GAI-Tronics 13380-001, 13380-004, 13380-002, 13380-003 Instruction And Service Manual

G AI - TRO NI CS®
A HUBBELL CO MPANY
Model 13380-xxx Series
Loudspeakers
This manual covers the following loudspeaker models:
Model 13380-001, 8-ohm, 15 watts, 10.95 volts
Pub. 42004-394C
Model 13380-002, 16-ohm, 15 watts, 15.49 volts
Model 13380-003, 70 V line, 15 watts, 70 volts
Model 13380-004, 100 V line, 15 watts, 100 volts
GAI-TRONICS 3030 KUTZTOWN RD. READING, PA 19605 USA
610-777-1374 800-492-1212 Fax: 610-796-5954
VISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS
INSTRUCTION & SERVICE MANUAL
15 Watt Loudspeaker
Max. Operating Temperature / Code at +55ºC Ambient
Hazardous Location
Temperature Code
Class I, Division 2, Groups A, B, C, D
T4 (135ºC)
Class II, Division 2, Groups F and G
T6 (85ºC)
Class III, Divisions 1 and 2
T6 (85ºC)
Max. Operating Temperature / Code at +40ºC Ambient
Hazardous Location
Temperature Code
Class I, Division 2, Groups A, B, C, D
T4A (120ºC)
Flat Washer
Spring Washer
M4 Hex Socket Screw
18° Increments
Release nut to rotate bracket.
70V or 100V Line Transformer with 15W, 7.5W, 3W and 1W tapings
8 ohm or 16 ohm
Type 4 / 4X / 13
Operating Temperature Range
20ºC to +55ºC
Unit Type No. 13380-XXX
Impedance: 8 ohm or 16 ohm
70V Line or 100V Line
13380-XXX 15W LOUDSPEAKERS
For Use In Hazardous Locations
MOUNTING The 13380 15W loudspeaker must be mounted using the
rotating bracket as shown.
7KA1
WARNING – EXPLOSION HAZARD - SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, II DIVISION 2.
The equipment is suitable for use in the hazardous locations listed above or non-haz ardou s locatio ns only
ARNING – DO NOT OPEN WHEN ENERGISED
W
CAUTI0N – DO NOT OPEN WHEN AN EXPLOSIVE GAS
.
OR DUST ATMOSPHERE IS PRESENT
WIRING INSTALLATION
The 13380 15W loudspeaker is provided with 1 M20 x 1.5 cable entry and one ½” NPT cable entry. The M20 entry is provided with a stopping plug in place.
Installation using Cable Glands without Field Wiring Leads
The cable connections are made into the terminal blocks on the electronic PCB assembly. Terminal blocks are suitable for field wiring (AWG 18-12). Strain relief has to be ensured by installation with a suitable cable gland. Follow the markings for the terminals on the PCB and install wiring as shown in the diagram below.
Cable glands need to be UL certified to ANSI/UL 2225 or C22.2 NO. 174-M1984, and to UL514B / CSA-C22.2 No. 18.3-12, ratings for hazardous locations must be equal to or better than the rating of the sounder used. If a high IP (Ingress Protection) rating is required then a suitable sealing washer must be fitted under the cable gland.
__________________________________________________________________________________________________________________ GAI-Tronics 3030 Kutztown Rd. Reading PA 19605 USA
ument No. IS4211-GAI-TRON Issue: A 24-06-14
Doc
info@gai-tronics.com Tel: 800-492-1212 www.gai-tronics.com Fax: 610-796-5954
Sheet
3 of 4