Pub. 42004-405A
GAI-TRONICS® CORPORATION
A HUBBELL COMPANY
Model 12598-002
Redundant 5 V DC Modul e
Confidentiality Notice
This manua l is provide d sole ly as an operatio nal, installation, and ma inte nance guide and conta ins
sensitive business and t e chnical informatio n tha t is confidentia l and pr opri et ary to GAI- Tronics.
GAI-Tr on ic s ret ains a ll intellec tua l prop erty and other ri ghts in or t o the informa tion c onta ined herei n, and
such information may on ly be u sed in conn e ction with the operatio n of you r GAI-Tr onics p rodu c t or
system. This manu al may not be dis clos e d in any form, in whole or in pa rt, direct ly or i ndir ectly, to a ny
third pa r ty.
General Information
The Model 12598-002 Redundant DC Module is designed to accept the outputs of two 5 V dc power
supplies while providing a single dc output. This module will typically be used in custom products,
name ly ADVANCE c abinet s requiring redundant ci rcui ts to me et various agency requ ireme n ts.
Figure 1. Model 12598-002 Redundant 5 V DC Module
GAI-Tronics Corporation P.O. Box 1060, Readi ng, PA 19607-1060 USA
610-777-1374 800-492-1212 Fax: 610-796-5954
ISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS
V
Pub. 42004-405A
Model 12598-002 Redundant 5 V DC Module Page: 2 of 5
Hardware Configuration
The Model 12598-002 Redundant 5 V DC Module consists of a single-sided printed circuit board
measuring 4 L × 4 W × 1.5 H inches (102 × 102 × 38.1 mm). It is equipped with two 15A rated diodes
each mounted t o a heat sink, two s mall DPDT relays to provide dry co ntact sta tus outpu ts for each po w er
supply, and four modular (plug-in type) terminal blocks. All components on the board are through-hole.
Installation
CAUTION
When insta lling or rep lacing this module, be s ure to disconnect power for
safety.
The Model 12598-002 Redundant 5 V DC Module is designed for chassis mounting or on 4-inch Snap
Trak®. When inserting the module in SnapTrak®, exer cise care when pressin g the module edges int o the
SnapTrak
Once installed in the SnapTrak
®
to avoid damage to th e module’s print e d circuit boar d and components .
®
, be sure the module edges are secured in the channels so that the module
does not dislodge during transport or operation if subjected to vibration. Also, if this module is used with
other modules in the SnapTrak
®
, be sure to leave spacing between modules to facilitate wiring at any
edge-mounted terminal blocks.
Terminations
The Model 12598-002 Redundant 5 V DC Module is equipped with modular (plug-in type) terminal
blocks, which simplify external wire connections during installation, and provide quick disconnect if
repla cement is ever required.
The following is a breakdown of each terminal block and its function(s):
TB1 – is the 5 V dc power input from Power Supply 1 (PS1) to the module.
TB2 – is the 5 V dc power input from Power Supply 2 (PS2) to the module.
TB3 – is the 5 V dc power output from the module to the load.
TB4 – are dry output contacts for the PS1 and PS2 faults respectively. Each connected power supply has
two sets of contacts, which are a Form “C” type. The maximum switching capacity for each contact set is
30 V dc @ 1 amp, and can be used for triggering a remote status indicator or a supervised input at a
system device for visual text display.
\\s_eng\gtc proddoc s \st andard iom s - current release\42004 instr. manuals \ 42004-405a. doc
01/08