THE INSTALLATION AND CONNECTION MUST COMPLY WITH LOCAL CODES, OR IN THE ABSENCE OF LOCAL
CODES, WITH CAN/CGA-B149 INSTALLATION CODE OR WITH THE NATIONAL FUEL GAS CODE, ANSI Z223.1/NFPA
NO. 54 - LATEST EDITION.
ALL BURNER ADJUSTMENTS AND SETTINGS SHALL BE MADE BY A QUALIFIED GAS TECHNICIAN .
POST IN A PROMINENT LOCATION, INSTRUCTIONS TO BE FOLLOWED IN THE EVENT THE USER SMELLS GAS.
THIS INFORMATION SHALL BE OBTAINED BY CONSULTING YOUR LOCAL GAS SUPPLIER.
THE APPLIANCE AND ITS INDIVIDUAL SHUT OFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY
PIPING SYSTEM DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1/2
PSIG. (3.45 KPA).
THE APPLIANCE MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS INDIVIDUAL
MANUAL SHUT OFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST
PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG. (3.45 KPA).
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR
OTHER FLAMMABLE VAPOURS AND
LIQUIDS IN THE VICINITY OF THIS OR
ANY OTHER APPLIANCE.
WARNING IMPROPER INSTALLATION,
ADJUSTMENT, ALTERATION, SERVICE OR
MAINTENANCE CAN CAUSE PROPERTY
DAMAGE, INJURY OR DEATH. READ THE
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
THOROUGHLY BEFORE INSTALLING OR
SERVICING THIS EQUIPMENT.
INSTALLATION INSTRUCTIONS
SERVICE CLEARANCES
NOT REQUIRED
SERIAL PLATE LOCATION
All burner inputs arc shown on the Serial/Rating Plate of
each unit, located directly behind the front panels. For
access, remove the two screws securing the upper front
panel to the body in the upper right and left hand corners,
then slightly raise the panel to lift off. Remove to a safe
location. Next.
GENERAL INFORMATION
1. Damage Check : Check carton or crate for possible
damages incurred in shipping. After carefully
examining, check for "Concealed" damage. Report any
damage immediately to your carrier.
2. The correct type of gas for which the unit was
manufactured is noted on the serial/rating plate,
remove the two screws securing the lower front panel to the
body in the upper right and left hand corners and hinge the
panel downwards. Reverse the procedure to replace both
front panels.
Note: Make sure no electrical connections have been
disturbed.
and this type of gas has to be used.
3. This unit must be installed in accordance with the
following clearances in order to provide proper
operation and servicing of the appliance. Also, it is
recommended that the unit be installed with sufficient
clearances to provide for proper cleaning and
maintenance.
4. A readily accessible gas shut-off valve is provided on
each unit, attached to the main mani fold under the unit.
Gas supply connection must be made with minimum
3/4 inch NPT pipe. Larger than 3/4 inch (19 mm)
supply pipe may be required when a long run of supply
pipe is necessary. Consult the pipe capacity tables in
the installation code.
5. Have a qualified gas technician check the gas pressure to
make certain that the existing gas facilities (meter,
piping, etc.), will deliver the BTU's of gas required at
the unit, with no more than 1/2 inch (12 mm) water
pressure drop. When checking pressure, be certain that
all the equipment on the same gas line is turned "ON".
LEFT RIGHT
SIDES
6. Make certain that new piping, joints and connections
have been made in a clean manner and have been
purged, so that the piping compound, chips, etc., will
not clog valves and/or controls. Use pipe joint sealant
that is approved for use with liquefied petroleum gas.
7. For models equipped with casters, installation shall be
made with a connection that complies with the
standard for Connectors for Moveable Gas Appliances,
ANSI Z21.69 (Latest Edition)/ CGA 6.16 and a quick disconnect device that complies with the standard for
Quick-Disconnect Devices for Use with Gas Fuel,
ANSI Z21.41 (Latest Edition)/CAN 1-6.9.
BACK
TYPE OF FLOOR OR
BASE
COMBUSTIBLE
2
8. Adequate means must be provided to limit movement of
the appliance without depending on the connector and
quick-disconnect device or associated piping. This can
be accomplished by attaching restraining chains/cables
from floor or rear wall to rear of unit.
9. WARNING: Check all gas connections for leaks, using a
soap solution or similar means. Do not check with an
open flame.
10. The unit must be installed on the legs or casters
provided. A minimum 4 inch (101 mm) air space must
be maintained below the unit for required air flow to the
burner systems. Avoid placing any objects under the
unit which could obstruct air flow to the burner
systems.
When the unit is installed in its operating location, level
the unit by adjusting the leveling legs. Use a spirit level
across the front, rear and sides of each unit.
Note: The griddle plate may not rest evenly on the unit
body if the unit is not properly leveled.
11. Each thermostat controls one zone burner through a
combination dual solenoid/pressure regulator valve,
complete with a pressure test spigot. The gas pressure
on each combination valve must be checked when the
unit is installed
to ensure that the gas pressure is the same as specified on
the Serial/Rating plate. For access to the pressure test
spigots, turn the main power switch and all zone power
switches to the "OFF" position as a safety precaution, and
hinge the lower front panel downwards. Pressure test
spigots are located at the rear of each combination valve,
including pilot combination valves.When your manometer is connected to the first combination valve for
test, turn the manual shut off valve, located under the unit,
to the open position (valve handle in line with piping).
Turn the main power switch to "ON" and turn all zone
power switches to "ON". All thermostat dials should be
set to approximately 350°F (182°C). When all burners are
operating, check the reading on the manometer. If not in
accordance with the pressure specified on the
Serial/Rating Plate, adjust the combination valve regula tor
accordingly. When satisfied with the manometer reading,
turn the main power switch to "OFF", remove the
manometer test tube and recap the test spigot. Repeat this
operation on each combination valve until each pressure
regulator is set correctly. Turn each thermostat, zone
power switch and main power switch to "OFF".
NOTE: Make certain no electrical connections have been
disturbed before replacing front panels.
ELECTRICAL CONNECTION
IMPORTANT: This appliance must be electrically
grounded in accordance with local codes, or in the absence
of local codes, with the Canadian Electrical Code C22.1 or
with the National Electrical Code ANSI/NFPA No. 70
(latest edition), whichever is applicable.
WARNING
Electrical Grounding Instructions
This appliance is equipped with a three-prong (grounding)
plug for your protection against shock hazard and should be
plugged directly into a properly
grounded three-prong receptacle. Do not cut or remove the
grounding prong from this plug.
A separate 15 amp service must be provided. For 120V
usage, each unit is electrically equipped with a cord set with
a three-prong plug which fits any standard 120 volt, threeprong grounded receptacle.
When the unit is ordered and built for 208/240 volt, the
supply line must be connected to the wiring terminations
located inside the terminal box. For ease in attaching the
supply line, there is a removable cover on the terminal box.
A wiring diagram is attached to the rear panel of each unit.
3
VENTILATION
The unit must be installed in a location in which the
facilities for ventilation permit satisfactory combustion of
gas and proper venting. Proper ventilation is imperative for
good operation of the appliance. The ideal method of
ventilating a gas unit is the use of a properly designed
ventilating canopy, which should extend at least 6" (152
mm) beyond all sides of the appliance (except against the
wall, if the canopy is a wall installation). This is usually
part of a mechanical exhaust system.
1. Appliances shall be located so as not to interfere with
proper circulation of air within the
OPERATING INSTRUCTIONS
LIGHTING INSTRUCTIONS
confined space. All gas burners require sufficient air to
operate.
2. Large objects should not be placed in front of the
appliance which might obstruct the air flow through the
front. Do not obstruct the flow of combustion and
ventilation air.
3. Do not permit fans to blow directly at the appliance, and
wherever possible, avoid open windows adjacent to the
appliance sides and back;
also wall type fans which create air cross-currents within
the room.
Wait 5 minutes, then turn the main power switch back to
"ON".
Adequate means must be provided to limit movement of the
appliance without depending on the connector and quick
disconnect device or associate piping. This can be
accomplished by attaching restraining chains/cables from
floor or rear wall to rear of unit.
On units equipped with casters, ensure that front casters are
in the locked position and that the movement restraint is
connected to the appliance.
During an electrical power interruption, turn power switch
to the "OFF" position. This unit cannot be made to operate
without electrical power.
1. First, make certain that all power switches and thermostat
switches are set to "OFF".
2. Connect electrical power cord to 120 volt supply.
3. Turn the gas shut-off valve to the "OPEN" position
(valve handle in line with piping).
4. Turn the main power switch to "ON", power switch green
indicator should illuminate. Wait until gas pilot, green
indicator illuminate.
NOTE: Should pilot ignition fail after a few minutes,
turn the main power switch to "OFF".
5. When the green indicators for their respective zones are
illuminated, turn the zone power switch for each zone
to "ON" and set the thermostats to the desired
temperature settings.
6. The amber burner indicators cycle with the ther mostat
operation.
SHUT DOWN INSTRUCTIONS
1. Turn all zone and power switches to "OFF" (thermostat
dial settings may be left at their set point if preferred)
at the end of daily operations.
2. For extended shut down, turn all zone power switches to
"OFF", turn main power switch to "OFF", close the
manual gas shut-off valve and unplug the electrical
cord set.
NOTE: Do not waste gas or abuse equipment by leaving
thermostats at a high temperature, if not required.
During idling periods, set ther mostats to a low
temperature setting. For example: 175° (79°C) to 200°F
(93°C), to keep griddle warm. Rest thermostats, as
required, for periods of heavy load.
4
ADJUSTMENTS
PILOT ADJUSTMENT
NOTE: Each griddle has been factory tested and adjusted
prior to shipment. It may be necessary to further adjust the
unit as part of a proper installation. Such adjustments are
the responsibility of the installer. Adjustments are not
considered to be defects in material and workmanship, and
they are not covered under the original equipment warranty.
A pilot adjustment valve is located in the line from each
pilot combination valve. Pilot adjustment is accessible from
behind the lower front panel. First remove the two screws
securing the upper front panel to the body, in the upper right
and left hand corners, then slightly raise the panel to lift off.
Remove to a safe area. Next, remove the two screws
securing the lower front panel to the body, in the upper right
and left hand corners and hinge the panel downwards.
Turning the small screw in the pilot adjusting valve
clockwise reduces the amount of gas provided to the
pilot(s). Turning the small screw counter-clockwise
increases the gas provided to the pilot(s). The gas should be
adjusted to a 7/16 (11 mm) inch long flame, to ensure that
the flame engulfs the top of the flame sensor.
When the air shutter adjustments are complete on each
burner, re-tighten the air shutter screw so that the correct
setting is locked in place.
NOTE: Make certain no electrical connections have been
disturbed. Replace both panels and secure to body.
THERMOSTAT CALIBRATION
This griddle thermostat is a precision instrument. It is
carefully calibrated at the factory so that the dial setting
matches the actual griddle temperature. Field re -calibration
is seldom necessary and should not be attempted unless
considerable experience with cooking results prove that the
thermostat is not maintaining the set temperature properly.
To check calibration, use a test instrument with a flat
temperature sensing surface, which can be placed on the
griddle plate surface. Place the sensor in the center of the
zone being tested.
1. Turn the griddle "ON" and set the thermostat to 350°F
(176°C). Allow the griddle zone to achieve
temperature and thermostat to cycle at least 3 times.
Take a temperature reading at the time that this
thermostat cycles on for the third time.
MAIN BURNER AIR ADJUSTMENT
Burners should always be warm when an adjustment to air
shutters is made. To adjust air shutters, loosen the small
screw along the side of the burner near the orifice. Lifting
flames on the burner indicates too much air and this air
shutter should be in a more closed position. Yellow tips on
the flames indicate not enough air and the air shutter should
be in a more open position.
2. If, when the thermostat indicates heating (amber
indicator illuminated), the surface tempera ture does not
exceed plus (+) or minus (-) 8°F (13°C) of the
thermostat set point, no re-calibration is necessary.
If the griddle plate surface temperature exceeds +/- 8°F
(13°C), it could indicate a defective thermostat or
sensor. The electronic thermostat is precisely calibrated
at the factory. Any work should be performed by a
qualified service technician.
5
MAINTENANCE AND CARE
Periodical inspections by your dealer or qualified service
agency are recommended to check temperatures,
adjustments and ensure moving parts are operative.
Whenever possible, avoid overheating idle equipment, as
this is the primary cause for increased service costs.
Always disconnect the power supply to appliance before
servicing. After servicing, ensure that all connectors are
suitably secured back in place.
SEASONING
Before being used for the first time, all griddle surfaces
must be carefully "broken in" or "seasoned".
1. Remove all factory applied protective materials by
washing with a hot mild detergent or soap solution.
Rinse and dry thoroughly.
2. Set the griddle thermostats to a low tempera ture, 150°F
(65°C)to 175°F (79°C) and allow griddle to operate for
thirty minutes.
3. Apply a thin coat of olive oil or other high grade, salt
free, cooking oil to the surface. Wipe away excess.
4. Allow oil to remain on the griddle surface for 5 minutes,
then wipe off.
5. Reset thermostat to a medium temperature, 275°F
(135°C) to 300°F (149°C), and apply a second thin
coat of oil. Wipe off excess after 5 minutes.
6. Reset thermostat to desire cooking temperature and apply
a final coat of oil. Wipe off excess after 3 minutes. The
griddle is now seasoned and ready for use.
NOTE: Griddle may be re-seasoned at any time by
thoroughly cleaning and following the above procedures.
Griddles should be re-seasoned prior to each day's
operation.
CLEANING
Griddle plates should be cleaned daily while still warm.
Remove carbonized grease and/or food residue with a
spatula.
When necessary, clean griddle surface thoroughly using a
fine griddle brick, or a liquid griddle cleaner (available
from your kitchen equipment dealer).
Polish the griddle surface to a bright finish. Wash griddle
surface, rinse and dry thoroughly. Re -season the griddle as
per the seasoning instructions.
* Avoid overheating the griddle as this may cause sticking
and grease carbonizing, resulting in a hard to clean
surface.
* Do not hit spatula on the griddle plate as this will nick the
surface.
* Empty the grease tray frequently to avoid over filling and
spill overs.
EXTERIOR CLEANING
Normal soil may be removed from stainless steel with a hot
detergent or soap solution. To remove grease that has baked
on, apply cleanser on the metal in the direction of the
polishing lines of the metal. Never rub in a circular motion.
Soil and burned deposits which do not respond can usually
be removed by rubbing the surface with SCOTCH-BRITE
scouring pads or STAINLESS scouring pads. Do not use ordinary steel wool.
Heat tint can be removed by a vigorous scouring in the
direction of the polish lines, using SCOTCH-BRITE
scouring pads or STAINLESS scouring pads in
combination with a powdered cleanser.
6
SERVICE BULLETIN
Bulletin No:
98017
From: Garland Group Service Department To:
Authorized Service Agencies
SUBJECT: Chain Griddle Panel Cover
Models Effected: CG & CE -36, 48, 60 & 72
A Griddle Panel Cover has been made available to help prevent water and grease from entering the control
compartment and damaging the controls. The panel cover can easily be installed onto existing units.
Date: March 25, 1998
Kit numbers are as follows.
KIT Number Used on Model's
CK171-36 CG & CE36
CK171-48 CG & CE48
CK171-60 CG & CE 60
CK171-72 CG & CE 72
See attached page for mounting instructions.
8
CHAIN GRIDDLE PANEL COVER MOUNTING
INSTRUCTIONS
1. DRILL (5) 0.125"∅ HOLES IN UPPER FRONT PANEL AS SHOWN
2. MOUNT PANEL COVER TO UPPER FRONT PANEL WITH SELF-TAPPING SCREWS (4)
3. INSTALL LOCKING SCREW (1)
9
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.