Pub. 42004-451A
GAI-TRONICS®
A HUBBEL L COMPAN Y
Model 13314-004 Div. 2 Hazardous Area
100-Volt Horn Driver
Confidentiality Notice
This manual is provided solely as an operational, installation, and maintenance guide and contains
sensitive business and technical information that is confidential and proprietary to GAI-Tronics. GAITronics retains all intellectual property and other rights in or to the information contained herein, and
such information may only be used in connection with the operation of your GAI-Tronics product or
system. This manual may not be disclosed in any form, in whole or in part, directly or indirectly, to any
third party.
Introduction
The GAI-Tronics Model 13314-004 Div. 2 Hazardous Area 100-Volt Horn Driver is constructed of black
glass and fiber-reinforced polyester thermoplastic and has a rain-tight construction. It is built to
withstand harsh industrial environments and is approved for installation in hazardous areas.
Mounting Instructions
A typical installation of a 13314 Series Driver with associated horn and mounting assembly is shown in
Figure 3. The recommended mounting height for the driver is 9 feet (2.7 meters) from the floor. Refer to
the following chart to verify that the horn is paired with the correct speaker mounting assembly.
Horn
Series
13302 411A
13304 411A
13305 411A
13306 414-002
Speaker Mounting
Assembly
13309 411A
13340 411A
GAI-TRONICS 3030 KUTZTOWN RD. READING, PA 19605 USA
610-777-1374 800-492-1212 Fax
VISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS
Fig
ure 1. Model 13314-004 Div. 2
Hazardous Area 100-Volt
: 610-796-5954
Horn Driver

Pub. 42004-451A
Model 13314-004 Div. 2 Hazardous Area 100-Volt Horn Driver Page:
2 of 4
Fig
ure 2. Typical Installation
The installation of this speaker assembly must conform to regulations governing electrical equipment for
hazardous locations and provisions of the National Electrical Code.
Install the mounting assembly and the horn, then complete the following instructions to install the driver
onto the horn.
Wiring Instructions
Refer to the following chart to determine the appropriate gauge speaker cable.
Distance of Cable
C
able Options
No. 18 AWG 8,900
No. 16 AWG 14,000
No. 14 AWG 22,500
Run in Feet
Field wiring
to the driver must be made using the attached three-conductor type SO cord. Connect these
wires as follows:
• Green: earth gr
• Black: am
hite: amplifier 100V − (com) term
• W
The horn driv
ound
plifier 100V + term
inal
inal
er is factory-connected for 30-watt tap setting. If no wattage tap changes are required,
screw the driver assembly onto the rear of the horn as shown in Figure 2.