skid tank moves.
A GFI works by having a sensor that detects changes in current to the load, by comparing the
current owing to and from the load. A drop off in the current equivalent to about 5 mA, turns
off all power by tripping a relay within the GFI within a few hundredths of a second.
When powering a dispenser with a GFI, any device that the dispenser supplies power must
have its return to the same neutral as the dispenser (for example, the STP control relay).
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014 Page 5-1
with a skid tank platform
Control Lines for Atlas Mechanical SeriesReset Motor Feed
Reset Motor Feed
The reset motor feed is a 115 VAC (230 VAC international) input supplied through the pump
handle switch to activate the reset motor. Without power being supplied to this line, the unit
will not reset when the pump handle is turned on. Two feed lines are provided for twins. This
feed is also connected to the input of one of the internal switches of the electric reset. When
the reset finishes its cycle, the 115 VAC (230 VAC international) input to the switch will be
passed through as an output, causing the solenoid valve (optional in some models) to open and
the reset complete line to indicate 115 VAC (230 VAC international).
Pump Motor Feed
The pump motor feed is a 115 VAC (230 VAC international) input supplied to the input side of
one of the internal switches of the electric reset. When the reset finishes its cycle, the
115 VAC (230 VAC international) input to the switch
the pump motor to receive power and begin operation. Without power to this line, the unit will
reset and will be unable to fuel. Two feed lines are provided in twins that contain two motors.
The gauge of this wire (and its neutral wire) must be determined according to the size of the
motor, the voltage at which the motor will be powered (115 VAC or 230 VAC), and the
distance from the breaker panel to the pump. It is possible to combine pump motor feeds for
twins and supply them from one breaker. However, the gauge of the wire must be adjusted to
handle the load of two motors.
is passed through as an output, causing
Return (Neutral)
The return is the AC current return line back to the breaker panel for all attached devices
(pump motor, reset motor, and solenoid valves). The gauge of this wire must be equal to that of
the pump motor feed (suction pumps) or submersible feed (remote dispensers). This wire is
commonly referred to as the neutral wire.
Submersible Feed, Submersible Drive
The submersible feed is a 1 15 VAC (230 VAC international) input supplied to the input side of
one of the internal switches of the electric reset. When the reset finishes its cycle, the
115 VAC (230 VAC international) input to the switch is pas
(submersible drive) to drive a starter relay or to directly drive a submersible motor up to one
HP at 115 VAC/230 VAC. Any submersible motor exceeding this limitation must use a starter
relay.
sed through as an output
Reset Complete (Switch Detect)/Slow Flow
The reset complete is a 115 VAC (230 VAC international) output used to indicate that the reset
is complete and the dispensing unit is ready to dispense the product. T wo lines are provided for
twins. Use this line only when monitoring a dispensing unit that is connected to a FMS. This
line must be capped when not in use, and is connected to the slow-flow stage of the solenoid in
the pump.
Page 5-2 MDE-4331M Atlas® Fuel Systems In stallation Manual · September 2014
Fast FlowControl Lines for Atlas Mechanical Series
Fast Flow
The fast flow is a 115 VAC (230 VAC international) input that controls the fast flow valve of
the pump/remote dispenser (when a slow/fast flow valve is available). If slow/fast-flow
control is not required, this line must be tied to reset the complete/slow-flow line. The line
must be switched through the FMS and be turned on only when the pump/remote dispenser is
authorized and in the fast-flow mode. This line will be switched on when the pump/remote
dispenser is in the manual mode.
Light Feed
The light feed is a 115 VAC (230 VAC international) input required to power fluorescent
lights. In a site configuration using multiple remote dispensers (or pumps), power for lights for
up to eight units can be supplied by one breaker. If separate control of lights is not required,
the light feed for each dispensing unit may be taken from its reset motor feed, provided the
unit is not connected to a FMS.
Light Neutral
The light neutral is a return line for AC from lights to the breaker panel. When a separate
breaker is not used to control lights, the light neutral is attached to the neutral, which is
connected to the reset motor.
Phase 2 Feed
The phase 2 feed is a hot feed, which is the opposite phase of pump motor feed. This line and
pump motor feed are used for domestic 230 VAC motor applications.
Pulser
The pulser supplies a DC output that indicates the quantity of product dispensed. Pulsers are
optional and are used only when monitoring the dispensing unit that is connected to a FMS.
The pulser wiring must run in a separate conduit away from AC power control lines.
MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014 Page 5-3
Control Lines for Atlas Mechanical SeriesPulser
This page is intentionally left blank.
Page 5-4 MDE-4331M Atlas® Fuel Systems In stallation Manual · September 2014
Loading...
+ 70 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.