GAI-Tronics 13380-xxx User Manual

Page 1
Pub. 42004-394C
GAI-TRONICS® CORPORATION
A HUBBELL COMPANY
Loudspeakers
Instruction and Service Manual
This manual covers the follow ing loudspeaker models:
Model 13380-001, 8-ohm, 15 watts, 10.95 volts
Model 13380-002, 16-ohm, 15 watts, 15.49 volts
Model 13380-003, 70 V line, 15 watts, 70 volts
Model 13380-004, 100 V line, 15 watts, 100 volts
GAI-Tronics Corporation 400 E. Wyomissing Ave. Mohnton, PA USA
610-777-1374 800-492-1212 Fax: 610-796-5954
V
ISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS
Page 2
Pub. 42004-394C

Warranty

Equipment.
GAI-Tronics warrants for a period of one (1) year from the date of shipment, that any GAI-Tronics equipment supplied hereunder shall be free of defects in material and workmanship, shall comply with the then-current product specifications and product literature, and if applicable, shall be fit for the purpose specified in the agreed-upon quotation or proposal document. If (a) Seller’s goods prove to be defective in workmanship and/or material under normal and proper usage, or unfit for the purpose specified and agreed upon, and (b) Buyer’s claim is made within the warranty period set forth above, Buyer may return such goods to GAI-Tronics’ nearest depot repair facility, freight prepaid, at which time they will be repaired or replaced, at Seller’s option, without charge to Buyer. Repair or replacement shall be Buyer’s sole and exclusive remedy. The warranty period on any repaired or replacement equipment shall be the greater of the ninety (90) day repair warranty or one (1) year from the date the original equipment was shipped. In no event shall GAI-Tronics warranty obligations with respect to equipment exceed 100% of the total cost of the equipment supplied hereunder. Buyer may also be entitled to the manufacturer’s warranty on any third-party goods supplied by GAI-Tronics hereunder. The applicability of any such third-party warranty will be determined by GAI-Tronics.
Services.
Any services GAI-Tronics provides hereunder, whether directly or through subcontractors, shall be performed in accordance with the standard of care with which such services are normally provided in the industry. If the services fail to meet the applicable industry standard, GAI-Tronics will re-perform such services at no cost to buyer to correct said deficiency to Company's satisfaction provided any and all issues are identified prior to the demobilization of the Contractor’s personnel from the work site. Re-performance of services shall be Buyer’s sole and exclusive remedy, and in no event shall GAI-Tronics warranty obligations
Warranty Periods. Every claim by Buyer alleging a defect in the goods and/or services provided hereunder shall be
.
deemed waived unless such claim is made in writing within the applicable warranty periods as set forth above. Provided, however, that if the defect complained of is latent and not discoverable within the above warranty periods, every claim arising on account of such latent defect shall be deemed waived unless it is made in writing within a reasonable time after such latent defect is or should have been discovered by Buyer.
Limitations / Exclusions. The warranties herein shall not apply to, and GAI-Tronics shall not be responsible for,
any damage to the goods or failure of the services supplied hereunder, to the extent caused by Buyer’s neglect, failure to follow operational and maintenance procedures provided with the equipment, or the use of technicians not specifically authorized by GAI-Tronics to maintain or service the equipment. THE WARRANTIES AND REMEDIES CONTAINED HEREIN ARE IN LIEU OF AND EXCLUDE ALL OTHER WARRANTIES AND REMEDIES, WHETHER EXPRESS OR IMPLIED BY OPERATION OF LAW OR OTHERWISE, INCLUDING ANY WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
Return Policy
If the equipment requires service, contact your Regional Service Center for a return authorization number (RA#). Equipment should be shipped prepaid to GAI-Tronics with a return authorization number and a purchase order number. If the equipment is under warranty, repairs or a replacement will be made in accordance with the warranty policy set forth above. Please include a written explanation of all defects to assist our technicians in their troubleshooting efforts. Call 800-492-1212 (inside the USA) or 610-777-1374 (outside the USA) for help identifying the Regional Service Center closest to you.
_______________________________________________________________________________________________________________ GAI-Tronics 400 E. Wyomissing Ave. Mohnton, PA USA info@gai-tronics.com Tel: 800-492-1212
Document No. IS4211-GAI-TRON Issue: A 24-06-14 www.gai-tronics.com Fax: 610-796-5954
2 of 4
Sheet
Page 3
INSTRUCTION & SERVICE MANUAL
13380-XXX 15W LOUDSPEAKERS
For Use In Hazardous Locations
15 Watt Loudspeaker 70V or 100V Line Transformer
with 15W, 7.5W, 3W and 1W tapings
8 ohm or 16 ohm  Type 4 / 4X / 13  Operating Temperature Range
20ºC to +55ºC
7KA1

Unit Type No. 13380-XXX

Impedance: 8 ohm or 16 ohm
70V Line or 100V Line

Max. Operating Temperature / Code at +55ºC Ambient

Hazardous Location Temperature Code
Class I, Division 2, Groups A, B, C, D T4 (135ºC) Class II, Division 2, Groups F and G T6 (85ºC) Class III, Divisions 1 and 2 T6 (85ºC)

Max. Operating Temperature / Code at +40ºC Ambient

Hazardous Location Temperature Code
Class I, Division 2, Groups A, B, C, D T4A (120ºC)
The equipment is suitable for use in the hazardous locations listed above or non-hazardous locations only
.

MOUNTING

The 13380 15W loudspeaker must be mounted using the rotating bracket as shown.
18° Increments
Release nut to rotate bracket.
WARNING – EXPLOSION HAZARD - SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, II DIVISION 2.

WIRING INSTALLATION

The 13380 15W loudspeaker is provided with 1 M20 x 1.5 cable entry and one ½” NPT cable entry. The M20 entry is provided with a stopping plug in place.

Installation using Cable Glands without Field Wiring Leads

The cable connections are made into the terminal blocks on the electronic PCB assembly. Terminal blocks are suitable for field wiring (AWG 18-12). Strain relief has to be ensured by installation with a suitable cable gland. Follow the markings for the terminals on the PCB and install wiring as shown in the diagram below.
Cable glands need to be UL certified to ANSI/UL 2225 or C22.2 NO. 174-M1984, and to UL514B / CSA-C22.2 No. 18.3-12,
M4 Hex Socket Screw
Spring Washer
Flat Washer
ratings for hazardous locations must be equal to or better than the rating of the sounder used. If a high IP (Ingress Protection) rating is required then a suitable sealing washer must be fitted under the cable gland.
WARNING – DO NOT OPEN WHEN ENERGISED
CAUTI0N – DO NOT OPEN WHEN AN EXPLOSIVE GAS
OR DUST ATMOSPHERE IS PRESENT
__________________________________________________________________________________________________________________ GAI-Tronics 400 E. Wyomissing Ave. Mohnton, PA USA info@gai-tronics.com Tel: 800-492-1212
Document No. IS4211-GAI-TRON Issue: A 24-06-14 www.gai-tronics.com Fax: 610-796-5954
Sheet
3 of 4
Page 4
WARNING – ALL ELECTRICAL WIRING MUST BE
INSTALLED IN ACCORDANCE TO THE NATIONAL ELECTRICAL CODE

100V and 70V Loudspeakers

White Common Red 15 Watts Orange 7.5 Watts Yellow 3 Watts Violet 1 Watt Green/Yellow Ground
Common 15 Watts
7.5 Watts 3 Watts 1 Watt
Watts
7,5
315C
1
Watts
7,5
Watts
1315C
7,5

8 ohm and 16 ohm Loudspeakers

Black Common Red 15 Watts Green/Yellow Ground
15 WattsC
Common
15 Watts
15 WattsC 15 WattsC
POWER AMPIFIER SELECTION
It is important that the 13380 15W loudspeakers are connected to power amplifiers that have outputs that are compatible to the type of loudspeaker being used. Loudspeakers with a 70V or 100V line matching transformer fitted must be connected to a power amplifier with a 70V or 100V line output. Low impedance 8 ohm or 16 ohm loudspeakers must be connected to amplifiers with a suitable low impedance output.
1315C
Unit Type Input Wattage Max. I/P Volts
13380-001 8 ohm 15 Watt 10.95V 13380-002 16 ohm 15 Watt 15.49V 13380-004 100V Line 15 Watt 100V 13380-003 70V Line 15 Watt 70V
WARNING – HIGH VOLUME MAY CAUSE HARM TO
PERSONNEL IN CLOSE PROXIMITY
__________________________________________________________________________________________________________________ GAI-Tronics 400 E. Wyomissing Ave. Mohnton, PA USA info@gai-tronics.com Tel: 800-492-1212
Document No. IS4211-GAI-TRON Issue: A 24-06-14 www.gai-tronics.com Fax: 610-796-5954