Gasboy 9820A User Manual

Page 1
SERIES 9820A
ELECTRONIC
COMMERCIAL PUMPS
INSTALLATION/OPERATION
MANUAL
035391
INSTALLERS - IMPORTANT
In addition to installation information, this manual contains warnings, safeguards and procedures on the use and care of the Series 9820A pumps. Please leave this manual with the pump owner after the installation is complete.
The information in this document is confidential and proprietary. No further disclosure shall be made without permission from Gasboy International LLC. Gasboy International believes that the information in this document is accurate and reliable. However, we assume no responsibility for its use, nor for any infringements of patents or other rights of third parties resulting from its use. We reserve the right to make changes at any time without notice.
Copyright 2003 by Gasboy International LLC All rights reserved.
GASBOY INTERNATIONAL LLC
Page 2
IMPORTANT WARNINGS AND SAFEGUARDS
Gasoline and petroleum products are flammable. To avoid injury or death to persons or damage to equipment or property, follow these listed warnings and other warnings and precautions outlined in this manual when installing, using, or working around this equipment. Check with GASBOY Technical Services for compatibility of liquids with pump materials.
TURN OFF AND LOCK OUT ALL POWER TO PUMP BEFORE PERFORMING SERVICE, MAINTENANCE OR IN THE EVENT
All products must be installed by a qualified installer and used in conformance with all building, fire, and environmental codes and other safety requirements applicable to its installation and use, including, but not limited to, NFPA 30, NFPA 30A, NFPA 395 & NFPA 70. A qualified installer is familiar with fuel systems installations under the above stated building, fire, and environmental codes and other safety requirements for the particular type of installation.
This product is only part of a fuel dispensing system and additional equipment and accessories, such as, but not limited to, breakaway connectors, shear valves, pressure regulators, flow limiters, and other safety devices may be necessary to meet the applicable codes.
For maximum safety, we recommend that all employees be trained as to the location and procedure for turning off power to th e en ti re syste m. Inst ruct ion s regarding proper operation of the equipment along with the appropriate safety warnings should be posted in plain view at the fuel island.
Before performing service or maintenance (including changing of fuel filters or strainers) or in the event of a fuel spill, turn off and lock out all power to the system. In battery-powered pumps, disconnect power source. In submersible pump applications, turn off and lock out power at the master panel and close any impact valves to the submersible pump and any other dispensers which use that submersible pump. AC power can feed back into a shut-off dispenser when dispensers share a common submersible pump or starter relay. Also block islands so no vehicles can pull up to the dispenser when the dispenser is being worked on.
DO NOT use Teflon tape for any pipe threads in the product.
DO NOT use consumer pumps for pumping fuel or additives into aircraft.
DO NOT use commercial pumps for direct fueling of aircraft without filters and separators necessary to ensure product purity.
DO NOT use where sanitary design is required (for food products for human consumption) or with water-based liquids.
DO NOT smoke near the pump or when using the pump.
DO NOT use near open flame or electrical equipment which may ignite fumes.
DO NOT permit the dispensing of gasoline or other petroleum products into a vehicle with its motor running.
DO NOT permit the dispensing of gasoline or other petroleum products into unapproved containers or into approved containers in or on vehicles includin g tru cks. All conta iners mu st be filled on the ground to prevent static discharge. Always use Approved and Listed hoses and nozzles with electric pumps and dispensers.
DO NOT block open the nozzle in any manner. Nozzles shall conform to UL and NFPA code requirements for attended or unattended service.
DO ensure that the pump is equipped with proper filters based on the product being dispensed and its intended use.
DO wear safety goggles and protective clothes when dispensing any liquid which may be potentially harmful or hazardous.
DO keep all parts of body and loose clothing clear of belts, pulleys, and other exposed moving parts at all times.
OF A FUEL SPILL.
DO require washing and changing of
clothes if fuel is spilled on a person or his/her clothing. Keep away from open flames, sparks, or people smoking.
DO provide a receptacle for catching product from pump/meter when servicing.
DO clean up product spills on the driveway. Turn off and lock out all power prior to cleanup.
DO insure pump is properly grounded. DO insure hose is compatible with fluid
being dispensed. DO inspect hose, nozzle, and pump on
a regular basis for wear, damage, or other conditions which may create a safety or environmental hazard.
DO make sure all pipe threads are properly cut and the inside reamed to remove burrs. Use UL classified gasoline-resisting compound on all joints of gasoline handling piping. Sealing compound must also be resistant to Gasohol (Ethanol and Methanol). Use gasoline-resistant pipe compound on male threads only; pipe compound used on female threads can be squeezed into the supply line where it can enter the product stream and become lodged in the pump or meter.
DO ensure that junction box covers are in place and properly tightened. Mating surfaces between the box and cover must be free of dirt, nicks, and scratches. All unused entries into the junction box must be properly plugged.
035282 Rev. 1267
GASBOY INTERNATIONAL LLC.
707 North Valley Forge Rd. Lansdale, PA, 19446 (215) 855-4631 FAX: (215) 855-0341
Page 3
FCC INFORMATION
The US Federal Communications Commission (FCC) requires specific information be supplied to the users of any equipment which may emit radio frequency energy. Please read the following information.
FCC PART 15
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the device is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful inter ference, in which case, the user will be required to correct the interference at his own expense.
Page 4
Page 5
CONTENTS
IMPORTANT WARNINGS AND SAFEGUARDS
FCC Information
Section 1: INTRODUCTION
Purpose .................................................................................................... 1-1
General Description .................................................................................. 1-1
Standard Features............................................................................... 1-1
Optional Features ................................................................................ 1-2
Section 2: INSTALLATION
Installation Precautions ............................................................................ 2-1
Vapor Recovery Option ............................................................................ 2-2
Hose Length Estimator ............................................................................. 2-2
Typical Installation .................................................................................... 2-4
011930 Base Layout (View 1 - Pumping Unit Assembly).......................... 2-5
011930 Base Layout (View 2 - Register Assembly).................................. 2-6
011884 Base Layout (Optional Post) ........................................................ 2-7
011885 Base Layout (Side and Rear Brackets - View 1).......................... 2-8
011885 Base Layout (Side and Rear Brackets - View 2).......................... 2-9
Section 3: CONTROL LINES
Purpose .................................................................................................... 3-1
Ground ..................................................................................................... 3-1
Micro Feed ................................................................................................ 3-1
Micro Neutral............................................................................................. 3-1
Pump Motor Feed .................................................................................... 3-1
Neutral Feed ............................................................................................ 3-2
Slow Flow (Reset Complete/Switch Detect).............................................. 3-2
Fast Flow................................................................................................... 3-2
Phase 2 Feed ........................................................................................... 3-2
Pulser ....................................................................................................... 3-2
Pulse Output.............................................................................................. 3-3
RS-485...................................................................................................... 3-3
Section 4: WIRING
Wiring Precautions ................................................................................... 4-1
Ground ..................................................................................................... 4-2
Circuit Breakers ........................................................................................ 4-2
Pump Motor .............................................................................................. 4-2
Pulse Output ............................................................................................. 4-2
RS-485 ..................................................................................................... 4-2
Wire Size .................................................................................................. 4-3
Conduit ..................................................................................................... 4-4
Terminal Block ID...................................................................................... 4-5
023866 Wiring Diagram (9822A, 9823A) .................................................. 4-6
023867 Wiring Diagram (9822A-25, 9823A-25)........................................ 4-8
03/07/03 Contents-1
Page 6
GASBOY Series 9820A
Section 5: PUMP OPERATION
Overview ................................................................................................... 5-1
Electronic Component Access .................................................................. 5-2
CPU Switch Settings................................................................................. 5-3
Battery Back-up Power Supply.................................................................. 5-6
View/Reset Totalizers................................................................................ 5-6
Electronic Totalizer............................................................................... 5-6
Mechanical Totalizer............................................................................ 5-7
Operating Sequence ................................................................................. 5-8
Nozzle Locking ......................................................................................... 5-9
Section 6: START-UP AND TEST
Installation Completion Checklist ............................................................. 6-1
Start-Up .................................................................................................... 6-1
Post Start-Up Tests .................................................................................. 6-2
Voltage ................................................................................................ 6-2
Tightness ............................................................................................. 6-2
Belts .................................................................................................... 6-2
Calibration ........................................................................................... 6-2
Section 7: PREVENTIVE MAINTENANCE
General .................................................................................................... 7-1
Hints for Better Pump Performance ......................................................... 7-1
Demand Competent Service................................................................ 7-1
Use Authorized Parts........................................................................... 7-1
Operate With Reasonable Care........................................................... 7-1
Preventive Maintenance Checklist ........................................................... 7-2
Keep Water Out .................................................................................. 7-2
Lubricate the Pumping Unit ................................................................. 7-2
Clean the Dial Face ............................................................................. 7-2
Clean the Strainer ............................................................................... 7-2
Change the Filter ................................................................................ 7-2
Adjust the Belts ................................................................................... 7-2
Preserve the Finish of Your Pumps .................................................... 7-3
Warranty
Contents-2 03/07/03
Page 7
Section 1
INTRODUCTION
PURPOSE
The GASBOY ASTRA Series 9820A Electronic Commercial Pumps Installation/Oper ation Manual is provided to assist the installer in installing and operating the unit. This manual should be supplied to the electrician prior to the installation of conduit and wiring to ensure the unit is installed properly. Faulty installations are the major cause of unit malfunctions. The unit must be installed and operated as described in this manual to ensure the reliability and proper operation of the Series 9820A unit. In addition to installation information, this manual contains warnings, safeguards and procedures on the use and care of the Series 9820A pumps. Be sure to leave this manual with the pump owner after the installation is complete.
GENERAL DESCRIPTION
The GASBOY Series 9820A ASTRA (aboveground storage tank remote access) pump units are UL-listed and are available in two models. Model 9822A is available in standard speed (up to 15 GPM/56 LPM) with an intermittent-duty motor. Model 9823A is available in high speed (up to 22 GPM/83LPM) with a continuous-duty motor. The deliver y rate varies depending upon installation conditions and added accessories. Both models of the 9820A offer electronic registration of the quantity dispensed.
NOTE: NFPA regulations do not allow tank-mounted pumps to be used for the resale of fuel.
The Series 9820A consists of two metal cabinet assemblies. One assembly is mounted on top of the tank and contains the pumping unit, meter, electronic pulser, and all hydraulics. The hose and nozzle are connected to this assembly. The second assembly is mounted at a height to permit easy access by a user. It contains the electronic register, controls, display and nozzle boot.
The following lists detail the standard and optional features for the Series 9820A.
Standard Features
One-inch high, 6-digit, backlighted LCD display
1000:1 dual-phase, error-checking pulser (gallons); 250:1 dual-phase, er ror-checking pulser
(liters)
AC authorization line for control of the unit
Reset complete (switch detect) output which allows monitoring of the unit's operation when it
is connected to an automated fueling system
Resettable electronic totalizer
Discharge elbow
Both models use a quiet and efficient gear pump which features an air eliminator, built into
the pump casting. The pump meter is a three piston, positive displacement meter which is tested and calibrated for accuracy at any speed or pressure up to the maximum working pressure of 50 psi.
The standard pumping cabinet finish is white. The electronic r egister cabinet is black with a
blue graphics panel.
03/07/03 1-1
Page 8
GASBOY Series 9820A
Optional Features
Pulser output drive line (open collector), capable of driving 1, 10, 100, 250, 500, or 1000
pulses per unit (gallons) or 1, 10, 100, or 250 pulses per unit (liters)
RS-485 communication for direct connect to Gasboy CFN equipment
Battery backup for display of last transaction and capture of remnant pulse count in the event
of a power failure
Mechanical totalizer
Dual stage solenoid valve
A working voltage of 115 VAC (115/230 for motor) 60 HZ for domestic use, 230 VAC 50
HZ/60 HZ for international use
Other options include Listed automatic nozzles, special lengths of Listed hose assembly,
Listed dual swivels, UL-recognized filters, vapor recovery, and vapor recovery ready.
1-2 03/07/03
Page 9
Section 2
INSTALLATION
INSTALLATION PRECAUTIONS
All installations must conform with all building/fire codes, all Federal, State, and Local codes, National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine Service Station Code (NFPA 30A) codes and regulations. Canadian users must also comply with the Canadian Electrical Code.
Plan your installation carefully. A pump cannot be expected to work satisfactorily unless the installation is correct. Dispensing troubles, which seem to be pump-related, are frequently traced to faulty installation. Review the following list of installation DO's and DON'T's to avoid potential problems:
1. DO read the WARNINGS page at the fr ont of this manual, preceding the Table of Contents. It contains important information regarding the safe use of your dispensing equipment.
2. DO install an emergency power cutoff. In addition to circuit breaker requirements of NFPA 70 and NFPA 30A, a single control which simultaneously removes AC power from all site dispensing equipment is recommended. This control must be readily accessible, clearly labeled, and in accordance with all local codes.
In a fuel management system application, the EMERGENCY STOP and STOP keys on the
console and/or the optional EMERGENCY STOP button on the Island Card Reader do not remove AC power from equipment and under certain conditions, will not stop product flow.
In order to provide the highest level of safety to you, your employees, and customers, we
recommend that all employees be trained as to the location and procedure for turning off power to the entire system.
3. DO have the pump installed by a competent installer/electrician.
4. DO install breakaway coupling on discharge hose. If using a high hose retriver, install breakaway approximately 12" downstream of hose clamp on nozzle side of clamp.
5. DO NOT experiment with a pump if you are not sure the installation is correct.
6. DO NOT overload sub- or main breaker panels.
7. DO NOT use power line wir ing of inadequate capacity. (Use gauge specified by the wiring diagram or wire chart provided in Section 4).
8. DO NOT use a circuit breaker of improper size. (See Section 4).
9. DO NOT use the GASBOY fuel dispensing equipment to remove water ballast from the storage tank.
10. DO NOT use gaskets on covers of explosion-proof type boxes. The sealing compound found around wires at various locations within conduit is a requirement of the National Electrical Code and should not be disturbed. Ensure that the mating surfaces between the junction box and cover are free of dirt, debris, nicks and scratches. Tighten junction box covers before replacing panels.
11. DO NOT use knock-out boxes or flexible conduit for installing this unit. All power wires should be run in threaded, rigid, metal conduit. All threaded connections must be drawn up tight. All but one opening in the power junction box are provided with plugs at the factory. At completion of the installation, it is the installer's responsibility to ensure that any unused openings are plugged.
03/07/03 2-1
Page 10
GASBOY Series 9820A
VENT LINE
The vent line for standard units is vented to the atmosphere. Whenever possible, it is recommended that the line be returned to the tank. A hole is pr ovided above the normal vent opening to allow this line to exit the pumping unit and return to the tank.
VAPOR RECOVERY OPTION
This dispenser can be supplied with components necessary to provide vapor recovery. If the dispenser is equipped for vapor recovery, a splitter is located in the pump housing. A 3/4" discharge line will exit from the rear of the pump housing to return vapor/fluid to the tank. No changes are required to the nozzle hook or boot assembly when using vapor re covery nozzles. Please note that the vapor recovery nozzles approved for use ar e the "short spout" type. The following nozzles and hose are approved for use with vapor recovery systems:
Nozzles: Emco Wheaton Model A4015 Husky Corp. Model 5010 OPW Model 211V Hose: UL-Listed Hose Assembly
HOSE LENGTH ESTIMATOR
Use the chart on the next page to estimate the length of hose needed for your 9820A application. The correct length will prevent the hose from touching the ground when the nozzle is placed into the nozzle boot/hook arrangement of the register. This chart assumes that the 9820A register is mounted on the standard pedestal and that the bottom of the pedestal is mounted flush with the bottom of the tank. The illustration below provides a visual reference for the chart.
2-2 03/07/03
Page 11
Installation
Key for Chart Headings
Height Measurement from the ground to the hose connection assuming the
Tank height + 6" , standard units; tank height + 12" for vapor recovery units.
Hose Length Length of hose less nozzles and fittings. Register Minimum Radius Indicates the closest the register assembly can be to the specified starting
Fueling Radius Indicates the approximate fueling radius. Measured from a point directly
pumping unit is mounted on top of the tank with the feet provided.
point; any closer than this distance may allow hose to touch the ground when unit is not in use. This radius is measured starting from a point directly below pumping unit discharge to the center of the nozzle boot/hook of the register assembly.
below pumping unit discharge to the nozzle.
03/07/03 2-3
Page 12
GASBOY Series 9820A
TYPICAL INSTALLATION
2-4 03/07/03
Page 13
Installation
011930 BASE LAYOUT Models 9822A
(View 1 - Pumping Unit Assembly) 9823A
03/07/03 2-5
Page 14
GASBOY Series 9820A
011930 BASE LAYOUT Models 9822A
(View 2 - Register Assembly) 9823A
2-6 03/07/03
Page 15
Installation
011884 BASE LAYOUT Models 9822A
(Optional Post) 9823A
03/07/03 2-7
Page 16
GASBOY Series 9820A
011885 BASE LAYOUT Models 9822A
(Side and Rear Brackets - View 1) 9823A
2-8 03/07/03
Page 17
Installation
011885 BASE LAYOUT Models 9822A
(Side and Rear Brackets - View 2) 9823A
03/07/03 2-9
Page 18
Page 19
Section 3
CONTROL LINES
PURPOSE
This section is provided to familiarize the installer with the control inputs and outputs that are available for the Series 9820A. It is recommended the installer read these descriptions to obtain a better working knowledge of the unit in order to guide him in planning the site wiring. Reference Section 4 for a specific wiring diagram and installation notes.
The Series 9820A may be provided for use with 230 VAC power for international applications. The operating voltage for control lines to these units is shown in parentheses as (230 VAC Int'l).
If connecting the 9820A to a GASBOY fuel management system, refer to the appropriate fuel management system Installation Manual for detailed installation information.
GROUND
To ensure proper operation of the equipment and provide the necessary safety factors, a good ground line must be provided. A ground wire (prefer ably green) must be connected between the ground screw of the register and the main electrical service panel. One (1) earth ground connection is required per unit. The ground rod is to be a solid, corr osion-resistant conductor and must be installed at the main electrical panel in accordance with the National Electrical Code. It should be properly tied into the ground bus strip of the panel. We recommend the neutral and ground bus strips be bonded together (unless prohibited by local codes).
MICRO FEED
The Micro Feed is a 115 VAC (230 VAC Int'l) input required to power the microprocessor of the register's electronics. This power must always remain on and must be on a separate breaker from the control lines (Pump Motor Feed). In a site configuration using multiple units, the power for the microprocessors of up to 8 units can be supplied by one breaker.
MICRO NEUTRAL
The Micro Neutral is a return line for AC current fr om the microprocessor of the dispensing unit to the breaker panel.
PUMP MOTOR FEED
The Pump Motor Feed is a 115VAC (230 VAC Int'l) input which is required to power the pump and authorize the control line. This line is used to provide authorization for the unit ( when enabled through the DIP switches). If this line is controlled by a fuel management system using solid state relays, a resistor assembly must be installed between the Pump Motor Feed line and Feed Neutral to prevent false triggering of the authorization input. The resistor assembly is 8.2K OHM, 10 Watt (P/N C05818) for 115/230 VAC domestic and 30K OHM, 10 Watt (P/N C06683) for 230 VAC international wiring.
03/07/03 3-1
Page 20
GASBOY Series 9820A
The Pump Motor Feed line is used to power the slow flow and fast flow valves (when installed) . The power used to control the pump is also provided by this line. The Reset Complete signal used for external monitoring of the pump originates from the Pump Motor Feed line.
NEUTRAL FEED
The Neutral Feed is the AC current return line back to the breaker panel for all attached devices (pump motor, solenoid valves).
SLOW FLOW (RESET COMPLETE/SWITCH DETECT)
The Slow Flow line is a 115VAC (230VAC Int'l) output which is used to control the slow flow valve of the optional solenoid valve. This line also indicates when the reset pr ocess is complete and the unit is ready to dispense product. This line can be used in conjunction with a fuel management system (for systems other than the Gasboy CFN Series systems).
This line is capable of supplying 300 mA AC maximum (170 mA maximum if already connected to the optional valve). This line must not be shorted to any conduit or chassis metal, mis-
wired, or be conn ected to any equipment requiring more than stated maximum allowable current. If these restrictions are not followed, damage to the CPU PCB will occur.
FAST FLOW
The Fast Flow line is a 115VAC (230VAC Int'l) output which is used to control the fast flow valve of the optional solenoid valve.
This line is capable of supplying 300 mA AC maximum (170 mA maximum if already connected to the optional valve). This line must not be shorted to any conduit or chassis metal, mis-
wired, or be conn ected to any equipment requiring more than stated maximum allowable current. If these restrictions are not followed, damage to the CPU PCB will occur.
PHASE 2 FEED
The Phase 2 Feed is a hot feed which is the opposite phase of the pump motor feed. This line and the pump motor feed are used for 230VAC motor applications. If connected to equipment requiring control of the authorization input, the Phase 2 Feed should be switched through a separate relay to prevent false triggering of the authorization signal.
PULSER
These lines are used to connect the pulser, mounted in the pumping unit, to the electronics in the register assembly. These are DC voltage lines and provide the information necessary for the register assembly to monitor the quantity of product dispensed. These lines are for internal use only and must not be used for the pulse output (for external monitoring of the unit). Use the optional Pulse Output interface if external pulses are required.
3-2 03/07/03
Page 21
Control Lines
PULSE OUTPUT
This option provides a DC pulser output to indicate the quantity dispensed. This is an open collector output. This output can sink up to 150 milliamps DC at voltages up to 24 VDC. The pulse rate can be configured by a sealable DIP switch for rates of 1, 10, 100, 250, 500, or 1000 pulses per gallon or 1, 10, 100 or 250 pulses per liter. This output should only be used when monitoring of the unit's operation is desired.
RS-485
When the dispensing unit includes the optional RS-485 interface, RS-485 lines are provided. This interface allows the user to connect a GASBOY CFN Series System directly to the Series 9820A dispensing unit.
03/07/03 3-3
Page 22
Page 23
Section 4
WIRING
Customers and installers having any questions pertaining to the installation should
contact their GASBOY distributor.
WIRING PRECAUTIONS
The quality of the electrical installation is a major factor in maintaining proper safety levels and providing trouble-free operation of your GASBOY pump. To assure a quality installation, follow these rules:
1. All wiring must be installed to conform with all building/fire codes, all Federal, State, and Local codes, National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine Service Station Code (NFPA 30A) codes and regulations. Canadian users must also comply with the Canadian Electrical Code.
2. Use only threaded, rigid, metal conduit.
3. Use only UL-Labeled insulated gasoline- and oil-resistant stranded copper wiring of the proper size.
4. Wire connections should be tightly spliced and secured with a wire nut; close off the open end of the wire nut with electrical tape.
5. The line to the motor should be on a separate cir cuit and installed on a 20 to 30 AMP breaker depending on the motor size and/or the voltage setting.
6. Install an emergency power cutoff. In addition to circuit breaker requirements of NFPA 70 and NFPA 30A, a single control which simultaneously removes AC power from all site dispensing equipment is recommended. This control must be readily accessible, clearly labeled, and in accordance with all local codes.
In a fuel management system application, the EMERGENCY STOP and STOP keys on the
console and/or the optional EMERGENCY STOP button on the Island Card Reader do not remove AC power from equipment and under certain conditions, will not stop product flow.
In order to provide the highest level of safety to you, your employees, and customers, we
recommend that all employees be trained as to the location and procedure for turning off power to the entire system.
WARNING:
To reduce the risk of electrical shock when servicing, turn off and lock out all power to the pump.
AVERTISSEMENT
Pour réduire le risque de choc électrique lors de l'entretien/révision, coupez totalement le courant à la pompe/distributeur.
7. Have the pump installed by a competent installer/electrician.
03/07/03 4-1
Page 24
GASBOY Series 9820A
GROUND
To ensure proper operation of the equipment and provide the necessary safety factors, this unit must be grounded. A ground wire (preferably green) must be connected between the ground screw of the register and the main electrical service panel. One (1) earth ground connection is required per unit. The ground rod is to be a solid, corrosion-resistant conductor and must be installed at the main electrical panel in accordance with the National Electrical Code. It should be properly tied into the ground bus strip of the panel. We recommend the neutral and ground bus strips be bonded together (unless prohibited by local codes).
CIRCUIT BREAKERS
Power to the unit must be supplied from dedicated breakers. No other equipment should be powered from these breakers. AC power for the micro power must come from a different breaker than that of the pump. This not only provides electrical isolation for the micro power, but allows the unit to be disabled without shutting off power to the microprocessor PCB. The AC power for the micro power may be grouped together for multiple units. It is recommended that no more than 8 units be supplied from one breaker.
PUMP MOTOR
Pumps are shipped from the factory with motors wired according to the specifications given on the order as to kind of current, frequency and voltage.
Very often on installation, it becomes necessary to change the original setting to suit the AC power source. To do this, locate the motor change-over plate and remove the scr ew which secures it in place. Slide the plate so that the desired voltage, as marked on the plate, lines up with the screw hole. Reinsert the screw and secure the plate in place.
Many motor failures result from improper setting of the motor change-over plate. If set for 115 VAC and a 230 VAC feed is used, the motor will burn out after running only a short time. If set for 230 VAC and a 115 VAC feed is used, the motor will run very slowly and the starting field will soon burn out.
PULSE OUTPUT
The Pulse Output option provides the means for an external system to monitor the quantity that is dispensed by the 9820A dispensing unit. A description of the interface is provided in Control Lines, Pulse Output, in Section 3. Consult the wiring diagrams provided in Wiring in Section 4, along with the installation manual of the system that will be connected to the 9820A dispensing unit.
RS-485
The RS-485 option provides the means for direct connection to a GASBOY CFN Series System. Consult the wiring diagrams provided in Wiring in Section 4, along with the installation manual of the CFN Series System for proper wiring.
4-2 03/07/03
Page 25
Wiring
WIRE SIZE
The AC wire size for the Micro Feed and Neutral should be 14 AWG. This gauge of wire will be sufficient for runs up to 300 feet from the breaker panel to the dispensing unit. Sites with distances over 300 feet should use 12 AWG wire. In cases where multiple units are powered from the same breaker through the same wires, the gauge of the wires should be increased to handle the added load according to the distance from the breaker panel.
The AC wire size of the Pump Motor Feed, Pump Motor, Feed Neutral, and Neutral is dependent upon the HP rating of the pump motor, the voltage at which the pump will be oper ated (115/230 VAC), and the distance from the circuit breaker panel to the pump. The chart below should be used as a guide in selecting the proper wire size according to the specific installation requirements.
The AC wire size for the Slow Flow, Fast Flow lines should be 14 AWG (when they are used). The DC wire size for the Pulser lines connecting the pumping unit to the register assembly must
use four conductor, 18 AWG shielded cable (Belden 89418, Gasboy P/N C08864). This cable allows the pulser wires to run in the same conduit as the AC wiring for the short distance between the pumping unit and the register assembly. Belden 89418 is rated as follows:
Gas and Oil resistant insulation & jacket 18 AWG tinned, stranded, copper Four conductors 300 volt maximum operating voltage Aluminum/Mylar shielded with drain wire
Twisted-pair shielded cable is highly recommended for the Pulse Out put or RS-485 field wiring (when they are used). This type of cable provides superior noise immunity and must be used for distances over 100 feet or any time pulse output or RS-485 wiring is included in the same conduit as the AC wires. This cable must meet the following specifications:
Conductor: 18 AWG stranded wire. 2 twisted-pairs. Shield: Foil-wrapped 100% coverage and/or tinned copper braid 90% coverage Drain Wire: Stranded, tinned copper, 20 AWG or larger/or braided shield Voltage Rating: Maximum operating voltage of 600V Environmental: Gas- and oil-resistant; suitable for wet or dry locations.
GASBOY can supply Belden 1063A (P/N C09655) which is a UL-Listed, 4-conductor cable that meets the requirements listed above. NOTE: Belden 1063A is UL-Listed but not CSA listed.
Cable with a voltage rating of less than 600V must be installed in a conduit separate from all AC wires.
See the GASBOY Fuel Management System Installation Manual for specific requirements.
03/07/03 4-3
Page 26
GASBOY Series 9820A
CONDUIT
All wiring to the GASBOY Series 9820A dispensing unit must be installed in threaded, rigid, metal conduit. PVC IS NOT ACCEPTABLE. Wiring between the 9820A register and
pumping unit is installed in a single conduit. This includes the wiring for the AC control of the pumping unit and the internal pulser. A special cable, as described in Section 4, Wire Size, must be used for the connection between the pulser inside the pumping unit to the register assembly.
It is recommended that high voltage AC power wires to the register assembly (not between the register and pumping unit), be installed in separate conduit from the low voltage pulser output wires (when used). However, if AC and DC power wires share conduit, DC wiring must consist of UL-Listed cable with the specifications described in Section 4, Wire Size. Only AC wires for the system and dispensers can be installed in this conduit for this application. Wiring between a Fuel Point Reader (FPR) and its pre-amp junction box is intrinsically safe and must be run in a conduit with only other intrinsically safe wiring. It cannot be run in conduit with AC, DC, RS-485, or pulser wiring, regardless of the cable type used. See the Fuel Point Reader Installation and Retrofit Manual, C35628 for details.
The GASBOY Warranty will not apply to any dispenser in which the AC and DC wires are run in the same conduit, J-Box or wireway except as noted. The GASBOY Warranty will not apply to any dispenser using PVC as conduit.
When the GASBOY Series 9820A dispensing unit is being installed with a fuel management system other than a GASBOY system, see the manufacturer's installation manual for their specific conduit requirements.
All wiring and conduit runs must conform with all building/fire codes, all Federal, State, and Local codes, National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine Service Station Code (NFPA 30A) codes and regulations. Canadian users must also comply with the Canadian Electrical Code.
Use the following charts as a guideline for determining the necessary conduit sizes for wiring of the GASBOY Series 9820A dispensing unit. When actually determining the size of conduit, it may be necessary to increase the size of conduit because of a long run or large amount of bends. The installer should determine the orientation of the wire runs according to the layout of the components at the site and the applicable GASBOY wiring diagrams.
To determine conduit size needed, use the THHN/THWN Wire Areas table (left) to find the area for each wire gauge. Add up all wire areas. Use the Areas of Tr ade Size Conduit Table (r ight) to select the smallest number in the 25% fill area (based on NEC 501-1) that comes closest without exceeding the total wire area.
4-4 03/07/03
Page 27
Wiring
TERMINAL BLOCK ID
The terminal blocks shown below are located in the register assembly.
03/07/03 4-5
Page 28
GASBOY Series 9820A
023866 WIRING DIAGRAM Models 9822A
Domestic 115/230 VAC 9823A
NOTES:
1. All wiring and conduit runs must conform with all building/fire codes, all Federal, State, and Local codes, National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine Service Station Code (NFPA 30A) codes and regulations. Canadian users must also comply with the Canadian Electrical Code.
2. Pump motor can be wired as 230 VAC to reduce current draw. See breakaway view of 230 VAC PUMP MOTOR. All other wiring should remain the same except for the addition of the L2 (requires 230 VAC breaker for control). If connected to equipment requiring control of the authorization input, the Phase 2 Feed should be switched through a separate relay to prevent false triggering of the authorization signal.
3. If the PUMP MOTOR line is contr olled by a fuel management system using solid state relays, a resistor assembly must be installed between the Pump Motor Feed line and Neutral to prevent false triggering of the authorization input. The resistor assembly is 8.2K OHM, 10 Watt (P/N C05818) for 115/230 VAC domestic and 30K OHM, 10 Watt (P/N C06683) for 230 VAC international wiring.
4. SLOW FLOW and FAST FLOW lines are typically used when connecting to an optional valve. Each of these lines is capable of supplying 300 mA AC maximum (170 mA AC maximum if already connected to the optional valve). These lines must not be short ed to
any conduit or chassis metal, mis-wired, or connected to any equipment requiring more than stated maximum allowable current . If these restrictions are not followed, damage to the CPU PCB will occur.
5. Use the wire size chart listed when determining the wire size for the control wiring.
4-6 03/07/03
Page 29
Wiring
023866 WIRING DIAGRAM Models 9822A
Domestic 115/230 VAC 9823A
WARNING: Failure to follow the correct wiring diagram and all the listed notes and precautions may result in damage to the CPU PCB.
03/07/03 4-7
Page 30
GASBOY Series 9820A
023867 WIRING DIAGRAM Models 9822A-2
International 230VAC 9823A-2
NOTES:
1. All wiring and conduit runs must conform with all building/fire codes, all Federal, State, and Local codes, National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine Service Station Code (NFPA 30A) codes and regulations. Canadian users must also comply with the Canadian Electrical Code.
2. If the PUMP MOTOR line is contr olled by a fuel management system using solid state relays, a resistor assembly must be installed between the Pump Motor Feed line and Neutral to prevent false triggering of the authorization input. The resistor assembly is 30K OHM, 10 Watt (P/N C06683) for 230 VAC international wiring.
3. SLOW FLOW and FAST FLOW lines are typically used when connecting to an optional valve. Each of these lines is capable of supplying 300 mA AC maximum (170 mA AC maximum if already connected to the optional valve). These lines must not be short ed to
any conduit or chassis metal, mis-wired, or connected to any equipment requiring more than stated maximum allowable current . If these restrictions are not followed, damage to the CPU PCB will occur.
4. Use the wire size chart listed when determining the wire size for the control wiring.
4-8 03/07/03
Page 31
Wiring
023867 WIRING DIAGRAM Models 9822A-2
International 230VAC 9823A-2
WARNING: Failure to follow the correct wiring diagram and all the listed notes and precautions may result in damage to the CPU PCB.
03/07/03 4-9
Page 32
Page 33
Section 5
PUMP OPERATION
OVERVIEW
This section describes the operation of the pump. It shows how to access the electronic components, how to set the internal switches, the optional battery back-up power supply, how to view and reset the electronic totalizers using the actuator, how to operate the pump, and how to lock the nozzle.
03/07/03 5-1
Page 34
GASBOY Series 9820A
ELECTRONIC COMPONENT ACCESS
Before attempting to start-up the 9820A, it is important to become familiar with the location of some key components as well as the various switch-selectable operating modes.
1. Unlock and remove the front panel. Remove the two screws located at the top of the door assembly. Pull out on the top of the door and lift the door assembly to remove it.
2. Loosen the two screws located on the left and right door support brackets and pivot display panel down.
5-2 03/07/03
Page 35
Pump Operation
CPU SWITCH SETTINGS
The 9820A can be configured for various operating conditions using the switches located on the CPU PCB. Check these switches and change their settings if necessary. Switch settings should be changed with the power switch OFF. The new settings are read by the CPU PCB when the power is turned ON again.
SW1
SW1-1 Baud Rate
This switch is set to reflect the communication rate of the GASBOY RS-485 pump loop; open for 9600 baud or closed for 1200 baud. The GASBOY CFN system and TopKAT communicate at 9600 baud.
SW1-2 Mode If the 9820 is controlled by a GASBOY CFN or TopKAT electronic fuel management system, the switch should
Mode On-line
be open (on-line mode). If the 9820 is controlled by a GASBOY Series 1000 or TopKAT mechanical system, or controlled by any non-GASBOY system, or not controlled by any fuel management system at all, the switch should be closed (standalone mode).
NOTE: The 9820 is shipped in standalone mode. SW1-3, SW1-4 Delay Time
These two switches set the delay time used by leak detectors in submersible pump applications. The delay time is the period between activation of the submersible pump and activation of the slow flow valve. This time should be set according to the type of leak detector installed on the submersible pump to allow a normal leak test for each transaction. The delay time should be set to zero seconds for suction pumps.
SW1-5
Not used.
Baud Rate
9600
SW1-2 Open
Closed Series 1000Standalone
SW1-1 Open
Fuel System CFN
TopKAT top-mount TopKAT electronic
None currentlyClosed1200 supported
Fuel System CFN
TopKAT top-mount TopKAT electronic
TopKAT Mechanical All non-GASBOY systems No fuel system
Delay Time 0 seconds 4 seconds 5 seconds 6 seconds
SW1-3 Closed Closed Open Open Open
SW1-4 Closed Open Closed
03/07/03 5-3
Page 36
GASBOY Series 9820A
SW1-6 Authorization
This switch allows activation of the 9820A from some types of fuel management systems. When the switch is closed, a 115 VAC (230 VAC Int’l) signal must be present on the Control Feed line for pump activation to occur (required setting for Series 1000, TopKAT mechanical, and all non­GASBOY systems ). When open, the 9800
Authorization
Yes
SW1-6 Closed
OpenNo CFN
Fuel System Series 1000
TopKAT mechanical All Non-GASBOY systems
TopKAT top-mount TopKAT electronic No fuel system
ignores the Control Feed line (required setting for CFN, TopKAT electronic, or no fuel system).
SW1-7 Totalizers
This switch should be set to open for normal operation. When closed, this switch enables the reset of the electronic totalizers. See View/Reset Totalizers later in this section for details.
Reset Normal
SW1-7Totalizers Closed Open
SW1-8 Not used.
SW2 This four-position switch pack serves a dual purpose: as an address setting when communicating on the GASBOY RS-485 loop or TopKAT, or as a pulser output rate selector when pulser data is sent to a fuel management system other than a GASBOY CFN or TopKAT.
Address Switches
A unique address identifier must be set when the 9820A is connected to the GASBOY RS-485 pump loop via the 9820A RS-485 I/F PCB. Because there are 16 possible address combinations, up to 16 units (single or twin) may be connected to the pump loop. Addressing should start at 1 and continue sequentially through 16. The physical wiring order does not have to correspond with the address order; that is the first unit on the RS-485 loop doesn't have to be address 1. The char t at right gives the switch settings and address selections.
Address
SW2-1 1Closed 2
Open Closed 3Closed 4
Open 5Closed 6
Open 7Closed 8
Open 9
Closed ClosedClosed Open 10
Open ClosedClosed Open 11
Closed ClosedOpen Open 12
Open ClosedOpen Open 13
Closed 14
Open 15
Closed
Open
SW2-2
Closed Open Open Closed Closed Open Open
Closed Closed Open Open Open Open Open Open16
SW2-3 ClosedClosed
Closed Closed Open Open Open Open
Open
Open
SW2-4 Closed Closed Closed Closed Closed Closed Closed Closed
Open
Open
5-4 03/07/03
Page 37
Pump Operation
Pulser Output Rate Switches
When the 9820A is connected to external control equipment other than a GASBOY CFN system (standalone), the pulser signals are sent out via the 9820A Pump I/F PCB. The pulse rate required by the monitoring equipment can be configured by setting the switches as shown in the chart at right. The pulse rate represents pulses per gallon (PPG, domestic) or pulses per liter ( PPL, international). For domestic units, the pulse rate can be up to 1000 PPG. For international units, the pulse rate can be up to 250 PPL for all other models. This switch may need
Pulse Rate SW2-1 SW2-2 SW2-3
1Closed 10 100 250 500 1000 None None
Open Closed Closed Open Closed Open Closed Open
Closed Open Open Closed Closed Open Open
ClosedClosed
Closed Closed Open Open Open Open
to be sealed by a Weights and Measures paper seal if the 9820A is used for the resale of product.
Leading zeros are always suppressed in the hundreds and tens positions to the left of the decimal point. When in standalone mode, positions to the right of the decimal point are displayed based on the pulse rate selected as shown in the table at right.
Pulse Rate Display
1:1 XXX. 10:1 100:1 250:1 500:1 1000:1
XXX.X XXX.XX XXX.XXX XXX.XXX XXX.XXX
Timeout Switch
When the 9820A is in standalone mode, it will turn off an active hose if it doesn't detect pulses for 4 minutes, 15 seconds. This timeout feature can be disabled by setting
Timeout Enabled Disabled
SW2-4 Closed Open
switch SW2-4 to OPEN.
03/07/03 5-5
Page 38
GASBOY Series 9820A
BATTERY BACK-UP POWER SUPPLY
9820A models can be equipped with an optional battery back-up power supply. This allows the last transaction data to be displayed for a minimum of 15 minutes. After the batteries reach a certain low-voltage point, the power will automatically shut off. If you need to shut off the battery power before the low-voltage point is reached, momentarily disconnect, then re-connect, the cable that plugs into P1 on the power supply.
VIEW/RESET TOTALIZER
Electronic Totalizer
The 9820A stores a running quantity total. This electronic totalizer works independent of the optional mechanical totalizer that may be installed, and is shown as whole gallons (liters) on the displays (decimal point is shown, although it is disregarded). The totalizer data is stored in battery-backed memory. The 9820A is supplied with an actuator (shown in the above illustration) which allows you to view and reset the electronic totalizer. When the 9820A is shipped, the actuator is attached with a tie wrap to the electronic chassis behind the register door. At installation or startup, cut the tie wrap and remove actuator. Retain for future use.
5-6 03/07/03
Page 39
Pump Operation
To view the pump totalizer, make sure the pump handle is off and no transaction is in progress. Locate the unit of measure indication (i.e., GALLONS) below the display window. Touch this area with the actuator as shown. The totalizer data will be displayed for 10 seconds. If more time is needed, touch the actuator to the same area for an additional 10 second period.
To reset the electronic totalizer, follow the disassembly procedure outlined under Electronic Component Access earlier in this section. Turn off the breaker supplying the 9820A AC power . Close SW1-7 on the CPU PCB. Hold the actuator against the totalizer bracket and have someone turn the breaker on. The display should change to all zeroes. Remove the actuator and open SW1-7.
NOTE: Returning switch 1-7 to the open position prevents the totalizer from being reset the next
Mechanical Totalizer
time the actuator is used to read it.
Some 9820A models contain an optional mechanical totalizer. The totalizer has 8 digits; 7 whole gallons and 1 tenth-gallon column, 8 whole digits for liters. The mechanical totalizer is located on the front right side of the pumping unit.
03/07/03 5-7
Page 40
GASBOY Series 9820A
OPERATING SEQUENCE
The exact sequence of events that occurs during the operation of the pump is determined by various switch settings, inputs, and the user. A typical transaction is explained below.
1. Turn on the pump handle. If AC is present on the Pump Motor Feed line, the reset cycle begins. The display:
goes blank for one second
shows all 8's for one second
goes to 0.000 (gallons) or 0.00 (liters) and remains for one second.
The pump motor turns on. If equipped, the slow flow valve turns on.
2. The user begins to dispense fuel. Quantity will not be recorded on the display until 0.010 gallons (0.04 liters) are reached, however, all pulses will be sent out on the Pulse Output line, if equipped. At 0.010 gallons (0.04 liters), the fast flow valve turns on, if equipped.
3. The pump continues to run until one of the following conditions occurs. These conditions turn off all relays.
The handle is turned off.
The Pump Motor Feed line is turned off.
A pulser error is detected.
A timeout of 255 seconds is reached. If connected to a fuel management system, the
4. The 9820A continues to monitor for pulses until a 2 second period with no pulses occurs. At
timeout loaded into the system will be used.
A quantity of 990.000 gallons (9900.00 liters) is reached. If connected to a fuel
management system, the limit set in the system will be used.
The pump is halted by an operator of a fuel management system.
An AC power failure occurs.
this time the transaction is considered completed.
5-8 03/07/03
Page 41
Pump Operation
NOZZLE LOCKING
A locking mechanism is supplied as part of the hook arrangement on each 9820A. This will allow the unit to be locked thus preventing use of the dispenser. A lock with a shackle clearance of at least 2-1/2" is required to lock the pump (i.e., Master No. 1LJ-D). T o lock the nozzle in place, follow the instructions below:
1. Insert the nozzle onto the hook assembly with the nozzle tip inside of the boot.
2. Slide the rear bracket of the nozzle hook assembly upward until the holes near the bottom of the nozzle are aligned.
3. Slide the open padlock through holes in the moveable and stationary portions of the hook arrangement, thus capturing the nozzle in place. (Note that the four holes will not align until the moveable bracket has been slid upward.)
4. Close the lock.
While the nozzle is locked in place, the nozzle cannot be removed from the nozzle hook and the dispenser cannot be turned on.
03/07/03 5-9
Page 42
Page 43
Section 6
START-UP AND TEST
INSTALLATION COMPLETION CHECKLIST
Review the information below to verify the proper installation of the Series 9820A dispensing unit.
If the installation does not meet criteria listed, correct the problem before the start-up is performed.
1. To avo id damage to the CPU PC board, verify that t he SLOW FLOW and FAST FLOW wires are not shorted to any conduit or chassis metal, mis-wired, or connected to any equipment requiring more than stated maximum allowable current.
2. The register and pumping unit must be properly secured.
3. All plumbing must be complete and tight. All liquid-carrying lines mu st be checked for leaks.
4. When DC pulse output lines are used in the pump for connecting to GASBOY fuel management systems, the AC and DC wires must not share any conduits, junction boxes, or troughs except as noted in Section 4, Wire Size.
5. All conduit work must be complete. All junction box covers must be secured. Conduits should not be sealed until the wiring is verified through proper operation.
6. The unit must be properly grounded.
7. Before any testing begins, remove any water in the tank through a fill opening, using a suitable pump. Do not use the GASBOY pump to remove water. Serious damage may occur.
8. A sufficient volume of fuel must be put in the tank to insure that the liquid level is above the bottom of the suction pipe.
03/07/03 6-1
Page 44
GASBOY Series 9820A
START-UP
After successfully verifying the installation against the completion checklist, the unit is ready for start-up. Follow the procedure below to perform an orderly start-up of the Series 9820A.
1. Verify that all switches on the CPU PCB are set properly for the various operating conditions as explained in Section 5.
2. Turn on the circuit breakers for the microprocessor.
3. Authorize the unit through the fuel management system, if available.
4. Remove the nozzle from its holder and turn on the pump handle. Verify that the display goes through the proper reset sequence as explained in Section 5, Operating Sequence.
5. Dispense fuel. Verify that the high flow valve opens, if equipped. Check all plumbing for leaks at this time.
6. Turn the pump handle off. Open the nozzle. No fuel should be dispensed at this time.
7. Verify that the correct quantity was recorded by the fuel management system, if available.
8. Run the unit through all standard calibration procedures.
9. Reset the electronic totalizer as described in View/Reset Totalizer in Section 5.
6-2 03/07/03
Page 45
Start-Up and Test
POST START-UP TESTS
Voltage
The incoming voltage to the pump should be checked and any reading not within 10% of rated voltage should be corrected before testing is continued. It is good practice to take voltage readings while the pump is operating on bypass and also while making a delivery. Any voltage drop in excess of 10% during either of these operating states should be considered a low voltage condition. Corrective action should be taken to insure an adequate power supply to the pump.
Tightness
After determining that the pump is operating satisfactorily and the system is fully primed, check the pump and piping to make sure that all connections are tight.
Belts
Since belts do stretch slightly during the first few minutes of operation, check the belt tension after completing the operational test; a properly tightened belt will permit twisting the belt 180 degrees midway between the motor and pump pulleys.
On the 9822A and 9823A, the belt can be tightened by loosening the cap screw which holds the idler arm and sliding the arm to obtain the correct belt tension of 6-3/4 lbs. (+ adjustment is complete, remember to retighten the cap screw.
Calibration
All GASBOY pumps are adjusted for accurate measure at the factory. However, since the conditions of the installation can affect pump accuracy, it is the responsibility of the installer to check the pump for accuracy and make any needed adjustments. Where required, it is the owner's responsibility to report this device to the local Weights and Measures officials for their inspection before the unit is put into service.
The adjustment of measurement is accomplished by breaking the seal wire and removing the Seal Pin. This will permit the Index Disc, to be turned either counterclockwise (-), decreasing the measurement, or clockwise (+), increasing the measurement. A variation of approximately one cubic inch in measurement is obtained by turning the Index Disc five holes. After measurement has been properly adjusted, the Seal Pin and seal wire should be replaced.
3/4). When the
03/07/03 6-3
Page 46
Page 47
Section 7
PREVENTIVE MAINTENANCE
GENERAL
GASBOY pumps are designed and constructed to give many years of uninterrupted service. In fact, operators report years of trouble-free operation with absolutely no service expense. Yet, certain parts of a pump are bound to wear, and GASBOY therefore recommends a periodic inspection, at least twice a year, for such things as fuel leaks, belt tension and condition, lubrication and strainer cleanliness. If such a procedure is followed, any small adjustments that are necessary can be made before expensive, annoying breakdowns occur. The result of this sound approach is continuous, profitable service from all of your GASBOY equipment.
To reduce the risk of electrical shock when servicing, turn off all power to the pump.
HINTS FOR BETTER PUMP PERFORMANCE
Demand Competent Service
If your pump should stop or fail to operate properly, don't depend upon the repair service of a general mechanic unless he is thoroughly familiar with the mechanism. Experience shows that the repair results will be much more satisfactory if you demand the service of a competent representative of the pump manufacturer. GASBOY has a Distributor Network which services fuel dispensing and management systems in every section of the country.
Use Authorized Parts
Should excessive wear, rust, or corr osion of parts cause inefficient operation, it is always best to replace them immediately; but if you want the best results and continuity of the Underwriters' Label on your pump, be sure they are new authorized service parts supplied by GASBOY. Every part of a pump is carefully designed for a particular purpose. If it is replaced by an incorrect or substandard substitute, pump operation will be unsatisfactory. Always use new gaskets or seals when servicing or rebuilding GASBOY equipment; do not re-use the old ones.
Operate With Reasonable Care
Like any machine, the pump that is operated with reasonable care will last longer and give better service. Abuse should be avoided (such as dropping the nozzle on the ground, operating the unit with a dirty strainer, dragging the hose across the concrete island or driveway, running the pump with the nozzle closed for more than two minutes, etc.). The time and care given to your pumps will be returned to you in the form of dependable service.
WARNING:
03/07/03 7-1
Page 48
GASBOY Series 9820A
PREVENTIVE MAINTENANCE CHECKLIST
Keep Water Out
Water tends to collect in storage tanks. This is due to moisture-laden air being drawn into the storage tank and condensing, or to defective fill openings that are not properly protected with watertight covers. Storage tanks should be checked after every fill-up for water and removed with a sump pump, to forestall serious damage to equipment. Water, sediment, and other foreign matter that accumulates in the tank can be drawn up into the pump and cause failures.
Lubricate the Pumping Unit
The pumping unit should be lubricated every six months or every 100,000 gallons. Do this by applying a few drops of a light grade oil (SAE 10) to the felt pad located on the pump body slightly above the shaft which connects to the pump pulley. Oil used should be suitable for temperatures ranging from -40 F to 180 F.
Clean the Dial Face
Clean the dial face with a soft, clean, damp cloth as often as necessary.
Clean the Strainer
Clean the strainer immediately after the pump has been installed and tested, and again after a few hundred gallons have been delivered. Thereafter, once every six months, or as required.
The symptoms of a dirty or clogged strainer in a pump are slow delivery, noisy operation, and pulsation. To clean the strainer, turn off AC power to the pump. Locate the Suction Strainer Cap on the plumbing unit and unscrew it to access and remove the strainer. Use compressed air blow the dirt out of the strainer.
*Wear protective safety goggles or glasses when using compressed air.
Change the Filter
If the unit is equipped with a filter, check and change it at regular inter vals. A dirty filter in a pump will cause a slower delivery rate. Refer to the accessories section of your parts manual to ensure that you replace the filter with one designed for your model. Always use a drip pan directly below the filter when removing the cartridges to pr event contamination of both the soil and the electrical components within the cabinet.
Adjust the Belts
With the proper care, belts will give exceptionally good ser vice. A loose belt not only cuts down dispensing speed, due to slipping, but also results in excessive wear. A properly tightened belt will allow twisting the belt 180 degrees midway between the motor and the pump pulleys.
On the 9822A and 9823A models, the belt can be tightened by loosening the cap screw which holds the idler arm and sliding the arm to obtain the correct belt tension of 6 3/4 lbs (+ the adjustment is complete, remember to retighten the cap screw.
3/4). When
* to
7-2 03/07/03
Page 49
Preventive Maintenance
Preserve the Finish of Your Pumps
Nearly all gasoline pumps are installed outdoors where their surfaces are subjected to the action of the weather. As a result, it is necessary to give the finish a r easonable amount of care if an attractive appearance is to be maintained.
The finish on GASBOY pump housings is a heat baked urethane paint. The life of this finish can be lengthened several years if, at regular intervals, the painted surfaces are thor oughly cleaned with a high grade automobile polish and then protected with a coat of paste wax. Do not use abrasive cleaners or polish. Do not use high-pressure spraying equipment.
03/07/03 7-3
Page 50
GW01 - 6/04/02 Rev. 1
WARRANTY
General Statements:
Gasboy International LLC. warrants all new equipment manufactured by Gasboy agai nst defective material and/or workmanship, for t he warranty period specified below, when the equipment i s installed in accordanc e with specifications prepared by Gasboy. This warranty does not cover damage caused by acci dent, abuse, Acts of God, lack of surveillance of autom atic recording systems, negligence, mis-application, faulty installation, i mproper or unauthorized maintenance, installation or use in vi ol ation of product manuals, instructions , or warnings. Under no circumstanc e shall Gasboy be liable for any indirect, special, or cons equential damages, losses, or expenses to include, but not limited to, loss of product, los s of profits, litigation fees, or the use, or inability to use, our produc t for any for any purpose whatsoever. Parts Only - During the warranty period, Gasboy will, at its option, repair or replace def ective parts returned transportat i on prepai d to its factory. On-Site Labor Included - Gasboy will also provide, within the Continental United St ates and during the warranty period, the services of an Authorized Service Representati ve (A SR) for on-site repair or replacem ent of defective parts. Replacement Parts - Any system components that are not part of the original system order, i ncluding Island Card Readers, Pump Control Units, et c., are considered replacement part s.
Equipment Term Coverage
Commercial Pumps and Dispensers Full-Cabinet Consumer Pumps
Small Transfer Pumps, Meters, Pressure Regulators
Keytrol One year from date of instal l ation or 18 mos. from date of
Fuel Management Systems :
- CFN/ Profit Point
- Series 1000/Fleetkey
- TopKAT
- Fuel Point Readers (sold with new systems) Additional Fuel Point Items:
- Fuel Point Readers sold for retrofitting existing sys t ems.
- Fuel Point vehicle and dispenser components. Encoders, Embos sers, Modems, CRTs, and Logger Printers
Air Diaphragm Pumps Three years from date of purchas e (for full warranty
Items not m anufactured by Gasboy (ex. automatic nozzles, hoses, swivels, etc.) Replacement Parts One year from date of Gasboy International's invoice to the
To the extent permitted by law, this warranty is made in lieu of all other warranties, expressed or implied, inc l udi ng warranti es of freedom from patent infringement, or merchant ability, or fitness for a particular purpose, or arising from a cours e of dealing or usage of trade. No one is authori zed t o vary the terms of the warranty nor may anyone make any warranty of representation, or assume any liability other than that herein stat ed, in connection with the sale described herein. The acceptance of any order by Gasboy International is expressly made subject to the purchaser's agreement to these condit i ons.
One year from date of instal l at i on or 18 mos. from date of Gasboy International’s invoi ce to the purchaser, whichever comes first. One year from date of instal l at i on or 18 mos. from date of Gasboy International’s invoi ce to the purchaser, whichever comes first.- Excepting the Model 2020 Hand Pump, which has a 90-day warranty from date of GASBOY International’s invoice.
Gasboy International’s invoi ce to the purchaser, whichever comes first. One year from date of start-up or 15 mos. from date of Gasboy International’s invoi ce to the purchaser, whichever comes first .- The basic warranty only applies to s ys tems which have been started up by a Gasboy Authorized Servi ce Representative (ASR).
One year from date of start-up or 15 mos. from date of Gasboy International’s invoi ce to the purchaser, whichever comes first.
Purchased with Fuel Management Syst em (Encoders, Embossers only): 90 days from the date of s tart-up by a Gasboy ASR, or 180 days from date of Gasboy I nternational's invoice, whichever occurs first.
Purchased with Fuel Management System (Modems, CRTs, and Logger Printers only): Matches system warranty.
Purchased Separately: 90 days from date of Gasboy I nt ernational's invoice to the purchaser.
description, see Price List). Not warranted by Gasboy International (consul t original manufacturer’s warranty).
purchaser.
Parts and Labor.
Parts Only.
Parts and Labor.
Parts and Labor.
Parts Only.
Purchased with System (Encoders, Embos sers only): Parts only.
Purchased with System (Modems, CRTs, Logger Printers only): Matches system warranty.
Purchased Separately: Parts Only.
Parts Only.
Not Applicable.
Parts Only.
GASBOY INTERNATIONAL LLC
P.O. Box 309, Lansdale, PA 19446 (800) 444-5579 FAX: (800) 444-5569 ● www.gasboy.com
Loading...