INSTRUCTIONS FOR REPAIRING
067026 SOLENOID VALVE W/STEEL INSERT
MODELS: 9152AX, 9152AXTW1, 9152AXTW2
A small amount of ¾” flanged solenoid valves were s upplied to Gasboy with stee l inserts in the i nlet bolt holes.
With force on the discharge piping, the inserts m ay slide out of the valve c ausing a le ak bet ween the val ve and the
flange. These valves (P/N 067026) were used in some shipments of Gasboy commercial dispensers (Models
9152AX, 9152AXTW1 and 9152AXTW2).
Before or during installation and startup of the
dispensers, a qualified repair technician should check
the valve. The technician should inspect the valve where
the bolts protrude through the bac k side of the brass in let
flange. If the area im mediately surrounding the bolts is
brass, there is no problem. If there is a st eel ring (steel
insert) immediately surrounding the bolt (it may be
recessed), the bolts must be replaced to avoid a
potential leak.
This Gasboy repair kit, P/N 032140, will remedy the
problem. It contains the following:
Item Part No. Description Qty
1 051925 5/16-18 x 1-1/4” long Hex Head Bolt 2
2 068875 5/16 Lockwasher 2
3 068080 5/16 Washer 2
4 038605 5/16-18 Locknut 2
5 031673 Instructions (this sheet) 1
Refer to the Installation/Operation Manual supplied with your dispenser for all applicable Warnings and
Safeguards before proceeding with any repairs
If you have determ ined that your dis penser requires this valv e repair k it, you
should perform the following:
1. Disconnect all po wer to your dispens er and block the island to prevent
unauthorized access.
2. Remove and discard the existing bolts that thread into the steel inserts.
3. Install the 1-1/4” long bolt (item 1) with the lockwasher (item 2) and
tighten securely.
4. Install the washer (item 3) and locknut (item 4) and tighten securely.
5. Reapply power to the dispenser and inspect for leaks.
031673 04/16/01