Garland CE-72 Installation Manual

INSTALLATION/OPERATION
INSTRUCTIONS FOR CHAIN
GRIDDLES
THE INSTALLATION AND CONNECTION MUST COMPLY WITH LOCAL CODES, OR IN THE ABSENCE OF LOCAL CODES, WITH CAN/CGA-B149 INSTALLATION CODE OR WITH THE NATIONAL FUEL GAS CODE, ANSI Z223.1/NFPA NO. 54 - LATEST EDITION.
ALL BURNER ADJUSTMENTS AND SETTINGS SHALL BE MADE BY A QUALIFIED GAS TECHNICIAN . POST IN A PROMINENT LOCATION, INSTRUCTIONS TO BE FOLLOWED IN THE EVENT THE USER SMELLS GAS.
THIS INFORMATION SHALL BE OBTAINED BY CONSULTING YOUR LOCAL GAS SUPPLIER. THE APPLIANCE AND ITS INDIVIDUAL SHUT OFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY
PIPING SYSTEM DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1/2 PSIG. (3.45 KPA).
THE APPLIANCE MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS INDIVIDUAL MANUAL SHUT OFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG. (3.45 KPA).
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR
OTHER FLAMMABLE VAPOURS AND
LIQUIDS IN THE VICINITY OF THIS OR
ANY OTHER APPLIANCE.
WARNING IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, INJURY OR DEATH. READ THE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR
SERVICING THIS EQUIPMENT.
INSTALLATION INSTRUCTIONS
SERVICE CLEARANCES
NOT REQUIRED
SERIAL PLATE LOCATION
All burner inputs arc shown on the Serial/Rating Plate of each unit, located directly behind the front panels. For access, remove the two screws secur ing the upper front panel to the body in the upper right and left hand corners, then slightly raise the panel to lift off. Remove to a safe location. Next.
GENERAL INFORMATION
1. Damage Check : Check carton or crate for possible damages incurred in shipping. After carefully examining, check for "Concealed" damage. Report any damage immediately to your carrier.
2. The correct type of gas for which the unit was manufactured is noted on the serial/rating plate,
remove the two screws securing the lower front panel to the body in the upper right and left hand corners and hinge the panel downwards. Reverse the procedure to replace both front panels.
Note: Make sure no electrical connections have been disturbed.
and this type of gas has to be used.
3. This unit must be installed in accordance with the following clearances in order to provide proper operation and servicing of the appliance. Also, it is recommended that the unit be installed with sufficient clearances to provide for proper cleaning and maintenance.
COMBUSTIBLE CLEARANCES 6" (152 mm) 6" (152mm) 6" (152mm) NON-COMBUSTIBLE CLEARANCES 0" 0" 0"
4. A readily accessible gas shut-off valve is provided on each unit, attached to the main mani fold under the unit. Gas supply connection must be made with minimum 3/4 inch NPT pipe. Larger than 3/4 inch (19 mm) supply pipe may be required when a long run of supply pipe is necessary. Consult the pipe capacity tables in the installation code.
5. Have a qualified gas technician check the gas pressure to make certain that the existing gas facilities (meter, piping, etc.), will deliver the BTU's of gas required at the unit, with no more than 1/2 inch (12 mm) water pressure drop. When checking pressure, be certain that all the equipment on the same gas line is turned "ON".
LEFT RIGHT
SIDES
6. Make certain that new piping, joints and connections have been made in a clean manner and have been purged, so that the piping compound, chips, etc., will not clog valves and/or controls. Use pipe joint sealant that is approved for use with liquefied petroleum gas.
7. For models equipped with casters, installation shall be made with a connection that complies with the standard for Connectors for Moveable Gas Appliances, ANSI Z21.69 (Latest Edition)/ CGA 6.16 and a quick ­disconnect device that complies with the standard for Quick-Disconnect Devices for Use with Gas Fuel, ANSI Z21.41 (Latest Edition)/CAN 1-6.9.
BACK
TYPE OF FLOOR OR BASE
COMBUSTIBLE
2
8. Adequate means must be provided to limit movement of the appliance without depending on the connector and quick-disconnect device or associated piping. This can be accomplished by attaching restraining chains/cables from floor or rear wall to rear of unit.
9. WARNING: Check all gas connections for leaks, using a soap solution or similar means. Do not check with an open flame.
10. The unit must be installed on the legs or casters provided. A minimum 4 inch (101 mm) air space must be maintained below the unit for required air flow to the burner systems. Avoid placing any objects under the unit which could obstruct air flow to the burner systems.
When the unit is installed in its operating location, level the unit by adjusting the leveling legs. Use a spirit level across the front, rear and sides of each unit.
Note: The griddle plate may not rest evenly on the unit body if the unit is not properly leveled.
11. Each thermostat controls one zone burner through a combination dual solenoid/pressure regulator valve, complete with a pressure test spigot. The gas pressure on each combination valve must be checked when the unit is installed
to ensure that the gas pressure is the same as specified on the Serial/Rating plate. For access to the pressure test spigots, turn the main power switch and all zone power switches to the "OFF" position as a safety precaution, and hinge the lower front panel downwards. Pressure test spigots are located at the rear of each combination valve, including pilot combination valves. When your ma­nometer is connected to the first combination valve for test, turn the manual shut off valve, located under the unit, to the open position (valve handle in line with piping). Turn the main power switch to "ON" and turn all zone power switches to "ON". All thermostat dials should be set to approximately 350°F (182°C). When all burners are operating, check the reading on the manometer. If not in accordance with the pressure specified on the Serial/Rating Plate, adjust the combination valve regula tor accordingly. When satisfied with the manometer reading, turn the main power switch to "OFF", remove the manometer test tube and recap the test spigot. Repeat this operation on each combination valve until each pressure regulator is set correctly. Turn each thermostat, zone power switch and main power switch to "OFF".
NOTE: Make certain no electrical connections have been disturbed before replacing front panels.
ELECTRICAL CONNECTION
IMPORTANT: This appliance must be electrically grounded in accordance with local codes, or in the absence of local codes, with the Canadian Electrical Code C22.1 or with the National Electrical Code ANSI/NFPA No. 70 (latest edition), whichever is applicable.
WARNING
Electrical Grounding Instructions
This appliance is equipped with a three-prong (grounding) plug for your protection against shock hazard and should be plugged directly into a properly
grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
A separate 15 amp service must be provided. For 120V usage, each unit is electrically equipped with a cord set with a three-prong plug which fits any standard 120 volt, three­prong grounded receptacle.
When the unit is ordered and built for 208/240 volt, the supply line must be connected to the wiring terminations located inside the terminal box. For ease in attaching the supply line, there is a removable cover on the terminal box. A wiring diagram is attached to the rear panel of each unit.
3
VENTILATION
The unit must be installed in a location in which the facilities for ventilation permit satisfactory combustion of gas and proper venting. Proper ventilation is imperative for good operation of the appliance. The ideal method of ventilating a gas unit is the use of a properly designed ventilating canopy, which should extend at least 6" (152 mm) beyond all sides of the appliance (except against the wall, if the canopy is a wall installation). This is usually part of a mechanical exhaust system .
1. Appliances shall be located so as not to interfere with
proper circulation of air within the
OPERATING INSTRUCTIONS
LIGHTING INSTRUCTIONS
confined space. All gas burners require sufficient air to operate.
2. Large objects should not be placed in front of the appliance which might obstruct the air flow through the front. Do not obstruct the flow of combustion and ventilation air.
3. Do not permit fans to blow directly at the appliance, and
wherever possible, avoid open windows adjacent to the appliance sides and back;
also wall type fans which create air cross-currents within
the room.
Wait 5 minutes, then turn the main power switch back to "ON".
Adequate means must be provided to limit movement of the appliance without depending on the connector and quick disconnect device or associate piping. This can be accomplished by attaching restraining chains/cables from floor or rear wall to rear of unit.
On units equipped with casters, ensure that front casters are in the locked position and that the movement restraint is connected to the appliance.
During an electrical power interruption, turn power switch to the "OFF" position. This unit cannot be made to operate without electrical power.
1. First, make certain that all power switches and thermostat switches are set to "OFF".
2. Connect electrical power cord to 120 volt supply.
3. Turn the gas shut-off valve to the "OPEN" position (valve handle in line with piping).
4. Turn the main power switch to "ON", power switch green indicator should illuminate. Wait until gas pilot, green indicator illuminate.
NOTE: Should pilot ignition fail after a few minutes, turn the main power switch to "OFF".
5. When the green indicators for their respective zones are illuminated, turn the zone power switch for each zone to "ON" and set the thermostats to the desired temperature settings.
6. The amber burner indicators cycle with the ther mostat operation.
SHUT DOWN INSTRUCTIONS
1. Turn all zone and power switches to "OFF" (thermostat dial settings may be left at their set point if preferred) at the end of daily operations.
2. For extended shut down, turn all zone power switches to "OFF", turn main power switch to "OFF", close the manual gas shut-off valve and unplug the electrical cord set.
NOTE: Do not waste gas or abuse equipment by leaving thermostats at a high temperature, if not required. During idling periods, set ther mostats to a low temperature setting. For example: 175° (79°C) to 200°F (93°C), to keep griddle warm. Rest thermostats, as required, for periods of heavy load.
4
ADJUSTMENTS
PILOT ADJUSTMENT
NOTE: Each griddle has been factory tested and adjusted prior to shipment. It may be necessary to further adjust the unit as part of a proper installa tion. Such adjustments are the responsibility of the installer. Adjustments are not considered to be defects in material and workmanship, and they are not covered under the original equipment warranty.
A pilot adjustment valve is located in the line from each pilot combination valve. Pilot adjustment is acces sible from behind the lower front panel. First remove the two screws securing the upper front panel to the body, in the upper right and left hand corners, then slightly raise the panel to lift off. Remove to a safe area. Next, remove the two screws securing the lower front panel to the body, in the upper right and left hand corners and hinge the panel downwards.
Turning the small screw in the pilot adjusting valve clockwise reduces the amount of gas provided to the pilot(s). Turning the small screw counter-clockwise increases the gas provided to the pilot(s). The gas should be adjusted to a 7/16 (11 mm) inch long flame, to ensure that the flame engulfs the top of the flame sensor.
When the air shutter adjustments are complete on each burner, re -tighten the air shutter screw so that the correct setting is locked in place.
NOTE: Make certain no electrical connections have been disturbed. Replace both panels and secure to body.
THERMOSTAT CALIBRATION
This griddle thermostat is a precision instrument. It is carefully calibrated at the factory so that the dial setting matches the actual griddle temperature. Field re -calibration is seldom necessary and should not be attempted unless considerable experience with cooking results prove that the thermostat is not maintaining the set temperature properly.
To check calibration, use a test instrument with a flat temperature sensing surface, which can be placed on the griddle plate surface. Place the sensor in the center of the zone being tested.
1. Turn the griddle "ON" and set the thermostat to 350°F
(176°C). Allow the griddle zone to achieve temperature and thermostat to cycle at least 3 times. Take a temperature reading at the time that this thermostat cycles on for the third time.
MAIN BURNER AIR ADJUSTMENT
Burners should always be warm when an adjustment to air shutters is made. To adjust air shutters, loosen the small screw along the side of the burner near the orifice. Lifting flames on the burner indicates too much air and this air shutter should be in a more closed position. Yellow tips on the flames indicate not enough air and the air shutter should be in a more open position.
2. If, when the thermostat indicates heating (amber
indicator illuminated), the surface tempera ture does not exceed plus (+) or minus (-) 8°F (13°C) of the thermostat set point, no re-calibration is necessary.
If the griddle plate surface temperature exceeds +/- 8°F (13°C), it could indicate a defective thermostat or sensor. The electronic thermostat is precisely calibrated at the factory. Any work should be performed by a qualified service technician.
5
MAINTENANCE AND CARE
Periodical inspections by your dealer or qualified service agency are recommended to check temperatures, adjustments and ensure moving parts are operative. Whenever possible, avoid overheating idle equipment, as this is the primary cause for increased service costs.
Always disconnect the power supply to appliance before servicing. After servicing, ensure that all connectors are suitably secured back in place.
SEASONING
Before being used for the first time, all griddle surfaces must be carefully "broken in" or "seasoned".
1. Remove all factory applied protective materials by washing with a hot mild detergent or soap solution. Rinse and dry thoroughly.
2. Set the griddle thermostats to a low tempera ture, 150°F (65°C)to 175°F (79°C) and allow griddle to operate for thirty minutes.
3. Apply a thin coat of olive oil or other high grade, salt free, cooking oil to the surface. Wipe away excess.
4. Allow oil to remain on the griddle surface for 5 minutes, then wipe off.
5. Reset thermostat to a medium temperature, 275°F (135°C) to 300°F (149°C), and apply a second thin coat of oil. Wipe off excess after 5 minutes.
6. Reset thermostat to desire cooking temperature and apply a final coat of oil. Wipe off excess after 3 minutes. The griddle is now seasoned and ready for use.
NOTE: Griddle may be re-seasoned at any time by thoroughly cleaning and following the above procedures. Griddles should be re-seasoned prior to each day's operation.
CLEANING
Griddle plates should be cleaned daily while still warm. Remove carbonized grease and/or food residue with a spatula.
When necessary, clean griddle surface thoroughly using a fine griddle brick, or a liquid griddle cleaner (available from your kitchen equipment dealer).
Polish the griddle surface to a bright finish. Wash griddle surface, rinse and dry thoroughly. Re -season the griddle as per the seasoning instructions.
* Avoid overheating the griddle as this may cause sticking
and grease carbonizing, resulting in a hard to clean surface.
* Do not hit spatula on the griddle plate as this will nick the
surface.
* Empty the grease tray frequently to avoid over filling and
spill overs.
EXTERIOR CLEANING
Normal soil may be removed from stainless steel with a hot detergent or soap solution. To remove grease that has baked on, apply cleanser on the metal in the direction of the polishing lines of the metal. Never rub in a circular motion.
Soil and burned deposits which do not respond can usually be removed by rubbing the surface with SCOTCH-BRITE scouring pads or STAINLESS scouring pads. Do not use ordinary steel wool.
Heat tint can be removed by a vigorous scouring in the direction of the polish lines, using SCOTCH-BRITE scouring pads or STAINLESS scouring pads in combination with a powdered cleanser.
6
SERVICE BULLETIN
Bulletin No:
98017
From: Garland Group Service Department To: Authorized Service Agencies
SUBJECT: Chain Griddle Panel Cover
Models Effected: CG & CE -36, 48, 60 & 72
A Griddle Panel Cover has been made available to help prevent water and grease from entering the control compartment and damaging the controls. The panel cover can easily be installed onto existing units.
Date: March 25, 1998
Kit numbers are as follows.
KIT Number Used on Model's
CK171-36 CG & CE36
CK171-48 CG & CE48
CK171-60 CG & CE 60 CK171-72 CG & CE 72
See attached page for mounting instructions.
8
CHAIN GRIDDLE PANEL COVER MOUNTING
INSTRUCTIONS
1. DRILL (5) 0.125" HOLES IN UPPER FRONT PANEL AS SHOWN
2. MOUNT PANEL COVER TO UPPER FRONT PANEL WITH SELF-TAPPING SCREWS (4)
3. INSTALL LOCKING SCREW (1)
9
Loading...
+ 16 hidden pages