This manual is provided solely as an operational, installation, and maintenance guide and contains
sensitive business and technical information that is confidential and proprietary to GAI-Tronics.
GAI-Tronics retains all intellectual property and other rights in or to the information contained herein,
and such information may only be used in connection with the operation of your GAI-Tronics product or
system. This manual may not be disclosed in any form, in whole or in part, directly or indirectly, to any
third party.
General Information
The Model 379-002 Monitored Relay Module (MRM) Station is used in SmartSeries ADVANCE
Systems. Operation is controlled by the system’s Master Control Unit (MCU) programming.
The MRM provides eight relay output circuits. Each relay contains two type “C” contacts rated for 5A.
Relay outputs are typically used for switching power to signaling devices such as beacons or strobes but
can be used for any switching application that does not exceed the relay’s current rating. Relay circuits
can be programmed to activate during system alarms, pages, or trouble condition.
The MRM also contains eight input circuits. Input circuits can be used supervise the cable integrity
connecting the relay output to the signaling device (as described above). During an inactive state, the
cable is monitored for open circuit, short circuit and ground fault conditions. If a cable fault is detected,
the relay circuit will not activate, preventing a possible dangerous condition. The fault condition is
automatically reported to the MCU.
For each relay circuit not requiring supervision, one input circuit is available for other functions. Inputs
are activated by a voltage-free contact (either opening or closing) or the presence/absence of a 24 V dc
input voltage. When using inputs from voltage-free contacts, the MRM can supervise the cabling
between the input terminal and the remote contact closure device. The cable is monitored for open
circuit, short circuit and ground fault conditions. The fault condition is automatically reported to the
MCU.
Each input circuit can be programmed to initiate one of the following functions in the ADVANCE
system.
Activate an alarm
Reset all alarms
Cancel the current alarm
Report a fault condition
Reset the system MCU
GAI-Tronics Corporation 400 E. Wyomissing Ave. Mohnton, PA 19540 USA
610-777-1374 800-492-1212 Fax: 610-796-5954
V
ISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS
Page 2
Pub. 42004-491A
Model 379-002 Monitored Relay Module Station Page 2 of 13
The Model 379-002 Monitored Relay Module (MRM) Station components are housed in a NEMA 4X
stainless steel enclosure measuring 13.00 W 14.30 H 6.23 D inches. Components include a 12 V dc
power supply and a 12579-002 Monitored Relay Module.
The 12579-002 Monitored Relay Module is comprised of three components: the 69248-102TR CPU and
the 69251-201TR Monitored-Input PCBA, and the 69252-001TR Relay PCBA. Refer to Figure 1 for
component locations.
The scope of this manual is limited to the mounting and wiring connections for the Model 379-002
Station. Refer to Pub. 42004-712L2 for additional information on the 12579-002 Monitored Relay
Module.
Figure 1. Model 379-002 MRM Station (Interior View)
f:\standard ioms - current release\42004 instr. man uals\42004-491a.doc
03/14
Page 3
Pub. 42004-491A
Model 379-002 Monitored Relay Module Station Page 3 of 13
Installation
CAUTION
Do not install this equipment in hazardous areas. Disconnect power before installing or removing
the MRM.
Mounting
The Model 379-002 MRM Station enclosure is not supplied with conduit or cable gland holes since cable
quantity, size, and entry location vary with each installation.
Drill or punch openings at the required locations before mounting the enclosure. Typically multiple
cables entries are required for power, serial data line, and input wiring. Refer to the Wiring section
below. Use caution when drilling or punching the enclosure to avoid damaging the internal components.
Bottom cable entry is recommended to prevent moisture from entering the enclosure and dripping onto
the terminals or circuit boards.
Mount the enclosure to a suitable surface using appropriate customer-supplied hardware. Refer to Figure
1 for mounting hole dimensions.
Remove the shipping tie-wrap that is securing the PCBA to its mounting Snaptrack.
Wir in g
The MRM Station requires 120 V ac power and a serial data line connection (RS-485) to the ADVANCE
System Control Cabinet. Up to eight input and relay output circuits are connected as needed. Each
connection is explained below.
Power
120 V ac power is connected to terminal block TB13 at the top of the panel. Refer to Figure 1.
WARNING
Earth grounding provisions are provided.
Function Terminal Block Wire Color
AC Line (hot) TB13-1 Black
Neutral TB13-2 White
Ground TB13-3 Green/yellow
Insure proper grounding to protective earthing.
Table 1.
f:\standard ioms - current release\42004 instr. man uals\42004-491a.doc
03/14
Page 4
Pub. 42004-491A
Model 379-002 Monitored Relay Module Station Page 4 of 13
Data Communications
Terminal blocks TB11 and TB12 are for “feed-thru” connection of the RS-485 data cable. The data cable
should consist of a twisted pair with shield. One end of the data cable must be terminated to the
ADVANCE System Control Cabinet. A total of ten MR M and MIM modules can be parallel wired to
the data cable. The most distant MRM or MIM should have a termination resistor installed to the data
line by installing jumper P2 on the 69248-xxx CPU PCBA.
CAUTION
The RS-485 line is polarity-sensitive. Be sure to maintain circuit polarity throughout installation.
OTES:
N
Only one termination resistor should be installed across the RS-485 data line. Be sure jumper P2 is
installed on only the most distant MRM or MIM.
Address Setting
Each MRM and MIM on the RS-485 data line must be set with a unique hardware address. Consult the
System Administrator for the proper address prior to setting the address switch on the MRM or MIM.
Addresses for each module are determined by the System Administrator’s software configuration of the
ADVANCE system. The address is set using the hexadecimal switch on the 69248-xxx CPU PCBA.
Valid addresses are 5–F.
Relay - Co ntact Outpu ts
The MRM contains eight individually configurable relay-contact outputs, allowing it to control field
devices such as beacons. Connections with these field devices are made at connectors TB1 through TB8
of the 69252-xxx Power Relay Module.
Each connector corresponds to a single output (TB1 is used for output #1, TB2 is used for output #2, etc.).
If fewer than eight supervised relay-contact outputs are required, the unused outputs may be used to
receive inputs (dry contact closures or non-supervised 24 V dc wet contact closures) from field devices.
In this case, connections with these field devices are made at connectors TB1 through TB8 of the 69251xxx Monitored-In-8 PCBA. Each of these outputs may be configured to operate in one of six modes.
Two of these six modes are used to control signaling devices, while the remaining four modes are used to
receive inputs (contact closures) from field devices.
Each mode requires a unique connection scheme between the external field devices and the appropriate
connector on the MRM. The connection scheme for each mode is described below. Since the connection
scheme is independent of which output is used, only Output #1 will be discussed.
To ensure proper termination, ferrules must be crimped on the ends of all conductors that are terminated
on the terminal blocks. The size of the ferrule is dependent upon the size of the conductor used and can
be sourced from any supplier such as Phoenix, Altec or Weidmuller. The terminals accept a maximum
conductor size of No. 12 AWG and a minimum conductor size of No. 28 AWG.
f:\standard ioms - current release\42004 instr. man uals\42004-491a.doc
03/14
Page 5
Pub. 42004-491A
Model 379-002 Monitored Relay Module Station Page 5 of 13
Mode 0: Deactivate Circuit
In Mode 0, outputs may be used to control several signaling devices by connecting/disconnecting power
to these devices. In this mode, no supervision of the loop is supported. This mode supports both ac- and
dc-powered signaling devices.
Figure 2. Deactivate Circuit - AC-Powered Beacons
Figure 2 shows the recommended wiring diagram for ac-powered signaling devices, while Figure 3 shows
the recommended wiring diagram for dc-powered signaling devices (using Output #1 as an example.)
*NOTE: The MRM does not contain any current-limiting for the signaling device power. It is
recommended that an external fuse be provided for each output circuit with the appropriate voltage and
current ratings. The selected fuse should be of the slow-blow variety.
Figure 3. Deactivate Circuit - DC-Powered Beacons
f:\standard ioms - current release\42004 instr. man uals\42004-491a.doc
03/14
Page 6
Pub. 42004-491A
Model 379-002 Monitored Relay Module Station Page 6 of 13
Mode 1: IDC Line Supervision Multiple Switch
In this mode any number of normally-open dry contact closures may be installed on the line. The loop is
monitored for ground faults and open circuits in Mode 1. The end-of-line device is a 20 k, 5% tolerance
resistor.
Figure 4. IDC Line Supervision Multiple Switch
NOTE: The 20 k, 5% tolerance resistor is not included with the MRM. The resistor is included in a kit
(12509-004), which must be ordered separately.
f:\standard ioms - current release\42004 instr. man uals\42004-491a.doc
03/14
Page 7
Pub. 42004-491A
Model 379-002 Monitored Relay Module Station Page 7 of 13
Mode 2: IDC Single Normally-Open (N.O.) Switch
In this configuration, only one normally-open dry contact closure may be installed per supervised line. In
this mode, the loop is monitored for open circuits, wire-to-wire short circuits (across + and −), and ground
faults. When the contact closure is not active (open), the loop appears as 20.1 k load (15 k in series
with 5.1 k). This appears on the input to the MIM and indicates a healthy loop. When the contact
closure is active (closed), the 15 k resistor is bypassed.
Figure 5. IDC Single Normally-Open Switch
When the contact closure is active (closed), the 15 k resistor is bypassed. In this case, output #1 only
sees a 5.1 k load. When this occurs, it indicates to the MRM that the contact closure is active. If there
is a short across L1 and L2, if either leg is grounded, or if a break occurs on either leg, the MRM indicates
that a fault has occurred.
NOTE: The terminating resistors are not included with the MRM. These resistors are included in a kit
(12509-004), which must be ordered separately.
f:\standard ioms - current release\42004 instr. man uals\42004-491a.doc
03/14
Page 8
Pub. 42004-491A
Model 379-002 Monitored Relay Module Station Page 8 of 13
Mode 3: IDC Single Normally-Closed (N.C.) Switch
In this configuration, only one normally-closed dry contact closure may be installed per supervised line.
In this mode, the loop is monitored for open circuits, wire-to-wire short circuits (across + and –), and
ground faults. When the contact closure is not active (closed), the 15 k is bypassed and the circuit sees
only the 5.1 k load.
Figure 6. IDC Single Normally-Closed Switch
This change is sensed by the MRM and indicates to the MRM that the contact closure is active. If there is
a short across L1 and L2, if either leg is grounded, or if a break occurs on either leg, the MRM indicates
that a fault has occurred.
NOTE: The terminating resistors are not included with the MRM. These resistors are included in a kit
(12509-004), which must be ordered separately.
f:\standard ioms - current release\42004 instr. man uals\42004-491a.doc
03/14
Page 9
Pub. 42004-491A
Model 379-002 Monitored Relay Module Station Page 9 of 13
Mode 4: IAC Line Super vision
In Mode 4, outputs can be used to control several dc-powered signaling devices by connecting/
disconnecting power to these devices. In addition, this loop is monitored for open circuits, wire-to-wire
short circuits (across + and -), and ground faults. If any of these three conditions are detected by the
MRM, the MRM indicates that a fault has occurred. Please note that monitoring of the loop only occurs
while the loop is
inactive (signaling devices are off).
Figure 7. IAC Line Supervision – DC-Powered Beacons
It is recommended that Mode 4 only be used with dc-powered signaling devices. In Mode 4, one
blocking diode must be provided for every signaling device connected to the loop. Note that some
signaling devices already include a blocking diode in the unit - in this case, no additional blocking diode
is required. The end-of-line device is a 20 k, 2-watt, 5% tolerance resistor. Please observe all polarities
as indicated in Figure 7 above.
NOTE: The blocking diodes, the wire jumpers, and the 20 k, 2-watt, 5% tolerance resistor are not
included with the MRM. These components are included in a kit (12509-004), which must be ordered
separately.
*NOTE: The MRM does not contain any current-limiting for the signaling device power. It is
recommended that an external fuse be provided for each output circuit with the appropriate voltage and
current ratings. The selected fuse should be of the slow-blow variety.
f:\standard ioms - current release\42004 instr. man uals\42004-491a.doc
03/14
Page 10
Pub. 42004-491A
Model 379-002 Monitored Relay Module Station Page 10 of 13
CAUTION
If ac-powered signaling devices are being used on an output loop configured for Mode 4 (Figure 8),
observe the following limitations necessary for reliable operation for the loop monitoring feature:
The dc-resistance measured across the loop (with both end-of-line device and the MRM
removed from the loop must be at least 100 k
Do NOT use blocking diodes in this loop.
Figure 8. IAC Line Supervision – AC-Powered Beacons
f:\standard ioms - current release\42004 instr. man uals\42004-491a.doc
03/14
Page 11
Pub. 42004-491A
Model 379-002 Monitored Relay Module Station Page 11 of 13
In this wet contact mode, shorting jumpers for each input must be moved from the factory default of
“dry” to “wet” contact mode. When in “wet” contact mode, the input can be activated during a 0 V
condition or a 24 V condition. The factory default setting is “24 V dc input when active” (position 2-3).
If “0 V dc input when active” is desired, move jumper from position 2-3 to position 1-2. The loop will
not
be monitored for any faults in Mode 5. Ensure the polarity of input connection is correct as it is
polarity sensitive.
Figure 10. IDC Non-Supervision (Wet Contact)
f:\standard ioms - current release\42004 instr. man uals\42004-491a.doc
03/14
Page 12
Pub. 42004-491A
Model 379-002 Monitored Relay Module Station Page 12 of 13
Table 2. Jumper Settings for Mode 5 Input Operation
Input No. Dry Contact
Input Selection
1 P1 – Pins 2 & 3
P2 – Pins 2 & 3
P3 – Pins 2 & 3
2 P4 – Pins 2 & 3
P5 – Pins 2 & 3
P6 – Pins 2 & 3
3 P7 – Pins 2 & 3
P8 – Pins 2 & 3
P9 – Pins 2 & 3
4 P10 – Pins 2 & 3
P11 – Pins 2 & 3
P12 – Pins 2 & 3
24 V DC Wet Contact Input
Selection
P1 – Pins 1 & 2
P2 – Pins 1 & 2
0 V dc – Active: P3 – Pins 1 & 2
24 V dc – Active: P3 – Pins 2 & 3
P4 – Pins 1 & 2
P5 – Pins 1 & 2
0 V dc – Active: P6 – Pins 1 & 2
24 V dc – Active: P6 – Pins 2 & 3
P7 – Pins 1 & 2
P8 – Pins 1 & 2
0 V dc – Active: P9 – Pins 1 & 2
24 V dc – Active: P9 – Pins 2 & 3
P10 – Pins 1 & 2
P11 – Pins 1 & 2
0 V dc – Active: P12 – Pins 1 & 2
24 V dc – Active: P12 – Pins 2 & 3
Factory Default
Setting
P1 – Pins 2 & 3
P2 – Pins 2 & 3
P3 – Pins 2 & 3
P4 – Pins 2 & 3
P5 – Pins 2 & 3
P6 – Pins 2 & 3
P7 – Pins 2 & 3
P8 – Pins 2 & 3
P9 – Pins 2 & 3
P10 – Pins 2 & 3
P11 – Pins 2 & 3
P12 – Pins 2 & 3
5 P13 – Pins 2 & 3
P14 – Pins 2 & 3
P15 – Pins 2 & 3
6 P16 – Pins 2 & 3
P17 – Pins 2 & 3
P18 – Pins 2 & 3
7 P19 – Pins 2 & 3
P20 – Pins 2 & 3
P21 – Pins 2 & 3
8 P22 – Pins 2 & 3
P23 – Pins 2 & 3
P24 – Pins 2 & 3
P13 – Pins 1 & 2
P14 – Pins 1 & 2
0 V dc – Active: P15 – Pins 1 & 2
24 V dc – Active: P15 – Pins 2 & 3
P16 – Pins 1 & 2
P17 – Pins 1 & 2
0 V dc – Active: P18 – Pins 1 & 2
24 V dc – Active: P18 – Pins 2 & 3
P19 – Pins 1 & 2
P20 – Pins 1 & 2
0 V dc – Active: P21 – Pins 1 & 2
24 V dc – Active: P21 – Pins 2 & 3
P22 – Pins 1 & 2
P23 – Pins 1 & 2
0 V dc – Active: P22 – Pins 1 & 2
24 V dc – Active: P22 – Pins 2 & 3
P13 – Pins 2 & 3
P14 – Pins 2 & 3
P15 – Pins 2 & 3
P16 – Pins 2 & 3
P17 – Pins 2 & 3
P18 – Pins 2 & 3
P19 – Pins 2 & 3
P20 – Pins 2 & 3
P21 – Pins 2 & 3
P22 – Pins 2 & 3
P23 – Pins 2 & 3
P24 – Pins 2 & 3
f:\standard ioms - current release\42004 instr. man uals\42004-491a.doc
03/14
Page 13
Pub. 42004-491A
Model 379-002 Monitored Relay Module Station Page 13 of 13
Specification s
Electrical
Power requirements ............................................................................ 120 V ac, 50/60 Hz @ 1A maximum
NOTE: Power requirements do NOT include power switched to external devices such as strobe lights.
Maximum current draw and switching voltage (per outlet) .......................... 5 amps @ 30 V dc or 132 V ac
Mechanical
Dimensions ........................................................................................... 13.00 W 14.30 H 6.23 D inches
Temperature range .................................................................................. −22º F to 158º F (−30º C to 70º C)
Environmental rating .................................................................................................................... NEMA 4X
Replac ement Parts
Part Number Description
69248-102TR PCBA, CPU Module with RS-485
69251-201TR PCBA, Monitored-In-8
69252-001TR PCBA, Relay Module
40404-009 Power Supply, 12 V dc, 25W
f:\standard ioms - current release\42004 instr. man uals\42004-491a.doc
03/14
Page 14
Warranty
Equipment. GAI-Tronics warrants for a period of one (1) year from the date of shipment, that any
GAI-Tronics equipment supplied hereunder shall be free of defects in material and workmanship, shall
comply with the then-current product specifications and product literature, and if applicable, shall be fit
for the purpose specified in the agreed-upon quotation or proposal document. If (a) Seller’s goods prove
to be defective in workmanship and/or material under normal and proper usage, or unfit for the purpose
specified and agreed upon, and (b) Buyer’s claim is made within the warranty period set forth above,
Buyer may return such goods to GAI-Tronics’ nearest depot repair facility, freight prepaid, at which time
they will be repaired or replaced, at Seller’s option, without charge to Buyer. Repair or replacement shall
be Buyer’s sole and exclusive remedy. The warranty period on any repaired or replacement equipment
shall be the greater of the ninety (90) day repair warranty or one (1) year from the date the original
equipment was shipped. In no event shall GAI-Tronics warranty obligations with respect to equipment
exceed 100% of the total cost of the equipment supplied hereunder. Buyer may also be entitled to the
manufacturer’s warranty on any third-party goods supplied by GAI-Tronics hereunder. The applicability
of any such third-party warranty will be determined by GAI-Tronics.
Services. Any services GAI-Tronics provides hereunder, whether directly or through subcontractors,
shall be performed in accordance with the standard of care with which such services are normally
provided in the industry. If the services fail to meet the applicable industry standard, GAI-Tronics will
re-perform such services at no cost to buyer to correct said deficiency to Company's satisfaction provided
any and all issues are identified prior to the demobilization of the Contractor’s personnel from the work
site. Re-performance of services shall be Buyer’s sole and exclusive remedy, and in no event shall GAITronics warranty obligations with respect to services exceed 100% of the total cost of the services
provided hereunder.
Warranty Periods. Every claim by Buyer alleging a defect in the goods and/or services provided
hereunder shall be deemed waived unless such claim is made in writing within the applicable warranty
periods as set forth above. Provided, however, that if the defect complained of is latent and not
discoverable within the above warranty periods, every claim arising on account of such latent defect shall
be deemed waived unless it is made in writing within a reasonable time after such latent defect is or
should have been discovered by Buyer.
Limitations / Exclusions. The warranties herein shall not apply to, and GAI-Tronics shall not be
responsible for, any damage to the goods or failure of the services supplied hereunder, to the extent
caused by Buyer’s neglect, failure to follow operational and maintenance procedures provided with the
equipment, or the use of technicians not specifically authorized by GAI-Tronics to maintain or service the
equipment. THE WARRANTIES AND REMEDIES CONTAINED HEREIN ARE IN LIEU OF AND
EXCLUDE ALL OTHER WARRANTIES AND REMEDIES, WHETHER EXPRESS OR IMPLIED BY
OPERATION OF LAW OR OTHERWISE, INCLUDING ANY WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
Return Policy
If the equipment requires service, contact your Regional Service Center for a return authorization number
(RA#). Equipment should be shipped prepaid to GAI-Tronics with a return authorization number and a
purchase order number. If the equipment is under warranty, repairs or a replacement will be made in
accordance with the warranty policy set forth above. Please include a written explanation of all defects to
assist our technicians in their troubleshooting efforts.
Call 800-492-1212 (inside the USA) or 610-777-1374 (outside the USA) for help identifying the
Regional Service Center closest to you.
(Rev. 10/06)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.