In addition to installation information, this manual contains warnings,
safeguards and procedures on the use and care of the Series 9820A pumps.
Please leave this manual with the pump owner after the installation is
complete.
The information in this document is confidential and proprietary. No further disclosure shall be made
without permission from Gasboy International LLC. Gasboy International believes that the information in
this document is accurate and reliable. However, we assume no responsibility for its use, nor for any
infringements of patents or other rights of third parties resulting from its use. We reserve the right to make
changes at any time without notice.
Copyright 2003 by Gasboy International LLC All rights reserved.
GASBOY INTERNATIONAL LLC
Page 2
IMPORTANT WARNINGS AND SAFEGUARDS
Gasoline and petroleum products are flammable. To avoid injury or death to persons or damage to equipment or
property, follow these listed warnings and other warnings and precautions outlined in this manual when installing, using,
or working around this equipment. Check with GASBOY Technical Services for compatibility of liquids with pump
materials.
TURN OFF AND LOCK OUT ALL POWER TO PUMP BEFORE PERFORMING SERVICE, MAINTENANCE OR IN THE EVENT
All products must be installed by a
qualified installer and used in
conformance with all building, fire, and
environmental codes and other safety
requirements applicable to its
installation and use, including, but not
limited to, NFPA 30, NFPA 30A, NFPA
395 & NFPA 70. A qualified installer is
familiar with fuel systems installations
under the above stated building, fire,
and environmental codes and other
safety requirements for the particular
type of installation.
This product is only part of a fuel
dispensing system and additional
equipment and accessories, such as,
but not limited to, breakaway
connectors, shear valves, pressure
regulators, flow limiters, and other
safety devices may be necessary to
meet the applicable codes.
For maximum safety, we recommend
that all employees be trained as to the
location and procedure for turning off
power to th e en ti re syste m. Inst ruct ion s
regarding proper operation of the
equipment along with the appropriate
safety warnings should be posted in
plain view at the fuel island.
Before performing service or
maintenance (including changing of fuel
filters or strainers) or in the event of a
fuel spill, turn off and lock out all power
to the system. In battery-powered
pumps, disconnect power source. In
submersible pump applications, turn off
and lock out power at the master panel
and close any impact valves to the
submersible pump and any other
dispensers which use that submersible
pump. AC power can feed back into a
shut-off dispenser when dispensers
share a common submersible pump or
starter relay. Also block islands so no
vehicles can pull up to the dispenser
when the dispenser is being worked on.
DO NOT use Teflon tape for any pipe
threads in the product.
DO NOT use consumer pumps for
pumping fuel or additives into aircraft.
DO NOT use commercial pumps for
direct fueling of aircraft without filters
and separators necessary to ensure
product purity.
DO NOT use where sanitary design is
required (for food products for human
consumption) or with water-based
liquids.
DO NOT smoke near the pump or when
using the pump.
DO NOT use near open flame or
electrical equipment which may ignite
fumes.
DO NOT permit the dispensing of
gasoline or other petroleum products
into a vehicle with its motor running.
DO NOT permit the dispensing of
gasoline or other petroleum products
into unapproved containers or into
approved containers in or on vehicles
includin g tru cks. All conta iners mu st be
filled on the ground to prevent static
discharge. Always use Approved and
Listed hoses and nozzles with electric
pumps and dispensers.
DO NOT block open the nozzle in any
manner. Nozzles shall conform to UL
and NFPA code requirements for
attended or unattended service.
DO ensure that the pump is equipped
with proper filters based on the product
being dispensed and its intended use.
DO wear safety goggles and protective
clothes when dispensing any liquid
which may be potentially harmful or
hazardous.
DO keep all parts of body and loose
clothing clear of belts, pulleys, and
other exposed moving parts at all times.
OF A FUEL SPILL.
DO require washing and changing of
clothes if fuel is spilled on a person or
his/her clothing. Keep away from open
flames, sparks, or people smoking.
DO provide a receptacle for catching
product from pump/meter when
servicing.
DO clean up product spills on the
driveway. Turn off and lock out all
power prior to cleanup.
DO insure pump is properly grounded.
DO insure hose is compatible with fluid
being dispensed.
DO inspect hose, nozzle, and pump on
a regular basis for wear, damage, or
other conditions which may create a
safety or environmental hazard.
DO make sure all pipe threads are
properly cut and the inside reamed to
remove burrs. Use UL classified
gasoline-resisting compound on all
joints of gasoline handling piping.
Sealing compound must also be
resistant to Gasohol (Ethanol and
Methanol). Use gasoline-resistant pipe
compound on male threads only; pipe
compound used on female threads can
be squeezed into the supply line where
it can enter the product stream and
become lodged in the pump or meter.
DO ensure that junction box covers are
in place and properly tightened. Mating
surfaces between the box and cover
must be free of dirt, nicks, and
scratches. All unused entries into the
junction box must be properly plugged.
035282 Rev. 1267
GASBOY INTERNATIONAL LLC.
707 North Valley Forge Rd. Lansdale, PA, 19446 ●(215) 855-4631 ●FAX: (215) 855-0341
Page 3
FCC INFORMATION
The US Federal Communications Commission (FCC) requires specific information be supplied to
the users of any equipment which may emit radio frequency energy. Please read the following
information.
FCC PART 15
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection
against harmful interference when the device is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed in
accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful inter ference, in which
case, the user will be required to correct the interference at his own expense.
Keep Water Out .................................................................................. 7-2
Lubricate the Pumping Unit ................................................................. 7-2
Clean the Dial Face ............................................................................. 7-2
Clean the Strainer ............................................................................... 7-2
Change the Filter ................................................................................ 7-2
Adjust the Belts ................................................................................... 7-2
Preserve the Finish of Your Pumps .................................................... 7-3
Warranty
Contents-2 03/07/03
Page 7
Section 1
INTRODUCTION
PURPOSE
The GASBOY ASTRA Series 9820A Electronic Commercial Pumps Installation/Oper ation Manual
is provided to assist the installer in installing and operating the unit. This manual should be
supplied to the electrician prior to the installation of conduit and wiring to ensure the unit is
installed properly. Faulty installations are the major cause of unit malfunctions. The unit must be
installed and operated as described in this manual to ensure the reliability and proper operation of
the Series 9820A unit. In addition to installation information, this manual contains warnings,
safeguards and procedures on the use and care of the Series 9820A pumps. Be sure to leave this
manual with the pump owner after the installation is complete.
GENERAL DESCRIPTION
The GASBOY Series 9820A ASTRA (aboveground storage tank remote access) pump units are
UL-listed and are available in two models. Model 9822A is available in standard speed (up to 15
GPM/56 LPM) with an intermittent-duty motor. Model 9823A is available in high speed (up to 22
GPM/83LPM) with a continuous-duty motor. The deliver y rate varies depending upon installation
conditions and added accessories. Both models of the 9820A offer electronic registration of the
quantity dispensed.
NOTE: NFPA regulations do not allow tank-mounted pumps to be used for the resale of fuel.
The Series 9820A consists of two metal cabinet assemblies. One assembly is mounted on top of
the tank and contains the pumping unit, meter, electronic pulser, and all hydraulics. The hose and
nozzle are connected to this assembly. The second assembly is mounted at a height to permit
easy access by a user. It contains the electronic register, controls, display and nozzle boot.
The following lists detail the standard and optional features for the Series 9820A.
• Reset complete (switch detect) output which allows monitoring of the unit's operation when it
is connected to an automated fueling system
• Resettable electronic totalizer
• Discharge elbow
• Both models use a quiet and efficient gear pump which features an air eliminator, built into
the pump casting. The pump meter is a three piston, positive displacement meter which is
tested and calibrated for accuracy at any speed or pressure up to the maximum working
pressure of 50 psi.
• The standard pumping cabinet finish is white. The electronic r egister cabinet is black with a
blue graphics panel.
03/07/03 1-1
Page 8
GASBOY Series 9820A
Optional Features
• Pulser output drive line (open collector), capable of driving 1, 10, 100, 250, 500, or 1000
pulses per unit (gallons) or 1, 10, 100, or 250 pulses per unit (liters)
• RS-485 communication for direct connect to Gasboy CFN equipment
• Battery backup for display of last transaction and capture of remnant pulse count in the event
of a power failure
• Mechanical totalizer
• Dual stage solenoid valve
• A working voltage of 115 VAC (115/230 for motor) 60 HZ for domestic use, 230 VAC 50
HZ/60 HZ for international use
• Other options include Listed automatic nozzles, special lengths of Listed hose assembly,
All installations must conform with all building/fire codes, all Federal, State, and Local codes,
National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine Service Station Code
(NFPA 30A) codes and regulations. Canadian users must also comply with the Canadian
Electrical Code.
Plan your installation carefully. A pump cannot be expected to work satisfactorily unless the
installation is correct. Dispensing troubles, which seem to be pump-related, are frequently traced
to faulty installation. Review the following list of installation DO's and DON'T's to avoid potential
problems:
1. DO read the WARNINGS page at the fr ont of this manual, preceding the Table of Contents.
It contains important information regarding the safe use of your dispensing equipment.
2. DO install an emergency power cutoff. In addition to circuit breaker requirements of NFPA 70
and NFPA 30A, a single control which simultaneously removes AC power from all site
dispensing equipment is recommended. This control must be readily accessible, clearly
labeled, and in accordance with all local codes.
In a fuel management system application, the EMERGENCY STOP and STOP keys on the
console and/or the optional EMERGENCY STOP button on the Island Card Reader do not
remove AC power from equipment and under certain conditions, will not stop product flow.
In order to provide the highest level of safety to you, your employees, and customers, we
recommend that all employees be trained as to the location and procedure for turning off
power to the entire system.
3. DO have the pump installed by a competent installer/electrician.
4. DO install breakaway coupling on discharge hose. If using a high hose retriver, install
breakaway approximately 12" downstream of hose clamp on nozzle side of clamp.
5. DO NOT experiment with a pump if you are not sure the installation is correct.
6. DO NOT overload sub- or main breaker panels.
7. DO NOT use power line wir ing of inadequate capacity. (Use gauge specified by the wiring
diagram or wire chart provided in Section 4).
8. DO NOT use a circuit breaker of improper size. (See Section 4).
9. DO NOT use the GASBOY fuel dispensing equipment to remove water ballast from the
storage tank.
10. DO NOT use gaskets on covers of explosion-proof type boxes. The sealing compound found
around wires at various locations within conduit is a requirement of the National Electrical
Code and should not be disturbed. Ensure that the mating surfaces between the junction box
and cover are free of dirt, debris, nicks and scratches. Tighten junction box covers before
replacing panels.
11. DO NOT use knock-out boxes or flexible conduit for installing this unit. All power wires
should be run in threaded, rigid, metal conduit. All threaded connections must be drawn up
tight. All but one opening in the power junction box are provided with plugs at the factory. At
completion of the installation, it is the installer's responsibility to ensure that any unused
openings are plugged.
03/07/03 2-1
Page 10
GASBOY Series 9820A
VENT LINE
The vent line for standard units is vented to the atmosphere. Whenever possible, it is
recommended that the line be returned to the tank. A hole is pr ovided above the normal vent
opening to allow this line to exit the pumping unit and return to the tank.
VAPOR RECOVERY OPTION
This dispenser can be supplied with components necessary to provide vapor recovery. If the
dispenser is equipped for vapor recovery, a splitter is located in the pump housing. A 3/4"
discharge line will exit from the rear of the pump housing to return vapor/fluid to the tank. No
changes are required to the nozzle hook or boot assembly when using vapor re covery nozzles.
Please note that the vapor recovery nozzles approved for use ar e the "short spout" type. The
following nozzles and hose are approved for use with vapor recovery systems:
Nozzles: Emco Wheaton Model A4015
Husky Corp. Model 5010
OPW Model 211V
Hose: UL-Listed Hose Assembly
HOSE LENGTH ESTIMATOR
Use the chart on the next page to estimate the length of hose needed for your 9820A application.
The correct length will prevent the hose from touching the ground when the nozzle is placed into
the nozzle boot/hook arrangement of the register. This chart assumes that the 9820A register is
mounted on the standard pedestal and that the bottom of the pedestal is mounted flush with the
bottom of the tank. The illustration below provides a visual reference for the chart.
2-2 03/07/03
Page 11
Installation
Key for Chart Headings
Height Measurement from the ground to the hose connection assuming the
Tank height + 6" , standard units; tank height + 12" for vapor recovery units.
Hose Length Length of hose less nozzles and fittings.
Register Minimum Radius Indicates the closest the register assembly can be to the specified starting
Fueling Radius Indicates the approximate fueling radius. Measured from a point directly
pumping unit is mounted on top of the tank with the feet provided.
point; any closer than this distance may allow hose to touch the ground
when unit is not in use. This radius is measured starting from a point
directly below pumping unit discharge to the center of the nozzle boot/hook
of the register assembly.
below pumping unit discharge to the nozzle.
03/07/03 2-3
Page 12
GASBOY Series 9820A
TYPICAL INSTALLATION
2-4 03/07/03
Page 13
Installation
011930 BASE LAYOUT Models 9822A
(View 1 - Pumping Unit Assembly) 9823A
03/07/03 2-5
Page 14
GASBOY Series 9820A
011930 BASE LAYOUT Models 9822A
(View 2 - Register Assembly) 9823A
2-6 03/07/03
Page 15
Installation
011884 BASE LAYOUT Models 9822A
(Optional Post) 9823A
03/07/03 2-7
Page 16
GASBOY Series 9820A
011885 BASE LAYOUT Models 9822A
(Side and Rear Brackets - View 1) 9823A
2-8 03/07/03
Page 17
Installation
011885 BASE LAYOUT Models 9822A
(Side and Rear Brackets - View 2) 9823A
03/07/03 2-9
Page 18
Page 19
Section 3
CONTROL LINES
PURPOSE
This section is provided to familiarize the installer with the control inputs and outputs that are
available for the Series 9820A. It is recommended the installer read these descriptions to obtain a
better working knowledge of the unit in order to guide him in planning the site wiring. Reference
Section 4 for a specific wiring diagram and installation notes.
The Series 9820A may be provided for use with 230 VAC power for international applications.
The operating voltage for control lines to these units is shown in parentheses as (230 VAC Int'l).
If connecting the 9820A to a GASBOY fuel management system, refer to the appropriate fuel
management system Installation Manual for detailed installation information.
GROUND
To ensure proper operation of the equipment and provide the necessary safety factors, a good
ground line must be provided. A ground wire (prefer ably green) must be connected between the
ground screw of the register and the main electrical service panel. One (1) earth ground
connection is required per unit. The ground rod is to be a solid, corr osion-resistant conductor and
must be installed at the main electrical panel in accordance with the National Electrical Code. It
should be properly tied into the ground bus strip of the panel. We recommend the neutral and
ground bus strips be bonded together (unless prohibited by local codes).
MICRO FEED
The Micro Feed is a 115 VAC (230 VAC Int'l) input required to power the microprocessor of the
register's electronics. This power must always remain on and must be on a separate breaker from
the control lines (Pump Motor Feed). In a site configuration using multiple units, the power for the
microprocessors of up to 8 units can be supplied by one breaker.
MICRO NEUTRAL
The Micro Neutral is a return line for AC current fr om the microprocessor of the dispensing unit to
the breaker panel.
PUMP MOTOR FEED
The Pump Motor Feed is a 115VAC (230 VAC Int'l) input which is required to power the pump and
authorize the control line. This line is used to provide authorization for the unit ( when enabled
through the DIP switches). If this line is controlled by a fuel management system using solid state
relays, a resistor assembly must be installed between the Pump Motor Feed line and Feed Neutral
to prevent false triggering of the authorization input. The resistor assembly is 8.2K OHM, 10 Watt
(P/N C05818) for 115/230 VAC domestic and 30K OHM, 10 Watt (P/N C06683) for 230 VAC
international wiring.
03/07/03 3-1
Page 20
GASBOY Series 9820A
The Pump Motor Feed line is used to power the slow flow and fast flow valves (when installed) .
The power used to control the pump is also provided by this line. The Reset Complete signal
used for external monitoring of the pump originates from the Pump Motor Feed line.
NEUTRAL FEED
The Neutral Feed is the AC current return line back to the breaker panel for all attached devices
(pump motor, solenoid valves).
SLOW FLOW (RESET COMPLETE/SWITCH DETECT)
The Slow Flow line is a 115VAC (230VAC Int'l) output which is used to control the slow flow valve
of the optional solenoid valve. This line also indicates when the reset pr ocess is complete and the
unit is ready to dispense product. This line can be used in conjunction with a fuel management
system (for systems other than the Gasboy CFN Series systems).
This line is capable of supplying 300 mA AC maximum (170 mA maximum if already connected to
the optional valve). This line must not be shorted to any conduit or chassis metal, mis-
wired, or be conn ected to any equipment requiring more than stated maximum allowable
current. If these restrictions are not followed, damage to the CPU PCB will occur.
FAST FLOW
The Fast Flow line is a 115VAC (230VAC Int'l) output which is used to control the fast flow valve of
the optional solenoid valve.
This line is capable of supplying 300 mA AC maximum (170 mA maximum if already connected to
the optional valve). This line must not be shorted to any conduit or chassis metal, mis-
wired, or be conn ected to any equipment requiring more than stated maximum allowable
current. If these restrictions are not followed, damage to the CPU PCB will occur.
PHASE 2 FEED
The Phase 2 Feed is a hot feed which is the opposite phase of the pump motor feed. This line
and the pump motor feed are used for 230VAC motor applications. If connected to equipment
requiring control of the authorization input, the Phase 2 Feed should be switched through a
separate relay to prevent false triggering of the authorization signal.
PULSER
These lines are used to connect the pulser, mounted in the pumping unit, to the electronics in the
register assembly. These are DC voltage lines and provide the information necessary for the
register assembly to monitor the quantity of product dispensed. These lines are for internal use
only and must not be used for the pulse output (for external monitoring of the unit). Use the
optional Pulse Output interface if external pulses are required.
3-2 03/07/03
Page 21
Control Lines
PULSE OUTPUT
This option provides a DC pulser output to indicate the quantity dispensed. This is an open
collector output. This output can sink up to 150 milliamps DC at voltages up to 24 VDC. The
pulse rate can be configured by a sealable DIP switch for rates of 1, 10, 100, 250, 500, or 1000
pulses per gallon or 1, 10, 100 or 250 pulses per liter. This output should only be used when
monitoring of the unit's operation is desired.
RS-485
When the dispensing unit includes the optional RS-485 interface, RS-485 lines are provided. This
interface allows the user to connect a GASBOY CFN Series System directly to the Series 9820A
dispensing unit.
03/07/03 3-3
Page 22
Page 23
Section 4
WIRING
☎ Customers and installers having any questions pertaining to the installation should
contact their GASBOY distributor.
WIRING PRECAUTIONS
The quality of the electrical installation is a major factor in maintaining proper safety levels and
providing trouble-free operation of your GASBOY pump. To assure a quality installation, follow
these rules:
1. All wiring must be installed to conform with all building/fire codes, all Federal, State, and
Local codes, National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine
Service Station Code (NFPA 30A) codes and regulations. Canadian users must also comply
with the Canadian Electrical Code.
2. Use only threaded, rigid, metal conduit.
3. Use only UL-Labeled insulated gasoline- and oil-resistant stranded copper wiring of the
proper size.
4. Wire connections should be tightly spliced and secured with a wire nut; close off the open end
of the wire nut with electrical tape.
5. The line to the motor should be on a separate cir cuit and installed on a 20 to 30 AMP breaker
depending on the motor size and/or the voltage setting.
6. Install an emergency power cutoff. In addition to circuit breaker requirements of NFPA 70
and NFPA 30A, a single control which simultaneously removes AC power from all site
dispensing equipment is recommended. This control must be readily accessible, clearly
labeled, and in accordance with all local codes.
In a fuel management system application, the EMERGENCY STOP and STOP keys on the
console and/or the optional EMERGENCY STOP button on the Island Card Reader do not
remove AC power from equipment and under certain conditions, will not stop product flow.
In order to provide the highest level of safety to you, your employees, and customers, we
recommend that all employees be trained as to the location and procedure for turning off
power to the entire system.
WARNING:
To reduce the risk of electrical shock when servicing, turn off and lock out all power to
the pump.
AVERTISSEMENT
Pour réduire le risque de choc électrique lors de l'entretien/révision, coupez totalement
le courant à la pompe/distributeur.
7. Have the pump installed by a competent installer/electrician.
03/07/03 4-1
Page 24
GASBOY Series 9820A
GROUND
To ensure proper operation of the equipment and provide the necessary safety factors, this unit
must be grounded. A ground wire (preferably green) must be connected between the ground
screw of the register and the main electrical service panel. One (1) earth ground connection is
required per unit. The ground rod is to be a solid, corrosion-resistant conductor and must be
installed at the main electrical panel in accordance with the National Electrical Code. It should be
properly tied into the ground bus strip of the panel. We recommend the neutral and ground bus
strips be bonded together (unless prohibited by local codes).
CIRCUIT BREAKERS
Power to the unit must be supplied from dedicated breakers. No other equipment should be
powered from these breakers. AC power for the micro power must come from a different breaker
than that of the pump. This not only provides electrical isolation for the micro power, but allows
the unit to be disabled without shutting off power to the microprocessor PCB. The AC power for
the micro power may be grouped together for multiple units. It is recommended that no more than
8 units be supplied from one breaker.
PUMP MOTOR
Pumps are shipped from the factory with motors wired according to the specifications given on the
order as to kind of current, frequency and voltage.
Very often on installation, it becomes necessary to change the original setting to suit the AC power
source. To do this, locate the motor change-over plate and remove the scr ew which secures it in
place. Slide the plate so that the desired voltage, as marked on the plate, lines up with the screw
hole. Reinsert the screw and secure the plate in place.
Many motor failures result from improper setting of the motor change-over plate. If set for 115
VAC and a 230 VAC feed is used, the motor will burn out after running only a short time. If set for
230 VAC and a 115 VAC feed is used, the motor will run very slowly and the starting field will soon
burn out.
PULSE OUTPUT
The Pulse Output option provides the means for an external system to monitor the quantity that is
dispensed by the 9820A dispensing unit. A description of the interface is provided in Control Lines, Pulse Output, in Section 3. Consult the wiring diagrams provided in Wiring in Section 4,
along with the installation manual of the system that will be connected to the 9820A dispensing
unit.
RS-485
The RS-485 option provides the means for direct connection to a GASBOY CFN Series System.
Consult the wiring diagrams provided in Wiring in Section 4, along with the installation manual of
the CFN Series System for proper wiring.
4-2 03/07/03
Page 25
Wiring
WIRE SIZE
The AC wire size for the Micro Feed and Neutral should be 14 AWG. This gauge of wire will be
sufficient for runs up to 300 feet from the breaker panel to the dispensing unit. Sites with
distances over 300 feet should use 12 AWG wire. In cases where multiple units are powered from
the same breaker through the same wires, the gauge of the wires should be increased to handle
the added load according to the distance from the breaker panel.
The AC wire size of the Pump Motor Feed, Pump Motor, Feed Neutral, and Neutral is
dependent upon the HP rating of the pump motor, the voltage at which the pump will be oper ated
(115/230 VAC), and the distance from the circuit breaker panel to the pump. The chart below
should be used as a guide in selecting the proper wire size according to the specific installation
requirements.
The AC wire size for the Slow Flow, Fast Flow lines should be 14 AWG (when they are used).
The DC wire size for the Pulser lines connecting the pumping unit to the register assembly must
use four conductor, 18 AWG shielded cable (Belden 89418, Gasboy P/N C08864). This cable
allows the pulser wires to run in the same conduit as the AC wiring for the short distance between
the pumping unit and the register assembly. Belden 89418 is rated as follows:
Gas and Oil resistant insulation & jacket
18 AWG tinned, stranded, copper
Four conductors
300 volt maximum operating voltage
Aluminum/Mylar shielded with drain wire
Twisted-pair shielded cable is highly recommended for the Pulse Out put or RS-485 field wiring
(when they are used). This type of cable provides superior noise immunity and must be used for
distances over 100 feet or any time pulse output or RS-485 wiring is included in the same conduit
as the AC wires. This cable must meet the following specifications:
Conductor: 18 AWG stranded wire. 2 twisted-pairs.
Shield: Foil-wrapped 100% coverage and/or tinned copper braid 90% coverage
Drain Wire: Stranded, tinned copper, 20 AWG or larger/or braided shield
Voltage Rating: Maximum operating voltage of 600V
Environmental: Gas- and oil-resistant; suitable for wet or dry locations.
GASBOY can supply Belden 1063A (P/N C09655) which is a UL-Listed, 4-conductor cable that
meets the requirements listed above. NOTE: Belden 1063A is UL-Listed but not CSA listed.
Cable with a voltage rating of less than 600V must be installed in a conduit separate from all AC
wires.
See the GASBOY Fuel Management System Installation Manual for specific requirements.
03/07/03 4-3
Page 26
GASBOY Series 9820A
CONDUIT
All wiring to the GASBOY Series 9820A dispensing unit must be installed in threaded,
rigid, metal conduit. PVC IS NOT ACCEPTABLE. Wiring between the 9820A register and
pumping unit is installed in a single conduit. This includes the wiring for the AC control of the
pumping unit and the internal pulser. A special cable, as described in Section 4, Wire Size, must
be used for the connection between the pulser inside the pumping unit to the register assembly.
It is recommended that high voltage AC power wires to the register assembly (not between the
register and pumping unit), be installed in separate conduit from the low voltage pulser output
wires (when used). However, if AC and DC power wires share conduit, DC wiring must consist of
UL-Listed cable with the specifications described in Section 4, Wire Size. Only AC wires for the
system and dispensers can be installed in this conduit for this application. Wiring between a Fuel
Point Reader (FPR) and its pre-amp junction box is intrinsically safe and must be run in a conduit
with only other intrinsically safe wiring. It cannot be run in conduit with AC, DC, RS-485, or pulser
wiring, regardless of the cable type used. See the Fuel Point Reader Installation and Retrofit Manual, C35628 for details.
The GASBOY Warranty will not apply to any dispenser in which the AC and DC wires are run in
the same conduit, J-Box or wireway except as noted. The GASBOY Warranty will not apply to any
dispenser using PVC as conduit.
When the GASBOY Series 9820A dispensing unit is being installed with a fuel management
system other than a GASBOY system, see the manufacturer's installation manual for their specific
conduit requirements.
All wiring and conduit runs must conform with all building/fire codes, all Federal, State, and Local
codes, National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine Service
Station Code (NFPA 30A) codes and regulations. Canadian users must also comply with the
Canadian Electrical Code.
Use the following charts as a guideline for determining the necessary conduit sizes for wiring of
the GASBOY Series 9820A dispensing unit. When actually determining the size of conduit, it may
be necessary to increase the size of conduit because of a long run or large amount of bends. The
installer should determine the orientation of the wire runs according to the layout of the
components at the site and the applicable GASBOY wiring diagrams.
To determine conduit size needed, use the THHN/THWN Wire Areas table (left) to find the area
for each wire gauge. Add up all wire areas. Use the Areas of Tr ade Size Conduit Table (r ight) to
select the smallest number in the 25% fill area (based on NEC 501-1) that comes closest without
exceeding the total wire area.
4-4 03/07/03
Page 27
Wiring
TERMINAL BLOCK ID
The terminal blocks shown below are located in the register assembly.
03/07/03 4-5
Page 28
GASBOY Series 9820A
023866 WIRING DIAGRAM Models 9822A
Domestic 115/230 VAC 9823A
NOTES:
1. All wiring and conduit runs must conform with all building/fire codes, all Federal, State, and
Local codes, National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine
Service Station Code (NFPA 30A) codes and regulations. Canadian users must also comply
with the Canadian Electrical Code.
2. Pump motor can be wired as 230 VAC to reduce current draw. See breakaway view of 230 VAC PUMP MOTOR. All other wiring should remain the same except for the addition of the
L2 (requires 230 VAC breaker for control). If connected to equipment requiring control of the
authorization input, the Phase 2 Feed should be switched through a separate relay to prevent
false triggering of the authorization signal.
3. If the PUMP MOTOR line is contr olled by a fuel management system using solid state relays,
a resistor assembly must be installed between the Pump Motor Feed line and Neutral to
prevent false triggering of the authorization input. The resistor assembly is 8.2K OHM, 10
Watt (P/N C05818) for 115/230 VAC domestic and 30K OHM, 10 Watt (P/N C06683) for 230
VAC international wiring.
4. SLOW FLOW and FAST FLOW lines are typically used when connecting to an optional
valve. Each of these lines is capable of supplying 300 mA AC maximum (170 mA AC
maximum if already connected to the optional valve). These lines must not be short ed to
any conduit or chassis metal, mis-wired, or connected to any equipment requiring
more than stated maximum allowable current . If these restrictions are not followed,
damage to the CPU PCB will occur.
5. Use the wire size chart listed when determining the wire size for the control wiring.
4-6 03/07/03
Page 29
Wiring
023866 WIRING DIAGRAM Models 9822A
Domestic 115/230 VAC 9823A
WARNING:
Failure to follow the correct wiring diagram and all the listed notes and
precautions may result in damage to the CPU PCB.
03/07/03 4-7
Page 30
GASBOY Series 9820A
023867 WIRING DIAGRAM Models 9822A-2
International 230VAC 9823A-2
NOTES:
1. All wiring and conduit runs must conform with all building/fire codes, all Federal, State, and
Local codes, National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine
Service Station Code (NFPA 30A) codes and regulations. Canadian users must also comply
with the Canadian Electrical Code.
2. If the PUMP MOTOR line is contr olled by a fuel management system using solid state relays,
a resistor assembly must be installed between the Pump Motor Feed line and Neutral to
prevent false triggering of the authorization input. The resistor assembly is 30K OHM, 10
Watt (P/N C06683) for 230 VAC international wiring.
3. SLOW FLOW and FAST FLOW lines are typically used when connecting to an optional
valve. Each of these lines is capable of supplying 300 mA AC maximum (170 mA AC
maximum if already connected to the optional valve). These lines must not be short ed to
any conduit or chassis metal, mis-wired, or connected to any equipment requiring
more than stated maximum allowable current . If these restrictions are not followed,
damage to the CPU PCB will occur.
4. Use the wire size chart listed when determining the wire size for the control wiring.
4-8 03/07/03
Page 31
Wiring
023867 WIRING DIAGRAM Models 9822A-2
International 230VAC 9823A-2
WARNING:
Failure to follow the correct wiring diagram and all the listed notes and
precautions may result in damage to the CPU PCB.
03/07/03 4-9
Page 32
Page 33
Section 5
PUMP OPERATION
OVERVIEW
This section describes the operation of the pump. It shows how to access the electronic
components, how to set the internal switches, the optional battery back-up power supply, how to
view and reset the electronic totalizers using the actuator, how to operate the pump, and how to
lock the nozzle.
03/07/03 5-1
Page 34
GASBOY Series 9820A
ELECTRONIC COMPONENT ACCESS
Before attempting to start-up the 9820A, it is important to become familiar with the location of
some key components as well as the various switch-selectable operating modes.
1. Unlock and remove the front panel.
Remove the two screws located at the
top of the door assembly. Pull out on
the top of the door and lift the door
assembly to remove it.
2. Loosen the two screws located on the left
and right door support brackets and pivot
display panel down.
5-2 03/07/03
Page 35
Pump Operation
CPU SWITCH SETTINGS
The 9820A can be configured for
various operating conditions using the
switches located on the CPU PCB.
Check these switches and change
their settings if necessary. Switch
settings should be changed with the
power switch OFF. The new settings
are read by the CPU PCB when the
power is turned ON again.
SW1
SW1-1 Baud Rate
This switch is set to reflect the communication rate
of the GASBOY RS-485 pump loop; open for 9600
baud or closed for 1200 baud. The GASBOY CFN
system and TopKAT communicate at 9600 baud.
SW1-2 Mode
If the 9820 is controlled by a GASBOY
CFN or TopKAT electronic fuel
management system, the switch should
Mode
On-line
be open (on-line mode). If the 9820 is
controlled by a GASBOY Series 1000 or
TopKAT mechanical system, or
controlled by any non-GASBOY system,
or not controlled by any fuel
management system at all, the switch
should be closed (standalone mode).
NOTE: The 9820 is shipped in standalone mode.
SW1-3, SW1-4 Delay Time
These two switches set the delay time used by leak detectors in
submersible pump applications. The delay time is the period
between activation of the submersible pump and activation of the
slow flow valve. This time should be set according to the type of
leak detector installed on the submersible pump to allow a normal
leak test for each transaction. The delay time should be set to
zero seconds for suction pumps.
SW1-5
Not used.
Baud Rate
9600
SW1-2
Open
Closed Series 1000Standalone
SW1-1
Open
Fuel System
CFN
TopKAT top-mount
TopKAT electronic
None currentlyClosed1200
supported
Fuel System
CFN
TopKAT top-mount
TopKAT electronic
TopKAT Mechanical
All non-GASBOY systems
No fuel system
Delay Time
0 seconds
4 seconds
5 seconds
6 seconds
SW1-3
Closed
Closed
Open
OpenOpen
SW1-4
Closed
Open
Closed
03/07/03 5-3
Page 36
GASBOY Series 9820A
SW1-6 Authorization
This switch allows activation of the 9820A from
some types of fuel management systems. When
the switch is closed, a 115 VAC (230 VAC Int’l)
signal must be present on the Control Feed line
for pump activation to occur (required setting for
Series 1000, TopKAT mechanical, and all nonGASBOY systems ). When open, the 9800
Authorization
Yes
SW1-6
Closed
OpenNoCFN
Fuel System
Series 1000
TopKAT mechanical
All Non-GASBOY systems
TopKAT top-mount
TopKAT electronic
No fuel system
ignores the Control Feed line (required setting for
CFN, TopKAT electronic, or no fuel system).
SW1-7 Totalizers
This switch should be set to open for normal operation. When closed,
this switch enables the reset of the electronic totalizers. See
View/Reset Totalizers later in this section for details.
Reset
Normal
SW1-7Totalizers
Closed
Open
SW1-8
Not used.
SW2
This four-position switch pack serves a dual purpose: as an address setting when communicating
on the GASBOY RS-485 loop or TopKAT, or as a pulser output rate selector when pulser data is
sent to a fuel management system other than a GASBOY CFN or TopKAT.
Address Switches
A unique address identifier must be set when the
9820A is connected to the GASBOY RS-485 pump
loop via the 9820A RS-485 I/F PCB. Because there
are 16 possible address combinations, up to 16 units
(single or twin) may be connected to the pump loop.
Addressing should start at 1 and continue
sequentially through 16. The physical wiring order
does not have to correspond with the address order;
that is the first unit on the RS-485 loop doesn't have
to be address 1. The char t at right gives the switch
settings and address selections.
When the 9820A is connected to external control
equipment other than a GASBOY CFN system
(standalone), the pulser signals are sent out via the 9820A
Pump I/F PCB. The pulse rate required by the monitoring
equipment can be configured by setting the switches as
shown in the chart at right. The pulse rate represents
pulses per gallon (PPG, domestic) or pulses per liter ( PPL,
international). For domestic units, the pulse rate can be up
to 1000 PPG. For international units, the pulse rate can be
up to 250 PPL for all other models. This switch may need
Pulse Rate SW2-1 SW2-2 SW2-3
1Closed
10
100
250
500
1000
None
None
OpenClosed
Closed
Open
Closed
Open
Closed
Open
Closed
Open
Open
Closed
Closed
Open
Open
ClosedClosed
Closed
Closed
Open
Open
Open
Open
to be sealed by a Weights and Measures paper seal if the
9820A is used for the resale of product.
Leading zeros are always suppressed in the hundreds and
tens positions to the left of the decimal point. When in
standalone mode, positions to the right of the decimal point
are displayed based on the pulse rate selected as shown in
the table at right.
Pulse Rate Display
1:1XXX.
10:1
100:1
250:1
500:1
1000:1
XXX.X
XXX.XX
XXX.XXX
XXX.XXX
XXX.XXX
Timeout Switch
When the 9820A is in standalone mode, it will turn off an
active hose if it doesn't detect pulses for 4 minutes, 15
seconds. This timeout feature can be disabled by setting
Timeout
Enabled
Disabled
SW2-4
Closed
Open
switch SW2-4 to OPEN.
03/07/03 5-5
Page 38
GASBOY Series 9820A
BATTERY BACK-UP POWER SUPPLY
9820A models can be equipped with an optional battery back-up power supply. This allows the
last transaction data to be displayed for a minimum of 15 minutes. After the batteries reach a
certain low-voltage point, the power will automatically shut off. If you need to shut off the battery
power before the low-voltage point is reached, momentarily disconnect, then re-connect, the cable
that plugs into P1 on the power supply.
VIEW/RESET TOTALIZER
Electronic Totalizer
The 9820A stores a running quantity total. This electronic totalizer works independent of the
optional mechanical totalizer that may be installed, and is shown as whole gallons (liters) on the
displays (decimal point is shown, although it is disregarded). The totalizer data is stored in
battery-backed memory. The 9820A is supplied with an actuator (shown in the above illustration)
which allows you to view and reset the electronic totalizer. When the 9820A is shipped, the
actuator is attached with a tie wrap to the electronic chassis behind the register door. At
installation or startup, cut the tie wrap and remove actuator. Retain for future use.
5-6 03/07/03
Page 39
Pump Operation
To view the pump totalizer, make sure the pump handle is off and no transaction is in progress.
Locate the unit of measure indication (i.e., GALLONS) below the display window. Touch this area
with the actuator as shown. The totalizer data will be displayed for 10 seconds. If more time is
needed, touch the actuator to the same area for an additional 10 second period.
To reset the electronic totalizer, follow the disassembly procedure outlined under Electronic Component Access earlier in this section. Turn off the breaker supplying the 9820A AC power .
Close SW1-7 on the CPU PCB. Hold the actuator against the totalizer bracket and have someone
turn the breaker on. The display should change to all zeroes. Remove the actuator and open
SW1-7.
NOTE: Returning switch 1-7 to the open position prevents the totalizer from being reset the next
Mechanical Totalizer
time the actuator is used to read it.
Some 9820A models contain an optional mechanical totalizer. The totalizer has 8 digits; 7 whole
gallons and 1 tenth-gallon column, 8 whole digits for liters. The mechanical totalizer is located on
the front right side of the pumping unit.
03/07/03 5-7
Page 40
GASBOY Series 9820A
OPERATING SEQUENCE
The exact sequence of events that occurs during the operation of the pump is determined by
various switch settings, inputs, and the user. A typical transaction is explained below.
1. Turn on the pump handle. If AC is present on the Pump Motor Feed line, the reset cycle
begins. The display:
• goes blank for one second
• shows all 8's for one second
• goes to 0.000 (gallons) or 0.00 (liters) and remains for one second.
The pump motor turns on. If equipped, the slow flow valve turns on.
2. The user begins to dispense fuel. Quantity will not be recorded on the display until 0.010
gallons (0.04 liters) are reached, however, all pulses will be sent out on the Pulse Output line,
if equipped. At 0.010 gallons (0.04 liters), the fast flow valve turns on, if equipped.
3. The pump continues to run until one of the following conditions occurs. These conditions turn
off all relays.
• The handle is turned off.
• The Pump Motor Feed line is turned off.
• A pulser error is detected.
• A timeout of 255 seconds is reached. If connected to a fuel management system, the
4. The 9820A continues to monitor for pulses until a 2 second period with no pulses occurs. At
timeout loaded into the system will be used.
• A quantity of 990.000 gallons (9900.00 liters) is reached. If connected to a fuel
management system, the limit set in the system will be used.
• The pump is halted by an operator of a fuel management system.
• An AC power failure occurs.
this time the transaction is considered completed.
5-8 03/07/03
Page 41
Pump Operation
NOZZLE LOCKING
A locking mechanism is supplied as part of the hook arrangement on each 9820A. This will allow
the unit to be locked thus preventing use of the dispenser. A lock with a shackle clearance of at
least 2-1/2" is required to lock the pump (i.e., Master No. 1LJ-D). T o lock the nozzle in place,
follow the instructions below:
1. Insert the nozzle onto the hook assembly with the nozzle tip inside of the boot.
2. Slide the rear bracket of the nozzle hook assembly upward until the holes near the bottom of
the nozzle are aligned.
3. Slide the open padlock through holes in the moveable and stationary portions of the hook
arrangement, thus capturing the nozzle in place. (Note that the four holes will not align until
the moveable bracket has been slid upward.)
4. Close the lock.
While the nozzle is locked in place, the nozzle cannot be removed from the nozzle hook and the
dispenser cannot be turned on.
03/07/03 5-9
Page 42
Page 43
Section 6
START-UP AND TEST
INSTALLATION COMPLETION CHECKLIST
Review the information below to verify the proper installation of the Series 9820A dispensing unit.
If the installation does not meet criteria listed, correct the problem before the start-up is
performed.
1. To avo id damage to the CPU PC board, verify that t he SLOW FLOW and FAST FLOW
wires are not shorted to any conduit or chassis metal, mis-wired, or connected to any
equipment requiring more than stated maximum allowable current.
2. The register and pumping unit must be properly secured.
3. All plumbing must be complete and tight. All liquid-carrying lines mu st be checked for leaks.
4. When DC pulse output lines are used in the pump for connecting to GASBOY fuel
management systems, the AC and DC wires must not share any conduits, junction boxes, or
troughs except as noted in Section 4, Wire Size.
5. All conduit work must be complete. All junction box covers must be secured. Conduits
should not be sealed until the wiring is verified through proper operation.
6. The unit must be properly grounded.
7. Before any testing begins, remove any water in the tank through a fill opening, using a
suitable pump. Do not use the GASBOY pump to remove water. Serious damage may
occur.
8. A sufficient volume of fuel must be put in the tank to insure that the liquid level is above the
bottom of the suction pipe.
03/07/03 6-1
Page 44
GASBOY Series 9820A
START-UP
After successfully verifying the installation against the completion checklist, the unit is ready for
start-up. Follow the procedure below to perform an orderly start-up of the Series 9820A.
1. Verify that all switches on the CPU PCB are set properly for the various operating conditions
as explained in Section 5.
2. Turn on the circuit breakers for the microprocessor.
3. Authorize the unit through the fuel management system, if available.
4. Remove the nozzle from its holder and turn on the pump handle. Verify that the display goes
through the proper reset sequence as explained in Section 5, Operating Sequence.
5. Dispense fuel. Verify that the high flow valve opens, if equipped. Check all plumbing for
leaks at this time.
6. Turn the pump handle off. Open the nozzle. No fuel should be dispensed at this time.
7. Verify that the correct quantity was recorded by the fuel management system, if available.
8. Run the unit through all standard calibration procedures.
9. Reset the electronic totalizer as described in View/Reset Totalizer in Section 5.
6-2 03/07/03
Page 45
Start-Up and Test
POST START-UP TESTS
Voltage
The incoming voltage to the pump should be checked and any reading not within 10% of rated
voltage should be corrected before testing is continued. It is good practice to take voltage
readings while the pump is operating on bypass and also while making a delivery. Any voltage
drop in excess of 10% during either of these operating states should be considered a low voltage
condition. Corrective action should be taken to insure an adequate power supply to the pump.
Tightness
After determining that the pump is operating satisfactorily and the system is fully primed, check the
pump and piping to make sure that all connections are tight.
Belts
Since belts do stretch slightly during the first few minutes of operation, check the belt tension after
completing the operational test; a properly tightened belt will permit twisting the belt 180 degrees
midway between the motor and pump pulleys.
On the 9822A and 9823A, the belt can be tightened by loosening the cap screw which holds the
idler arm and sliding the arm to obtain the correct belt tension of 6-3/4 lbs. (+
adjustment is complete, remember to retighten the cap screw.
Calibration
All GASBOY pumps are adjusted for accurate measure at the factory. However, since the
conditions of the installation can affect pump accuracy, it is the responsibility of the installer to
check the pump for accuracy and make any needed adjustments. Where required, it is the
owner's responsibility to report this device to the local Weights and Measures officials for their
inspection before the unit is put into service.
The adjustment of measurement is accomplished
by breaking the seal wire and removing the Seal
Pin. This will permit the Index Disc, to be turned
either counterclockwise (-), decreasing the
measurement, or clockwise (+), increasing the
measurement. A variation of approximately one
cubic inch in measurement is obtained by turning
the Index Disc five holes. After measurement
has been properly adjusted, the Seal Pin and
seal wire should be replaced.
3/4). When the
03/07/03 6-3
Page 46
Page 47
Section 7
PREVENTIVE MAINTENANCE
GENERAL
GASBOY pumps are designed and constructed to give many years of uninterrupted service. In
fact, operators report years of trouble-free operation with absolutely no service expense. Yet,
certain parts of a pump are bound to wear, and GASBOY therefore recommends a periodic
inspection, at least twice a year, for such things as fuel leaks, belt tension and condition,
lubrication and strainer cleanliness. If such a procedure is followed, any small adjustments that
are necessary can be made before expensive, annoying breakdowns occur. The result of this
sound approach is continuous, profitable service from all of your GASBOY equipment.
To reduce the risk of electrical shock when servicing, turn off all power to the
pump.
HINTS FOR BETTER PUMP PERFORMANCE
Demand Competent Service
If your pump should stop or fail to operate properly, don't depend upon the repair service of a
general mechanic unless he is thoroughly familiar with the mechanism. Experience shows that the
repair results will be much more satisfactory if you demand the service of a competent
representative of the pump manufacturer. GASBOY has a Distributor Network which services fuel
dispensing and management systems in every section of the country.
Use Authorized Parts
Should excessive wear, rust, or corr osion of parts cause inefficient operation, it is always best to
replace them immediately; but if you want the best results and continuity of the Underwriters' Label
on your pump, be sure they are new authorized service parts supplied by GASBOY. Every part of
a pump is carefully designed for a particular purpose. If it is replaced by an incorrect or
substandard substitute, pump operation will be unsatisfactory. Always use new gaskets or seals
when servicing or rebuilding GASBOY equipment; do not re-use the old ones.
Operate With Reasonable Care
Like any machine, the pump that is operated with reasonable care will last longer and give better
service. Abuse should be avoided (such as dropping the nozzle on the ground, operating the unit
with a dirty strainer, dragging the hose across the concrete island or driveway, running the pump
with the nozzle closed for more than two minutes, etc.). The time and care given to your pumps
will be returned to you in the form of dependable service.
WARNING:
03/07/03 7-1
Page 48
GASBOY Series 9820A
PREVENTIVE MAINTENANCE CHECKLIST
Keep Water Out
Water tends to collect in storage tanks. This is due to moisture-laden air being drawn into the
storage tank and condensing, or to defective fill openings that are not properly protected with
watertight covers. Storage tanks should be checked after every fill-up for water and removed with
a sump pump, to forestall serious damage to equipment. Water, sediment, and other foreign
matter that accumulates in the tank can be drawn up into the pump and cause failures.
Lubricate the Pumping Unit
The pumping unit should be lubricated every six months or every 100,000 gallons. Do this by
applying a few drops of a light grade oil (SAE 10) to the felt pad located on the pump body slightly
above the shaft which connects to the pump pulley. Oil used should be suitable for temperatures
ranging from -40 F to 180 F.
Clean the Dial Face
Clean the dial face with a soft, clean, damp cloth as often as necessary.
Clean the Strainer
Clean the strainer immediately after the pump has been installed and tested, and again after a few
hundred gallons have been delivered. Thereafter, once every six months, or as required.
The symptoms of a dirty or clogged strainer in a pump are slow delivery, noisy operation, and
pulsation. To clean the strainer, turn off AC power to the pump. Locate the Suction Strainer Cap
on the plumbing unit and unscrew it to access and remove the strainer. Use compressed air
blow the dirt out of the strainer.
*Wear protective safety goggles or glasses when using compressed air.
Change the Filter
If the unit is equipped with a filter, check and change it at regular inter vals. A dirty filter in a pump
will cause a slower delivery rate. Refer to the accessories section of your parts manual to ensure
that you replace the filter with one designed for your model. Always use a drip pan directly below
the filter when removing the cartridges to pr event contamination of both the soil and the electrical
components within the cabinet.
Adjust the Belts
With the proper care, belts will give exceptionally good ser vice. A loose belt not only cuts down
dispensing speed, due to slipping, but also results in excessive wear. A properly tightened belt will
allow twisting the belt 180 degrees midway between the motor and the pump pulleys.
On the 9822A and 9823A models, the belt can be tightened by loosening the cap screw which
holds the idler arm and sliding the arm to obtain the correct belt tension of 6 3/4 lbs (+
the adjustment is complete, remember to retighten the cap screw.
3/4). When
* to
7-2 03/07/03
Page 49
Preventive Maintenance
Preserve the Finish of Your Pumps
Nearly all gasoline pumps are installed outdoors where their surfaces are subjected to the action
of the weather. As a result, it is necessary to give the finish a r easonable amount of care if an
attractive appearance is to be maintained.
The finish on GASBOY pump housings is a heat baked urethane paint. The life of this finish can
be lengthened several years if, at regular intervals, the painted surfaces are thor oughly cleaned
with a high grade automobile polish and then protected with a coat of paste wax. Do not use
abrasive cleaners or polish. Do not use high-pressure spraying equipment.
03/07/03 7-3
Page 50
GW01 - 6/04/02 Rev. 1
WARRANTY
General Statements:
Gasboy International LLC. warrants all new equipment manufactured by Gasboy agai nst defective material and/or workmanship, for t he warranty
period specified below, when the equipment i s installed in accordanc e with specifications prepared by Gasboy.
This warranty does not cover damage caused by acci dent, abuse, Acts of God, lack of surveillance of autom atic recording systems, negligence,
mis-application, faulty installation, i mproper or unauthorized maintenance, installation or use in vi ol ation of product manuals, instructions , or warnings.
Under no circumstanc e shall Gasboy be liable for any indirect, special, or cons equential damages, losses, or expenses to include, but not limited
to, loss of product, los s of profits, litigation fees, or the use, or inability to use, our produc t for any for any purpose whatsoever.
Parts Only - During the warranty period, Gasboy will, at its option, repair or replace def ective parts returned transportat i on prepai d to its factory.
On-Site Labor Included - Gasboy will also provide, within the Continental United St ates and during the warranty period, the services of an
Authorized Service Representati ve (A SR) for on-site repair or replacem ent of defective parts.
Replacement Parts - Any system components that are not part of the original system order, i ncluding Island Card Readers, Pump Control Units, et c.,
are considered replacement part s.
Equipment Term Coverage
Commercial Pumps and Dispensers
Full-Cabinet Consumer Pumps
Small Transfer Pumps, Meters,
Pressure Regulators
Keytrol One year from date of instal l ation or 18 mos. from date of
Fuel Management Systems :
- CFN/ Profit Point
- Series 1000/Fleetkey
- TopKAT
- Fuel Point Readers
(sold with new systems)
Additional Fuel Point Items:
- Fuel Point Readers sold for
retrofitting existing sys t ems.
- Fuel Point vehicle and dispenser
components.
Encoders, Embos sers, Modems,
CRTs, and Logger Printers
Air Diaphragm Pumps Three years from date of purchas e (for full warranty
Items not m anufactured by Gasboy
(ex. automatic nozzles, hoses, swivels,
etc.)
Replacement Parts One year from date of Gasboy International's invoice to the
To the extent permitted by law, this warranty is made in lieu of all other warranties, expressed or implied, inc l udi ng warranti es of freedom from patent
infringement, or merchant ability, or fitness for a particular purpose, or arising from a cours e of dealing or usage of trade. No one is authori zed t o
vary the terms of the warranty nor may anyone make any warranty of representation, or assume any liability other than that herein stat ed, in
connection with the sale described herein. The acceptance of any order by Gasboy International is expressly made subject to the purchaser's
agreement to these condit i ons.
One year from date of instal l at i on or 18 mos. from date of
Gasboy International’s invoi ce to the purchaser, whichever
comes first.
One year from date of instal l at i on or 18 mos. from date of
Gasboy International’s invoi ce to the purchaser, whichever
comes first.- Excepting the Model 2020 Hand Pump, which
has a 90-day warranty from date of GASBOY International’s
invoice.
Gasboy International’s invoi ce to the purchaser, whichever
comes first.
One year from date of start-up or 15 mos. from date of
Gasboy International’s invoi ce to the purchaser, whichever
comes first .- The basic warranty only applies to s ys tems
which have been started up by a Gasboy Authorized Servi ce
Representative (ASR).
One year from date of start-up or 15 mos. from date of
Gasboy International’s invoi ce to the purchaser,
whichever comes first.
Purchased with Fuel Management Syst em (Encoders,
Embossers only):
90 days from the date of s tart-up by a Gasboy ASR, or 180
days from date of Gasboy I nternational's invoice, whichever
occurs first.
Purchased with Fuel Management System
(Modems, CRTs, and Logger Printers only):
Matches system warranty.
Purchased Separately:
90 days from date of Gasboy I nt ernational's
invoice to the purchaser.
description, see Price List).
Not warranted by Gasboy International (consul t original
manufacturer’s warranty).
purchaser.
Parts and Labor.
Parts Only.
Parts and Labor.
Parts and Labor.
Parts Only.
Purchased with System
(Encoders, Embos sers only):
Parts only.
Purchased with System (Modems,
CRTs, Logger Printers only):
Matches system warranty.