Pub. 42004-437B
GAI-TRONICS® CORPORATION
A HUBBELL COMPANY
Model 531A Strobe with
Constant-On Feature
Confidential ity Notice
This manual is provided solely as an operational, installation, and maintenance guide and contains sensitive
business and technical information that is confidential and proprietary to GAI-Tronics. GAI-Tronics
retains all intellectual property and other rights in or to the information contained herein, and such
information may only be used in connection with the operation of your GAI-Tronics product or system.
This manual may not be disclosed in any form, in whole or in part, directly or indirectly, to any third party.
General Information
The Model 531A Strobe features an incandescent lamp for constant-on operation and a high-intensity
xenon tube for flashing operation, with secondary contact for auxiliary equipment. The incandescent
lamp remains constantly on for area location while the xenon tube flashes on and off, 65 flashes per
minute, when activated by an emergency telephone.
The Model 531A Strobe is designed for top-of-pole mounting, wall mounting, or surface mounting.
The unit is equipped with a ¾-inch NPT female pipe thread in the base; a pipe nipple or conduit with a
corresponding thread should be used for mounting the units. For wall or surface mounting, the
GAI-Tronics Model 4115A Mounting Assembly Kit is recommended.
WARNING
Research indicates that a small portion of the general population,
(approximately 1 in 100,000) with Photosensitive Epilepsy (PSE) may experience
epileptiform seizures upon exposure to certain visual stimuli including lights flashing in
excess of 3 Hz (180 cpm). Individuals with positive photic response to visual stimuli who
are prone to seizures, such as persons with epilepsy, should avoid prolonged exposure to
environments in which flashing lights are activated.
Installation
CAUTION
These installation instructions are for use by qualified service personnel only.
All field wiring to the beacon must meet the requirements of the National Electric Code (NEC) and
any other applicable local or state codes.
Before beginning any installation or modification, be sure the main electrical disconnect switch is in
the OFF position. TAG THE DISCONNECT SWITCH WITH A SUITABLE WARNING LABEL.
Electrical ground is required on this appliance.
Improper connection of the equipment can result in electrical shock.
GAI-Tronics Corporation 400 E. Wyomissing Ave. Mohnton, PA 19540 USA
610-777-1374 800-492-1212 Fax: 610-796-5954
V
ISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS

Pub. 42004-437B
Model 531A Strobe with Constant-On Feature Page 2 of 3
Wiring
The Model 531A Strobe is equipped with seven 15-foot conductor leads. Refer to Figure 1. The red (+)
and white (−) leads are connected to the 24 V dc
power source. The green lead is the earth ground
wire.
The violet (+) and orange (–) leads are connected to
the emergency telephone to signal the strobe to flash.
The blue and black leads are provided to activate
auxiliary equipment.
1. Connect the red (+) lead to the local power
source.
2. Connect the white (−) lead to the local power
source.
3. Connect the green lead to a ground connection.
4. Open the front cover of the emergency telephone
to expose the printed circuit board assembly
(PCBA) and locate the terminal block labeled
TB-2 (OUT1).
5. Bring the violet (+) and orange (–) leads through
the entry hole used for the telephone line.
6. Connect the violet (+) lead to terminal 1 and the
orange (–) lead to terminal 2
7. Replace the front cover on the emergency
on TB2.
Figure 1. Model 531A Strobe Outline
telephone and test the unit by pressing the
E
MERGENCY button. The strobe is only activated by pressing the EMERGENCY button, not the CALL
button (if so equipped).
N
OTE: The strobe provides a blue and black wire to activate auxiliary equipment such as signaling
devices or camera call-up controls. These wires provide a dry contact closure rated for 2 amps @
240 V ac, or 2 amps @ 30 V dc, for the duration of the emergency telephone/strobe activation.