Furrion F30MLP-SY, F30MLP-SS, F20MLP-SS, F20MLP-SY User Manual

Size: A5, 1C printed on woodfree paper
INSTALLATION INSTRUCTIONS
F20MLP-SS / F20MLP-SY / F30MLP-SS / F30MLP-SY
WIRING INSTRUCTIONS:
• Strip conductor and jacket using strip gage on device
• Loosen Terminal Screws.
• Insert conductors fully into copper terminals as below.
• Take caution that there are no stray wire strands.
• Tighten terminals screws 14~16 in-lbs torque.
• Use copper conductors only
MARKING:
DIMENSIONS OF STRIP CONDUCTOR AND JACKET:
The length of strip conductor: 16mm (5/8” Inches) The length of strip jacket: 40mm (1½” Inches)
EXPLODED VIEW
WARNING:
• For installation by a qualied electrician in accordance with national and local electrical codes and the following instructions.
• Check that the device’s type and rating are suitable for the application.
• Risk of electric shock. Disconnect power before installing.
• Terminal capacity: 12AWG to 10AWG for 20Amp; 10AWG for 30Amp
IM-FXXMLP-XX REV1.2
Loading...